Instruction Manual
Modular Flaker
Models F-450MAJ(-C)
F-801MAJ(-C), MWJ(-C) F-1002MAJ(-C), MWJ(-C), MRJ(-C), MLJ F-1501MAJ(-C), MWJ(-C), MRJ(-C) F-2001MWJ, MRJ/3(-C), MLJ FD-650MAJ-C, MWJ-C, MRJ-C FD-1002MAJ-C, MRJ-C
|
|
|
|
|
hoshizakiamerica.com |
Issued: 7-27-2017 |
|
|
|
|
|
||
|
|
|
|
|
|
Revised: 5-30-2018 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
WARNING
Only qualified service technicians should install and service the appliance. To obtain the name and phone number of your local Hoshizaki Certified Service
Representative, visit www.hoshizaki.com. No installation or service should be undertaken until the technician has thoroughly read this Instruction Manual. Likewise, the owner/manager should not proceed to operate the appliance until the installer has instructed them on its proper operation. Failure to install, operate, and maintain the appliance in accordance with this manual will adversely affect safety, performance, component life, and warranty coverage and may result in costly water damage. Proper installation is the responsibility of the installer. Product failure or property damage due to improper installation is not covered under warranty.
Hoshizaki provides this manual primarily to assist qualified service technicians in the installation, maintenance, and service of the appliance.
Should the reader have any questions or concerns which have not been satisfactorily addressed, please call, send an e-mail message, or write to the Hoshizaki Technical Support Department for assistance.
Phone: 1-800-233-1940; (770) 487-2331
Fax: 1-800-843-1056; (770) 487-3360
E-mail: techsupport@hoshizaki.com
618 Highway 74 South
Peachtree City, GA 30269
Attn: Hoshizaki Technical Support Department
NOTE: To expedite assistance, all correspondence/communication MUST include the following information:
•Model Number
•Serial Number
•Complete and detailed explanation of the problem.
2
IMPORTANT
This manual should be read carefully before the appliance is installed and operated.
Read the warnings and guidelines contained in this manual carefully as they provide essential information for the continued safe use and maintenance of the appliance. Retain this manual for any further reference that may be necessary.
CONTENTS |
|
Important Safety Information.................................................................................................. |
5 |
I. Specifications...................................................................................................................... |
7 |
A. Electrical and Refrigerant Data...................................................................................... |
7 |
1. F-450MAJ(-C)........................................................................................................... |
7 |
2. F-801M_J(-C)........................................................................................................... |
7 |
3. F-1002M_J(-C)......................................................................................................... |
8 |
4. F-1501M_J(-C)......................................................................................................... |
8 |
5. F-2001M_J(-C)......................................................................................................... |
9 |
6. F-2001MRJ3............................................................................................................. |
9 |
7. FD-650M_J-C......................................................................................................... |
10 |
8. FD-1002M_J(-C).................................................................................................... |
10 |
B. Dimensions/Connections.............................................................................................. |
11 |
1. Air-Cooled Models (MAJ(-C))................................................................................... |
11 |
2. Water-Cooled Models (MWJ(-C))........................................................................... |
12 |
3. Remote Models (MRJ/3(-C)).................................................................................. |
13 |
4. Low Side, Parallel Rack System Models (MLJ)...................................................... |
14 |
5. Remote Condenser Unit URC-5F |
|
(use with F-1002MRJ(-C), FD-650MRJ-C, FD-1002MRJ-C).................................. |
15 |
6. Remote Condenser Unit URC-14F |
|
(use with F-1501MRJ(-C))....................................................................................... |
15 |
7. Remote Condenser Unit URC-22F |
|
(use with F-2001MRJ/3(-C)) .................................................................................. |
16 |
II. Installation and Operating Instructions............................................................................. |
17 |
A. Location....................................................................................................................... |
17 |
B. Checks Before Installation........................................................................................... |
17 |
C. How to Remove Panels................................................................................................ |
18 |
D. Dispenser Unit/Ice Storage Bin and Icemaker Setup................................................... |
19 |
E. Electrical Connection................................................................................................... |
20 |
F. Water Supply and Drain Connections........................................................................... |
22 |
1. Icemaker................................................................................................................. |
23 |
2. Water-Cooled Condenser....................................................................................... |
24 |
G. Remote Condenser Unit Installation............................................................................ |
26 |
1. Location.................................................................................................................. |
26 |
