Maytag Amana PTH Series, Amana PTH Z Series, Amana PTH M Series, Amana PTC073A AA Series, Amana PTH R Series, Amana PTC074A AA Series, Amana PTC093A AA Series, Amana PTC094A AA Series, Amana PTC123A AA Series, Amana PTC124A AA Series, Amana PTC153A AA Series, Amana PTC154A AA Series, Amana PTH073A AA Series, Amana PTH074A AA Series, Amana PTH093A AA Series, Amana PTH094A AA Series, Amana PTH123A AA Series, Amana PTH124A AA Series, Amana PTH153A AA Series, Amana PTH154A AA Series, Amana PTC073A AC Series, Amana PTC073A AB Series, Amana PTC074A AB Series Service Instructions Manual
0
(0)
Service Instructions
Package Terminal
AirConditioners & Heat Pumps
This manual is to be used by qualified, professionally trained HVAC technicians only.
Goodman does not assume any responsibility for property damage or personal injury
due to improper service procedures or services performed by an unqualified person.
®
is a registered trademark of Maytag Corporation or its related companies and is used under license to Goodman Company, L.P., Houston, TX. All rights reserved.
FRONT REMOVAL ................................................................................................................................................ 18
SEQUENCE OF OPERATION ............................................................................................................................... 36
Pride and workmanship go into every product to provide our customers with quality products. It is possible, however, that
during its lifetime a product may require service. Products should be serviced only by a qualified service technician who
is familiar with the safety procedures required in the repair and who is equipped with the proper tools, parts, testing
instruments and the appropriate service manual. REVIEW ALL SERVICE INFORMATION IN THE APPROPRIATE
SERVICE MANUAL BEFORE BEGINNING REPAIRS.
IMPORTANT NOTICES FOR CONSUMERS AND SERVICERS
RECOGNIZE SAFETY SYMBOLS, WORDS AND LABELS
WARNING
WARNING
GOODMAN WILL NOT BE RESPONSIBLE FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM
IMPROPER SERVICE OR SERVICE PROCEDURES. IF YOU INSTALL OR PERFORM SERVICE ON THIS UNIT,
YOU ASSUME RESPONSIBILITY FOR ANY PERSONAL INJURY OR PROPERTY DAMAGE WHICH MAY
RESULT. MANY JURISDICTIONS REQUIRE A LICENSE TO INSTALL OR SERVICE HEATING AND AIR
CONDITIONING EQUIPMENT.
2
WARNING
THIS AIR CONDITIONER IS NOT MEANT TO PROVIDE
UNATTENDED COOLING OR LIFE SUPPORT FOR
PERSONS OR ANIMALS WHO ARE UNABLE TO
REACT TO THE FAILURE OF THIS PRODUCT.
THE FAILURE OF AN UNATTENDED AIR CONDITIONER MAY RESULT IN EXTREME HEAT IN THE CONDITIONED SPACE CAUSING OVERHEATING OR
DEATH OF PERSONS OR ANIMALS.
PRECAUTIONS MUST BE TAKEN TO WARN OF OR
GUARD AGAINST SUCH AN OCCURENCE.
WARNING
WARNING
INSTALLATION AND REPAIR OF THIS UNIT SHOULD BE PERFORMED ONLY BY INDIVIDUALS MEETING THE
REQUIREMENTS OF AN “ENTRY LEVEL TECHNICIAN” AS SPECIFIED BY THE AIR-CONDITIONING, HEATING
AND REFRIGERATION INSTITUTE (AHRI). ATTEMPTING TO INSTALL OR REPAIR THIS UNIT WITHOUT SUCH
BACKGROUND MAY RESULT IN PRODUCT DAMAGE, PERSONAL INJURY OR DEATH.
To locate an authorized servicer, please consult your telephone book or the dealer
from whom you purchased this product. For further assistance, please contact:
CONSUMER INFORMATION LINE -
AMANA® BRAND PRODUCTS TOLL FREE
1-877-254-4729 (U.S. only)
email us at: hac.consumer.affairs@amanahvac.com
fax us at: (931) 438- 4362
(Not a technical assistance line for dealers.)
Outside the U.S., call 1-931-433-6101.
(Not a technical assistance line for dealers.)
Your telephone company will bill you for the call.
3
PRODUCT IDENTIFICATION
n
PT C 07 3 B 35 A M
BASIC MODEL TYPEMAJOR/MINOR DESIGN REV.
PT = Stand ard PTAC
GM = Go odman PTAC
DRY = Dehumid PTAC
DESIGN STYLEB = Power VentA = PAC-10
Old MAJ OR DESIGN SER IESC = Seacoast ProtectionB =
A = 3/ 8" Slab C ond. Coil UnitD = Conens ated Dis posal PumpC = PAC-20
B = Bent Con de nser Coil UnitF = H & BD = +EER, PAC-20
C = Sound Re ductionG = H & JE = w/ " B" Design Series
D = 5/1 6" S lab Co nd . Coil Un itH = HydronicF = +EE R w/ "B" Des i gn Series
J = Power DoorG = M60
K = D & BH = +EER, M60 (o ld)
