KROHNE OPTISOUND 3040 C Operating Manual

Page 1
Operating Instructions
OPTISOUND 3040 C 4 ... 20 mA/HART - four-wire
Page 2

Contents

Contents
1 About this document
1.1 Function .............................
1.2 Target group ..........................
1.3 Symbolism used .......................
2.1 Authorised personnel....................
2.2 Appropriate use........................
2.3 Warning about misuse ...................
2.4 General safety instructions ................
2.5 CE conformity .........................
2.6 Compatibility acc. to NAMUR NE 53 .........
2.7 Safety information for Ex areas.............
3 Product description
3.1 Conguration..........................
3.2 Principle of operation ....................
3.3 Adjustment ...........................
3.4 Storage and transport ...................
4 Mounting
4.1 General instructions.....................
4.2 Mounting preparations ...................
4.3 Mounting information ....................
5 5 5
6 6 6 6 6 7 7
8 9 9 9
11 13 17
5 Connecting to power supply
5.1 Preparing the connection .................
5.2 Connection procedure ...................
5.3 Wiring plans, double chamber housing .......
5.4 Switch on phase .......................
6 Setup with the indicating/adjustment module
6.1 Short description .......................
6.2 Installation of the indicating/adjustment module .
6.3 Adjustment system .....................
6.4 Setup procedure .......................
6.5 Menu schematic .......................
7 Maintenance and fault rectication
7.1 Maintenance ..........................
7.2 Fault rectication .......................
7.3 Exchanging the electronics................
7.4 Instrument repair .......................
2 OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire
23 24 25 27
28 28 30 31 35
38 38 39 40
30515-EN-050914
Page 3
8 Dismounting
8.1 Dismounting procedure ..................
8.2 Disposal .............................
9 Supplement
9.1 Technical data.........................
9.2 Dimensions ...........................
9.3 CE declaration of conformity...............
Contents
41 41
42 47 50
Supplementary operating instructions manuals
Information:
OPTISOUND 3040 C is available in dierent versions and is supplied specically acc. to the order. Depending on the selected version, supplementary operating instructions man­uals come with the shipment. The supplementary operating instructions are stated in paragraph "3. Product description".
30515-EN-050914
OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire 3
Page 4
About this document

1 About this document

1.1 Function

This operating instructions manual has all the information you need for quick setup and safe operation of OPTISOUND 3040 C. Please read this manual before you start setup.

1.2 Target group

This operating instructions manual is directed to trained personnel. The contents of this manual should be made available to these personnel and put into practice by them.

1.3 Symbolism used

Information, tip, note
This symbol indicates helpful additional information.
Caution, warning, danger
This symbol informs you of a dangerous situation that could occur. Ignoring this cautionary note can impair the person and/ or the instrument.
Ex applications
This symbol indicates special instructions for Ex applications.
l List
The dot set in front indicates a list with no implied sequence.
à Action
This arrow indicates a single action.
1 Sequence
Numbers set in front indicate successive steps in a procedure.
4 OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire
30515-EN-050914
Page 5
For your safety

2 For your safety

2.1 Authorised personnel

All operations described in this operating instructions manual must be carried out only by trained, specialised personnel authorised by the operator. For safety and warranty reasons, any internal work on the instruments must be carried out only by personnel authorised by the manufacturer.

2.2 Appropriate use

OPTISOUND 3040 C is a sensor for continuous level measurement.

2.3 Warning about misuse

Inappropriate or incorrect use of the instrument can give rise to application-specic hazards, e.g. vessel overll or damage to system components through incorrect mounting or adjustment.

2.4 General safety instructions

OPTISOUND 3040 C is a high-tech instrument requiring the strict observance of standard regulations and guidelines. The user must take note of the safety instructions in this operating instructions manual, the country-specic installation standards (e.g. the VDE regulations in Germany) as well as all prevailing safety regulations and accident prevention rules.

2.5 CE conformity

OPTISOUND 3040 C is in CE conformity with EMC (89/336/ EWG) and NSR (73/23/EWG).
Conformity has been judged acc. to the following standards:
l EMC:
- Emission EN 61326: 1997 (class A)
- Susceptibility EN 61326: 1997/A1: 1998
l LVD: EN 61010-1: 2001
OPTISOUND 3040 C is designed for industrial use. Hence, conducted as well as radiated interference must be reckoned with, as is customary with a class A instrument acc. to EN
61326. If OPTISOUND 3040 C is used in a dierent environ- ment, the electromagnetic compatibility to other instruments must be ensured by suitable measures.
30515-EN-050914
OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire 5
Page 6
For your safety
2.6 Compatibility acc. to NAMUR NE 53
OPTISOUND 3040 C meets NAMUR recommendation NE 53.
The parameter adjustment of the basic sensor functions is
independent of the software version. The range of available functions depends on the respective software version of the individual components.
The software version of OPTISOUND 3040 C can be determined as follows:
l on the type label of the electronics l via the indicating/adjustment module.
You can nd all software histories on our website www.krohne. com.
2.7 Safety information for Ex areas
Please note the Ex-specic safety information for installation and operation in Ex areas. These safety instructions are part of the operating instructions manual and come with the Ex­approved instruments.
6 OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire
30515-EN-050914
Page 7

3 Product description

3.1 Conguration
Product description
Scope of delivery
Components
The scope of delivery encompasses:
l OPTISOUND 3040 C ultrasonic sensor l Documentation
- this operating instructions manual
- Ex-specic safety instructions (with Ex versions) and, if
necessary, further certicates
- Operating instructions manual "Indicating and adjust- ment module" - optional
OPTISOUND 3040 C consists of the following components:
l transducer with process fitting (depending on version
ange, swivelling holder or thread)
l housing with electronics (depending on version remote) l Housing cover, optionally available with indicating/adjust-
ment module
The components are available in dierent versions:
l Version A: compact in ange version l Version B: compact with swivelling holder l Version C: separately with swivelling holder l Version D: separately with threaded tting
1
2
3
4
Fig. 1: OPTISOUND 3040 C compact with swivelling holder 1 Housing cover, optionally available with indicating/adjustment module 2 Housing with electronics 3 Swivelling holder with ange 4 Transducer
30515-EN-050914
OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire 7
Page 8
Product description