2. Checks Before Installation...................................................................................... |
27 |
3. Setup...................................................................................................................... |
27 |
4. Line Set Size and Refrigerant Charge.................................................................... |
28 |
5. Line Set Installation................................................................................................ |
29 |
6. Electrical Connection............................................................................................. |
32 |
7. Stacking Remote Condenser Unit........................................................................... |
33 |
3
H. Parallel Rack System Connection................................................................................ |
34 |
1. Line Set Size and Rack System Requirements...................................................... |
34 |
2. Line Set Installation................................................................................................ |
34 |
I. Final Checklist............................................................................................................... |
37 |
J. Startup.......................................................................................................................... |
38 |
K. Bin Control Check........................................................................................................ |
39 |
1. Infrared Sensor Check............................................................................................ |
39 |
2. Infrared Sensor Shutdown Delay........................................................................... |
41 |
L. Alarm Safeties.............................................................................................................. |
42 |
III. Maintenance.................................................................................................................... |
43 |
A. Maintenance Schedule................................................................................................ |
44 |
B. Cleaning and Sanitizing Instructions............................................................................ |
45 |
IV. Preparing the Appliance for Periods of Non-Use............................................................. |
49 |
V. Disposal............................................................................................................................ |
51 |
4
Throughout this manual, notices appear to bring your attention to situations which could result in death, serious injury, damage to the appliance, or damage to property.
WARNING |
Indicates a hazardous situation which could result in death or |
|
serious injury. |
NOTICE |
Indicates a situation which could result in damage to the |
|
appliance or property. |
IMPORTANT |
Indicates important information about the installation, use, and |
|
care of the appliance. |
WARNING
The appliance should be destined only to the use for which it has been expressly conceived. Any other use should be considered improper and therefore dangerous. The manufacturer cannot be held responsible for injury or damage resulting
from improper, incorrect, and unreasonable use. Failure to install, operate, and maintain the appliance in accordance with this manual will adversely affect safety, performance, component life, and warranty coverage and may result in costly water damage.
To reduce the risk of death, electric shock, serious injury, or fire, follow basic precautions including the following:
•Only qualified service technicians should install and service the appliance.
•The appliance must be installed in accordance with applicable national, state, and local codes and regulations.
•Electrical connection must be hard-wired and must meet national, state, and local electrical code requirements. Failure to meet these code requirements could result in death, electric shock, serious injury, fire, or damage.
•The icemaker requires an independent power supply of proper capacity. See the nameplate for electrical specifications. Failure to use an independent power supply of proper capacity can result in a tripped breaker, blown fuse, damage to existing
wiring, or component failure. This could lead to heat generation or fire.
•THE ICEMAKER MUST BE GROUNDED. Failure to properly ground the icemaker could result in death or serious injury.
•To reduce the risk of electric shock, do not touch the power switch or control switch with damp hands.
•Move the power switch to the "OFF" position and turn off the power supply before servicing. Lockout/Tagout to prevent the power supply from being turned back on inadvertently.
•Do not place fingers or any other objects into the ice discharge opening.
•Do not make any alterations to the appliance. Alterations could result in electric shock, injury, fire, or damage.
5
WARNING, continued
•The appliance is not intended for use by persons (including children) with reduced physical, sensory, or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
•Children should be properly supervised around the appliance.
•Do not climb, stand, or hang on the appliance or allow children or animals to do so. Serious injury could occur or the appliance could be damaged.
•Do not use combustible spray or place volatile or flammable substances near the appliance. They might catch fire.
•Keep the area around the appliance clean. Dirt, dust, or insects in the appliance could cause harm to individuals or damage to the appliance.
Additional Warning for Remote Models
•THE REMOTE CONDENSER UNIT MUST BE GROUNDED. The power supply and ground connection to the remote condenser unit are supplied from the icemaker.
Failure to properly ground the remote condenser unit could result in death or serious injury.
•Wire routing (conduit) and disconnect (if required) must meet national, state, and local electrical code requirements. Failure to meet these code requirements could result in death, electric shock, serious injury, fire, or damage.
