Successful application of this module requires a reasonable working knowledge of the Rockwell Automation
ControlLogix hardware, the
used. For this reason, it is important that those responsible for implementation satisfy themselves that the
combination will meet the needs of the application without exposing personnel or equipment to unsafe or
inappropriate working conditions.
This manual is provided to assist the user. Every attempt has been made to ensure that the information
provided is accurate and a true reflection of the product's installation requirements. In order to ensure a
complete understanding of the operation of the product, the user should read all applicable Rockwell
Automation documentation on the operation of the Rockwell Automation hardware.
Under no conditions will ProSoft Technology be responsible or liable for indirect or consequential damages
resulting from the use or application of the product.
Reproduction of the contents of this manual, in whole or in part, without written permission from ProSoft
Technology is prohibited.
Information in this manual is subject to change without notice and does not represent a commitment on the
part of ProSoft Technology Improvements and/or changes in this manual or the product may be made at any
time. These changes will be made periodically to correct technical inaccuracies or typographical errors.
MVI56-S3964R Module and the application in which the combination is to be
Warnings
UL Warnings
A Warning - Explosion Hazard - Substitution of components may impair suitability for
Class I, Division 2.
B Warning - Explosion Hazard - When in Hazardous Locations, turn off power before
replacing or rewiring modules.
Warning - Explosion Hazard - Do not disconnect equipment unless power has been
switched off or the area is known to be nonhazardous.
C Suitable for use in Class I, division 2 Groups A, B, C and D Hazardous Locations or
Non-Hazardous Locations.
ATEX Warnings and Conditions of Safe Usage:
Power, Input, and Output (I/O) wiring must be in accordance with the authority having
jurisdiction
A Warning - Explosion Hazard - When in hazardous locations, turn off power before
replacing or wiring modules.
B Warning - Explosion Hazard - Do not disconnect equipment unless power has been
switched off or the area is known to be non-hazardous.
C These products are intended to be mounted in an IP54 enclosure. The devices shall
provide external means to prevent the rated voltage being exceeded by transient
disturbances of more than 40%. This device must be used only with ATEX certified
backplanes.
D DO NOT OPEN WHEN ENERGIZED.
Electrical Ratings
Backplane Current Load: 800 mA @ 5 V DC; 3mA @ 24V DC
Operating Temperature: 0 to 60°C (32 to 140°F)
Storage Temperature: -40 to 85°C (-40 to 185°F)
Shock: 30g Operational; 50g non-operational; Vibration: 5 g from 10 to 150 Hz
Relative Humidity 5% to 95% (non-condensing)
All phase conductor sizes must be at least 1.3 mm(squared) and all earth ground
conductors must be at least 4mm(squared).
Markings:
II 3 G 0C <=Ta<= 60C EEx nA IIC T4 DEMKO 07ATEX0710717X
Battery Life Advisory
All modules in the MVI series use a rechargeable Lithium Vanadium Pentoxide battery to
backup the 512K SRAM memory, real-time clock, and CMOS. The battery should last for
the life of the module.
The module must be powered for approximately twenty hours before it becomes fully
charged. After it is fully charged, the battery provides backup power for the CMOS setup
and configuration data, the real-time clock, and the 512K SRAM memory for
approximately 21 days.
Before you remove a module from its power source, ensure that the battery within the
module is fully charged. A fully charged battery will hold the BIOS settings (after being
removed from its power source) for a limited number of days (15 for the PC56). When
the battery is fully discharged, the module will revert to the default BIOS settings.
Note: The battery is not user replaceable.
ProSoft® Product Documentation
In an effort to conserve paper, ProSoft Technology no longer includes printed manuals
with our product shipments. User Manuals, Datasheets, Sample Ladder Files, and
Configuration Files are provided on the enclosed CD and are available at no charge from
our web site:
Printed documentation is available for purchase. Contact ProSoft Technology for pricing
and availability.
Asia Pacific: +603.7724.2080
Europe, Middle East, South Africa: +33.5.34.36.87.20
Latin America: +1.281.298.9109
North America: +1.661.716.5100
http://www.prosoft-technology.com
Your Feedback Please
We always want you to feel that you made the right decision to use our products. If you have suggestions,
comments, compliments or complaints about the product, documentation or support, please write or call us.
Page 6 of 78 ProSoft Technology, Inc.
