13. PARTS LIST······················································39
14. OPTIONAL PARTS ···········································43
E3E3
Refer to the Service Manual OB227 REVISED EDITION-B when MCFH-13NV-
E1
with MXZ-32RV-
as multi system units.
E3
is connected
Page 2
1
TECHNICAL CHANGES
MCFH-13NV -→MCFH-13NV -
1. Indoor model name has changed.
2. MCFH-13NV-became possible to connect with MXZ-32RV-as multi system units.
MUCFH-13NV -→MUCFH-13NV -
1. Outdoor model has changed.
2
PART NAMES AND FUNCTIONS
E3E2
E1E3
E3E2
MCFH-13NV -
E3
INDOOR UNIT
(When installed on the floor)
Operation section
(When the air inlet grille is opened.)
Vertical vanes
Horizontal vane
Operation indicator lamp
Receiving section
Front panel
Air cleaning filter (white bellows type)(option)
Air inlet
Air filter
Deodorizing filter (gray sponge type)(option)
Remote controller
Emergency operation switch
(When installed on the ceiling)
2
Page 3
RESET
CLOCK
g
Signal transmitting section
Operation display section
OPERATE/STOP
(ON/OFF)button
OPERATION SELECT button
FAN SPEED CONTROL button
ON-TIMER button
CLOCK SET button
HR. button
MIN. button
(TIMER SET button)
TEMPERATURE buttons
VANE CONTROL button
SWING button
OFF-TIMER button
RESET button
MUCFH-13NV -
OUTDOOR UNIT
E3
Air inlet
(back and side)
Piping
Drain hose
Air outlet
Drain outlet
MCFH-13NV -
E3
REMOTE CONTROLLER
3
Page 4
Model
Function
Power supply
Capacity
Dehumidification
Air flow
Power outlet
Running current
Power input
Auxiliary heater
Power factor
Starting current
Compressor motor current
Fan motor current
kW
R/h
K/h
A
A
W
A(kW)
%
A
A
A
W
"
"
"
mm
mm
mm
mm
mm
mm
kg
kg
dB
dB
rpm
rpm
kg
cc
k"
k"
k"
Capacity
Electrical
data
Coefficient of performance(C.O.P)
Compressor
Indoor
fan motor
Outdoor
fan motor
Dimensions
Indoor unit
Indoor unit
Width
Height
Depth
Width
Height
Depth
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
RT11(at 25:)
RT12(at 25:)
RT61(at 0:)
Sound level
(Hi)
Fan speed
(Hi)
Fan speed
regulator
5m regardless of which unit,
indoor or outdoor position is high.
ADDITIONAL REFRIGERANT CHARGE (R-22 : g)
MCFH-13NV - E3
Model
Outdoor unit precharged
1,350
A: Refrigerant piping
Max.length
15m(49ft)
7m
0
8
5m(16ft)
Max. Height difference
✽
Refrigerant piping length (one way)
50
9m
100
8m
10m
150
11m
200
Liquid
[6.35(1/4)
350
15m
400
14m
250
13m
300
12m
Calculation : Xg=50g/mx(A-7)m
Page 9
8
Air in
Air out
Wet-and dry-bulb
thermometers
FRONT VIEW
Wet-and dry-bulb
thermometers
BACK VIEW
PERFORMANCE CURVES
MCFH-13NV -
E3
The standard data contained in these specifications apply only to the operation of the air conditioner under normal condition,
since operating conditions vary according to the areas where these units are installed. The following information has been
provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
Rated voltage : ±10% (198~264V), 50Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
COOLING
(1) Indoor intake air wet-bulb temperature : ˚CWB
(2) Indoor outlet air wet-bulb temperature : ˚CWB
(3) Outdoor intake air dry-bulb temperature : ˚CDB
(4) Total input : W
HEATING
(1) Indoor intake air dry-bulb temperature : ˚CDB
(2) Indoor outlet air dry-bulb temperature : ˚CDB
(3) Outdoor intake air wet-bulb temperature : ˚CWB
(4) Total input : W
Indoor air wet/dry-bulb temperature difference on the left side of the chart on this page shows the difference between the
indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at
service.
How to measure the indoor air wet-bulb/dry-bulb temperature difference
1. Attach at least 2 sets of wet-and-dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of
wet-and-dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed
is high.
2. Attach at least 2 sets of wet-and-dry-bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of the room.
5. Press the EMERGENCY OPERATION switch once(twice) to start the EMERGENCY COOL(HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
INDOOR UNIT
9.3
8.6
7.8
7.1
6.3
5.6
MCFH-13NV- E3
20.1
18.6
17.0
15.5
13.9
12.4
10.8
9.3
OUTDOOR UNIT
MCFH-13NV- E3
9
Page 10
OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
1832
506070 (%)
Ambient temperature (:) / Ambient humidity (%)
Outdoor low pressure
506070 (%)
Ambient temperature (:) / Ambient humidity (%)
Outdoor unit current (A)
Ambient temperature (:)
Outdoor unit current (A)
HEAT operation
Condition Indoor : Dry bulb temerature 20.0:
Wet bulb temerature 14.5:
Outdoor : Dry bulb temerature 7,15,20:
Wet bulb temerature 6,12,14.5:
(MPa•G)
(kgf/F• G)
15202530 35(:)
0.3
0.4
0.5
0.6
0.7
0.8
15202530 35(:)
3
4
5
6
7
8
5 7 101520 25(:)
3
4
5
6
7
8
220-240V220-240V
240V
220V
1832
7
8
5
6
4
3
COOL operation
1 Both indoor and outdoor units are under the same temperature/humidity condition.
Dry Bulb temperature (˚C)
20
25
30
2 Air flow should be set at MAX.
3 The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The conversion factor is : 1(MPa • G) =10.2(kgf/ff• G)
Difference
between set
temperatuer
and room
temperature
This shows that the air
conditioner is operating
to reach the target temperature.
Please wait until the
target temperature is
obtained.
This shows that the
room temperature is
approaching the target
temperature.
lighting
not lighting
Approx. 2 :
or more
Approx. 2 :
or less
Operation Indicator
OPERATION INDICATOR
lamp
The operation indicator at the right side of the indoor
unit indicates the operation state.
MICROPROCESSOR CONTROL
WIRELESS REMOTE CONTROLLER
MCFH-13NV -
E3
Once the operation mode are set, the same operation mode
can be repeated by simply turning the
OPERATE/STOP(ON/OFF) button ON.
Indoor unit receives the signal with a beep tone.
When the system turns off, 3-minute time delay will operate
to protect system from overload and compressor will not
restart for 3 minutes.