NOTICE
•Follow the water supply, drain connection, and maintenance instructions carefully to reduce the risk of costly water damage.
•In areas where water damage is a concern, install in a contained area with a floor drain.
•Install the icemaker in a location that stays above freezing. Normal operating ambient temperature must be within 45°F to 100°F (7°C to 38°C).
•Do not leave the icemaker on during extended periods of non-use, extended absences, or in sub-freezing temperatures. To properly prepare the icemaker for these occasions, follow the instructions in "IV. Preparing the Icemaker for Periods of
Non-Use."
•Do not place objects on top of the appliance.
•The dispenser unit/ice storage bin is for ice use only. Do not store anything else in the dispenser unit/ice storage bin.
6
The rating label and nameplate provide electrical and refrigerant data. The rating label can be seen by removing the front panel. The nameplate is located on the rear panel. For certification marks, see the nameplate.
We reserve the right to make changes in specifications and design without prior notice.
1. F-450MAJ(-C)
Single Phase |
||
Model Number |
F-450MAJ(-C) |
|
AC Supply Voltage |
115/60/1 |
|
Compressor |
115V |
8.4RLA 50LRA |
Gear Motor |
115V |
2.4FLA 1/4HP |
Fan Motor |
115V |
1FLA 50W |
Other |
115V |
0.03A |
Maximum Fuse Size |
15 AMPS |
|
Max. HACR Breaker |
15 AMPS |
|
(USA Only) |
|
|
Max. Circuit Breaker |
15 AMPS |
|
(Canada Only) |
|
|
Minimum Circuit |
15 AMPS |
|
Ampacity |
|
|
Design Pressure |
HI-427PSI LO-230PSI |
|
Refrigerant |
404A 15.2 OZ. |
2. F-801M_J(-C)
Single Phase
Model Number |
F-801MAJ(-C) |
F-801MWJ(-C) |
|
AC Supply Voltage |
115/60/1 |
115/60/1 |
|
Compressor |
115V |
7.5RLA 54.5LRA |
115V 7.5RLA 54.5LRA |
Gear Motor |
115V |
3.0FLA 200W |
115V 3.0FLA 200W |
Fan Motor |
115V |
1.0FLA 1/15HP |
– – – |
Other |
115V |
0.03A |
115V 0.03A |
Maximum Fuse Size |
15 AMPS |
15 AMPS |
|
Max. HACR Breaker |
15 AMPS |
15 AMPS |
|
(USA Only) |
|
|
|
Max. Circuit Breaker |
15 AMPS |
15 AMPS |
|
(Canada Only) |
|
|
|
Minimum Circuit |
15 AMPS |
15 AMPS |
|
Ampacity |
|
|
|
Design Pressure |
HI - 467PSI LO - 250PSI |
HI - 467PSI LO - 250PSI |
|
Refrigerant |
404A 1 LB. 12 OZ. |
404A 10.7 OZ. |
7
3. F-1002M_J(-C)
|
|
Single Phase |
|
|
Model Number |
F-1002MAJ(-C) |
F-1002MWJ(-C) |
F-1002MRJ(-C) |
F-1002MLJ(-C) |
AC Supply Voltage |
115/60/1 |
115/60/1 |
115/60/1 |
115/60/1 |
Compressor |
115V 11.2RLA |
115V 10.7RLA |