April 17, 2008
Start Here TMVI56-S3964RT ♦ TControlLogix PlatformT
TSiemens 3964R ProtocolT
Guide to the MVI56-S3964R User Manual
Function Section to Read Details
Introduction
(Must Do)
Verify Communication,
Diagnostic and
Troubleshooting
Reference
Product Specifications
Functional Overview
Glossary
Support, Service, and
Warranty
Index
→
→
→
→
Start Here (page 9)
Verifying
Communication
(page 47)
Diagnostics and
Troubleshooting
(page 37)
Reference (page
51)
Functional
Overview
Product
Specifications
(page 51)
Support, Service
and Warranty
(page 67)
(page 53)
This Section introduces the customer to the
module. Included are: package contents,
system requirements, hardware installation,
and basic configuration.
This section describes how to verify
communications with the network. Diagnostic
and Troubleshooting procedures.
These sections contain general references
associated with this product, Specifications,
and the Functional Overview.
This section contains Support, Service and
Warranty information.
Index of chapters.
ProSoft Technology, Inc. Page 7 of 78
April 17, 2008
TMVI56-S3964RT ♦ TControlLogix PlatformT Start Here
TSiemens 3964R ProtocolT
Page 8 of 78 ProSoft Technology, Inc.
April 17, 2008
Start Here MVI56-S3964RT ♦ TControlLogix PlatformT
TSiemens 3964R ProtocolT
1 Start Here
In This Chapter
System Requirements .............................................................................9
Install the Module in the Rack ...............................................................12
Connect your PC to the Processor ........................................................14
Open the Sample Ladder Logic............................................................. 15
Download the Sample Program to the Processor.................................. 18
Connect your PC to the Module ............................................................19
Installing the MVI56-S3964R module requires a reasonable working knowledge
of the Rockwell Automation hardware, the
application in which they will be used.
Caution: It is important that those responsible for implementati on can complete the
application without exposing perso nnel, or equipment, to unsafe or inappropr iate working
conditions. Safety, quality and experience are key factors in a successful installation.
1.1 System Requirements
The MVI56-S3964R module requires the following minimum hardware and
software components:
Rockwell Automation ControlLogix™ processor, with compatible power
supply and one free slot in the rack, for the
module requires 800mA of available power.
Rockwell Automation RSLogix 5000 programming software version 2.51 or
higher.
Rockwell Automation RSLinx communication software
Pentium® II 450 MHz minimum. Pentium III 733 MHz (or better)
recommended
Supported operating systems:
o
Microsoft Windows XP Professional with Service Pack 1 or 2
o
Microsoft Windows 2000 Professional with Service Pack 1, 2, or 3
o
Microsoft Windows Server 2003
128 Mbytes of RAM minimum, 256 Mbytes of RAM recommended
MVI56-S3964R Module and the
MVI56-S3964R module. The
ProSoft Technology, Inc. Page 9 of 78
April 17, 2008
MVI56-S3964RT ♦ TControlLogix PlatformT Start Here
TSiemens 3964R ProtocolT
100 Mbytes of free hard disk space (or more based on application
requirements)
256-color VGA graphics adapter, 800 x 600 minimum resolution (True Color
1024
× 768 recommended)
CD-ROM drive
HyperTerminal or other terminal emulator program.
Note: You can install the module in a local or remote rack. For remote rack installation, the modul e
requires EtherNet/IP or ControlNet communication with the processor.
1.2 Package Contents
The following components are included with your MVI56-S3964R module, and
are all required for installation and configuration.
Important: Before beginning the installati on, please verify that all of the following items ar e
present.
Qty. Part Name Part Number Part Description
1
1 Cable
3 Cable
2 Adapter 1454-9F
1
MVI56S3964R
Module
ProSoft
Solutions
CD
MVI56-S3964RSiemens 3964R Protocol
Cable #15, RS232
Null Modem
Cable #14, RJ45 to
DB9 Male Adapter
cable
For RS232 Connection to the CFG Port
For DB9 Connection to Module's Port
Two Adapters, DB9 Female to Screw Terminal.
For RS422 or RS485 Connections to Port 1 and 2
of the Module
Contains sample programs, utilities and
documentation for the
MVI56-S3964R module.
If any of these components are missing, please contact ProSoft Technology
Support for replacement parts.
You must install the ProSoft Configuration Builder (PCB) software in order to
configure the
ProSoft Configuration Builder from the ProSoft Technology web site.
To install ProSoft Configuration Builder from the ProSoft Web Site
1 Open your web browser and navigate to http://www.prosoft-
technology.com/pcb
2 Click the
Configuration Builder.
