Hoshizaki F2001MLJ, F1501MRJC, F2001MWJ, F1002MWJ, FD1002MRJC User Manual

...
0 (0)

Instruction Manual

Modular Flaker

Models F-450MAJ(-C)

F-801MAJ(-C), MWJ(-C) F-1002MAJ(-C), MWJ(-C), MRJ(-C), MLJ F-1501MAJ(-C), MWJ(-C), MRJ(-C) F-2001MWJ, MRJ/3(-C), MLJ FD-650MAJ-C, MWJ-C, MRJ-C FD-1002MAJ-C, MRJ-C

 

 

 

 

 

hoshizakiamerica.com

Issued: 7-27-2017

 

 

 

 

 

 

 

 

 

 

 

Revised: 5-30-2018

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WARNING

Only qualified service technicians should install and service the appliance. To obtain the name and phone number of your local Hoshizaki Certified Service

Representative, visit www.hoshizaki.com. No installation or service should be undertaken until the technician has thoroughly read this Instruction Manual. Likewise, the owner/manager should not proceed to operate the appliance until the installer has instructed them on its proper operation. Failure to install, operate, and maintain the appliance in accordance with this manual will adversely affect safety, performance, component life, and warranty coverage and may result in costly water damage. Proper installation is the responsibility of the installer. Product failure or property damage due to improper installation is not covered under warranty.

Hoshizaki provides this manual primarily to assist qualified service technicians in the installation, maintenance, and service of the appliance.

Should the reader have any questions or concerns which have not been satisfactorily addressed, please call, send an e-mail message, or write to the Hoshizaki Technical Support Department for assistance.

Phone: 1-800-233-1940; (770) 487-2331

Fax: 1-800-843-1056; (770) 487-3360

E-mail: techsupport@hoshizaki.com

618 Highway 74 South

Peachtree City, GA 30269

Attn: Hoshizaki Technical Support Department

NOTE: To expedite assistance, all correspondence/communication MUST include the following information:

Model Number

Serial Number

Complete and detailed explanation of the problem.

2

IMPORTANT

This manual should be read carefully before the appliance is installed and operated.

Read the warnings and guidelines contained in this manual carefully as they provide essential information for the continued safe use and maintenance of the appliance. Retain this manual for any further reference that may be necessary.

CONTENTS

 

Important Safety Information..................................................................................................

5

I. Specifications......................................................................................................................

7

A. Electrical and Refrigerant Data......................................................................................

7

1. F-450MAJ(-C)...........................................................................................................

7

2. F-801M_J(-C)...........................................................................................................

7

3. F-1002M_J(-C).........................................................................................................

8

4. F-1501M_J(-C).........................................................................................................

8

5. F-2001M_J(-C).........................................................................................................

9

6. F-2001MRJ3.............................................................................................................

9

7. FD-650M_J-C.........................................................................................................

10

8. FD-1002M_J(-C)....................................................................................................

10

B. Dimensions/Connections..............................................................................................

11

1. Air-Cooled Models (MAJ(-C))...................................................................................

11

2. Water-Cooled Models (MWJ(-C))...........................................................................

12

3. Remote Models (MRJ/3(-C))..................................................................................

13

4. Low Side, Parallel Rack System Models (MLJ)......................................................

14

5. Remote Condenser Unit URC-5F

 

(use with F-1002MRJ(-C), FD-650MRJ-C, FD-1002MRJ-C)..................................

15

6. Remote Condenser Unit URC-14F

 

(use with F-1501MRJ(-C)).......................................................................................

15

7. Remote Condenser Unit URC-22F

 

(use with F-2001MRJ/3(-C)) ..................................................................................

16

II. Installation and Operating Instructions.............................................................................

17

A. Location.......................................................................................................................

17

B. Checks Before Installation...........................................................................................

17

C. How to Remove Panels................................................................................................

18

D. Dispenser Unit/Ice Storage Bin and Icemaker Setup...................................................

19

E. Electrical Connection...................................................................................................

20

F. Water Supply and Drain Connections...........................................................................

22

1. Icemaker.................................................................................................................

23

2. Water-Cooled Condenser.......................................................................................

24

G. Remote Condenser Unit Installation............................................................................

26

1. Location..................................................................................................................

26

2. Checks Before Installation......................................................................................

27

3. Setup......................................................................................................................

27

4. Line Set Size and Refrigerant Charge....................................................................

28

5. Line Set Installation................................................................................................

29

6. Electrical Connection.............................................................................................

32

7. Stacking Remote Condenser Unit...........................................................................

33

3

H. Parallel Rack System Connection................................................................................

34

1. Line Set Size and Rack System Requirements......................................................

34

2. Line Set Installation................................................................................................

34

I. Final Checklist...............................................................................................................

37

J. Startup..........................................................................................................................

38

K. Bin Control Check........................................................................................................

39

1. Infrared Sensor Check............................................................................................

39

2. Infrared Sensor Shutdown Delay...........................................................................

41

L. Alarm Safeties..............................................................................................................

42

III. Maintenance....................................................................................................................

43

A. Maintenance Schedule................................................................................................

44

B. Cleaning and Sanitizing Instructions............................................................................

45

IV. Preparing the Appliance for Periods of Non-Use.............................................................

49

V. Disposal............................................................................................................................

51

4

Important Safety Information

Throughout this manual, notices appear to bring your attention to situations which could result in death, serious injury, damage to the appliance, or damage to property.

WARNING

Indicates a hazardous situation which could result in death or

 

serious injury.

NOTICE

Indicates a situation which could result in damage to the

 

appliance or property.

IMPORTANT

Indicates important information about the installation, use, and

 

care of the appliance.