L = D & JH = M61S , Rech i
HEATE R SIZEM = STCJ = PAC -20, LCDI
0 0 = no el ec t r ic heatN = C & JK = M60, LCDI
15 = 1.5 kWP = C & H & BL = +EER, M60, LCDI
2 5 = 2. 5 kWR = Added Drain V alve (PTC)M = M61
35 = 3.5 kw (230/2 08V)T = Aux TransformerN = +EER, M61
= 3.7kW (265 V)X = H ard Wire d OnlyP = M6 1S
5 0 = 5.0 kWY = 230V F use Holder KitQ = Mechanical Contr ol
U = openR = M61, Rech i
V = openS = op e n
W = openT = M61, 7-Button
Z = C & DU = M61, Alt Pana sonic
V = open
W = M61
Out of Pro duction
X = ope
Y = M61, 7-Button, & DT01A
Z = M61, DT01A , Rechi
BM
Wireless Ready
DT 01A
4
PRODUCT IDENTIFICATION
NTE12A35A3A
Package
T e r mina l Units
Model TypeVoltage
E - Cooler3 = 230/208-1-60
P - Heat Pump4 = 265-1-60
Nominal Cooling Capacity
07: 7,000 BtuhA = Standard Model
09: 9,000 BtuhC = Seacoast Model
12 : 1 2 ,0 00 Btuh
15 : 1 5 ,0 00 Btuh
1. All 265V models must use Amana® brand’s subbase (PTSB4**C) or Amana® brand’s hard wire kit (PTPWHWK4).
2. Minimum branch circuit ampacity rating conform to the National Electric Code. However, local codes should apply .
3. Minimum voltage on 230/208 volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265 volt models is 238.5 volts; maximum is 291.5
volts.
4. Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265 volt models must be cartridge-style time
delay fuses (included and factory installed on Amana® brand chassis).
5. Heating capacity and efficiency are based on unit operation without condensate pump. Unit automatically switches to electric heat at 25°F
outdoor coil temperature.
6. Tot al watts for 15,000 Btuh models; subtract 30 watts for PT12*A**AA and 70 watts for PT07/09*A**AA.
7. Please specify 2-digit heater kW size to complete model number.
8. Total amp s for 12,000 and 15,000 Btuh models; subtract 0.2 amps for PT07/09*A*AA.
6
EER - Energy Efficiency Ratio per The Air-Conditioning,
Heating, and Refrigeration Institute (AHRI) Test
Procedures and Canadian Standards Association
(CSA) Test Procedures
1. All 265V models must use Amana® brand’s subbase (PTSB4**C) or Amana® brand’s hard wire kit (PTPWHWK4).
2. Minimum branch circuit ampacity rating conform to the National Electric Code. However, local codes should apply .
3. Minimum voltage on 230/208 volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265 volt models is 238.5 volts; maximum is 291.5
volts.
4. Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265 volt models must be cartridge-style time
delay fuses (included and factory installed on Amana® brand chassis).
5. Heating capacity and efficiency are based on unit operation without condensate pump. Unit automatically switches to electric heat at 25°F
outdoor coil temperature.
6. Tot al watts for 15,000 Btuh models; subtract 30 watts for PT12*A**AA and 70 watts for PT07/09*A**AA.
7. Please specify 2-digit heater kW size to complete model number.
8. Total amp s for 12,000 and 15,000 Btuh models; subtract 0.2 amps for PT07/09*A*AA.
PTC074A**AB
PTC074A**AC
PTC093A**AB
PTC093A**AC
PTC094A** AB
PTC094A** AC
Cool, Wet Coil
Dr y Co il
Ventilated Air
PTC123A**AB
PTC123A**AC
PTC124A**AB
PTC124A**AC
EER - Energy Efficiency Ratio per The Air-Conditioning,
COP - Coefficient of Performance per AHRI T est
PTC153A**AB
PTC153A**AC
Heating, and Refrigeration Institute (AHRI) Test
Procedures and Canadian Standards Association
(CSA) Test Procedures
1. All 265V models must use Amana® brand’s subbase (PTSB4**C) or an Amana® brand hard wire kit (PTPWHWK4).
2. Minimum branch circuit ampacity ratings conform to the National Electric Code. However, local codes should apply .
3. Minimum voltage on 230/208 volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265 volt models is 238.5 volts; maximum is 291.5 volts.
4. Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265 volt models must be cartridge-style time delay fuses (included
and factory installed on Amana® brand all 265 volt chassis).
5. Heating capacity and efficiency are based on unit operation without condensate pump. Unit automatically switches to electric heat at approximately 24°F outdoor ambient.
6. Total watt s for 12,000 and 15,000 Btuh models. Subtract 70 watts for PT07/09*B*AE.
7. Please specify 2-digit heater kW size to complete model number.
9. Refrigerant used in all systems is R-22.
8. Total amp s for 12,000 and 15,000 Btuh models; subtract 0.2 amps for PT07/09*B*AE.
10. All units meet or exceed ASHRAE 90.1 standards..
PTH74A**AB
PTH074A**AC
PTH093A**AB
PTH093A**AC
PTH094A**AB
PTH094A**AC
Cool, Wet Coil
Dry Coil
Ventilated Air
PTH123A**AB
PTH123A**AC
PTH124A**AB
PTH124A**AC
PTH153A**AB
PTH153A**AC
8
PTH154A**AB
PTH154A**AC
SPECIFICATIONS
COO LING DATA (COOLING with ELECTRIC HEAT )
PTC073B***
E - Y
1&3
Voltage
Capacity (BUTH)7,100/6,9007,1009,100/8,9009,10012,000/11,90012,00014,000/13,90014,000
Amps2.8/3.023.7/3.834.6/5.04.36.3/6.95.9
Watts610/595610790/7757901,110/1,1001,1301,470/1,4501,470
EER11.611.611.511.510.810.89.59.5
UNIT WITHOUT
ELEC TR IC HEATER
Min i mu m C ircuit Ampa city
CFM
HIGH245/240245245/240245325/315325325/315325
LOW220/205220220/205220250/229250250/220250
HIGH265/260265265/260265345/335345345/335345
LOW230/215230230/215230265/235265265/235265
COMPR ESSOR & FAN*6565656570707070
Deh umidific ation
(pints/hr)
Net Weight90909595105105110110
Shipping Weight
(approx. lbs.)