3.2 Principle of operation

Area of application
Physical principle
Power supply
OPTISOUND 3040 C is an ultrasonic sensor for continuous level measurement. It is particularly suitable for solids, but is also good for liquids.
The transducer of the ultrasonic sensor emits short ultrasonic pulses in the direction of the measured product. These pulses are reected by the product surface and received by the transducer as echoes. The running time of the ultrasonic pulses from emission to reception is proportional to the distance and hence to the level. The determined level is converted into an appropriate output signal and outputted as measured value.
Four-wire electronics with separate power supply.
The power supply range can dier depending on the instru-
ment version. The exact range is stated in the "Technical data" in the "Supplement".
Measured value transmission is carried out via the 4 ... 20 mA/ HART output, which is separated from the power supply.

3.3 Adjustment

OPTISOUND 3040 C can be adjusted with two dierent adjustment media:
l the indicating/adjustment module l a HART handheld
The entered parameters are generally saved in OPTISOUND 3040 C, optionally also in the indicating/adjustment module.

3.4 Storage and transport

Packaging
Storage and transport tem-
perature
8 OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire
Your instrument was protected by packaging during transport. Its capacity to handle normal loads during transport is assured by a test acc. to DIN EN 24180.
The packaging of standard instruments consists of environ-
ment-friendly, recyclable cardboard. For special versions, PE foam or PE foil is also used. Dispose of the packaging material via specialised recycling companies.
l Storage and transport temperature see "Supplement –
Technical data – Ambient conditions"
30515-EN-050914
Page 9
l Relative humidity 20 85 %
Product description
30515-EN-050914
OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire 9
Page 10
Mounting

4 Mounting

4.1 General instructions

Installation position
Moisture
Select an installation position you can easily reach for mounting and connecting as well as later retrotting of an indicating and adjustment module. The housing can be rotated by 330° without the use of any tools. You can also install the indicating and adjustment module in four dierent positions (each displaced by 90°).
Use the recommended cable (see chapter "Connecting to power supply") and tighten the cable gland.
You can give your OPTISOUND 3040 C additional protection against moisture penetration by leading the connection cable downward in front of the cable entry. Rain and condensation water can thus drain off. This applies mainly to mounting outdoors, in areas where moisture is expected (e.g. by cleaning processes) or on cooled or heated vessels.
Fig. 2: Measures against moisture penetration
Measuring range
The reference plane for the measuring range (version A) is the lower edge of the ange. The reference plane for versions B, C and D is the lower edge of the transducer.
10 OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire
30515-EN-050914
Page 11
Mounting
Make sure that for all versions a min. distance - the so called
dead zone - below the reference plane is maintained in which a measurement is not possible. The exact value of the dead zone is stated in the Technical data in the Supplement.
Information:
If the product reaches the transducer, buildup can form on it over a period of time and later cause measurement errors.
132
4
100%
0%
Fig. 3: Version A Measuring range (operating range) and max. measuring distance
1 full (dead zone) 2 empty (max. measuring distance) 3 Measuring range 4 Reference plane
30515-EN-050914
OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire 11
Page 12
Mounting
Pressure/Vacuum
132
4
100%
0%
Fig. 4: Version B, C, D Measuring range (operating range) and max. measuring distance
1 full (dead zone) 2 empty (max. measuring distance) 3 Measuring range 4 Reference plane
Gauge pressure in the vessel does not inuence OPTISOUND
3040 C. Low pressure or vacuum, however, damp the ultrasonic pulses. This inuences the measuring result, particularly if the level is very low. With pressures under -
0.2 bar (-20 kPa) you should use a dierent measuring principle, e.g. radar or guided radar (TDR).