9-1. “I FEEL CONTROL” () OPERATION
(1) Press OPERATE/STOP(ON/OFF) button on the
remote controller. OPERATION INDICATOR lamp of
the indoor unit turns on with a beep tone.
(2) Select “I FEEL CONTROL”
OPERATION SELECT button.
(3) The operation mode is determined by the room
temperature at start-up of the operation.
Initial room temperature
25: or more
23:to 25:
less than 23:
() mode with the
Mode
COOL mode of
"I FEEL CONTROL"
DRY mode of
"I FEEL CONTROL"
HEAT mode of
"I FEEL CONTROL"
INDOOR UNIT DISPLAY SECTION
● Once the mode is fixed, the mode does not change by
room temperature afterwards.
● Under the ON-TIMER () operation, mode is
determined according to the room temperature at set
time the operation starts.
● When the system is stopped with the
OPERATE/ STOP(ON/OFF) button on the remote
controller, and restarted within 2 hours in “I FEEL
CONTROL”
() mode, the system operates in
previous mode automatically regardless of the room
temperature.
Example
Previous operation
COOL mode of
“I FEEL CONTROL”
Restart
COOL mode of
“I FEEL CONTROL”
or COOL mode
When the system is restarted after 2 hours and more,
the operation mode is determined by the room
temperature at start-up of the operation.
Example
Previous operation
COOL mode of
“I FEEL CONTROL”
or COOL mode
Restart
COOL or DRY or
HEAT mode of “I
FEEL CONTROL” that
is determined by room
temperature at start-up
of the operation.
16
Page 17
(4) The initial set temperature is decided by the initial room temperature.
Model
COOL mode of
"I FEEL CONTROL"
Initial room temperatureInitial set temperature
26: or more
25: to 26:
Initial room temperature
24:
minus 2:
DRY mode of
"I FEEL CONTROL"
HEAT mode of
"I FEEL CONTROL"
23: to 25:
less than 23:
Initial room temperature
minus 2:
26:
❈1 When the system is restarted with the remote controller, the system operates with the previous set temperature
regardless of room temperature at restart.
The set temperature is calculated by the previous set temperature.
(5) TEMPERATURE buttons
In “I FEEL CONTROL” mode, set temperature is decided by the microprocessor based on the room temperature.
In addition, set temperature can be controlled by or TOO WARM or TOO COOL buttons when you feel too warm or too
cool. Each time the TOO WARM or TOO COOL button is pressed, the indoor unit receives the signal and emits a beep
tone.
● Fuzzy control
When the TOO COOL or TOO WARM button is pressed, the microprocessor changes the set temperature,
considering the room temperature, the frequency of pressing TOO COOL or TOO WARM button, and the user’s
preference to heat or cool. So this is called “Fuzzy control”, and works only in “I FEEL CONTROL” mode.
In DRY mode of “I FEEL CONTROL”, the set temperature doesn’t change.
❈1
▲TOO
COOL… To raise the set temperature 1~2 degrees(°C)
▼ TOO
WARM … To lower the set temperature 1~2 degrees(°C)
— COOL mode of “I FEEL CONTROL” —
1. Indoor fan speed control
Indoor fan operates at the set speed by FAN SPEED CONTROL button.
In AUTO the fan speed is as follows.
Initial temperature difference Fan Speed
Room temperature minus set temperature : 2 degrees or more
Room temperature minus set temperature : Between 1 and 2 degrees
Room temperature minus set temperature : less than 1 degree
········································Hi
·····························Me
········································
Lo
2. Coil frost prevention
① Temperature control
When the indoor coil thermistor RT12 reads -1°C or below, the coil frost prevention mode starts immediately.
However, the coil frost prevention doesn’t work for 5 minutes since the compressor has started.
The indoor fan operates at the set speed and the compressor stops for 5 minutes.
After that, if RT12 still reads below -1°C, this mode prolonged until the RT12 reads over -1°C.
Difference between room
temperature and set temperature
during operation.
1deg. 1.7deg.
2deg. 4deg.
17
Page 18
Compressor
Outdoor fan
Indoor fan
ON
OFF
(continuously at set speed)
OFF
ON
ON
② Time control
When the three conditions as follows have been satisfied for 1 hour and 45 minutes, compressor stops for 3 minutes.
a. Compressor has been continuously operating.
b. Indoor fan speed is Lo or Me.
c. Room temperature is below 26°C.
When compressor stops, the accumulated time is cancelled and when compressor restarts, time counting starts from
the beginning.
Time counting also stops temporarily when the indoor fan speed becomes Hi or the room temperature exceeds 26°C.
However, when two of the above conditions (b. and c.) are satisfied again, Time accumulation is resumed.
Operation chart
Example
—DRY mode of “I FEEL CONTROL”—
The system for dry operation uses the same refrigerant circuit as the cooling circuit.
The compressor and the indoor fan are controlled by the room temperature.
By such controls, indoor air flow amounts will be reduced in order to lower humidity without much room temperature
decrease.
1. Indoor fan speed control
Indoor fan operates at the set speed by FAN SPEED CONTROL button.
However, in AUTO fan operation, fan speed becomes Lo.
2. The operation of the compressor and indoor/ outdoor fan
Compressor operates by temperature control and time control.
Set temperature is controlled to fall 2°C from initial room temperature.
Indoor fan and outdoor fan operate in the same cycle as the compressor.
• When the room temperature is 23°C or over:
When the thermostat is ON, the compressor repeats 8 minutes ON and 3 minutes OFF.
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
• When the room temperature is under 23°C.
When the thermostat is ON, the compressor repeats 2 minutes ON and 3 minutes OFF.
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
Operation time chart
Example
Thermostat
Indoor fan
Outdoor fan
Compressor
3. Coil frost prevention
• The operation is as same as coil frost prevention during COOL mode of “I FEEL CONTROL”.
• Indoor fan operates at the set speed and the compressor stops for 5 minutes, because protection (Coil frost
prevention) has the priority.
However, when coil frost prevention works while the compressor is not operating, it’s speed becomes Lo.
OFF
OFF
OFF
8 min.
ON
ON
ON
OFF
OFF
ON
ON
3 min.
OFF
OFF
4 min.
18
OFF
ON
ON
1 min.
ON
Page 19
— HEAT mode of “I FEEL CONTROL” —
Difference between room
temperature and set temperature
during operation.
1deg. 1.7deg.
2deg. 4deg.
Released
Cold Air Prevention
18: 22:
Fan speed
Set speed
VLo or stop
High pressure protection
Released
48:52:
ON
Outdoor fan
OFF
1. Indoor fan speed control
(1) In AUTO the fan speed is as follows.