*Approximately 95 CFM with optional power vent kit. Actual vent CFM performance will vary due to application and installation conditions.
230/208265230/208265230/208265230/208265
2&4
4.03.65.14.46.45.78.87.7
1.61.62.62.63 .53.54.44.4
105105110110120120125125
PTC 074B* **
E - Y
PTC093B***
E - Y
PTC094B***
E - Y
Cool, Wet Coil
Ventilated Air
Dr y Co il
PTC123B***
E - Y
PTC124B***
E - Y
PTC 153B* **
E - Y
PTC154B***
E - Y
COO LING DATA (COOLING with ELECTRIC HEAT)
PTH073B***
E - Y
1&3
Voltage
Capacity (BUTH)7,000/6,8007,0009,100/8,9009,10012,000/11,80012 ,00014,000/13,90014,000
Amps2.8/3.023.5/3.834.6/5.04.36.3/6.95.9
Watts605/585605790/7757901,110/1,0901,1101,505/1,4951,505
EER11.611.611.511.510.810.89.39.3
UNIT WITHOUT
ELEC TR IC HEATER
Min i mu m C i r cuit Am pa city
CFM
HIGH245/240245245/240245325/315325325/315325
LOW220/205220220/205220250/229250250/220250
HIGH265/260265265/260265345/335345345/335345
LOW230/215230230/215230265/235265265/235265
COMPR ESSOR & FAN*6565656570707070
Deh umidific ation
(pints/hr)
Net Weight9595100100110110115115
Shipping Weight
(approx. lbs.)
230/208265230/208265230/208265230/208265
2&4
4.03.65.14.46.45.78.87.7
1.61.62.62.63.53.54.44.4
110110115115125125130130
PTH 074B* **
E - Y
PTH093B***
E - Y
PTH094B***
E - Y
Cool, Wet Coil
Ventilated Air
Dr y Co il
PTH123B***
E - Y
PTH124B***
E - Y
PTH 153B* **
E - Y
PTH154B***
E - Y
NOTES:
1. All 265V models must use Amana® brand’s subbase (PTSB4**E) or an Amana® brand hard wire kit (PTPWHWK4).
2. Minimum branch circuit ampacity ratings conform to the National Electric Code. However, local codes should apply .
3. Minimum voltage on 230/208 volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265 volt models is 238.5 volts; maximum is 291.5 volts.
4. Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265 volt models must be cartridge-style time delay fuses (included
and factory installed on Amana® brand all 265 volt chassis).
5. Heating capacity and efficiency are based on unit operation without condensate pump. Unit automatically switches to electric heat at approximately 24°F outdoor ambient.
6. Total watt s for 12,000 and 15,000 Btuh models. Subtract 70 watts for PT07/09*B*AE.
7. Please specify 2-digit heater kW size to complete model number.
9. Refrigerant used in all systems is R-22.
8. Total amp s for 12,000 and 15,000 Btuh models; subtract 0.2 amps for PT07/09*B*AE.
10. All units meet or exceed ASHRAE 90.1 standards..
HEAT PER FORMANCE (EL ECT RIC HEAT) EL ECT RIC DATA
(A LL BTUH SI ZES, ALL MODEL S)
Voltage
230/208
230/208
230/208
265
265
265
* PTH/PTC09*B50*G/K have the same airflow as a PTC/PT H12*B***G (not available on 7,000 BTU/h models).
NOTES:
1. All 265V models must use Amana® brand’s subbase (PTSB4**E) or an Amana® brand hard wire kit (PTPWHWK4).
2. Minimum branch circuit ampacity ratings conform to the National Electric Code. However, local codes should apply .
3. Minimum voltage on 230/208 volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265 volt models is 238.5 volts; maximum is 291.5 volts.
4. Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265 volt models must be cartridge-style time delay fuses (included
and factory installed on Amana® brand all 265 volt chassis).
5. Heating capacity and efficiency are based on unit operation without condensate pump. Unit automatically switches to electric heat at approximately 24°F outdoor ambient.
6. Total watt s for 12,000 and 15,000 Btuh models. Subtract 70 watts for PT07/09*B*AE.
7. Please specify 2-digit heater kW size to complete model number.
9. Refrigerant used in all systems is R-22.
8. Total amp s for 12,000 and 15,000 Btuh models; subtract 0.2 amps for PT07/09*B*AE.
10. All units meet or exceed ASHRAE 90.1 standards.
11. Some units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meeat UL 484 standards.
12. Refer to electric heat performance data for total MCA and recommended overcurrent protection. Amp s and Watts notation refers to compressor only .
Electric Heater S ize
(kW)
2 .5/ 2.018 ,5006,800- --2,650/2, 140 11.6/10. 514.5156 - 15 P
3 .5/2.9112,000 9,900---3, 650/3,040 15.9/14.519.9206 - 20 P
5. 0/4.11*17,100 14,000---5,150/ 4,240 22.4/20.428.1306 -30 P
1. All 265V models must use Amana® brand’s subbase (PTSB4**D) or an Amana® brand hard wire kit (PTPWHWK4).
2. Minimum branch circuit ampacity ratings conform to the National Electric Code. However, local codes should apply .
3. Minimum voltage on 230/208 volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265 volt models is 238.5 volts; maximum is 291.5 volts.
4. Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265 volt models must be cartridge-style time delay fuses (included
and factory installed on Amana® brand all 265 volt chassis).
5. Heating capacity and efficiency are based on unit operation without condensate pump. Unit automatically switches to electric heat at approximately 24°F outdoor ambient.