4.2 Mounting preparations

Assembly version B
12 OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire
Version B is supplied in two parts:
l Transducer l electronics housing
Assemble the version as follows:
1 Loosen the screws on the xing ring (4) with a hexagon
spanner (size 4), remove the transducer tube out of the swivelling holder
2 Mount the ange
3 Insert the transducer tube in the requested length from
below into the swivelling holder
4 Fasten with screws (4); torque max. 10 Nm
30515-EN-050914
Page 13
Mounting
5 Remove the plug from below out of the instrument housing
and plug it into the socket of the transducer tube
6 Plug the electronics housing to the transducer tube. Do not
squeeze any cables. The housing is in the correct position, if the lower notch (2) of the transducer tube is no longer visible
7 Tighten the screws (5) on the housing moderately with a
hexagon spanner (size 4)
8 Loosen the screw of the swivelling holder (3) with a fork
spanner (SW 13)
9 Direct the sensor with the swivelling holder to the
measured product
10 Fasten the swivelling holder with screw (3), torque max.
20 Nm
11 Secure screw (3) with lacquer or similar to ensure
permanent tightness of the swivelling holder
12 Rotate the housing in such a way that the cable entry
points downwards (moisture can drain off). Fasten the housing with the screws (5); torque Aluminium housing max. 5 Nm, torque plastic housing max. 2 Nm
30515-EN-050914
OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire 13
Page 14
Mounting
5
1
4
2
3
Fig. 5: Assembling – version B 1 Groove for locking the housing 2 Marking notch 3 Screw of swivelling holder (hexagon SW 13) 4 Screws of xing ring (hexagon spanner - size 4) 5 Screws of housing (hexagon spanner - size 4)
Assembly version C
Version C is supplied in three parts:
l Transducer l Transducer cable l electronics for wall mounting
Assemble the version as follows:
1 Loosen the screws on the xing ring (4) with a hexagon
spanner (size 4), remove the transducer tube out of the swivelling holder
2 Mount the ange
3 Insert the transducer tube in the requested length from
below into the swivelling holder
4 Fasten with screws (4); torque max. 10 Nm
5 Remove the plug from below out of the connection cylinder
and plug it into the socket of the transducer tube
6 Plug the connection cylinder to the transducer tube. Do not
squeeze any cables. The cylinder is in the correct position, if the lower notch (2) of the transducer tube is no longer visible
14 OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire
30515-EN-050914
Page 15
Mounting
7 Tighten the screws (5) on the cylinder moderately with a
hexagon spanner (size 4)
8 Loosen the screw of the swivelling holder (3) with a fork
spanner (SW 13)
9 Direct the sensor with the swivelling holder to the
measured product
10 Fasten the swivelling holder with screw (3), torque max.
20 Nm
11 Secure screw (3) with lacquer or similar to ensure
permanent tightness of the swivelling holder
12 Rotate the connection cylinder in such a way that the cable
entry points downwards (moisture can drain off). Fasten the cylinder with screws (5); torque max. 5 Nm
13 Insert the plug at the end of the transducer cable into the
socket on the remote electronics
5
1
4
2
3
Fig. 6: Assembling – version C 1 Groove for locking the connection cylinder 2 Marking notch 3 Screw of swivelling holder (hexagon SW 13) 4 Screws of xing ring (hexagon spanner - size 4) 5 Screws of connection cylinder (hexagon spanner - size 4)
Assembling version D
Version D is supplied in three parts:
l Transducer l Transducer cable l electronics for wall mounting
Assemble the version as follows:
30515-EN-050914
OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire 15
Page 16
Mounting
1 Loosen the hexagon nut (3) on the transducer cable
2 Insert the transducer tube from below into the mounting
opening G1A
3 Fasten (SW 46) the hexagon nut (3)
4 Remove the plug from below out of the connection cylinder
and plug it into the socket of the transducer tube
5 Plug the connection cylinder to the transducer tube. Do not
squeeze any cables. The cylinder is in the correct position, if the lower notch (2) of the transducer tube is no longer visible
6 Tighten the screws (4) on the cylinder moderately with a
hexagon spanner (size 4)
7 Rotate the connection cylinder in such a way that the cable
entry points downwards (moisture can drain off). Fasten the cylinder with screws (4); torque max. 5 Nm
8 Insert the plug at the end of the transducer cable into the
socket on the remote electronics
4
1
3
2
Fig. 7: Assembling – version D 1 Groove for locking the connection cylinder 2 Marking notch 3 Hexagon nut SW 46 4 Screws of connection cylinder (hexagon spanner - size 4)

4.3 Mounting information

Installation position
16 OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire
When mounting OPTISOUND 3040 C, keep a distance of at
least 500 mm to the vessel wall. If the sensor is installed in the center of concave or arched vessel tops, multiple echoes can arise. These can, however, be faded out by an appropriate adjustment (see chapter "Setup").
30515-EN-050914
Page 17
Mounting
If this distance cannot be maintained, a false echo storage
should be carried out during setup. This applies particularly if buildup on the vessel wall is expected. In this case, we recommend repeating the false echo storage later on with existing buildup.
1
> 500 mm
Fig. 8: Installation position 1 Reference plane
In vessels with conical bottom it can be advantageous to align the sensor to the center of the vessel, as measurement is then possible down to the lowest points of the vessel bottom.
Fig. 9: Vessel with conical bottom
30515-EN-050914
OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire 17
Page 18
Mounting
Socket
Sensor orientation
Vessel installations
The transducer should be mounted preferably without socket,
ush with the vessel top.
If the reective properties of the medium are good, you can mount OPTISOUND 3040 C on a socket piece. The socket end should be smooth and burr-free, if possible also rounded.
Carry out a false echo storage.
In liquids, direct the sensor as perpendicular as possible to the
product surface to achieve optimum measurement results.
Fig. 10: Orientation in liquids
To optimally align the sensor to solid products, a swivelling holder can be implemented.
The ultrasonic sensor should be installed at a location where no installations cross the ultrasonic beam.
Vessel installations such as for example, ladders, limit switches, heating spirals, struts etc. can cause false echoes superimposed on the useful echo. Make sure when planning your measuring site that the ultrasonic signals have "free access" to the measured product.
If there are existing vessel installations, a false echo storage should be carried out during setup.
If large vessel installations such as struts or supports cause false echoes, these can be attenuated through supplementary measures. Small, inclined sheet metal or plastic baes above the installations scatter the ultrasonic signals and avoid direct false echoes.
18 OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire
30515-EN-050914
Page 19
Fig. 11: Cover smooth proles with deectors
Mounting
Agitators
Material heaps
If there are agitators in the vessel, a false echo storage should be carried out with the agitators in motion. This ensures that the interfering reections from the agitators are saved with the blades in dierent positions.
Fig. 12: Agitators
Large material heaps are detected with several instruments, which can be mounted on e.g. traverse cranes. For this type of application, it is best to orient the sensor toward the solid surface.
30515-EN-050914
OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire 19
Page 20
Mounting
Fig. 13: Transducers on traverse crane
Inowing material
Foam
Do not mount the instruments in or above the lling stream. Make sure that you detect the product surface and not the
inowing product.
Fig. 14: Inowing material
Through the action of lling, stirring and other processes in the vessel, dense foams which considerably damp the emitted signals may form on the product surface.
If foams are causing measurement errors, the sensor should be used in a standpipe or, alternatively, the more suitable guided radar sensors (TDR) should be used.
Guided radar is not inuenced by foam generation and is particularly suitable for such applications.
30515-EN-050914
20 OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire
Page 21
Mounting
Air ow
Heat uctuations
If there are strong air currents in the vessel, e.g. due to strong winds in outdoor installations, or because of air turbulence, e. g. through cyclone exhausting, you should mount OPTI- SOUND 3040 C in a standpipe or use a dierent measuring principle, e.g. radar or guided radar (TDR).
Strong heat uctuations, e.g. caused by the sun, can cause measurement errors. In this case, you should use a sun shield.
Fig. 15: Heat uctuations
30515-EN-050914
OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire 21
Page 22
Connecting to power supply