115V 11.2RLA |
– – – |
|
93LRA |
93LRA |
93LRA |
|
Gear Motor |
115V 3.0FLA 200W |
115V 3.0FLA 200W |
115V 3.0FLA 200W |
115V 3.0FLA 200W |
Fan Motor |
115V 1.0FLA |
– – – |
115V 3A MAX |
– – – |
|
1/15HP |
|
(Fan in URC) |
|
Other |
115V 0.03A |
115V 0.03A |
115V 0.53A |
115V 0.53A |
Maximum Fuse Size |
20 AMPS |
20 AMPS |
20 AMPS |
15 AMPS |
Max. HACR Breaker |
20 AMPS |
20 AMPS |
20 AMPS |
15 AMPS |
(USA Only) |
|
|
|
|
Max. Circuit Breaker |
20 AMPS |
20 AMPS |
20 AMPS |
15 AMPS |
(Canada Only) |
|
|
|
|
Minimum Circuit |
20 AMPS |
20 AMPS |
20 AMPS |
15 AMPS |
Ampacity |
|
|
|
|
Design Pressure |
HI-467PSI |
HI-427PSI |
HI-467PSI |
HI-467PSI |
|
LO-250PSI |
LO-250PSI |
LO-250PSI |
LO-250PSI |
Refrigerant |
404A 2 LB. 4 OZ. |
404A 12.3 OZ. |
404A |
Use only with 404A, |
|
|
|
Total Refrigerant |
407A, or 407F |
|
|
|
Charge with |
|
|
|
|
Hoshizaki Remote |
|
|
|
|
Condenser Unit |
|
|
|
|
URC-5F: 4 LB. 1.2 |
|
|
|
|
OZ. |
|
4. F-1501M_J(-C)
Single Phase
Model Number |
F-1501MAJ(-C) |
F-1501MWJ(-C) |
F-1501MRJ(-C) |
|||
AC Supply Voltage |
208-230/60/1 (3 wire with |
208-230/60/1 (3 wire with |
208-230/60/1 (3 wire with |
|||
|
neutral) |
neutral) |
neutral) |
|||
Compressor |
208-230V 9.3RLA 56LRA |
208-230V 9.3RLA 56LRA |
208-230V 9.3RLA 56LRA |
|||
Gear Motor |
115V 5.6FLA 400W |
115V 5.6FLA 400W |
115V 5.6FLA 400W |
|||
Fan Motor |
115V 1.0FLA 1/15HP |
Cabinet: 115V 0.51FLA 8W |
Cabinet: 115V 0.51FLA 8W |
|||
|
|
|
|
|
Remote: 115V 3A MAX |
|
Other |
115V |
0.03A |
115V |
0.03A |
115V |
0.03A |
Maximum Fuse Size |
20 AMPS |
20 AMPS |
20 AMPS |
|||
Max. HACR Breaker |
20 AMPS |
20 AMPS |
20 AMPS |
|||
(USA Only) |
|
|
|
|
|
|
Max. Circuit Breaker |
20 AMPS |
20 AMPS |
20 AMPS |
|||
(Canada Only) |
|
|
|
|
|
|
Minimum Circuit |
20 AMPS |
20 AMPS |
20 AMPS |
|||
Ampacity |
|
|
|
|
|
|
Design Pressure |
HI-467PSI LO-250PSI |
HI-427PSI LO-250PSI |
HI-467PSI LO-250PSI |
|||
Refrigerant |
404A 2 LB. 5 OZ. |
404A 1 LB 4.5 OZ. |
404A |
|
||
|
|
|
|
|
Total Refrigerant Charge |
|
|
|
|
|
|
with Hoshizaki Remote |
|
|
|
|
|
|
Condenser Unit URC-14F: |
|
|
|
|
|
|
9 LB. 9 OZ. |
8
5. F-2001M_J(-C)
Single Phase
Model Number |
F-2001MWJ(-C) |
F-2001MRJ(-C) |
F-2001MLJ |
AC Supply Voltage |
208-230/60/1 |
208-230/60/1 |
115/60/1 |
Compressor |
240V 10.8RLA 96LRA |
240V 10.8RLA 96LRA |
– – – |
Gear Motor |
120V 5.6 FLA 400W |
120V 5.6 FLA 400W |
120V 5.6 FLA 400W |
Cabinet Fan Motor |
115V 0.51 FLA 8W |
115V 0.51 FLA 8W |
115 0.51 FLA 8W |