6. Total watt s for 12,000 and 15,000 Btuh models. Subtract 70 watts for PT07/09*B*AE.
7. Please specify 2-digit heater kW size to complete model number.
9. Refrigerant used in all systems is R-22.
8. Total amp s for 12,000 and 15,000 Btuh models; subtract 0.2 amps for PT07/09*B*AE.
10. All units meet or exceed ASHRAE 90.1 standards..
* Approximately 95 CFM with optional power vent kit. Actual vent
CFM performance will vary due to application and installation
conditions.
NOTES:
1. All 265V models must use Amana® brand’s subbase (PTSB4**E) or an Amana
brand hard wire kit (PTPWHWK4).
2. Minimum circuit ampacity ratings conform to the National Electric Code.
However, local codes should apply . Minimum voltage on 230/208 volt models is
197 volts; maximum is 253 volts.
3. Minimum voltage on 265 volt models is 238.5 volts; maximum is 291.5 volts.
4. Overcurrent protection for all units without electric heaters is 15 amps.
Overcurrent protection on 265 volt models must be cartridge-style time delay
fuses (included and factory installed on Amana® brand all 265 volt chassis).
See heater performance for total MCA.
5. Heating capacity and efficiency are based on unit operation without condensate
pump. Unit automatically switches to electric heat at approximately 24°F
outdoor ambient.
6. Total watts for 12,000 and 15,000 Btuh models. Subtract 70 watts for PT07/09
7. Please specify 2-digit heater kW size to complete model serial number.
8. Total amps for 12,000 and 15,000 Btuh models; subtract 0.2 amps for PT07/09
9. Refrigerant used in all systems is R-22.
10. All units meet or exceed ASHRAE 90.1 standards..
1 1 . All units less than 250 volts have a Leak Current Detector Interrupter (LCDI)
power cord and meeat UL 484 standards.
12. Refer to electric heat performance data for total MCA and recommended
overcurrent protection. Amps and Watts notation refers to compressor models
only.
- Denotes M or N Models
*Approximately 95 CFM with optional power vent kit.
Actual vent CFM performance will vary due to application and installation conditions.
NOTES:
1. All 265V models must use Amana® brand’s subbase (PTSB4**E) or an Amana® brand hard wire kit (PTPWHWK4).
2. Minimum circuit ampacity ratings conform to the National Electric Code. However, local codes should apply.
Minimum voltage on 230/208 volt models is 197 volts; maximum is 253 volts.
3. Minimum voltage on 265 volt models is 238.5 volts; maximum is 291.5 volts.
4. Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265 volt models must be cartridge-style time delay fuses
(included and factory installed on Amana® brand all 265 volt chassis). See heater performance for total MCA.
5. Heating capacity and efficiency are based on unit operation without condensate pump. Unit automatically switches to electric heat at approximately 24°F outdoor ambient.
6. Total watts for 12,000 and 15,000 Btuh models. Subtract 70 watts for PT07/09
7. Please specify 2-digit heater kW size to complete model serial number.
8. Total amps for 12,000 and 15,000 Btuh models; subtract 0.2 amps for PT07/09
9. Refrigerant used in all systems is R-22.
10. All units meet or exceed ASHRAE 90.1 standards..
1 1 . All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.
12. Refer to electric heat performance data for total MCA and recommended overcurrent protection. Amp s and Watts notation refers to compressor models only .
HEAT P ERF ORMANCE ( ELE CTR IC HEAT ) ELE CTR IC DATA
(ALL BTUH SIZES, ALL MODELS)
Voltage
230/2082.5/2.018,500 6,800---2,650/ 2,14 0 11.6 / 10.514.5156 - 15 P
230/2083.5/2.9112,000 9,900---3,650/3,040 15.9/14.519.9206 - 20 P
230/2085.0/4.11*17,100 14,000 ---5,150/4,240 22.4/20.428.1306 -30 P
* PTH/PTC09*B50*G/K have the same a irflow as a PTC/PTH12*B***G (not available on 7,000 BTU/h models).
Electric Heater Size
(kW)
265
2653.71------12,6003,85014.718. 3207 - 20 P
2655.01*------17,1005,15019.624. 5257 - 30 P
2.51------8,5002,65010.112. 7157 - 20 P
Num ber
Stages
Nom ina l Heat in g
of
230V 2 08V 265V
(BTUH)
To tal
Watts
To tal
Amps
Minimum
Ampa city
Overcurrent
1
Protection
NOTES:
1. All 265V models must use Amana® brand’s subbase (PTSB4**E) or an Amana® brand hard wire kit (PTPWHWK4).
2. Minimum circuit ampacity ratings conform to the National Electric Code. However, local codes should apply.
Minimum voltage on 230/208 volt models is 197 volts; maximum is 253 volts.
3. Minimum voltage on 265 volt models is 238.5 volts; maximum is 291.5 volts.
4. Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265 volt models must be cartridge-style time delay fuses
(included and factory installed on Amana® brand all 265 volt chassis). See heater performance for total MCA.
5. Heating capacity and efficiency are based on unit operation without condensate pump. Unit automatically switches to electric heat at approximately 24°F outdoor ambient.
6. Total watts for 12,000 and 15,000 Btuh models. Subtract 70 watts for PT07/09
7. Please specify 2-digit heater kW size to complete model serial number.
8. Total amps for 12,000 and 15,000 Btuh models; subtract 0.2 amps for PT07/09
9. Refrigerant used in all systems is R-22.
10. All units meet or exceed ASHRAE 90.1 standards..
1 1 . All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meeat UL 484 standards.
12. Refer to electric heat performance data for total MCA and recommended overcurrent protection. Amps and Watts not ation refers to compressor only.
14
Power
5
1
Cor d
SPECIFICATIONS
OPERATING VOLTAGES
WARNING
USE EXTREME CAUTION WHEN CHECKING HIGH VOLTAGE.
Use a voltmeter, check the voltage at the outlet.
The reading must be within the minimums and maximums shown below for the operating voltage.