5 Connecting to power supply

5.1 Preparing the connection

Note safety instructions
Take note of safety
instructions for Ex applications
Select power supply
Selecting the connection ca-
ble
Always observe the following safety instructions:
l Connect only in the complete absence of line voltage l If overvoltages are expected, overvoltage arresters should
be installed.
In hazardous areas you should take note of the appropriate regulations, conformity and type approval certicates of the sensors and power supply units.
Power supply and current output are transmitted via separate two-wire connection cables. The power supply range can dier depending on the instrument version. The exact range is stated in the "Technical data" in the Supplement.
The standard version can be operated with an earth­connected current output, the Exd version must be operated with a oating output.
This instrument is designed in protection class I. To maintain this protection class, it is absolutely necessary that the ground conductor be connected to the internal ground terminal. Take note of the general installation regulations.
As a rule, connect OPTISOUND 3040 C to vessel ground (potential equalisation), or in case of plastic vessels, to the
next ground potential. There is a ground terminal on the side of the instrument housing.
For power supply, an approved installation cable with PE conductor is necessary.
The 4 ... 20 mA current output is connected with standard two­wire cable without screen. An outer cable diameter of 5 ... 9 mm ensures the seal eect of the cable entry. If electro­magnetic interference is expected, we recommend the use of screened cable.
Cable screening and ground­ing
Connect the cable screen on both ends to ground potential. In the sensor, the screen must be connected directly to the internal ground terminal. The ground terminal outside on the housing must be connected to the potential equalisation (low impedance).
22 OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire
30515-EN-050914
Page 23
Connecting to power supply
If potential equalisation currents are expected, the connection
on the evaluation side must be made via a ceramic capacitor (e.g. 1 nF, 1500 V). The low frequency potential equalisation currents are thus suppressed, but the protective eect against high frequency interference signals remains.
Select connection cable for Ex applica- tions
Take note of the corresponding installation regulations for Ex applications. In particular, make sure that no potential equal­isation currents ow over the cable screen. In case of grounding on both sides this can be achieved by the use of a capacitor or a separate potential equalisation.

5.2 Connection procedure

Proceed as follows:
1 Unscrew the housing cover
2 Loosen compression nut of the cable entry
3 Remove approx. 10 cm (4 in) of the cable mantle (current
output), strip approx. 1 cm (0.4 in) insulation from the ends of the individual wires
4 Insert the cable into the sensor through the cable entry
5 Lift the opening levers of the terminals with a screwdriver
6 Insert the wire ends into the open terminals according to
the wiring plan
7 Press down the opening levers of the terminals, you will
hear the terminal spring closing
8 Check the hold of the wires in the terminals by lightly
pulling on them
9 Connect the screen to the internal ground terminal and the
external ground terminal to potential equalisation
10 Tighten the compression nut of the cable entry, the seal
ring must completely encircle the cable
11 Connect the lead cable for power supply in the same way
acc. to the wiring plan, in addition connect the ground conductor to the inner ground terminal.
12 Screw the housing cover back on
The electrical connection is nished.
30515-EN-050914
OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire 23
Page 24
Connecting to power supply
Housing overview
Fig. 16: Connection steps 5 and 6

5.3 Wiring plans, double chamber housing

1 2 3
4
Fig. 17: Double chamber housing 1 Housing cover, connection compartment 2 Blind stopper 3 Housing cover, electronics compartment 4 Filter element for pressure compensation 5 Cable gland
5
24 OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire
30515-EN-050914
Page 25
Electronics compartment
Connecting to power supply
Connection compartment
Display
I2C
12 5678
Fig. 18: Electronics compartment, double chamber housing 1 Internal connection cable to the connection compartment
Display
1
12
I2C
1
2
Fig. 19: Connection compartment, double chamber housing 1 Spring-loaded terminals for power supply 2 Ground terminal for connection of the cable screen
30515-EN-050914
OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire 25
Page 26
3
Connecting to power supply
Wiring plan
Switch on phase
L1 N
12
/ L
1 2
/ N PE
Fig. 20: Wiring plan, double chamber housing 1 Supply voltage 2 Signal output
4...20mA IS GND
4 ... 20 mA

5.4 Switch on phase

After OPTISOUND 3040 C is connected to power supply, the instrument carries out a self-test for approx. 30 seconds. The following steps are carried out:
l Internal check of the electronics l Indication of the instrument type, the rmware version as
well as the sensor TAGs (sensor name)
l Output signal jumps briey (approx. 10 seconds) to the set
fault current
Then the actual measured value is displayed and the corresponding current is transmitted to the cable.
1)
1)
The values correspond to the actual level as well as to the settings already carried out, e.g. default setting.
26 OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire
30515-EN-050914
Page 27