Remote Fan Motor |
– – – |
120V 3A MAX |
|
Other |
120V 0.03A |
120V 0.03A |
120V 0.3A |
Maximum Fuse Size |
30 AMPS |
30 AMPS |
15 AMPS |
Max. HACR Breaker |
30 AMPS |
30 AMPS |
15 AMPS |
(USA Only) |
|
|
|
Max. Circuit Breaker |
30 AMPS |
30 AMPS |
15 AMPS |
(Canada Only) |
|
|
|
Minimum Circuit |
30 AMPS |
30 AMPS |
15 AMPS |
Ampacity |
|
|
|
Design Pressure |
HI-467PSI |
HI-467PSI |
HI-467PSI |
|
LO-290PSI |
LO-290PSI |
LO-290PSI |
Refrigerant |
404A 2 LB. |
404A |
Use only with 404A, |
|
|
Total Refrigerant Charge |
407A, or 407F |
|
|
with Hoshizaki Remote |
|
|
|
Condenser Unit |
|
|
|
URC-22F: 15 LB. 14 OZ. |
|
6. F-2001MRJ3
Three Phase
Model Number |
F-2001MRJ3 |
AC Supply Voltage |
208-230/60/3 |
Compressor |
240V 9.0RLA 75LRA |
Gear Motor |
120V 5.6 FLA 400W |
Cabinet Fan Motor |
115V 0.51 FLA 8W |
Remote Fan Motor |
120V 3A MAX |
Other |
120V 0.03A |
Maximum Fuse Size |
20 AMPS |
Max. HACR Breaker |
20 AMPS |
(USA Only) |
|
Max. Circuit Breaker |
20 AMPS |
(Canada Only) |
|
Minimum Circuit |
20 AMPS |
Ampacity |
|
Design Pressure |
HI-467PSI |
|
LO-290PSI |
Refrigerant |
404A |
|
Total Refrigerant Charge |
|
with Hoshizaki Remote |
|
Condenser Unit |
|
URC-22F: 15 LB. 14 OZ. |
9
7. FD-650M_J-C
|
Single Phase |
|
|
Model Number |
FD-650MAJ-C |
FD-650MWJ-C |
FD-650MRJ-C |
AC Supply Voltage |
115/60/1 |
115/60/1 |
115/60/1 |
Compressor |
115V 7.9RLA 54.5LRA |
115V 5.5RLA 50LRA |
115V 5.5RLA 50LRA |
Gear Motor |
120V 2.3FLA 1/4HP |
120V 2.3FLA 1/4HP |
120V 2.3FLA 1/4HP |
Fan Motor |
115V 1.0FLA 1/15HP (each) |
- |
120V 3A MAX (Fan in URC) |
Other |
115-120V 0.3A |
115-120V 0.3A |
115-120V 0.3A |
Maximum Fuse Size |
20 AMPS |
20 AMPS |
20 AMPS |
Max. HACR Breaker |
20 AMPS |
20 AMPS |
20 AMPS |
(USA Only) |
|
|
|
Max. Circuit Breaker |
20 AMPS |
20 AMPS |
20 AMPS |
(Canada Only) |
|
|
|
Minimum Circuit |
20 AMPS |
20 AMPS |
20 AMPS |
Ampacity |
|
|
|
Design Pressure |
HI-427PSI LO-230PSI |
HI-427PSI LO-230PSI |
HI-427PSI LO-230PSI |
Refrigerant |
404A 12.4 OZ. |
404A 15.0 OZ. |
404A |
|
|
|
Total Refrigerant Charge |
|
|
|
with Hoshizaki Remote |
|
|
|
Condenser Unit URC-5F: |
|
|
|
4 LB. 1.2 OZ. |
8. FD-1002M_J(-C)
Single Phase
Model Number |
FD-1002MAJ-C |
FD-1002MRJ-C |
||
AC Supply Voltage |
115/60/1 |
115/60/1 |
||
Compressor |
115V |
11.2RLA 93LRA |
115V |
11.2RLA 93LRA |
Gear Motor |
115V |
3.0FLA 200W |
115V |
3.0FLA 200W |
Fan Motor |
115V |
1.0FLA 1/15HP |
115V |
3A MAX (Fan in URC) |
Other |
115V |