Operating Voltages
Operating VoltageMinimum VoltageMaximum Voltage
230/208197253
265238291
NOTE:
1. All 265 volt models must use subbase or hard wire kit.
2. Minimum branch circuit ampacity ratings conform to the National Electric Code. However, local codes should apply if in
conflict.
3. Minimum voltage on 230/208 volt models is 197 volts; maximum is 253 volts. Minimum on 265 volts is 238 volts; maximum
is 291 volts.
4. Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265 volt models must be
cartridge-style time delay fuses (included and factory installed on chassis).
5. Heating capacity and efficiency is based on unit operation without condensate pump. Unit automatically switches to
electric heat at 25° F outdoor coil temperature.
6. Total watts for 15,000 BTUH models; subtract 30 watts for PT*12*A**AA and 70 watts for PT*07/09*A**AA.
7. Please specify 2-digit heater kW size to compete model number.
8. Total amps for 12,000 and 15,000 BTUH models; subtract 0.2 amps for PT*07/09*A**AA
• LCDI or AFCI Power Cords - Underwrites Laboratories and the National Electric Code (NEC) now require power cords that
sense current leakage and can open the electrical circuit to the unit on units rated at 250 volts or less. In the event that unit
does not operate, check the reset button located on or near the head of the power cord as part of the normal troubleshooting
procedure.
LCDI Power Cord
15
A
PROPER INSTALLATION
WALL SLEEVE INSTALLATION
The wall sleeve must be installed before the air conditioner or
heat pump chassis can be set in place. Read the instructions
thoroughly before proceeding.
Pre-installation Considerations
Before proceeding with the sleeve installation, ensure the following guidelines for locating the wall opening and sleeve are
met:
•The wall opening must be the correct size. See the figures
below for wall sleeve Dimensions and minimum wall opening size.
1
1
6
6
1
/
"
4
m
0
1
m
"
4
/
3
3
1
m
m
0
5
Wall Receptacle Within 58" From
Bottom R ight Side C orner on
208/230 VAC Units Only
3
•If installed in a concrete or masonry wall, a lintel must be
provided in the wall opening for support. Do not use thewall sleeve as a lintel. See Framing with Lintel Figure
for a typical lintel construction.
Framing with Lintel
•When installed in the opening, the wall sleeve must be
horizontally level from side to side and pitched (one quarter bubble in the sight glass) to the outside. DO NOT INSTALL LEVEL (FRONT TO BACK) OR SLOPE THE WALL
SLEEVE TOWARD THE ROOM.
•The installer must determine and supply the mounting bolts
and/or screws to attach the wall sleeve to the sides of the
wall opening. Make sure the wall opening is adequate for
strong support.
•The installer must provide adequate sealing and insulation
around the sleeve after it is installed (air and water tight).
See Block and Brick Veneer Installation Figure for one of
many types of constructions.
13 1/2" (340 mm)
Maximum
(No Accessories)
Wall Sleeve Dimensions
Outside
Wall
Caulk Top,
Bottom, and
Both Sides
Internal
Adjacent
Wall
Allow Front Clearance (See Table 1)
Internal
djacent
Wall
Steel
Lintel
Minimum Unit Clearances
•The wall sleeve will need to be installed with minimum
clearances to the floor and adjacent walls. Minimum projections of the sleeve into and out of the room will also
have to be met. See Minimum Unit Clearances and Minimum Interior and Exterior Projections Figures as well as
Minimum Clearances and Projections table for details.
16
Block and Brick Veneer Installation
PROPER INSTALLATION
Minimum Interior and Exterior Projections
4
2
1
1
0
/
4
7
"
M
5
i
m
n
i
m
m
u
m
m
"
m
4
u
/
m
1
m
i
5
6
n
1
i
1
4
M
Dimension "B"
in Table 1
MINIMUM CLEARANCES AND PROJECTIONS
Minimum
Option
in.mmin.mmin.mm
Wall Sleeve Only3750000
Subbase Kit3753 1/4852 3/470
Leveling Legs Kit375375250
Duct Kit375001 3/835
Drain Kit375
Hard Wire Kit3751 1/43000
Hydronic Heat Kit
"A" Series
Hydronic Heat Kit
"J" Series
1
If inside mounted then B = 1 1/2 inches (40 mm).
2
To achieve a flush fit between the hydronic front and the finished wall,
9230
6150002 1/265
Clearances
ABC
1
0
0 to 3 1/4
3
1
0
0 to 85
Dimension “C” must be between 3” and 3 1/8”. If this dimension is more
than 3 1/8” there will be a gap between the front and the wall. This gap
could permit occupant access to hydronic lines or other dangerous parts.
3
This dimension can be from 0” to 3-1/4”, but cannot exceed 3-1/4”. If this
dimension exceeds 3-1/4”, the skirt around the front will not reach the
floor.
Minimum
Projection
00
3
32752
•For installations in walls deeper than 13-1/2 inches, special care is necessary to prevent problems with rain water,
condensate drainage and intake/discharge air. Under these
circumstances, careful job site analysis and precautions
are required. You must consult with your Sales Representative and receive approval before attempting such installations.
•If used, a 230/208 volt wall receptacle must be located
within 58 inches of the lower right sleeve corner. Extension cords must not be used with the unit. See the note on
Wall Sleeve Dimensions Figure.
Minimum Wall Opening Dimensions
When 230/208 volt units are to be installed, the power supply
may be either cord connected or permanent wiring. Permanent
wiring may be done through the accessory hard wire junction
box, or the accessory subbase.
When 265 volt units are to be installed, the power supply must
be permanent wiring. Permanent wiring may be done through
the accessory hard wire junction box, or the accessory subbase. An exposed cord connection on 265 volt units is not
permitted.
