KROHNE OPTISWITCH-3100C User Manual

Operating Instructions
OPTISWITCH 3100 C with NAMUR output

Contents

Contents
1 About this document
1.1 Function .............................
1.2 Target group ..........................
1.3 Symbolism used .......................
2.1 Authorised personnel....................
2.2 Appropriate use........................
2.3 Warning about misuse ...................
2.4 CE conformity .........................
2.5 SIL conformity .........................
2.6 Safety instructions for Ex areas ............
3 Product description
3.1 Conguration..........................
3.2 Principle of operation ....................
3.3 Operation ............................
3.4 Storage and transport ...................
4 Mounting
4.1 General instructions.....................
4.2 Mounting instructions....................
4 4 4
5 5 5 5 6 6
7 7 8 9
10 11
5 Connecting to voltage supply
5.1 Preparing the connection .................
5.2 Connection steps.......................
5.3 Wiring plan, single chamber housing.........
6 Set up
6.1 General..............................
6.2 Adjustment elements ....................
6.3 Function chart .........................
6.4 Recurring function test ...................
7 Maintenance and fault rectication
7.1 Maintenance ..........................
7.2 Rectify faults ..........................
7.3 Exchange the electronics .................
7.4 Instrument repair .......................
8 Dismounting
8.1 Dismounting procedure ..................
8.2 Disposal .............................
2 OPTISWITCH 3100 C - with NAMUR output
15 15 16
19 19 20 21
24 24 25 27
28 28
31356-EN-060830
9 Supplement
9.1 Technical data.........................
9.2 Dimensions ...........................
Contents
29 33
Supplementary operating instructions manuals
Information:
OPTISWITCH 3100 C is available in dierent versions. Depending on the selected version, supplementary operating
instructions manuals may also come with the shipment. The supplementary operating instructions manuals are listed in section "Product description.
Operating instructions manuals for accessories and replacement parts
Tip:
To ensure reliable setup and operation of your OPTISWITCH
3100 C, we oer accessories and replacement parts. The associated documents are:
l Operating instructions manual "Oscillator"
31356-EN-060830
OPTISWITCH 3100 C - with NAMUR output 3
About this document

1 About this document

1.1 Function

This operating instructions manual has all the information you need for quick setup and safe operation. Please read this manual before you start setup.

1.2 Target group

This operating instructions manual is directed to trained, qualied personnel. The contents of this manual should be made available to these personnel and put into practice by them.

1.3 Symbolism used

Information, tip, note
This symbol indicates helpful additional information.
Caution: If this warning is ignored, faults or malfunctions can result. Warning: If this warning is ignored, injury to persons and/or serious damage to the instrument can result. Danger: If this warning is ignored, serious injury to persons and/or destruction of the instrument can result.
Ex applications
This symbol indicates special instructions for Ex applications.
l List
The dot set in front indicates a list with no implied sequence.
à Action
This arrow indicates a single action.
1 Sequence
Numbers set in front indicate successive steps in a procedure.
4 OPTISWITCH 3100 C - with NAMUR output
31356-EN-060830
For your safety

2 For your safety

2.1 Authorised personnel

All operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the operator. For safety and warranty reasons, any internal work on the instruments must be carried out only by personnel authorised by the manufacturer.

2.2 Appropriate use

OPTISWITCH 3100 C is a sensor for level detection.
Detailed information on the application range of OPTISWITCH 3100 C is available in chapter "Product description".

2.3 Warning about misuse

Inappropriate or incorrect use of the instrument can give rise to application-specic hazards, e.g. vessel overll or damage to system components through incorrect mounting or adjustment.

2.4 General safety instructions

OPTISWITCH 3100 C is a high-tech instrument requiring the strict observance of standard regulations and guidelines. The user must take note of the safety instructions in this operating instructions manual, the country-specic installation standards (e.g. the VDE regulations in Germany) as well as all prevailing safety regulations and accident prevention rules.

2.5 CE conformity

OPTISWITCH 3100 C is in CE conformity with EMC (89/336/ EWG), fulls NAMUR recommendation NE 21 and is in CE conformity with LVD (73/23/EWG).
Conformity has been judged according to the following
standards:
l EMC:
- Emission EN 61326: 1997 (class B)
- Susceptibility EN 61326: 1997/A1:1998
l LVD: EN 61010-1: 2001
31356-EN-060830
OPTISWITCH 3100 C - with NAMUR output 5
For your safety

2.6 SIL conformity

OPTISWITCH 3100 C fullls the requirements of functional safety according to IEC 61508/IEC 61511. You can nd further information in the supplementary instructions manual "Safety
Manual - Functional safety (SIL) OPTISWITCH 3XXX".