Set temperature minus room temperature: 2 degrees or more·······························Hi
Set temperature minus room temperature: Between 1 and 2 degrees···················Me
Set temperature minus room temperature: less than 1 degree ······························Lo
(2) Cold air prevention control
The fan runs at set speed when the indoor coil thermistor RT12 temperature exceeds 22°C. The fan operates at VLo
when the temperature of indoor coil thermistor RT12 is below 18°C. But the fan stops when the indoor fan operates at
VLo and the room temperature is 15°C or less.
NOTE : If the temperature of RT12 reads from 18°C to 22°C at the air conditioner starting and also after defrosting, this
control works.
(3) Warm air control
When compressor starts in heating operation or after defrosting, the fan changes the speed due to the indoor coil
thermistor RT12 temperature to blow out warm air.
After releasing of cold air prevention, when the indoor coil temperature is 37°C or above, the fan speed shifts to the set
speed, and when the fan speed is changed by the remote controller, the fan speed is the set speed.
When the indoor coil temperature is less than 37°C, the fan speed is controlled by time as below.
<Time condition> <Indoor fan speed>
less than 2 minutes························Lo
2 minutes to 4 minutes···················Me
4 minutes or more··························Hi
The upper limit of the fan speed is the set speed.
If the thermostat turns off, this operation changes to flow soft control.
(4) Flow soft control
After the thermostat turns off, the indoor fan operates at VLo.
NOTE : When the thermostat turns on, the fan operates at the set speed. Due to the cold air prevention control, the fan
does not start at set speed until the indoor coil thermistor RT12 reads 22°C or more.
Initial temperature differenceFan speed
2. High pressure protection
During heating operation, the outdoor fan motor is controlled by the temperature of indoor coil thermistor RT12 temperature
for excess rise protection of compressor discharge pressure.
Outdoor fan OFF : 52°C
Outdoor fan ON : 48°C
High pressure protection chart
Example
Indoor coil thermistor
RT12 temperature
NOTE1 : When the outdoor fan is OFF in heating, defrosting of outdoor heat exchanger is not detected by the defrost
NOTE2 : When connected to MXZ-32RV- outdoor unit, the indoor unit sends the data for the temperature to the outdoor
52˚C
48˚C
ONON
Outdoor fan motor
OFF
OFF
thermistor RT61.
E1
unit according to the indoor coil temperature.
For the further information, refer to the service manual OB227 REVISED EDITION-B.
19
Outdoor fan motor
turn OFF
Outdoor fan motor
turn ON
Page 20
3. Defrosting
Defrosting of outdoor heat exchanger is controlled by DEICER P.C. board, with detection by the defrost thermistor RT61.
(1) Starting conditions of defrost
When all conditions of a) ~ c) are satisfied, the defrosting operation starts.
a) The compressor cumulative operation time exceeds 40 minutes without the defrosting operation working.
b) The defrost thermistor RT61 reads - 3°C or less.
c) After releasing the high pressure protection 4 minutes and 15 seconds have elapsed.
(2) Releasing conditions of defrost
When the condition d) or e) is satisfied, the defrosting operation stops.
d) The defrost thermistor RT61 reads 3°C or more.
e) The defrosting time exceeds 10 minutes.
(3) Defrosting time chart
Defrost thermistor RT61
3: or more
-3: or less
Outdoor 52C contactor
(Compressor)
ON
OFF
X62
(Reversing valve.coil)
ON
15 sec.
30 sec.
OFF
30 sec.
5 sec.
SR61
Outdoor fan
ON
OFF
Defrost
counter
Indoor fan
ON
OFF
ON
Max 10 min.
NOTE1
VLo
OFF
Indoor vane
Position 1
Set
Position
NOTE1 : When the indoor coil thermistor reads above 18°C, indoor fan operates at VLo for 30 seconds.
When the indoor coil thermistor reads 18°C or less, the indoor fan stops.
NOTE2 : Refer to the Service Manual OB227 REVISED EDITION-B when MCFH-13NV-is connected with MXZ-32RV-
as multi system units.
E1E3
20
Page 21
4. Reversing valve control
35
30
25
20
15
10
:
10 15 20 25 30 35
Set temperature
Initial room temperature
Set temperature and
initial room temperature in DRY mode
:
Heating · · · · · ON
Cooling · · · · · OFF
Dry · · · · · · · · OFF
NOTE1 : The reversing valve reverses for 5 seconds right before start-up of the compressor.
NOTE2 : Refer to the Service Manual OB227 REVISED EDITION-B when MCFH-13NV-is connected with MXZ-32RV-
as multi system units.
E1E3
Compressor
Reversing valve
Outdoor fan
9-2. COOL () OPERATION
(1) Press OPERATE/STOP(ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a
beep tone.
(2) Select COOL mode with the OPERATION SELECT button.
(3) Press the TEMPERATURE buttons
(TOO WARM or TOO COOL button)
to select the desired temperature.
The setting range is 16 ~ 31°C
w Indoor fan continues to operate regardless of thermostat’s OFF-
ON at set speed.
w Coil frost prevention is as same as COOL mode of “I FEEL
CONTROL”.
9-3. DRY () OPERATION
(1) Press OPERATE/STOP(ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a
beep tone.
(2) Select DRY mode with the OPERATION SELECT button.
(3) The microprocessor reads the room temperature and determines
the set temperature. Set temperature is as shown on the right
chart.
Thermostat (SET TEMP.) does not work.
The other operations are as same as DRY mode of “I FEEL
CONTROL”.
(4) DRY operation will not function when the room temperature is 13°C or below.
(5) When DRY operation functions, the fan speed is lower than cool operation.
9-4. HEAT () OPERATION
(1) Press OPERATE/STOP(ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select HEAT mode with the OPERATION SELECT button.
(3) Press TEMPERATURE buttons (TOO WARM or TOO COOL button) to select the desired temperature.
The setting range is 16 ~ 31°C.
(4) Indoor fan speed control, high pressure protection, defrosting, reversing valve control are the same as HEAT mode of “I
FEEL CONTROL”.
ON
OFF
ON
OFF
ON
OFF
(COOL / DRY)
5 sec.
(HEAT)
5 sec.
ON
OFF
ON
OFF
ON
OFF
21
Page 22
9-5. AUTO VANE OPERATION
1
2
3
4
5
AUTO
4
1
1
2
3
4
5
(1) Vane motor drive
This model is equipped with a stepping motor for the vane. The rotating direction, speed, and angle of the motor are
controlled by pulse signals (approx. 12V) transmitted from indoor microprocessor.