The subbase accessory includes leveling legs. If added wall
sleeve support is required and the subbase is not to be used
as an accessory, leveling leg kit may be installed.
Drain Kit
An indoor/outdoor drain kit is available as an accessory item.
When a drain kit is to be installed, do so before installing the
wall sleeve in the wall. See the drain kit for actual installation
instructions.
Subbase, Leveling Legs, Main Duct, and Hydronic Heat
Kits
Installation of these kits requires drilling of mounting holes on
both sides of the wall sleeve. The minimum required clearance
distance between the wall sleeve and wall is shown in Minimum Clearances and Projections Table. If the distance between wall sleeve and wall will be at or near the minimum clearance distance, mount these kits on the sleeve before installing
the sleeve in the wall. The kit installation instructions are included with the accessory kits.
17
PROPER INSTALLATION
Wall Receptacle Within 58" From
Bottom R ight Side C orner on
208/230 VAC Units Only
Wall Sleeve Dimensions
Outside Enclosure Panel Removal
The sleeve stiffener must be taken out before the enclosure
panel can be removed from the sleeve.
The enclosure panel can be removed by folding the four flaps
up and downward and manipulating the front ends of the top
plus bottom towards the center. The entire panel can be pulled
out diagonally from one side.
Install the wall sleeve condenser air grille by using the screws
and holes provided.
Installation (WS900B or WS900D)
After the wall opening is checked and approved for location,
size, and clearances, complete the following to install the wall
sleeve.
NOTE: Check with Amana® Technical Service when a chassis
is installed in any wall sleeve not supplied by Goodman.
1. Remove the outside enclosure panel from the wall sleeve.
2. Slide the wall sleeve into the wall opening. Do not distort
the cabinet shape to fit the wall opening. The unit chassis
must fit snugly and uniformly into the wall sleeve.
3. Locate the sleeve within the range of minimum projections,
as shown in Minimum Wall Opening Dimensions and Minimum Interior and Exterior Projections Figures, so both
sides are at least the minimum projection from the wall.
4. Check the level of the wall sleeve. For proper drainage, the
sleeve should be level from side to side and one-quarter
bubble in the sight glass sloping to the outside.
5. Two holes will need to be drilled in both sides of the wall
sleeve for mounting into the wall. Drill holes of proper size
and in the proper location so the screws will engage into
strong supporting members of the wall. DO NOT DRILLTHROUGH BOTTOM OF SLEEVE. The following figure
shows possible fastening methods.
Expansi on
Anchor Bolt
Plastic
Anchor
Attaching Wall Sleeve to Opening
6. Check the level of the wall sleeve and adjust if necessary.
7. Caulk or seal around the outside of the entire sleeve.
8. If the unit chassis will not be installed immediately, replace the enclosure panel on the outside opening of the
sleeve. This will prevent weather damage to the building
interior.
9. Recycle or dispose of packaging materials per local codes.
OUTDOOR GRILLE
An outside grille must be installed to direct air flow for proper
unit operation and also protect the outdoor coil. The grille must
be installed before installing the chassis. Refer to the Installation Instructions supplied with the outdoor grille kit for a complete description of the installation procedure.
This model requires either a Stamped Grille Kit (Model SGK-B) or an Architectural Grille Kit (Model AGK--B). When replacing an old chassis with an existing grille, please check with
your sales representative to determine if the new chassis should
be used with the old outdoor grille. An improper outdoor grille
can decrease cooling or heating capacity, increase energy
usage and shorten compressor life.
FRONT REMOVAL
1. Grasp the cabinet front as shown.
2. Pull the bottom of the cabinet front away from the chassis
until the retaining clips disengage.
18
PROPER INSTALLATION
3. Lift the cabinet front off the chassis. Reverse this procedure to reinstall the cabinet front.
CHASSIS INSTALLATION
1. Remove the cabinet front from the chassis as described in
Front Removal.
2. Insert the chassis into the wall sleeve.
Wall Sleeve
Chassis
Slide Chassis In
3. Slide the chassis into the wall sleeve until the chassis
flanges contact the front edge of the wall sleeve.
Outside
Wall
Wall Sleeve
Front Mounting Holes - Two mounting holes are provided to
give the owner the option of securing the front to the chassis.
The mounting holes are located behind the intake grille. The
owner must supply two 1/2 inch long #8 sheet metal screws
per unit. The two screws must be removed before the front can
be removed.
Mounting Screws
Location
Front Mounting Screws
WIRING
CAUTION
TO AVOID PROPERTY DAMAGE, PERSONAL INJURY
OR DEATH DUE TO ELECTRICAL SHOCK:
• DO NOT USE AN EXTENSION CORD WITH THIS UNIT.
• USE ONLY COPPER CONDUCTORS.
• WIRING TO THE UNIT MUST BE PROPERLY POLAR-
IZED AND GROUNDED.
Chassis
4. Secure the chassis to the wall sleeve using three screws
on each side of the chassis to ensure a proper seal between the chassis and the wall sleeve. The screws are
supplied in a plastic bag which is attached to the power
cord.
IMPORTANT NOTES:
1. The unit is equipped with a rubber grommet mounted compressor. These grommets are factory set and require no
adjustment.
2. If a standard subbase is used, be sure the right hand subbase cover is removed before the chassis is installed in
the sleeve.
3. Check the indoor and outdoor grilles for obstructions to air
flow. The unit must be located where curtains, furniture,
trees, shrubs or other objects do not block the air flow to
and from the unit. If air is obstructed and/or deflected back
into the unit, the air conditioner’s compressor may cycle
on and off rapidly. This could damage the compressor and
void the warranty.
Outside
Wall
Cord connection to a wall socket is not permitted for 265-volt
units. All 265-volt units must be hard wired using the hard wire
kit or make use of the plug-in receptacle in the standard subbase.