Page 10 of 78 ProSoft Technology, Inc.
MVI56-S3964R module. You can always get the newest version of
Download Here link to download the latest version of ProSoft
April 17, 2008
Start Here MVI56-S3964RT ♦ TControlLogix PlatformT
TSiemens 3964R ProtocolT
3 Choose "Save" or "Save File" when prompted. The following illustrations
show the file download prompt for two of the most common web browsers.
4 Make a note of the location where you saved the file, for example "Desktop",
or "My Documents", so you can start the installation program.
5 When the download is complete, locate and open the file, and then follow the
instructions on your screen to install the program.
If you do not have access to the Internet, you can install ProSoft Configuration
Builder from the ProSoft Solutions CD-ROM, included in the package with your
MVI56-S3964R module.
To install ProSoft Configuration Builder from the CD-ROM
1 Insert the ProSoft Solutions CD-ROM into the CD drive of your PC. Wait for
the startup screen to appear.
2 On the startup screen, click
Product Documentation. This action opens an
explorer window.
3 Click to open the
Utilities folder. This folder contains all of the applications
and files you will need to set up and configure your module.
4 Double-click the
ProSoft Configuration Builder Setup program and follow the
instructions on your screen to install the software on your PC.
Note: Many of the configuration and maintenance procedures use files and other utilities on the
CD-ROM. You may wish to copy the files from the Utilities folder on the CD-ROM to a convenient
location on your hard drive.
ProSoft Technology, Inc. Page 11 of 78
April 17, 2008
MVI56-S3964RT ♦ TControlLogix PlatformT Start Here
TSiemens 3964R ProtocolT
1.4 Setting Jumpers
If you use an interface other than RS-232 (default), you must change the jumper
configuration to match the interface. There are three jumpers located at the
bottom of the module.
The following illustration shows the MVI56-S3964R jumper configuration:
1 Set the PRT 2 (for application port 1) and PRT 3 (for application port 2)
jumpers for RS232, RS422 or RS485 to match the wiring needed for your
application. The default jumper setting for both application ports is RS-232.
2 The Setup Jumper acts as "write protection" for the module's flash memory.
In "write protected" mode, the Setup pins are not connected, and the
module's firmware cannot be overwritten. Do not jumper the Setup pins
together unless you are directed to do so by ProSoft Technical Support.
1.5 Install the Module in the Rack
If you have not already installed and configured your ControlLogix processor and
power supply, please do so before installing the
your Rockwell Automation product documentation for installation instructions.
Warning: You must follow all safety instructions when installing this or any other electronic
devices. Failure to follow safety procedures could result in damage to hardware or data, or even
serious injury or death to personnel. Refer to the documentation for each device you plan to
connect to verify that suitable safety procedures are in place before installing or servicing the
device.
MVI56-S3964R module. Refer to
Page 12 of 78 ProSoft Technology, Inc.
April 17, 2008
Start Here MVI56-S3964RT ♦ TControlLogix PlatformT
TSiemens 3964R ProtocolT
After you have checked the placement of the jumpers, insert
MVI56-S3964R into
the ControlLogix chassis. Use the same technique recommended by Rockwell
Automation to remove and install ControlLogix modules.
Warning: When you insert or remove the module while backplane power is on, an electrical arc
can occur. This could cause an explosion in hazardous location installations. Verify that power is
removed or the area is non-hazardous before proceeding. Repeated electrical arcing causes
excessive wear to contacts on both the module and its mating con nector. Worn contacts may
create electrical resistance that can affect module operation.
1 Turn power OFF.
2 Align the module with the top and bottom guides, and slide it into the rack
until the module is firmly against the backplane connector.
3 With a firm but steady push, snap the module into place.
4 Check that the holding clips on the top and bottom of the module are securely
in the locking holes of the rack.
5 Make a note of the slot location. You will need to identify the slot in which the
module is installed in order for the sample program to work correctly. Slot
numbers are identified on the green circuit board (backplane) of the
ControlLogix rack.
6 Turn power ON.
ProSoft Technology, Inc. Page 13 of 78
April 17, 2008
MVI56-S3964RT ♦ TControlLogix PlatformT Start Here
TSiemens 3964R ProtocolT
Note: If you insert the module improperly, the system may stop working, or may behave
unpredictably.
Note: If you are installing MVI56-S3964R with other modules connected to the PCI bus, the
peripheral modules will not have holdi ng clips. Make sure all of the modules are alig ned with their
respective slots before you snap them into place.