0.03A |
115V |
0.53A |
Maximum Fuse Size |
20 AMPS |
20 AMPS |
||
Max. HACR Breaker |
20 AMPS |
20 AMPS |
||
(USA Only) |
|
|
|
|
Max. Circuit Breaker |
20 AMPS |
20 AMPS |
||
(Canada Only) |
|
|
|
|
Minimum Circuit |
20 AMPS |
20 AMPS |
||
Ampacity |
|
|
|
|
Design Pressure |
HI - 467PSI LO - 250PSI |
HI - 467PSI LO - 250PSI |
||
Refrigerant |
404A 2 LB. 4.1 OZ. |
404A |
|
|
|
|
|
Total Refrigerant Charge |
|
|
|
|
with Hoshizaki Remote |
|
|
|
|
Condenser Unit URC-5F: |
|
|
|
|
4 LB. 1.2 OZ. |
10
1. Air-Cooled Models (MAJ(-C)) |
Units: mm [in.] |
|
Side
|
|
|
|
|
|
|
|
|
Model Shown: F-801MAJ |
||||
|
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
||||||||
|
F-450MAJ(-C) |
F-801MAJ(-C) |
F-1501MAJ(-C) |
FD-650MAJ-C |
|
||||||||
|
|
|
|
F-1002MAJ(-C) |
F-2001MAJ(-C) |
FD-1002MAJ-C |
|
||||||
A |
560 |
[22] |
560 |
[22] |
768 [30-1/4] |
560 |
[22] |
|
|||||
B |
556 |
[21-7/8] |
556 |
[21-7/8] |
756 |
[29-3/4] |
556 |
[21-7/8] |
|
||||
C |
395 |
[15-9/16] |
395 |
[15-9/16] |
602 |
[23-3/4] |
395 |
[15-9/16] |
|
||||
D |
558 |
[21-15/16] |
659 |
[25-15/16] |
874 [34-3/8] |
659 |
[25-15/16] |
|
|||||
E |
499 |
[19-11/16] |
599 |
[23-9/16] |
817 [32-1/8] |
599 |
[23-9/16] |
|
|||||
F |
476 [18-11/16] |
575 |
[22-5/8] |
731 |
[28-13/16] |
575 |
[22-5/8] |
|
|||||
G |
169 [6-11/16] |
169 [6-5/8] |
165 [6-1/2] |
169 [6-5/8] |
|
||||||||
H |
22 |
[7/8] |
24 [15/16] |
25 |
[1] |
|
24 |
[15/16] |
|
||||
I |
42 |
[1-5/8] |
35 [1-3/8] |
44 |
[1-3/4] |
37 |
[1-1/2] |
|
|||||
J |
64 |
[2-1/2] |
67 [2-5/8] |
87 |
[3-7/16] |
64 |
[2-1/2] |
|
|||||
K |
672 |
[26-7/16] |
675 |
[26-9/16] |
676 [26-5/8] |
587 |
[23-182] |
|
|||||
L |
695 |
[27-3/8] |
692 |
[27-1/4] |
699 |
[27-1/2] |
607 |
[24] |
|
||||
M |
260 |
[10-3/16] |
------- |
323 |
[12-11/16] |
280 |
[11] |
|
|||||
N |
28 |
[1-1/8] |
------- |
30 |
[1-3/16] |
28 |
[1-1/8] |
|
|||||
O |
370 |
[14-1/2] |
------- |
330 |
[13] |
324 |
[12-11/16] |
|
|||||
P |
104 [4-1/8] |
------- |
113 [4-1/2] |
106 [4-3/16] |
|
NOTICE
•Allow 6" (15 cm) clearance at rear and sides for proper air circulation and ease of maintenance and/or service should they be required. Allow 24" (61 cm) clearance at top to allow for removal of the auger.
•The dispenser unit/ice storage bin opening must accommodate the bottom opening as in the illustration.
Rear
Model Shown: F-801MAJ
Bottom
F-801 and F-1002
Model Shown: F-801MAJ
Bottom
F-450, F-1501,
FD-650, and FD-1002
Model Shown: FD-650MAJ-C
11
Units: mm [in.]