Heaterless Units
If a heaterless unit is ordered, field provisions must be made
for supplemental heat if desired. Refer to the Installation Instructions supplied with the heater kit for a complete description of the installation procedures. All 208/230 volt heaterless
units are shipped with a 15 Amp power cord and all heaterless
265 volt units are shipped with a 20 Amp power cord.
When adding a heater kit to a unit, the power cord supplied
with the heater kit must be used in place of the power cord
supplied with the unit. The following table specifies power cord
rating requirements for the various heater kits.
19
A
PROPER INSTALLATION
POWER CORD REQUIREMENTS
Heater Size
(kW)
1.51520
2.51520
3.520Not Applicable
3.7Not Applicable20
530 30
230/208 Volt Units265 Volt Units
Power Cord Rating
(amp)
Power Cord Rating
(amp)
NOTE: Heaterless units are shipped with an auxiliary data label
on the front side of the mid-partition panel. If an electric heater
kit is field installed, the installer must mark the appropriate
box on the label to indicate the electric heater capacity. If no
heater is installed, the box labeled “None” must be marked.
Refer to the unit nameplate for over current protection data.
CAUTION
DO NOT INSTALL A 5kW HEATER KIT IN ANY 7,000
OR 9,000 BTU CHASSIS.
Switch
Position
OFF
FAN ONLY Unit operates on low fan speed to circulate room air.
LOW COOL
HIGH COOL
LOW HEAT
HIGH HEAT
Unit is completely off. However, before servicing, open all
disconnects and/or remove plug.
Unit operates on the low fan speed to circulate air
for cooling.
Unit operates on high fan speed to circulate air
for cooling.
Unit operates on the low fan speed to circulate air
for heating.
Unit operates on the high fan speed to circulate air
for heating.
Unit Function
Additional Control Inputs (Not used on NTE or NTP Models)
The control inputs shown below provide addition unit control
and features. To access these control inputs, the cabinet front
must be removed (see Front Removal).
MODE SWITCH SETTINGS
ON/OFF
W2 Y\W1
OPERATING CONTROLS
Users Controls
Two rotary knobs controlling temperature and operational mode
are located behind the control door located to the top-right of
the cabinet front.
High
Heat
WarmCoo l
Thermostat
Thermostat Setting
Turning the thermostat control clockwise will provide a cooler
room temperature; turning it counterclockwise will provide a
warmer room temperature. Adjusting the thermostat to the mid
setting (vertical) will set the room temperature at approximately
75° F.
Mode Switch
The table below describes the unit function corresponding to
the various mode switch settings.
Fan
Only
Mode Switch
High
Cool
C
ON
LED1
EH
IN LS FD1
FD2 TF1 TF2 C R GL W2 Y/W1B GH
ON/AUTO
RMT/STD
CONTROL
TF-
LS
FAN
B
Furthermore, to access the 24V accessory input connections,
the terminal strip cover must be removed as shown (A and B
Series units only).
Mode Switch
Terminal Strip
Cover
Master Switch (Not used on NTE or NTP Models)
The master switch disconnects power to all of the system components. When this switch is in the off position, the compressor, fan motor, reversing valve, and electric resistance heater
will all be de-energized.
20
PROPER INSTALLATION
s
X1
B
Y
Y/W1
W2
Control Board
Connections
Y/W1
W2
W1
W2
Thermostat
Connections
W1
W2
14 Pin
Connector
EHLS
Control Board
Connections
Thermostat
Connections
R
C
Control Board
Connections
14 Pin
Connector
LS
EH
Control B oard
Connection
Thermostat
Connections
B
Y
Thermostat
Connections
18 Pin Connector
R*
18 Pin Connector
21
PROPER INSTALLATION
A
REMOTE/STANDARD SWITCH (NOT USED ON NTE OR
NTP MODELS)
The remote/standard switch is used to change the control of
the unit from the standard on board controls in the standard
mode, to a remote wall mounted thermostat in the remote mode.
For remote control operation refer to Remote Operation section. To set remote switch on the "G & K" board, see
Configuration Settings.
Fan Cycle Switch
The fan cycle switch sets the operational mode of the fan. In
the ON position, the fan will run continuously whenever the
unit is in the heat or cool mode. In the AUTO position, the fan
will cycle on and off with the compressor or electric heater
when the unit is in the cool or heat mode.
Remote Control Inputs (Not used on NTE or NTP Models)
The C, R, G,(GL for low fan speed or GH for high speed fan on
"C Models and later") W2, Y/W1 and B terminals provide control inputs for a remote wall mounted thermostat. See sche-
matics page 20.
IMPORTANT NOTE: Disconnect power to the unit and/or turn
the Master Switch on the control board to OFF when connecting or altering wiring to any terminal. Failure to do so may
result in shorting the fuse or damaging the control board.
Front Desk Control (Not used on NTE or NTP Models)
The FD and RC terminals or FD1 and FD2 provide control inputs for a front desk switch. Shorting across these two terminals will disable unit operation. The only control function which
will remain active when these terminals are shorted is freeze
protection. Any switch which will produce a short circuit across
these two terminals can be used as a front desk switch. The
contact resistance of the switch, when closed, must be less
than 200 ohms for the front desk feature to operate properly.
The following table shows the maximum wire length and corresponding gage size for installation of a front desk switch.
MAXIMUM WIRE LENGTH
FOR FRONT DESK SWITCH
Wire Size
(AWG)
#24400
Maximum
Length Allowed
(ft)
ON/OFF
W2 Y\W1
Front Desk
Switch
ON / AUTO
B
111+1
RMT/STD
THERMOSTA T
Front Desk Switch Wiring Schematic
IMPORTANT NOTE: Do not apply 24VAC across these ter-
minals. Applying 24VAC to these terminals will result in failure
of the control board. Shorting these terminals to any other terminals may also result in control board failure.