(2) Each time the VANE CONTROL button is pressed, angle of horizontal vane is changed in sequence, from 1, 2, 3, 4, 5
to AUTO.
(3) Positioning
The vane is once pressed to the vane stopper below to confirm the standard position and then set to the desired angle.
Confirming of standard position is performed in case of follows.
(a) When the OPERATE/STOP(ON/OFF) button is pressed.
(b) When the vane control is changed from AUTO to MANUAL.
(c) When the SWING is finished.
(d) When the test run starts.
(e) When the power supply turns ON.
(4) VANE AUTO mode
In VANE AUTO mode, the microprocessor automatically determines the vane angle and operation to make the optimum
room-temperature distribution.
1. In COOL and DRY operation
Vane angle is fixed to position 1.
2. In HEAT operation
Vane angle is fixed to position 4.
(5) STOP (operation OFF) and ON-TIMER standby.
When the following cases occur, the vane returns to the closed position.
(a) When the OPERATE/STOP (ON/OFF) button is pressed (POWER OFF).
(b) When the operation is stopped by the emergency operation.
(c) When the ON-TIMER is on standby.
(6) Dew prevention
During COOL or DRY operation at position 4 or 5 when the compressor cumulative operation time exceeds 1 hour, the
angle of horizontal vane automatically changes to Position 1 for dew prevention.
(7) SWING () MODE
By pressing the SWING () button, horizontal vane swings vertically between Position 1 and 5 in COOL and DRY
operation, between Position 2 and 4 in HEAT operation. The remote controller displays “”. If the VANE CONTROL(
) button or SWING () button is pressed during SWING mode or the operation stops or changes to other mode,
SWING mode is released.
22
Page 23
(8) Cold air prevention in HEAT operation.
Released
Cold Air Prevention
24:28:
Position 1
Horizontal vane
Set position
When any of the following conditions occurs in HEAT operation, the angle of horizontal vane automatically changes to
Position 1 to prevent cold air blowing on users.
1 Compressor is not operating.
2 Defrosting is performed.
3 Indoor coil thermistor RT12 reads 24: or below.
4 Indoor coil thermistor RT12 temperature is raising from 24: or below, but it does not exceed 28:.
Indoor coil thermistor RT12 temperature
NOTE : If the temperature of RT12 reads from 24: to 28: at the air conditioner starting, this control works.
9-6. TIMER OPERATION
1. How to set the timer
(1) Press OPERATE/STOP(ON/OFF) button to start the air conditioner.
(2) Check that the current time is set correctly.
NOTE : Timer operation will not work without setting the current time. Initially “AM0:00” blinks at the current time display of
TIME MONITOR, so set the current time correctly with CLOCK SET button.
(3) Press ON-TIMER, OFF-TIMER button to select the operation.
“” button ... AUTO START operation (ON timer)
“” button ... AUTO STOP operation (OFF timer)
(4) Press HR. and MIN. button to set the timer. Time setting is 10-minute units.
HR. and MIN. button will work when “” or “” button is flashing.
These marks disappear in 1 minute.
After setting the ON timer, check that OPERATION INDICATOR lamp of the indoor unit lights.
NOTE1 : Be sure to place the remote controller at the position where its signal can reach the air conditioner even during
TIMER operation, or the set time may deviate within the range of about 10 minutes.
NOTE2 : Reset the timer in the following cases, or the set time may deviate and other malfunctions may occur.
● A power failure occurs.
● The circuit breaker functions.
2. Cancel
TIMER setting can be cancelled with the TIMER CONTROL buttons. (“” or “”)
To cancel the ON timer, press the “” button.
To cancel the OFF timer, press the “” button.
TIMER is cancelled and the display of set time disappears.
PROGRAM TIMER
●The OFF timer and ON timer can be used in combination.
● “➝” and “” display show the order of the OFF timer and ON timer operation.
(Example 1) The current timer is 8:00 PM.
➝
The unit turns off at 11:00 PM, and on at 6:00 AM.
(Example 2) The current time is 11:00 AM.
The unit turns on at 5:00 PM, and off at 9:00 PM.
23
Page 24
9-7. EMERGENCY-TEST OPERATION
When the remote controller is missing, has failed or the batteries run down, press the EMERGENCY OPERATION
switch on the front of the indoor unit. The unit will start and the OPERATION INDICATOR lamp will light.
The first 30 minutes of operation is the test run operation. This operation is for servicing. The indoor fan runs at high
notch and the system is in continuous operation. (The thermostat is ON)
After 30 minutes of test run operation the system shifts to EMERGENCY COOL or HEAT MODE with a set temperature
of 24˚C. The fan shifts to Me notch.
This operation continues until the EMERGENCY OPERATION switch is pressed again or the unit receives any signal
from the remote controller. In case of latter normal operation will start.
The coil frost prevention works even in this operation, and defrosting too.
In the test run or emergency operation, the horizontal vane operates in AUTO mode.
NOTE : Do not press the EMERGENCY OPERATION switch during normal operation.
EMERGENCY
OPERATION switch
Press once <Cool>
Press again <Heat>
Press once again <Stop>
OPERATION INDICATOR lamp
9-8. AUTO RESTART FUNCTION
When the indoor unit is controlled with the remote controller, the operation mode, set temperature, and the fan speed
are memorized by the the auto restart P.C. board.
The “AUTO RESTART FUNCTION” sets to work the moment the power has restored after power failure. Then, the unit
will restart automatically. However if the unit is operated in “I FEEL CONTROL” mode before power failure, the operation
is not memorized. In “I FEEL CONTROL mode”, the operation is decided by the initial room temperature.
NOTE :
•The operation settings are memorized when 10 seconds have passed after the remote controller was operated.
•If the main power is turned off or a power failure occurs while AUTO START/ STOP timer is active, the timer setting is
cancelled.
•If the unit has been off with the remote controller before power failure, the auto restart function does not work as the
power button of the remote controller is off.
•To prevent breaker off due to the rush of starting current, systematize other home appliances not to turn on at the same
time.
•When some air conditioners are connected to the same supply system, if they are operated before power failure, the
starting current of all the compressors may flow simultaneously at restart.
Therefore, the special counter-measures are required to prevent the main voltage-drop or the rush of the starting current
by adding to the system that allows the units to start one by one.
24
Page 25
10
Jumper wire
JPC
JPE
Change point
Defrost interval time changes from 40 minutes to 15 minutes
Deforst start temperature changes from -3: to 0:
Deforst finish temperature changes from 3: to 10:.