2.7 Safety instructions for Exareas

Please note the Ex-specic safety information for installation and operation in Ex areas. These safety instructions are part of the operating instructions manual and come with the Ex­approved instruments.
6 OPTISWITCH 3100 C - with NAMUR output
31356-EN-060830

3 Product description

3.1 Conguration
Product description
Scope of delivery
Components
The scope of delivery encompasses:
l OPTISWITCH 3100 C level sensor l Documentation
- this operating instructions manual
- Supplementary instructions manual "Plug connector for
level sensors" (optional)
- Ex specific safety instructions (with Ex versions), if
necessary further certicates
OPTISWITCH 3100 C consists of the following components:
l Housing cover l Housing with electronics l process tting with tuning fork
1
2
3
Fig. 1: OPTISWITCH 3100 C with plastic housing 1 Housing cover 2 Housing with electronics 3 Process tting

3.2 Principle of operation

Area of application
31356-EN-060830
OPTISWITCH 3100 C - with NAMUR output 7
OPTISWITCH 3100 C is a level sensor with tuning fork for level
detection.
It is designed for industrial use in all areas of process technology and is preferably used for bulk solids.
Typical applications are overll and dry run protection. Thanks to its simple and robust measuring system, OPTISWITCH 3100 C is virtually unaected by the chemical and physical properties of the bulk solid.
Product description
It functions even when exposed to strong external vibration or
changing products.
Solid detection in water
If OPTISWITCH 3100 C was ordered for detection of solids in water, the tuning fork is adjusted to the density of water. In the air or when covered by water (density: 1 g/cm³/0.036 lbs/in) OPTISWITCH 3100 C signals "uncovered". Only if the vibrating element is also covered with solids (e.g. sand, sludge, gravel etc.) will the sensor signal "covered".
Fault monitoring
The electronics of OPTISWITCH 3100 C continuously mon­itors the following criteria:
l Correct vibrating frequency l Line break to the piezo drive
If one of these faults is detected, the electronics signals this via adefined current to the signal conditioning instrument. The connection cable to the vibrating element is also monitored.
Physical principle
Power supply
The tuning fork is piezoelectrically energised and vibrates at its mechanical resonance frequency of approx. 150 Hz. When the tuning fork is submerged in the product, the vibration amplitude changes. This change is detected by the integrated oscillator and converted into a switching command.
OPTISWITCH 3100 C with NAMUR electronics can be connected to dierent NAMUR ampliers depending on your requirements. The specications for NAMUR ampliers are available in the "Technical data".
The exact range of the power supply is stated in the "Technical data" in the "Supplement".

3.3 Operation

With the factory setting, products with a density of >0.02 g/cm³ (>0.0008 lbs/in³) can be measured. The instrument can also be adapted to products with lower density >0.008 g/cm³ (>0.0003 lbs/in³).
On the electronics module you will nd the following indicating and adjustment elements:
l signal lamp for indication of the switching condition (yellow) l potentiometer for adaptation to the product density l Mode switch to select the switching condition (reverse
characteristics)
31356-EN-060830
8 OPTISWITCH 3100 C - with NAMUR output
l Simulation key

3.4 Storage and transport

Product description
Packaging
Storage and transport tem-
perature
Your instrument was protected by packaging during transport. Its capacity to handle normal loads during transport is assured by a test according to DIN 55439.
The packaging of standard instruments consists of environ-
ment-friendly, recyclable cardboard. In addition, the sensor is provided with a protective cover of cardboard. For special versions PE foam or PE foil is also used. Dispose of the packaging material via specialised recycling companies.
l Storage and transport temperature see "Supplement -
Technical data - Ambient conditions"
l Relative humidity 20 85 %
31356-EN-060830
OPTISWITCH 3100 C - with NAMUR output 9
Mounting

4 Mounting

4.1 General instructions

Switching point
Moisture
In general, OPTISWITCH 3100 C can be mounted in any position. The instrument must be mounted in such a way that the vibrating element is at the height of the requested switching point.
Use the recommended cables (see chapter "Connecting to power supply") and tighten the cable gland.
You can give your OPTISWITCH 3100 C additional protection against moisture penetration by leading the connection cable downward in front of the cable entry. Rain and condensation water can thus drain off. This applies mainly to mounting outdoors, in areas where moisture is expected (e.g. by cleaning processes) or on cooled or heated vessels.
Fig. 2: Measures against moisture penetration
Transport
Do not hold OPTISWITCH 3100 C on the vibrating element. Especially with ange and tube versions, the sensor can be
damaged by the weight of the instrument.
Remove the protective cover just before mounting.
Pressure/Vacuum
The process tting must be sealed if there is gauge or low pressure in the vessel. Before use, check if the seal material is resistant against the measured product and the process temperature.
The max. permissible pressure is stated in the "Technical data" in the "Supplement" or on the type label of the sensor.
10 OPTISWITCH 3100 C - with NAMUR output
31356-EN-060830
Mounting
Handling
Socket
Filling opening
The vibrating level switch is a measuring instrument and must be treated accordingly. Bending the vibrating element will destroy the instrument.
Warning:
The housing must not be used to screw in the instrument! Applying tightening force on the housing can damage its
internal mechanical parts.
To screw in, use the hexagon above the thread.

4.2 Mounting instructions

The vibrating element should protrude into the vessel to avoid buildup. For that reason, avoid using mounting bosses for anges and screwed ttings. This applies particularly to use with adhesive products.
Mount the instrument in such a way that the tuning fork does not protrude directly into the lling stream.
a.
b.
20°
Fig. 3: Horizontal mounting a Convex mounting b Concave mounting
If such an installation location should be necessary, mount a suitable protective sheet above or in front of the vibrating element - see illustration a.).
31356-EN-060830
OPTISWITCH 3100 C - with NAMUR output 11