Remote Temperature Sensing (Not used on NTE or NTP Models)
The RS and RC terminals provide control inputs for a remote
temperature sensor.
Remote
Sensor
23
#22600
#20900
#181500
#162000
CRGW2 BRSFD
The figures below shows a wiring schematic for connecting the
front desk switch to the unit.
“C” Models or Later
1. Remove indoor ambient thermistor from plastic holder on
indoor coil.
22
PROPER INSTALLATION
A
Indoor Ambient
Thermistor
Plastic
Holder
Indoor Coil
2. Cut off end of thermistor, separate leads 1” back from cut
and strip 1/2” of insulation from each lead.
3. Wire nut the stripped leads to the two sensor wires running from terminals 2 and 3 on the remote temperature
sensor base .
68° F71° F
75° F
82° F
85° F 87° F
Low End
Cooling Limits
64° F
87° F
69° F
76° F
Heating Limits
63° F66° F
63° F
86° F
79° F 83° F
High End
Temperature Limiter Settings
The temperature limits are set by selecting the proper holes to
use for the limiter screws. The figure above shows the high
and low end temperatures corresponding to the various limiter
holes. Since these temperatures correspond to the unit's thermistor sensor, actual room temperatures will vary depending
on the room heating/cooling load. For example, if the limiter
screws are put in the shaded holes, the coolest setting in the
cooling mode will be 68° F and the warmest setting in the
heating mode will be 83° F."A & B model units only, C mod-
els and later have DIP Switches to set the limits"
Temperature Limiter
4.Place the mode switch in the “OFF” position. Reestablish
power to the unit. The remote temperature will automatically activate.
NOTE: Ensure the mode switch is in the OFF position before
electrical power is applied to the unit. If the mode switch is not
in the OFF position when electrical power is applied to the unit,
the random restart feature will activate causing a two to four
minute start-up delay.
NOTE: Freeze protection temperatures will be sensed by the
remote temperature sensing device and not at the PTAC unit
(sensed at the PTAC unit when a remote thermostat is used).
Temperature Limiter
The temperature limiting feature can reduce energy costs by
controlling the maximum temperature available in heating and
the minimum temperature available in cooling. While approximate temperature settings are shown below, actual room temperature will vary slightly.
C
ON
LED1
EH
IN LS FD1
FD2 TF1 TF2 C R GL W2 Y/W1B GH
RMT/STD
CONTROL
ON/AUTO
FAN
B
POSITIONCOOLHEAT
A70-7865-73
B68-8163-76
C66-8361-78
D63-8858-83
Temperature Settings
NOTE: Select only on pin position.
After determining the temperature limits desired, set the limiter as follows:
1. Remove the front cabinet (see Front Removal) to allow access to the control panel.
2. Remove the unit control knobs by pulling the knobs off the
control shafts.
3. Remove the escutcheon plate by lifting it off the control
panel cover to expose the temperature limiter as shown.
23
PROPER INSTALLATION
Tem perat ure
Limiting Screws
Temperature Limiter
4. Remove the two screws supplied in the top of the control
panel cover, and drive them into the desired limiter holes.
5. Replace the escutcheon plate, control knobs and front.
NOTE: To achieve maximum efficiency, it may be necessary
to change the temperature limiter screws seasonally.
Users Controls "Digital Touch Pad"
A six button touch key pad located behind the control door
controls both temperature and operation mode. The key pads
can be used alone or in combination.
Diagnostic Light
The green diagnostic light located in the lower left hand corner
of the touchpad and indicates operation warnings. This light
usually indicates that either the filter or coils need cleaning.
Please refer to the Maintenance and Cleaning section for the
proper cleaning procedure. If this light is still on after cleaning,
please refer to the Diagnostic & Status Report section for assistance.
Additional Control Inputs
The control inputs provide additional unit control and features.
To access these control inputs, the cabinet front must be removed (see Front Removal).
Master Switch
The master switch disconnects power to all of the system components. When this switch is in the off position, the compressor, fan motor, reversing valve, and electric resistance heater
will all be de-energized.
WARNING
Status LED
User Controls
Thermostat Setting
Pressing the COOL thermostat control and the up or down
arrows will provide a cooler room temperature, respectively.
Pressing the HEAT thermostat control and the up or down arrow keys will provide a warmer room temperature.
Fan Speed
The fan speed touch key will deliver high, low or auto fan speed
to circulate room air. NOTE: The AUTO selection will not be
available if a fan speed is selected without COOL or Heat selection.
Fan Operation HIGH or LOW with HEAT or COOL mode selected - The selected fan speed shall run in the selected speed.
Fan Operation AUTO with HEAT or COOL mode selected - The
fan will run in low and high speed. The changes in fan speed
are automatic. See "Configuration Settings" section for further
details.
Remote Control Inputs
The C, R, GL, W2, Y/W1, B/O, and GH terminals provide control inputs for a “manufacturer-approved” remote wall mounted
thermostat. The “B” terminal can be configured to become “O”
if needed see Configuration Settings For remote control thermostat operation, refer to the Remote Thermostat Operation
section.
Vent Control
NOTE: Vent control is only used on units with the power vent
or power vent door kit not installed.
The vent control allows fresh air to be drawn into the conditioned area. This fresh air can provide ventilation when the blower
is operating, but it will increase the heating or cooling load and
operating costs.
To obtain access to the vent control, remove the cabinet front
(see Front Removal). Remove the shipping screw (if installed)
from the vent door. Then remove the label (if present) from over
the vent control lever on the left side of the chassis.
24
Loading...
+ 55 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.