SERVICE FUNCTIONS
MCFH-13NV -
E3
10-1. COMPULSORY DEFROSTING MODE FOR SERVICE
By short circuit of the connector JP607 and R853 on the outdoor deicer P.C. board, defrosting mode can be
accomplished regardless of the defrost interval restriction. See Page 34.
Defrost thermistor RT61 must read below -3:.
10-2. CHANGE IN DEFROST SETTING
<JPC> when the JPC wire of the deicer P.C. board is cut, the defrost interval time will be changed. (See page 34.)
<JPE> when the JPE wire of the deicer P.C. board is cut, the defrost temperature will be changed. (See page 34.)
10-3. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPG and JPS on the electronic control P.C. board.
The time will be shortened as follows.
3-minutes time delay : 3-minutes → 3-seconds
AUTO START : 1 hour → 1-minute
AUTO STOP : 1 hour → 1-minute
Short the connector during the timer mode.
}
10-4. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room. In this case, to operate each
indoor unit individually by each remote controller, P.C. boards of remote controller must be modified according to the
number of the indoor unit.
How to modify the remote controller P.C. board
Remove batteries before modification.
The board has a print as shown below;
“J1” and “J2” Jumper wires
NOTE : For remodelling, take out the
batteries at first.
After finish remodelling, put back
the batteries then push the RESET
button.
The P.C. board has the print “J1” and “J2”. Jumper wires are mounted to each “J1” and “J2”. Cut J1 and J2
according to the number of indoor unit as shown in Table 1.
After modification, push the RESET button.
Table1.
No.1 unit
No.2 unit
No.3 unit
1 unit operation
No modification
2 units operation
Same as at left
Cut J1
3 units operation
Same as at left
Same as at left
Cut J2
No.4 unit
4 units operation
Same as at left
Same as at left
Same as at left
Cut both J1 and J2
NOTE : At power supply failure or installation, indoor unit deletes the memory about remote controller. When the power
supply is turned on and indoor unit receives the first signals from the remote controller, the remote controller
number is designated as the indoor unit number. Therefore at and after the second time indoor unit accepts the
remote controller of the initial setting number.
At setting-error, turn the power supply off to cancel the individual operation and then turn the power supply on to
restart the setting.
10-5. RELEASE OF AUTO RESTART FUNCTION
The jumper line is soldered with “JHA (Refer to page 33.)” on the indoor electronic P.C. board.
Remove the auto restart P.C. board from “Connector CN104”.
25
Page 26
11
RTESET button
TROUBLESHOOTING
MCFH-13NV -
E3
11-1. Cautions on troubleshooting
1. Before troubleshooting, check the following:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care the following during servicing.
1) Before servicing the air conditioner, be sure to first turn off the remote controller to stop the main unit, and then after
confirming the horizontal vane is closed, turn off the breaker.
2) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the
components.
3) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
3. Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.
To make sure, check how many times the abnormality indication is flashing on and off before starting service work.
2) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and
the components for bursting and discoloration.
3) When troubleshooting, refer to the flow chart on page 27 and the check table on page 28.
4. How to replace batteries
Weak batteries may cause the remote controller malfunction.
In this case, the remote controller can not be repaired only by the battery replacement. To operate the remote controller
normally, replace the batteries in the following order.
This remote controller has the RESET button. After refilling new batteries, press the RESET button with tip end of ball
point pen or the like, and then use the remote controller.
NOTE: INFORMATION FOR MULTI SYSTEM AIR CONDITIONER (OUTDOOR UNIT : MXZ-32RV-)
Multi system air conditioner (Outdoor unit: MXZ-32RV-) can connect two or more indoor units with one outdoor unit.
According to the capacity, two or more units can operate simultaneously.
•When you try to operate two or more indoor units with one outdoor unit simultaneously, one for the cooling and the
other for heating, the operation mode of the indoor unit that operates earlier is selected. The other indoor units that
will start the operation later cannot operate, indicating as shown in the figure below. In this case, set all the indoor
units to the same operation mode.
Operation Indicator
E1
lighting
E1
flashing
•When indoor units starts the operation while the defrosting of outdoor unit is being done, it takes a few minutes
(max. 10 minutes) to blow out the warm air.
•In the heating operation, though indoor unit that does not operate may get warm or the sound of refrigerant flowing
may be heard, they are not malfunction. The reason is that the refrigerant continuously flows into it.
26
Page 27
11-2. Instruction of troubleshooting
Start
Indoor unit
operates. Outdoor
unit doesn’t
Outdoor unit
operates in
only Test
Run
operation.
Check room
temperature
thermistor.
When the remote controller
is pressed or when the
EMERGENCY OPERATION
switch is pressed, the fan
does not rotate with
OPERATION INDICATOR
Refer to “Check of indoor
fan motor” on page 30.
A
Outdoor unit
doesn’t
operate even
in Test Run
operation.
Refer to
“Check of
outdoor unit”
on page 31.
Indoor unit
doesn’t receive
the signal from
remote
controller.
Refer to
“Check of
receiver P.C.
board” on
page 30.
1-time flash
D
Cause:indoor/outdoor unit
Trouble of mis-wiring
(
Trouble of the serial signal
B
connecting
Refer to
“How to check miswiring and signal
error
(when outdoor unit
doesn’t work)”
on page 32.w1
E
OPERATION INDICATOR
lamp on the indoor unit is
flashing on and off.
2-time flash
2.5-second OFF
Cause:Indoor unit
2-time-Room
temperature/In
door coil
thermistor
trouble
Check indoor coil
thermistor. Refer to “Test
point diagram and
voltage” on page 33.
Indoor unit doesn’t
receive the signal from
remote controller.
Also, OPERATION
INDICATOR lamp doesn’t
flash, when the
EMERGENCY
OPERATION switch is
Refer to “Check of
indoor electronic control
P.C. board” on page 31.
6-time flash
Cause:outdoor unit
6-time-Replace the
Check room temperature
thermistor. Refer to “Test
point diagram and
voltage” on page 33.
C
2.5-second OFF
defrost thermistor
27
w1<The case of the trouble of the serial signal>
When the power is turned off and then turned
on again, the indication shows “the trouble
of mis-wiring”.
Page 28
1. troubleshooting check table
w Before taking measures, make sure that the symptom reappears, for accurate troubleshooting.
Self check table
Abnormal
NO.
point
Indication
Symptom
Detect method
Check point
Mis-wiring
1
Serial
signal
Indoor coil
thermistor
2
Room
temperatur
e
thermistor
Outdoor
power
3
system
❈
Defrost
4
thermistor
0.5-second ON
0.5-second OFF
1-time flash
2.5-second OFF
2-time flash
2.5-second OFF
5-time flash
6-time flash
2.5-second OFF
2.5-second OFF
Outdoor unit
does not run.