Side
Model Shown: F-801MWJ
F-801MWJ(-C) F-1501MWJ(-C) FD-650MWJ-C F-1002MWJ(-C) F-2001MWJ(-C)
A |
560 |
[22] |
768 [30-1/4] |
560 |
[22] |
|||
B |
550 |
[21-5/8] |
756 |
[29-3/4] |
550 |
[21-5/8] |
||
C |
395 |
[15-9/16] |
602 |
[23-3/4] |
395 |
[15-9/16] |
||
D |
659 |
[25-15/16] |
874 [34-3/8] |
659 |
[25-15/16] |
|||
E |
599 |
[23-9/16] |
817 |
[32-1/8] |
599 |
[23-5/8] |
||
F |
575 |
[22-5/8] |
731 |
[28-13/16] |
575 |
[22-5/8] |
||
G |
169 [6-5/8] |
165 |
[6-1/2] |
169 [6-5/8] |
||||
H |
24 |
[15/16] |
25 [1] |
23 |
[7/8] |
|||
I |
41 |
[1-5/8] |
44 [1-3/4] |
43 |
[1-3/4] |
|||
J |
67 |
[2-5/8] |
87 [3-7/16] |
62 |
[2-1/2] |
|||
K |
185 [7-5/16] |
371 |
[14-5/8] |
235 |
[9-1/4] |
|||
L |
145 [5-11/16] |
139 |
[5-1/2] |
95 |
[3-3/4] |
|||
M 80 |
[3-1/8] |
127 |
[5] |
83 |
[3-1/4] |
|||
N |
675 |
[26-9/16] |
676 |
[26-5/8] |
587 |
[23-1/8] |
||
O |
695 |
[27-3/8] |
699 |
[27-1/2] |
607 |
[24] |
||
Q |
------- |
323 |
[12-11/16] |
280 |
[11] |
|||
R |
------- |
30 [1-3/16] |
28 |
[1-1/8] |
||||
S |
------- |
330 |
[13] |
324 |
[12-11/16] |
|||
T |
------- |
113 [4-1/2] |
106 [4-3/16] |
NOTICE
•Allow 6" (15 cm) clearance at rear and sides for proper air circulation and ease of maintenance and/or service should they be required. Allow
24" (61 cm) clearance at top to allow for removal of the auger.
•The dispenser unit/ice storage bin opening must accommodate the bottom opening as in the illustration.
Rear
Model Shown: F-801MWJ
Bottom
F-801 and F-1002
Model Shown: F-801MWJ
Bottom
F-1501 and FD-650
Model Shown: FD-650MWJ-C
12
3. Remote Models (MRJ/3(-C)) |
Units: mm [in.] |
Side
Model Shown: FD-650MRJ-C
|
F-1002MRJ(-C) |
F-1501MRJ(-C) |
FD-650MRJ-C |
||||||
|
|
|
|
|
|
|
FD-1002MRJ-C |
||
|
|
|
|
|
|
|
F-2001MRJ/3(-C) |
||
A |
560 |
[22] |
768 [30-1/4] |
560 |
[22] |
||||
B |
556 |
[21-7/8] |
756 |
[29-3/4] |
556 |
[21-7/8] |
|||
C |
395 |
[15-9/16] |
602 |
[23-3/4] |
395 |
[15-1/2] |
|||
D |
659 |
[25-15/16] |
874 [34-3/8] |
659 |
[26] |
||||
E |
599 |
[23-9/16] |
817 [32-1/8] |
599 |
[23-5/8] |
||||
F |
575 |
[22-5/8] |
731 |
[28-13/16] |
575 |
[22-5/8] |
|||
G |
169 [6-5/8] |
165 [6-1/2] |
169 [6-5/8] |
||||||
H |
24 |
[15/16] |
25 |
[1] |
23 |
[7/8] |
|||
I |
35 |
[1-3/8] |
44 |
[1-3/4] |
43 |
[1-3/4] |
|||
J |
65 |
[2-1/2] |
87 |
[3-7/16] |
62 |
[2-1/2] |
|||
K |
434 |
[17-1/16] |
524 |
[20-5/8] |
434 |
[17-1/8] |
|||
L |
40 |
[1-9/16] |
92 |
[3-5/8] |
70 |
[2-3/4] |
|||
M |
100 [3-15/16] |
154 [6] |
60 |
[2-3/8] |
|||||
N |
70 |
[2-3/4] |
70 |
[2-3/4] |
70 |
[2-3/4] |
|||
O |
673 |
[26-1/2] |
676 [26-5/8] |
587 |
[23-1/8] |
||||
P |
708 |
[27-3/4] |
699 |
[27-1/2] |
607 |
[23-13/16] |
|||
Q |
------- |
323 |
[12-11/16] |
280 |
[11] |
||||
R |
------- |
30 |
[1-3/16] |
28 |
[1-1/8] |
||||
S |
------- |
330 |
[13] |
324 |
[12-11/16] |
||||
T |
------- |
113 [4-1/2] |
106 [4-3/16] |
NOTICE
•Allow 6" (15 cm) clearance at rear and sides for proper air circulation and ease of maintenance and/or service should they be required. Allow
24" (61 cm) clearance at top to allow for removal of the auger.