1.6 Connect your PC to the Processor
1 Connect the right-angle connector end of the cable to your controller at the
communications port.
2 Connect the straight connector end of the cable to the serial port on your
computer.
Page 14 of 78 ProSoft Technology, Inc.
April 17, 2008
Start Here MVI56-S3964RT ♦ TControlLogix PlatformT
TSiemens 3964R ProtocolT
1.7 Open the Sample Ladder Logic
The sample program for your MVI56-S3964R module includes custom tags, data
types and ladder logic for data I/O and status monitoring. For most applications,
you can run the sample ladder program without modification, or, for advanced
applications, you can incorporate the sample program into your existing
application.
The inRAx Solutions CD provides one or more versions of the sample ladder
logic. The version number appended to the file name corresponds with the
firmware version number of your ControlLogix processor. The firmware version
and sample program version must match.
1.7.1 To Determine the Firmware Version of your Processor
Important: The RSLinx service must be installed and running on your computer in order for
RSLogix to communicate with the processor. Refer to your RSLinx and RSLogix documentation for
help configuring and troubleshooting these applications.
1 Connect an RS-232 serial cable from the COM (serial) port on your PC to the
communication port on the front of the processor.
2 Start RSLogix 5000 and close any existing project that may be loaded.
3 Open the Communications menu and choose
establish communication with the processor. This may take a few moments.
4 When RSLogix has established communication with the processor, the
Connected To Go Online dialog box will open.
Go Online. RSLogix will
ProSoft Technology, Inc. Page 15 of 78
April 17, 2008
MVI56-S3964RT ♦ TControlLogix PlatformT Start Here
TSiemens 3964R ProtocolT
5 On the Connected To Go Online dialog box, click the General tab. This tab
shows information about the processor, including the Revision (firmware)
version. In the following illustration, the firmware version is 11.32
1.7.2 Select the Slot Number for the Module
The sample application is for a module installed in Slot 1 in a ControlLogix rack.
The ladder logic uses the slot number to identify the module. If you are installing
the module in a different slot, you must update the ladder logic so that program
tags and variables are correct, and do not conflict with other modules in the rack.
To change the slot number
1 In the Controller Organization list, select the module [1] 1756-MODULE
MVI56, and then click the right mouse button to open a shortcut menu.
2 On the shortcut menu, choose
Properties dialog box.
Properties. This action opens the Module
Page 16 of 78 ProSoft Technology, Inc.
April 17, 2008
Start Here MVI56-S3964RT ♦ TControlLogix PlatformT
TSiemens 3964R ProtocolT
3 In the
Slot: field, use the spinners on the right side of the field to select the
slot number where the module will reside in the rack, and then click OK.
RSLogix will automatically apply the slot number change to all tags, variables
and ladder logic rungs that use the MVI56-S3964R slot number for computation.
1.7.3 Configuring RSLinx
If RSLogix is unable to establish communication with the processor, follow these steps:
1 Open RSLinx.
2 Open the Communications menu, and choose Configure Drivers.
This action opens the Configure Drivers dialog box.
Note: If the list of configured drivers is blank, you must first choose and configure a driver from the
Available Driver Types list. The recommended driv er type to choose for serial communication with
the processor is "RS-232 DF1 Devices".
ProSoft Technology, Inc. Page 17 of 78
April 17, 2008
MVI56-S3964RT ♦ TControlLogix PlatformT Start Here
TSiemens 3964R ProtocolT
3 Click to select the driver, and then click Configure. This action opens the
4 Click the Auto-Configure button. RSLinx will attempt to configure your serial
port to work with the selected driver.
5 When you see the message "Auto Configuration Successful", click the OK
button to dismiss the dialog box.
Note: If the auto-configuration procedure fai ls, verify that the cables are connected correctly
between the processor and the serial p ort on your computer, and then try again. If you are still
unable to auto-configure the port, refer to your RSLinx documentation for further troubleshooti ng
steps.
1.8 Download the Sample Program to the Processor
Note: The key switch on the front of the ControlLogix module must be in the REM position.
To download the sample program from RSLogix 5000 to the ControlLogix processor
1 If you are not already online to the processor, open the Communications
menu, and then choose Download. RSLogix will establish communication
with the processor.
Page 18 of 78 ProSoft Technology, Inc.
April 17, 2008
Start Here MVI56-S3964RT ♦ TControlLogix PlatformT
TSiemens 3964R ProtocolT
2 When communication is established, RSLogix will open a confirmation dialog
box. Click the Download button to transfer the sample program to the
processor.