Outdoor unit
does not run.
Outdoor unit
does not run
Outdoor unit
does not run
When serial signal stops for 4
to 5 seconds after 1st on of
52C relay by POWER turning
on.
When serial signal from
outdoor unit stops for 4 to 5
seconds.
Detect Indoor coil/room
temperature thermistor short
or open circuit every 8
seconds during operation.
When compressor has
stopped due to over current
protection or start-up failure
protection 3 times in a row
within 1 min. after start-up.
When the defrost thermistor
shorts or opens after the
compressor start-up.
● Check switch SW2-2.(MU type or MUH
type)
● Check wiring (visual check and
conductivity check).
● Check indoor electronic control
P.C.board.
● Check outdoor DEICER P.C. board.
● Check electrical parts.
● Check resistance of thermistor.
● Reconnect connector.
● Check indoor electronic control P.C.board.
● Check inverter and compressor.
● Check outdoor DEICER P.C. board.(MUH)
● Check outdoor control P.C. board. (MXZ)
● Check resistance of thermistor.
● Reconnect connector.
Out door
control
system
5
error
❈
Out door
refrigeran
t
6
system
error
❈
❈Those indications are shown only when the indoor unit connects with the outdoor unit MXZ-32RV-.
7-time flash
10-time flash
2.5-second OFF
2.5-second OFF
Outdoor unit
does not run
Outdoor unit
does not run
When the compressor
operation has been
interrupted by LEV protection
continuously 5 times, the
compressor stops operation.
● Check outdoor control P.C. board.
● Amount of gas.
● Outdoor control P. C. board.
● Contact of LEV board connectors.
E1
28
Page 29
2. Trouble criterion of main parts
C
S
R
BLK
RED
WHT
P
BLK
RED
ORN
YLW
BLU
BRN
WHT
GRN
YLW
P
BLK
RED
WHT
MAIN
AUX
P
BRN
YLW
PNK
RED
ORN
BLU
ROTOR
MCFH-13NV -
E3
Part name
Room
temperature
thermistor
Measure the resistance with a tester.
(Part temperature 10°C ~ 30°C)
Indoor coil
thermistor
Measure the resistance with a tester.
Defrost
(Part temperature -10°C ~ 40°C)
thermistor
Measure the resistance between the terminals with a tester.
(Coil wiring temperature -10°C ~ 40°C)
Check method and criterion
Normal
8kΩ ~ 20kΩ
Normal
5kΩ ~ 60kΩ
Figure
Abnormal
Opened or short-circuited
Abnormal
Opened or short-circuited
Compressor
Indoor fan
motor
Outdoor fan
motor
Normal
C-R
C-S
1.86~2.28Ω
3.50~4.29Ω
Opened or
short-circuited
Measure the resistance between the terminals with a tester.
(Coil wiring temperature10°C ~ 30°C)
Measure the resistance between the terminals with a tester.
(Coil wiring temperature -10°C ~ 40°C)
Normal
Abnormal
Abnormal
WHT-BLK
BLK-RED
155 ~ 191Ω
363 ~ 445Ω
Opened or
short-circuited
Measure the resistance between the terminals with a tester.
(Part temperature10°C ~ 30°C)
Vane
motor
Resistant per phase
NormalAbnormal
329~357Ω
Opened or
short-circuited
29
: INNER THERMOSTAT
P
Page 30
A
● Re-install the unit away from lights.
● Attach a filter on receiving part.
Switch on the remote controller.
Is LCD display on the remote
controller visible?
Replace the batteries.(see page 26.)
Remove the batteries and then set them back.
Check if the unit operates with the remote controller.
Does the unit operate with remote controller?
Turn on a radio to AM and press
switch on remote controller.
Is noise heard from radio?
Replace the remote controller.
Are there any fluorescent lights
of inverter or rapid-start type
within the range of 1m?
Turn ON the power supply.
Measure the voltage between receiver P.C. board connector No.2(+) and No.1 when the remote controller button is pressed.
Is the voltage approx. 4V DC?
No
(5V DC or 0V DC)
Replace the receiver P.C. board.
No
(not clear)
Yes
Yes
No
OK
No
Yes
Yes
Yes
No
Replace the indoor electronic control P.C. board.
Replace the auto restart P.C. board.
Yes
Disconnect AUTO RESTART P.C. board from CN104
and short CN104 1 to 5.
Does the unit receive the signal
from the remote controller?
No
Check of indoor fan motor
Indoor fan does not operate.
Turn OFF the power supply.
Check connector (Fan motor) visually.
No
Reconnect the lead wires.
Check of remote controller and receiver P.C. board
B
Are lead wires connected?
Disconnect lead wires from connector (Fan motor) on indoor electronic control P.C. board.
Measure resistance between lead wires No.1 and No.4 and then No.3 and No.4 of the fan motor.
Yes
Is resistance 0 (short circuit) or ∞ (open circuit)?
Repair the indoor fan motor.
Yes ( 0 or ∞ )
Is soldered point normal?
Yes
Replace the indoor electronic control
P.C. board.
No
(others)
No
Resolder it.
Indoor unit operates by pressing the EMERGENCY OPERATION switch, but does not operate with the remote
controller.
WCheck if the remote controller is exclusive for this air conditioner.
30
Page 31
Check of indoor electronic control P.C. board
C
The unit doesn’t operate with the remote controller.
Also, the OPERATION INDICATOR lamp doesn’t light up by pressing the EMERGENCY OPERATION switch.
Replace the fuse.
Is fuse(F11)blown?
Check both “parts side” and “pattern
side” of indoor electronic control P.C.
board visually.
Check of outdoor unit
D
Be sure to check both fuse
and varistor in any case.
Is varistor(NR11)burnt?
Replace the varistor.
Compressor and outdoor fan do not operate.
Yes
No
Replace the indoor electronic
control P.C. board.
No
Yes
Start
Check the outdoor DEICER P.C. board and the
compressor contactor at first, then check the
outdoor fan motor and compressor.
Check the continuity of indoor and outdoor unit
connection.
Press the EMERGENCY
OPERATION switch. 3-minute time
delay works. Test run operation
operates for 30 minutes.
Yes
Yes
Check the indoor electronic control P.C.board.
Check the voltage to the
terminal block of outdoor
unit. Is there 220-240V
AC to the terminal block
between 2 - N ?
No
Check the voltage to the
terminal block of indoor
unit. Is there 220-240V
AC to the terminal block
between 2 - N ?