•The dispenser unit/ice storage bin opening must accommodate the bottom opening as in the illustration.
Rear
Model Shown: FD-650MRJ-C
Bottom
F-1002
Model Shown: FD-650MRJ-C
Bottom
F-1501,
FD-650, and FD-1002
Model Shown: FD-650MRJ-C
13
Units: mm [in.]
|
|
Side |
|
|
Rear |
||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F-2001MLJ
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F-1002MLJ |
|||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Bottom |
||||||||||||
|
|
F-1002MLJ |
|
F-2001MLJ |
|
|
|||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
A |
560 |
[22] |
|
768 |
[30-1/4] |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||
|
B |
555 |
[21-7/8] |
|
762 |
[30] |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
C |
395 |
[15-9/16] |
|
602 [23-11/16] |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||
|
D |
658 |
[25-7/8] |
|
874 [34-7/16] |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||
|
E |
598 |
[23-1/2] |
|
817 |
[32-3/16] |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
F |
575 |
[22-5/8] |
|
705 [27-3/4] |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||
|
G |
169 [6-5/8] |
|
165 |
[6-1/2] |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||
|
H |
24 |
[15/16] |
|
24 |
[15/16] |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
I |
35 |
[1-3/8] |
|
43 |
[1-11/16] |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
J |
64 |
[2-1/2] |
|
75 |
[2-15/16] |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
K |
434 [17-1/16] |
|
524 [20-5/8] |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
L |
40 [1-9/16] |
|
92 [3-5/8] |
|
|
|
|
|
|
|
|
|
|
|
F-1002MLJ |
|||||||||||||||||||
|
M |
60 |
[2-3/8] |
|
62 |
[2-7/16] |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
Bottom |
|||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
NOTICE
• Allow 6" (15 cm) clearance at rear and sides for proper air circulation and ease of maintenance and/or service should they be required. Allow 24" (61 cm) clearance at top to allow for removal of the auger.
• The dispenser unit/ice storage bin |
F-2001MLJ |
|
opening must accommodate the |
||
|
||
bottom opening as in the illustration. |
|
14
5. Remote Condenser Unit URC-5F
(use with F-1002MRJ(-C), FD-650MRJ-C, FD-1002MRJ-C)
Units: mm [in.]
NOTICE
Allow 24" (61 cm) clearance at front and rear for proper air circulation and ease of maintenance and/or service should they be required.
|
URC-5F Heat of Rejection |
Icemaker |
AT 90°F (32°C) |
Model |
WT 70°F (21°C) |
F-1002MRJ |
7,660 BTU/hr |
F-1002MRJ-C |
7,840 BTU/hr |
FD-650MRJ-C |
4,900 BTU/hr |
FD-1002MRJ-C |
8,900 BTU/hr |
Top
Rear
6.Remote Condenser Unit URC-14F (use with F-1501MRJ(-C))
NOTICE
Allow 24" (61 cm) clearance at front and rear for proper air circulation and ease of maintenance and/or service should they be required.
|
URC-14F Heat of Rejection |
|
Icemaker |
AT 90°F (32°C) |
|
Model |
WT 70°F (21°C) |
|
F-1501MRJ |
13,194 BTU/hr |
|
F-1501MRJ-C |
||
|
Units: mm [in.]
Top
Rear
15
7.Remote Condenser Unit URC-22F (use with F-2001MRJ/3(-C))
NOTICE
Allow 24" (61 cm) clearance at front and rear for proper air circulation and ease of maintenance and/or service should they be required.
Units: mm [in.]
Top
|
URC-22F Heat of Rejection |
|
AT 90°F (32°C) |
Icemaker Model |
WT 70°F (21°C) |
F-2001MRJ |
16,475 BTU/hr |
F-2001MRJ-C |
17,690 BTU/hr |
F-2001MRJ3 |
16,890 BTU/hr |
Rear |
16