3 RSLogix will compile the program and transfer it to the processor. This
process may take a few minutes.
4 When the download is complete, RSLogix will open another confirmation
dialog box. Click OK to switch the processor from Program mode to Run
mode.
Note: If you receive an error message during these steps, refer to your RSLogix documentation to
interpret and correct the error.
1.9 Connect your PC to the Module
With the module securely mounted, connect your PC to the
Configuration/Debug port using an RJ45-DB-9 Serial Adapter Cable and a Null
Modem Cable.
1 Attach both cables as shown.
2 Insert the RJ45 cable connector into the Configuration/Debug port of the
module.
ProSoft Technology, Inc. Page 19 of 78
April 17, 2008
MVI56-S3964RT ♦ TControlLogix PlatformT Start Here
TSiemens 3964R ProtocolT
3 Attach the other end to the serial port on your PC or laptop.
Page 20 of 78 ProSoft Technology, Inc.
April 17, 2008
Installing and Configuring the Module MVI56-S3964RT ♦ TControlLogix PlatformT
TSiemens 3964R ProtocolT
[3964R Port x] .......................................................................................30
Download the Project to the Module...................................................... 32
This chapter describes how to install and configure the module to work with your
application. The configuration process consists of the following steps.
1 Use RSLogix 5000 to identify the module to the processor and add the
module to a project.
Note: The RSLogix 5000 software must be in "offline" mod e to a dd the module to a project.
2 Modify the example ladder logic to meet the needs of your application, and
copy the ladder logic to the processor. Example ladder logic files are provided
on the CD-ROM.
Note: If you are installing this module in an existin g a pplication, you can copy the necessary
elements from the example ladder logic into your application.
The rest of this chapter describes these steps in more detail.
2.1 Installation Instructions
The following setups/limitations are to be observed:
Please make sure that you are using an MVI56-S3964R with the original
parameters and image as delivered. Jumper SETUP: Please remove to run the
MVI56-S3964R in application mode.
ATTENTION: Incorrect setting of the jumpers may cause damage to the
MVI56-S3964R module.
The remaining jumpers for PRT1 and PRT2 have to be set according to the
requirements of the user.
The communication partners are to be connected to the serial interface PRT1
and/or PRT2 of the
The serial parameters of the communication partners are to be set to 9600
Baud, even parity, 8 bit and 1 stop bit if the standard parameters of the
S3964R
will be used.
MVI56-S3964R.
MVI56-
ProSoft Technology, Inc. Page 21 of 78
April 17, 2008
MVI56-S3964RT ♦ TControlLogix PlatformT Installing and Configuring the Module
TSiemens 3964R ProtocolT
The next step in the module's setup is to define the User Defined Data Types to
be used with the module. Copy these data types from the example ladder logic if
you are not using the example. They will be defined if you are starting from the
example ladder logic. The Controller Organization window should display the
User Defined Data Types shown below:
After you have defined the User Defined Data Types, the next step is to define
the data to be used to interface with the module and the ladder logic. Open the
Controller Tags Edit Tags dialog box and enter the values shown in the following
example. The
MVI56-S3964R module is defined in the example as S3964R. You
can set the tag name to any valid tag name you desire. If you are using the
example ladder logic, this step has already been performed.
2.1.1 Module Data Object
All data related to the MVI56-S3964R module is stored in a user defined data
type. An instance of the data type is required before the module can be used.
This is done by declaring a variable of the data type in the Controller Tags Edit
Tags dialog box.
Page 22 of 78 ProSoft Technology, Inc.
April 17, 2008
Installing and Configuring the Module MVI56-S3964RT ♦ TControlLogix PlatformT
TSiemens 3964R ProtocolT
The structure of the object is displayed in the following figure:
This object contains objects that define user and status data related to the
module. Each of these object types is discussed in the following topics of the
document.
ProSoft Technology, Inc. Page 23 of 78
April 17, 2008
MVI56-S3964RT ♦ TControlLogix PlatformT Installing and Configuring the Module
TSiemens 3964R ProtocolT
Status Object (S3964RInStat Data Structure)
This object views the status of the module. The
S3964RInstat object shown
below is updated each time a read block is received by the processor. Use this
data to monitor the state of the module at a "real-time rate".
Refer to
stored in this object.
Module Status Data Table (page 65) for a complete listing of the data
Backplane Object
Page 24 of 78 ProSoft Technology, Inc.
April 17, 2008
Loading...
+ 54 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.