Setup with the indicating/adjustment module

6 Setup with the indicating/adjustment
module

6.1 Short description

The indicating/adjustment module is used for measured value display, adjustment and diagnosis. It can be mounted in all sensors of the OPTISOUND instrument family, in the single as well as double chamber housing (optionally in the electronics or connection compartment).
6.2 Installation of the indicating/adjustment
module
The indicating/adjustment module can be inserted or removed at any time. It is not necessary to interrupt the power supply.
To mount, proceed as follows:
1 Unscrew the housing cover
2 Place the indicating/adjustment module in the desired
position on the electronics (you can choose any one of four dierent positions - each displaced by 90°)
3 Press the indicating and adjustment module onto the
electronics and turn it to the right until it snaps in.
4 Screw housing cover with inspection window tightly back
on
Removal is carried out in reverse order.
The indicating/adjustment module is powered by the sensor,
an additional connection is not necessary.
30515-EN-050914
OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire 27
Page 28
Setup with the indicating/adjustment module
Fig. 21: Installation of the indicating/adjustment module
Note:
If you intend to retrot OPTISOUND 3040 C with an indicating/ adjustment module for continuous measured value indication, a higher cover with an inspection glass is required.
28 OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire
30515-EN-050914
Page 29
Setup with the indicating/adjustment module

6.3 Adjustment system

Key functions
Adjustment system
1
1.1
2
3
Fig. 22: Indicating and adjustment elements 1 LC display 2 Indication of the menu item number 3 Adjustment keys
l [OK] key:
- move to the menu overview
- conrm selected menu
- edit parameter
- save value
l [–>] key to select:
- menu change
- list entry
- editing position
l [+] key:
- modify value of a parameter
l [ESC] key:
- interrupt input
- jump to the next higher menu
The sensor is adjusted via the four keys of the indicating and adjustment module. The LC display indicates the individual menu items. The functions of the individual keys are shown in the above illustration. Approx. 10 minutes after the last pressing of a key, an automatic reset to measured value indication is triggered. Any values not conrmed with [OK] will not be saved.
30515-EN-050914
OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire 29
Page 30
Setup with the indicating/adjustment module

6.4 Setup procedure

Address setting HART-Multi-
drop
Parameter adjustment
In HART-Multidrop mode (several sensors on one input) the address must be set before continuing with the parameter adjustment. You will nd a detailed description in the operating instructions manual of the indicating/adjustment module.
HART mode
Standard
Address 0
Because OPTISOUND 3040 C is a distance measuring instrument, its primary task is to measure the distance from the sensor to the product surface. In order to indicate the actual lling level, the measured distance must be allocated to a specic height percentage. To make this adjustment, the full and empty distances in the vessel are entered. If these values are not known, it is also possible to carry out the adjustment with other distances, e.g. 10 % and 90 %. The origin of these distance values is always the lower edge of the ange (with ange versions) or the lower edge of the transducer (all other versions).
The actual level is then calculated on the basis of these entered values. At the same time, the operating range of the sensor is limited from maximum range to the requested range.
The real product level during this adjustment is not important, because the min./max. adjustment is always carried out without changing the product level. These settings can be made ahead of time without the instrument having to be installed.
In the main menu item "Basic adjustment", the individual submenu items should be selected one after the other and provided with the correct parameter values.
Start your parameter adjustment with the following menu items of the basic adjustment:
Carrying out min. adjustment
Proceed as follows:
1
Move from the measured value display to the main menu by pushing [OK].
30 OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire
30515-EN-050914
Page 31
Setup with the indicating/adjustment module
Basic adjustment Display Diagnostics Service Info
2 Select the menu item "Basic adjustment" with [–>] and
conrm with [OK]. Now the menu item "Min. adjustment" is displayed.
Min. adjustment
0.00 %
=
5.000 m(d)
4.000 m(d)
3 Prepare the % value for editing with [OK] and set the
cursor to the requested position with [–>]. Set the requested percentage value with [+] and save with [OK]. The cursor jumps now to the distance value.
4 Enter the appropriate distance value in m (corresponding
to the percentage value) for the empty vessel (e.g. distance from the sensor to the vessel bottom).
5 Save the settings with [OK] and move to "Max. adjustment"
with [–>].
Carrying out max. adjustment
Proceed as follows:
Max. adjustment
100.00 %
=
1.000 m(d)
2.000 m(d)
1 Prepare the % value for editing with [OK] and set the
cursor to the requested position with [–>]. Set the requested percentage value with [+] and save with [OK]. The cursor jumps now to the distance value.
2 Enter the appropriate distance value in m (corresponding
to the percentage value) for the full vessel. Keep in mind that the max. level must lie below the dead band.
3 Save the settings with [OK] and move to "Medium
selection" with [–>].
Medium selection
Each product has dierent reective properties. In addition, there are various interfering factors which have to be taken into account: agitated product surfaces and foam generation (with liquids); dust generation, material cones and echoes from the
30515-EN-050914
OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire 31
Page 32
Setup with the indicating/adjustment module
vessel wall (with solids). To adapt the sensor to these dierent conditions, you should rst select in this menu item "Liquid" or
"Solid".
Medium
Liquid
With solids, you can also choose between "Powder/Dust", "Granular/Pellets" or "Ballast/Pebbels".
Through this additional selection, the sensor is adapted perfectly to the product and measurement reliability, partic­ularly in products with bad reective properties, is considerably increased.
Enter the requested parameter via the appropriate keys, save your settings and jump to the next menu item with the [–>] key.
Vessel shape
Damping
Apart from the medium, the shape of the vessel can also inuence the measurement. To adapt the sensor to these conditions, this menu item oers (depending on either liquid or solid is detected) dierent options. For Liquid these are
Storage tank, Stilling tube, Open vessel or Stirred vessel, for Solid Silo or Bunker
Vessel shape
Storage tank
.
Enter the requested parameter via the appropriate keys, save your settings and jump to the next menu item with the [–>] key.
To suppress uctuation in the measured value display, e.g. caused by a turbulent product surface, an integration time can be set. This time can be between 0 and 999 seconds. Please note that the reaction time of the entire measurement will be longer and the sensor will react to quick changes of the measured value with a corresponding delay. In general, a time of a few seconds is sucient to smooth the measured value display.
Damping
0 s
30515-EN-050914
32 OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire
Page 33
Setup with the indicating/adjustment module
Enter the requested parameter via the appropriate keys, save
your settings and jump to the next menu item with the [–>] key.
Linearization curve
Sensor-TAG
A linearization is necessary for all vessels in which the vessel volume does not increase linearly with the level – e.g. in a cylindrical or spherical tank -–and the indication or output of the volume is requested. Corresponding linearization curves are preprogrammed for these vessels. They represent the correlation between the level percentage and vessel volume. By activating the appropriate curve, the volume percentage of the vessel is displayed correctly. If the volume should not be displayed in percent but e.g. in l or kg, a scaling can be also set in the menu item "Display".
Linearization curve
Linear
Enter the requested parameter via the appropriate keys, save your settings and jump to the next menu item with the [–>] key.
In this menu item you can enter an unambiguous designation for the sensor, e.g. the measurement loop name or the tank or product designation. In digital systems and in the documen­tation of larger plants, a singular designation should be entered for exact identication of individual measuring sites.
Sensor-TAG
Sensor
With this menu item, the Basic adjustment is nished and you can now jump to the main menu with the [ESC] key.
False signal suppression
High sockets or vessel installations, such as e.g. struts or agitators as well as buildup and weld joints on the vessel walls cause interfering reections which can impair the measure­ment. A false signal suppression detects, marks and saves these false signals, so that they are no longer taken into account for the level measurement. This false signal sup­pression should be created with empty vessel so that all potential interfering reections will be detected.
30515-EN-050914
OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire 33
Page 34
Setup with the indicating/adjustment module
False signal suppression
Change now?
Proceed as follows:
1 Move from the measured value display to the main menu
by pushing [OK].
2 Select the menu item "Service" with [–>] and conrm with
[OK]. Now the menu item "False signal suppression" is
displayed.
3 Conrm "False signal suppression - Change now" with
[OK] and select in the below menu "Create new". Enter the actual distance from the sensor to the product surface. All false signals in this area are detected by the sensor and saved after conrming with [OK].
Note:
Check the distance to the product surface, because if an incorrect (too large) value is entered, the existing level will be saved as false signal. The lling level would then no longer be detectable in this area.
Optional settings
Additional adjustment and diagnosis options such as e.g. scaling, simulation or trend curve presentation are shown in the following menu schematic. You will nd a detailed description of these menu items in the operating instructions manual of the indicating and adjustment module.
34 OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire
30515-EN-050914
Page 35
Basic adjustment
Basic adjustment Display Diagnostics Service Info
Setup with the indicating/adjustment module