No
31
Page 32
How to check mis-wiring and serial signal error (when outdoor unit does not work)
E
Start
3 min. later, when 52C contactor turns ON, what self-check result
is displayed on OPERATION INDICATOR lamp indoor unit? ❈1
Repair wiring.
Is there 20V DC between both ends of R132 when
52C contactor turns ON?
(By tester, the stylus is between 0 ~ 20V.)
1. Turn OFF the power supply.
2. Reconnect in-out connecting wire.
3. Turn ON the power supply.
Yes
1. Turn OFF the power supply and disconnect in-out connecting wire on the indoor side.
2. Short-circuit between indoor terminal block and .
3. Turn ON the power supply and press the EMERGENCY OPERATION switch.
Yes
1. Turn OFF the power supply.
2. Turn ON the power supply.
3. Press the EMERGENCY OPERATION switch.
Mis-wiring is indicated.(1-sec.ON,1-sec.OFF)
Is there mis-wiring, poor contact, or wire disconnection?
No
N
3
No
❈1 Short circuit of JPG and JPS on the
indoor electronic control P.C. board
enables self-check to be displayed in 3
seconds.
Serial signal error is indicated.
(1-sec.ON, 2.5-sec.OFF)
Replace the indoor electronic control
P.C. board.
3 minutes later, when the EMERGENCY OPERATION switch is
pressed and 52C contactor turns ON, is there 220-240V AC between
the outdoor terminal block 2 and N ? ❈2
Yes
Is there 5V DC between J9 -J8 on the outdoor DEICER P.C.
board? ❈2
Is there 10V DC between both ends of R601? ❈2
(By tester, the stylus is between 5 ~10V)
Replace the outdoor DEICER P.C. board.
+
Yes
Yes
–
No
No
No
Rectify in-out connecting wire.
Check and rectify the fuse and varistor on
the outdoor DEICER P.C. board.
Rectify in-out connecting wire.
❈2 While the serial signal error is indicated,
52C contactor alternates ON for about 10
seconds and OFF for 3 minutes.
Measure the voltage when 52C contactor
is ON.
32
Page 33
DE00R697B
To the indoor
electronic control
P.C.board CN113
Indoor coil thermistor (RT12)
Room temperature thermistor (RT11)
RT11
EMERGENCY OPERATION switch
TH113
CH313
GILMS
12
0
0
10
20
30
40
10 20 30 40 50 60
Temperature ( C)
Resistance (K')
TEST POINT DIAGRAM AND VOLTAGE
MCFH-13NV -
Indoor electronic control P.C. board
Fan motor power supply 220-240V AC
E3
VLoMe
LoHi
75643218
Fuse 250V AC 3.15A
Power supply
input 220-240V AC
+
12V DC
}
–
+
5V DC
–
}
JHA(Release of AUTO RESTART
FUNCTION. Refer to page 25.)
Room temperature
thermistor(RT11)
Time short point
Indoor coil thermistor (RT12)
33
Page 34
MUCFH-13NV -
Outdoor deicer P.C. board
Outdoor fan motor
220-240V AC
}
E3
Solenoid coil
220-240V AC
}
R601
5~10V DC
}
+
INPUT
220-240V AC
}
Defrost thermistor(RT61)
}
}
12V DC
Fuse 2A/250V
Defrost interval
time short pin
Test point
+
J9
5V DC
}
J8
+
+
}
52C
12V DC
Jumper wire for change in
defrost setting (JPC, JPE)
(Refer to page 25.)
34
Page 35
DISASSEMBLY INSTRUCTIONS12
<"Terminal with lock mechanism" Detaching points>
In case of terminal with lock mechanism, detach the terminal as shown below.
There are two types ( Refer to (1) and (2)) of the terminal with lock mechanism.
The terminal with no lock mechanism can be removed by pulling it out.
Check the shape of the terminal and work.
(1) Slide the sleeve and check if there is a locking lever or not.
Sleeve
1Slide the sleeve.
2Pull the terminal while
Locking lever
12-1. MCFH-13NV -
E3
pushing the locking
lever.
INDOOR UNIT
OPERATING PROCEDUREPHOTOS
1. Removing the electronic control P.C . board.
(1) Pull out the upper part of the grill. (Photo 1)
(2) Remove the screws of the grill.
(3) Remove screws of terminal block cover.
Remove the terminal block cover and remove the terminal
block.
(4) Remove the screws of the electronic box cover.
(5) Pull out the electronic control P.C. board.
Photo 3
(2) The terminal with this connector is a terminal
with lock mechanism
1Hold the sleeve, and
pull out the terminal
slowly.
Connector
Photo 1
2. Removing the indoor fan motor
(1) Remove the grill. ( Refer to 1(1) (2) )
(2) Remove the screws of the pipe support assembly.
(3) Remove the fan casing.(upper).
(4) Disconnect the connector of the indoor fan motor.
(5) Disconnect the ground wire of the fan motor.
(6) Remove the screws of the motor band and remove the
catch.
(7) Take out the sirocco fan and the indoor fan motor.
Photo 2
Photo 4
Fan casing
(upper)
Screws of the grill
Electronic box
Terminal box
Motor band
35
Indoor fan motor
Screws of the
motor band
Fan
casing(upper)
Page 36
OPERATING PROCEDUREPHOTOS
3. Removing the indoor heat exchanger.
(1) Remove the grill. (Refer to 1(1) (2))
(2) Remove the screws on both side and in front of the front
panel. (Photo 5)
(3) Remove the screws of the nozzle assembly. (Photo 6)
(4) Remove the electronic box. (Refer to 1)
(5) Remove the indoor fan motor. (Refer to 2)
(6) Remove the screws of the motor support.
(7) Remove the fan casing. (Iower)
(8) Remove the installations of the drain pan and remove the
screws. (Photo 7)
(9) Remove the screws under the drain pan.(Photo 8)
)
(
Remove the drain pan.
10
(11)
Remove the indoor heat exchanger.
Photo 5
Screws of
the front
panel
Photo 6
Screws of
the nozzle
assembly
Photo 7
Photo 8
Installations and screws
36
Screws under
the drain pan
Page 37
12-2. MUCFH-13NV -
OUTDOOR UNIT
OPERATING PROCEDUREPHOTOS
E3
1. Removing the cabinet
(1) Remove the screws of the top panel.
(2) Remove the screws of the service panel.
(3) Remove the screws of the cabinet.
(4) Remove the screws of the front panel and motor support.
(5) Remove the service panel, and remove the screw from
the insides.
(6) Remove the top panel.