6.5 Menu schematic

1
Min. adjustment
0.00 %
=
4.000 m(d)
3.000 m(d)
Damping
0 s
Display
Basic adjustment
Display Diagnostics Service Info
Displayed value
scaled
Diagnostics
Basic adjustment Display
Diagnostics Service Info
1.1
1.5
2.1
2
3
Max. adjustment
100.00 %
=
1.000 m(d)
2.000 m(d)
Linearization curve
Linear
Display units
Volume m³
1.2
1.6
2.2
Medium
Solid
Sensor-TAG
Scaling
0 %=0.0 m³
100 %=100.0 m³
Sensor
1.3
1.7
2.3
Vessel shape
Silo
1.4
Peak values Distance-min.: 0.234 m(d) Distance-max: 5.385 m(d) T-min.: 16.5°C T-min.: 37.5°C
3.1
Meas. reliability
36dB
Sensor status
OK
3.2
Choose curve
Echo curve
3.3
Echo curve
Presentation of the echo
curve
30515-EN-050914
OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire 35
3.4
Page 36
Setup with the indicating/adjustment module
Service
Basic adjustment Display Diagnostics
Service Info
4
False signal suppression
Change now?
Reset
Reset?
Copy sensor data
Copy sensor data?
Info
Basic adjustment Display Diagnostics Service
Info
Sensor type
OPTISOUND 30x0 C
Serial number
12345678
4.1
4.5
4.9
5.1
5
Addl. adjustments
none
Units of measurement
m(d)
select?
PIN
Enable?
Date of manufacture
26. July 2005 Software version
3.26
4.2
4.6
4.10
5.2
Current output
Output mode 4-20 mA Failure mode: <3.6mA Min-current 3.8mA
Language
Deutsch
Date of last change using PC
26. July 2005
4.3
4.7
5.3
Simulation
Start simulation?
HART mode
Standard
Address 0
Sensor details
Display now?
4.4
4.8
5.4
36 OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire
30515-EN-050914
Page 37
Maintenance and fault rectication
7 Maintenance and fault rectication

7.1 Maintenance

When used as directed in normal operation, OPTISOUND 3040 C is completely maintenance-free.
7.2 Fault rectication
Causes of malfunction
Fault rectication
Checking the 4 20 mA sig-
nal
OPTISOUND 3040 C oers maximum reliability. Nevertheless faults can occur during operation. These may be caused by the following, e.g.:
l Sensor l Process l Power supply l Signal processing.
The rst measures to be taken are to check the output signal and evaluate fault messages via the indicating/adjustment module. The procedure is described below.
Connect a hand-held multimeter with a suitable measuring range acc. to the wiring plan.
? 4 20 mA signal not stable
l level uctuations
à set integration time via the indicating/adjustment
module
? 4 20 mA signal missing
l wrong connection
à Check connection acc. to chapter "Connection proce-
dure" and correct, if necessary, acc. to chapter "Wiring plans"
l no power supply
à check cables for line break, repair, if necessary
l load resistance too high
à check and adapt, if necessary
30515-EN-050914
OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire 37
Page 38
Maintenance and fault rectication
? Current signal greater than 22 mA or less than 3.6 mA
l Electronics module defective
à Exchange instrument or return it for repair
In Ex applications, the regulations for the wiring of intrinsically safe circuits must be observed.
Fault messages via the indi­cating/adjustment module
? E013
l no measured value available
à sensor in boot phase
à sensor does not nd an echo, e.g. because of faulty
installation or incorrect parameter adjustment
? E017
l adjustment span too small
à Carry out a fresh adjustment and increase the distance
between min. and max. adjustment
? E036
l no operable sensor software
à carry out a software update or return instrument for
repair
? E041
l hardware error, electronics defective
à Exchange instrument or return it for repair

7.3 Exchanging the electronics

If the electronics module is defective, it can be replaced by the user.
In Ex applications, only instruments and electronics modules with appropriate Ex approval may be used.
38 OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire
30515-EN-050914
Page 39
Maintenance and fault rectication
If there is no electronics module available on site, it can be ordered from the responsible Krohne agency.

7.4 Instrument repair

If a repair is necessary, please proceed as follows:
You can download a return form from our Internet homepage http://www.krohne-mar.com/leadmin/media-lounge/PDF- Download/Specimen_e.pdf.
By doing this you help us carry out the repair quickly and
without having to call back for needed information.
l Print and ll out one form per instrument l Clean the instrument and pack it damage-proof l Attach the completed form and possibly also a safety data
sheet to the instrument.
30515-EN-050914
OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire 39
Page 40
Dismounting

8 Dismounting

8.1 Dismounting procedure

Caution:
During operation, individual cores of the transducer cable carry a voltage of approx. 70 V. Therefore dismount OPTISOUND
3040 C only in voltage-free condition.
Take note of chapters "Mounting" and "Connecting to power
supply" and carry out the listed steps in reverse order.

8.2 Disposal

OPTISOUND 3040 C consists of materials which can be recycled by specialised recycling companies. We have purposely designed the electronic modules to be easily separable. Mark the instrument as scrap and dispose of it according to national government regulations (e.g. in G ermany acc. to the EU Directive on Waste Electrical and Electronic
Equipment, WEEE).
Materials: see "Technical data"
If you cannot dispose of the instrument properly, please
contact us about disposal methods or return.
40 OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire
30515-EN-050914
Page 41

9 Supplement

9.1 Technical data

General data
Materials, wetted parts
- Flange PP or Alu
- swivelling holder/ange galvanized steel
- Transducer PA (1.4301 with StEx)
- transducer diaphragm 316Ti (1.4571)
Materials, non-wetted parts
- Housing Alu die-casting powder-coated
- Seal ring between housing and
housing cover
- Inspection window in housing cover Polycarbonate (UL746-C listed)
- Ground terminal 316Ti (1.4571/1.4435)
- transducer cable with separate ver-
sion C and D
2)
Weight
- compact with ange (version A) 5.6 10.7 kg (12.3 23.6 lbs)
- compact with swivelling holder
(version B)
- separate with swivelling holder
(version C)
- separate with threaded tting
(version D)
silicone
PUR (1.1082
)
6.9 … 9.7 kg (15.2 … 21.4 lbs)
7.5 … 10.5 kg (16.5 … 23.1 lbs)
4.7 … 6.9 kg (10.4 … 15.2 lbs)
Supplement
utput variable
O
Output signal 4 … 20 mA/HART Resolution 1.6 µA Fault signal current output unchanged; 20.5 mA; 22 mA;
<3.6 mA (adjustable) Current limitation 22 mA Load max. 500 Ohm Integration time (63 % of the input
0 999 s, adjustable
3)
variable)
Fullled NAMUR recommendation NE 43
2)
Depending on size and process tting material.
3)
With inductive load, ohmic share at least 25 Ohm/mH.
30515-EN-050914
OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire 41
Page 42
Supplement
Input variable
Parameter
- Version A distance between lower edge of the ange and
product surface
- version B, C and D distance between lower edge of the transducer
and product surface
Dead zone 1 m (3.3 ft) Measuring range
- Liquids up to 25 m (82 ft)
- Solid up to 15 m (49.2 ft)
Accuracy (similar to DIN EN 60770-1)
Reference conditions acc. to DIN EN 61298-1
- Temperature 18 … +30°C (64 +86°F)
- Relative humidity 45 75 %
- Atmospheric pressure 860 1060 mbar
(86 106 kPa/
12.5 … 15.4 psi)
Characteristic curve deviation and measurement characteristics
Average temperature coecient of the
0.06 %/10 K
4)
zero signal (temperature error elec­tronics)
Resolution, general max. 1 mm Ultrasonic frequency 30 kHz Interval >2 s (dependent on the parameter adjustment) Beam angle at -3 dB 4° Adjustment time
5)
>3 s (dependent on the parameter adjustment)
Accuracy better than 0.2 % or ±6 mm (see diagram)
4)
Relating to the nominal range, incl. hysteresis and repeatability, determined acc. to the limit point method.
5)
Time to output the correct level (with max. 10 % deviation) after a sudden level change.
42 OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire
30515-EN-050914
Page 43
50 mm
25 mm
Supplement
6 mm
-6 mm
-25 mm
-50 mm
5 m 15 m 20 m
Fig. 23: Accuracy OPTISOUND 3040 C version A
50 mm
25 mm
6 mm
-6 mm
-25 mm
-50 mm
5 m 15 m 20 m
25 m10 m3 m
25 m10 m3 m
Fig. 24: Accuracy OPTISOUND 3040 C versions B, C, D
Ambient conditions
Ambient, storage and transport temperature
- without indicating/adjustment mod-
-40 +80°C (-40 +176°F)
ule
- the indicating/adjustment module -20 … +70°C (-4 … +158°F)
30515-EN-050914
OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire 43
Page 44
Supplement
Process conditions
Vessel pressure
- version A with PP ange 0 kPa (0 bar/0 psi)
- other versions -20 50 kPa (-0.2 0.5 bar/-2.9 7.3 psi)
Process temperature (transducer tem-
-40 +80°C (-40 +176°F)
perature)
Vibration resistance mechanical vibrations with 1 g in the frequency
range 5 200 Hz
6)
Electromechanical data
Cable entry
- Double chamber housing
l 1x cable entry M20x1.5 (cable-ø 5 ... 9 mm),
1x blind stopper M20x1.5
or:
l 1x closing cap ½ NPT, 1x blind stopper ½
NPT
Spring-loaded terminals for wire cross sections up to 2.5 mm² Transducer cable
7)
- length 5 ... 300 m (16.4 ... 984.3 ft)
- Diameter 7.2 ... 7.6 mm
Indicating and adjustment module
Power supply and data transmission through sensor via gold-plated sliding contacts
(I²C bus)
Indication LC display in full dot matrix Adjustment elements 4 keys Protection
- unassembled IP 20
- mounted into the sensor without
IP 40
cover
Materials
- Housing ABS
- Inspection window Polyester foil
Supply voltage
Supply voltage
- non-Ex and Exd instrument 20 … 72 VDC, 20 253 VAC, 50/60 Hz
6)
Tested acc. to the regulations of German Lloyd, GL directive 1
7)
With separate version C and D.
44 OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire
30515-EN-050914
Page 45
Power consumption max. 4 VA; 2.1 W
Electrical protective measures
Protection IP 66/IP 67 Overvoltage category III Protection class I
Supplement
Approvals
8)
ATEX ATEX II 1/2DIP66 T
8)
Deviating data with Ex applications: see separate safety instructions.
30515-EN-050914
OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire 45
Page 46
Supplement