(7) Remove the cabinet.
Photo 3
Screws of the
service panel
Screws of
the top panel
Service
panel
Photo 1
Screws
of the
cabinet
Photo 2
Screws of the front panel
and motor support
Screws of the cabinet
Screws of the
top panel
2. Removing the deicer P.C. board
(1) Remove the service panel and the cabinet.
(2) Disconnect all the connectors and the terminals on the
deicer P.C. board.
(3) Remove the deicer P.C. board.
Photo 4
Deicer
P.C. board
Screws of the
cabinet
Screws
37
Screw
Relay panel
Terminal
block
Page 38
OPERATING PROCEDUREPHOTOS
3. Removing the propeller fan and the outdoor fan
motor
(1) Remove the cabinet. (Refer to 1)
(2) Remove the propeller fan nut.
(3) Remove the propeller fan.
NOTE : Loose the propeller fan in the rotating direction for
removal.
When attaching the propeller fan, align the mark on the
propeller fan and the motor shaft cut section.
Set the propeller fan in position by using the cut on the
shaft and the mark on the propeller fan.
(4) Remove lead clamps and disconnect the outdoor fan motor
connector.
(5) Remove screws fixing the fan motor.
(6) Remove the outdoor fan motor.
Photo 5
Set screws of the
outdoor fan motor
Propeller fan
Propeller fan nut
Hook
Outdoor
fan motor
Lead clamps
Outdoor
fan motor
connector
4. Removing the compressor
(1) Remove the cabinet. (Refer to 1)
(2) Remove the relay panel.
(3) Remove the soundproof felt.
(4) Remove the terminal cover on the compressor.
(5) Disconnect lead wires from the glass terminal of the
compressor.
(6) Release gas from the refrigerant circuit.
(7) Disconnect the welded part of the discharge pipe.
(8) Disconnect the welded part of the suction pipe.
(9) Remove nuts fixing the compressor.
)
(
Remove the compressor.
10
NOTE
● Before using a burner, purge gas from the pipes until the
pressure gauge shows 0 kg/cm
● Use the burner under the condition that gas can be released
even when the inner pressure rises by heat.
FRONT PANEL(WH)
GRILLE(WH)
VANE(WH)
AIR FILTER
BACK PANEL(IN)
NOZZLE(WH)
FAN CASING(U)
FAN CASING(L)
INDOOR HERT EXCHANGER
DRAIN PAN
UNION(GAS)
UNION(LIQUID)
INSTALLATION METAL L
INSTALLATION METAL R
GRILLE CATCH(WH)
VANE MOTOR
{12.7
{6.35
3PCS/SET
1
1
1
2
1
1
2
2
1
1
1
1
1
1
3
1
MCFH-13NV-
E3 (WH)
MV
1718E02 257 426
E02 141 083
REMOTE CONTROLLER
REMOTE CONTROLLER HOLDER
1
1
MCFH-13NV -(WH)
E3
13-1. INDOOR UNIT
STRUCTURAL PARTS
3
16
13
1
4
2
95
6
UNION(LIQUID)
12
13-2. ACCESSORY P ART AND
REMOTE CONTROLLER
14
17
18
13-1. INDOOR UNIT STRUCTURAL PARTS
Part number that is circled is not shown in the illustration.
13-2. ACCESSORY P ART AND REMOTE CONTROLLER
10
UNION(LIQUID)
39
8711
Page 40
13-3. INDOOR UNIT
ELECTRICAL PARTS AND FUNCTIONAL PARTS
MCFH-13NV -(WH)
6
5
7
E3
1
10
9
4
2
3
Part numbers that are circled are not shown in the illustration.
No.Part No.
1
E02 228 300
2
E02 179 500
3
E02 179 505
E02 227 375
4
E02 257 375
5
E02 215 328
6
E02 327 450
7
E02 324 452
8
E02 127 382
9
E02 227 468
10
E02 327 307
11
E02 336 385
INDOOR FAN MOTOR
SIROCCO FAN
FAN MOTOR RUBBER MOUNT
TERMINAL BLOCK
TERMINAL BLOCK
SWITCH & ROOM TEMPERATURE
THERMISTOR P.C. BOARD
ELECTRONIC CONTROL P.C. BOARD
AUTO RESTART P.C. BOARD
FUSE
RECEIVER P.C. BOARD
INDOOR COIL THERMISTOR
VARISTOR
Part name
Symbol
in Wiring
Diagram
MF
TB
F11
RT12
NR11
Q'ty/unit
MCFH-13NV- E3 (WH)
1
2
2
1
1
1
1
1
1
1
1
1
Remarks
RB4V25-
2PCS/SET
FigureA
FigureB
3.15A
40
Page 41
13-4. OUTDOOR UNIT STRUCTURAL PARTS
MUCFH-13NV -
6
1
3
E3
2
11
413
Part number that is circled is not shown in the illustration.
No.Part No.
1
E02 336 232
2
E02 336 297
3
E02 336 521
4
E02 336 245
5
E02 141 900
6
E02 442 630
E02 156 936
7
E02 445 936
8
E02 139 662
9
E02 340 661
10
E02 340 290
11
E02 442 515
12
E02 075 506
13
E02 440 233
14
E02 444 961
CABINET
TOP PANEL
GRILLE(OUT)
SERVICE PANEL
COMPRESSOR
OUTDOOR HEAT EXCHANGER
CAPILLARY TUBE
CAPILLARY TUBE
STOP VALVE(LIQUID)
STOP VALVE(GAS)
BASE
MOTOR SUPPORT
COMPRESSOR RUBBER SET
BACK PANEL(OUT)
REVERSING VALVE
Part name
5
Symbol
in Wiring
Diagram
MC
10912
Q'ty/unit
MUCFH-13NV-
1
1
1
1
1
1
2
1
1
1
1
1
3
1
1
E3
8
14
Remarks
RH-231VHAT
{3.0X{1.4X500
{3.0X{1.8X200
{6.35
{12.7
3RUBBERS/SET
41
Page 42
MUCFH-13NV -
No.Part No.
Part name
Remarks
Symbol
in Wiring
Diagram
Q'ty/unit
MUCFH-13NV-
E3
RA6V3330+/440VAC
250V 2A
1
1
1
1
1
1
1
1
1
1
2
3
4
5
6
7
8
9
PROPELLER FAN
OUTDOOR FAN MOTOR
COMPRESSOR CAPACITOR
TERMINAL BLOCK(OUT)
DEFROST THERMISTOR
DEICER P.C. BOARD
SURGE ABSORBER
REVERSING VALVE COIL
FUSE