9.2 Dimensions

Housing
27
~ 87mm (3
Fig. 25: Housing versions (with integrated indicating/adjustment module the housing height or width is increased by 9 mm/
0.35 in)
M20x1,5/ ½ NPT
/64")
ø 84mm
(3 5/16")
")
")
32
64
/
/
5
23
120mm (4
* 129mm (5
46 OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire
30515-EN-050914
Page 47
OPTISOUND 3040 CVersion A and B
130mm (51/8")
1
")
64
/
29
240mm (9
b
")
64
/
21
110mm (4
ø189mm (7 7/16")
k
D
k
b
DN 50 PN16/40
DN 80 PN16/40
DN 200 PN16
DN 250 PN16
2" 150lb
3" 150lb
8" 150lb
10" 150lb
D
165mm
200mm
340mm
405mm
D
6"
7 1/2"
1
13
16"
/2"
20mm
24mm
24mm
26mm
b
3
/4"
15
/16"
1
/8"
1
3
1
/16"
125mm
160mm
295mm
355mm
k
3
/4"
4
6"
3
11
1
14
/4"
/4"
12x
12x
4x
8x
12x
d
ø18mm
ø18mm
ø22mm
ø26mm
d
4x
4x
8x
ø
ø
ø
ø 1"
3
3
7
34
>ø200mm
(7
/4"
/4"
/8"
Supplement
2
D
k
7
/8")
2
3
")
64
/
21
440mm (17
")
8
/
7
250mm (9
°
15
.
x
a
m
9
1
)
"
/
(
34
Fig. 26: OPTISOUND 3040 CVersion A and B 1 Version A 2 Version B 3 Dead zone: 1 m (3.3 ft) 4 Measuring range: with liquids up to 25 m (82 ft), with solids up to 15 m (49.2 ft)
30515-EN-050914
OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire 47
Page 48
Supplement
OPTISOUND 3040 CVersion C and D
150mm (5 29/32")
1 2
")
32
/
21
220mm (8
>ø200mm
7
/8")
(7
")
32
/
9
") 312mm (12
8
/
7
G1A
")
64
/
45
18mm
(
34
")
8
/
5
143mm (5
")
64
/
55
149mm (5
250mm (9
D
b
DN 50 PN16/40
DN 80 PN16/40
DN 200 PN16
DN 250 PN16
165mm
200mm
340mm
405mm
20mm
24mm
24mm
26mm
k
125mm
160mm
295mm
355mm
12x
12x
4x
8x
d
ø18mm
ø18mm
ø22mm
ø26mm
2" 150lb
3" 150lb
8" 150lb
10" 150lb
13
D
b
3
k
6"
1
15
/2"
7
1
1
/2"
16"
1
3
/4"
/4"
4
/16"
6"
1
3
/8"
11
3
1
14
/16"
d
3
ø
/4"
4x
3
/4"
ø
4x
7
ø
/4"
/4"
12x
/8"
8x
ø 1"
Fig. 27: OPTISOUND 3040 CVersion C and D 1 Version C 2 Version D 3 Dead zone: 1 m (3.3 ft) 4 Measuring range: with liquids up to 25 m (82 ft), with solids up to 15 m (49.2 ft)
48 OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire
30515-EN-050914
Page 49

9.3 CE declaration of conformity

CE declaration of conformity
Supplement
Fig. 28: CE declaration of conformity
30515-EN-050914
OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire 49
Page 50
Supplement
50 OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire
30515-EN-050914
Page 51
Supplement
30515-EN-050914
OPTISOUND 3040 C - 4 ... 20 mA/HART - four-wire 51
Page 52
Subject to change without notice
30515-EN-050914
Loading...