WARNING

The appliance should be destined only to the use for which it has been expressly conceived. Any other use should be considered improper and therefore dangerous. The manufacturer cannot be held responsible for injury or damage resulting

from improper, incorrect, and unreasonable use. Failure to install, operate, and maintain the appliance in accordance with this manual will adversely affect safety, performance, component life, and warranty coverage and may result in costly water damage.

To reduce the risk of death, electric shock, serious injury, or fire, follow basic precautions including the following:

Only qualified service technicians should install and service the appliance.

The appliance must be installed in accordance with applicable national, state, and local codes and regulations.

Electrical connection must be hard-wired and must meet national, state, and local electrical code requirements. Failure to meet these code requirements could result in death, electric shock, serious injury, fire, or damage.

The icemaker requires an independent power supply of proper capacity. See the nameplate for electrical specifications. Failure to use an independent power supply of proper capacity can result in a tripped breaker, blown fuse, damage to existing

wiring, or component failure. This could lead to heat generation or fire.

THE ICEMAKER MUST BE GROUNDED. Failure to properly ground the icemaker could result in death or serious injury.

To reduce the risk of electric shock, do not touch the power switch or control switch with damp hands.

Move the power switch to the "OFF" position and turn off the power supply before servicing. Lockout/Tagout to prevent the power supply from being turned back on inadvertently.

Do not place fingers or any other objects into the ice discharge opening.

Do not make any alterations to the appliance. Alterations could result in electric shock, injury, fire, or damage.

5

WARNING, continued

The appliance is not intended for use by persons (including children) with reduced physical, sensory, or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.

Children should be properly supervised around the appliance.

Do not climb, stand, or hang on the appliance or allow children or animals to do so. Serious injury could occur or the appliance could be damaged.

Do not use combustible spray or place volatile or flammable substances near the appliance. They might catch fire.

Keep the area around the appliance clean. Dirt, dust, or insects in the appliance could cause harm to individuals or damage to the appliance.

Additional Warning for Remote Models

THE REMOTE CONDENSER UNIT MUST BE GROUNDED. The power supply and ground connection to the remote condenser unit are supplied from the icemaker.

Failure to properly ground the remote condenser unit could result in death or serious injury.

Wire routing (conduit) and disconnect (if required) must meet national, state, and local electrical code requirements. Failure to meet these code requirements could result in death, electric shock, serious injury, fire, or damage.

NOTICE

Follow the water supply, drain connection, and maintenance instructions carefully to reduce the risk of costly water damage.

In areas where water damage is a concern, install in a contained area with a floor drain.

Install the icemaker in a location that stays above freezing. Normal operating ambient temperature must be within 45°F to 100°F (7°C to 38°C).

Do not leave the icemaker on during extended periods of non-use, extended absences, or in sub-freezing temperatures. To properly prepare the icemaker for these occasions, follow the instructions in "IV. Preparing the Icemaker for Periods of

Non-Use."

Do not place objects on top of the appliance.

The dispenser unit/ice storage bin is for ice use only. Do not store anything else in the dispenser unit/ice storage bin.

6

I. Specifications

A. Electrical and Refrigerant Data

The rating label and nameplate provide electrical and refrigerant data. The rating label can be seen by removing the front panel. The nameplate is located on the rear panel. For certification marks, see the nameplate.

We reserve the right to make changes in specifications and design without prior notice.

1. F-450MAJ(-C)

Single Phase

Model Number

F-450MAJ(-C)

AC Supply Voltage

115/60/1

Compressor

115V

8.4RLA 50LRA

Gear Motor

115V

2.4FLA 1/4HP

Fan Motor

115V

1FLA 50W

Other

115V

0.03A

Maximum Fuse Size

15 AMPS

Max. HACR Breaker

15 AMPS

(USA Only)

 

 

Max. Circuit Breaker

15 AMPS

(Canada Only)

 

 

Minimum Circuit

15 AMPS

Ampacity

 

 

Design Pressure

HI-427PSI LO-230PSI

Refrigerant

404A 15.2 OZ.

2. F-801M_J(-C)

Single Phase

Model Number

F-801MAJ(-C)

F-801MWJ(-C)

AC Supply Voltage

115/60/1

115/60/1

Compressor

115V

7.5RLA 54.5LRA

115V 7.5RLA 54.5LRA

Gear Motor

115V

3.0FLA 200W

115V 3.0FLA 200W

Fan Motor

115V

1.0FLA 1/15HP

– – –

Other

115V

0.03A

115V 0.03A

Maximum Fuse Size

15 AMPS

15 AMPS

Max. HACR Breaker

15 AMPS

15 AMPS

(USA Only)

 

 

 

Max. Circuit Breaker

15 AMPS

15 AMPS

(Canada Only)

 

 

 

Minimum Circuit

15 AMPS

15 AMPS

Ampacity

 

 

 

Design Pressure

HI - 467PSI LO - 250PSI

HI - 467PSI LO - 250PSI

Refrigerant

404A 1 LB. 12 OZ.

404A 10.7 OZ.

7

3. F-1002M_J(-C)

 

 

Single Phase

 

 

Model Number

F-1002MAJ(-C)

F-1002MWJ(-C)

F-1002MRJ(-C)

F-1002MLJ(-C)

AC Supply Voltage

115/60/1

115/60/1

115/60/1

115/60/1

Compressor

115V 11.2RLA

115V 10.7RLA

115V 11.2RLA

– – –

 

93LRA

93LRA

93LRA

 

Gear Motor

115V 3.0FLA 200W

115V 3.0FLA 200W

115V 3.0FLA 200W

115V 3.0FLA 200W

Fan Motor

115V 1.0FLA

– – –

115V 3A MAX

– – –

 

1/15HP

 

(Fan in URC)

 

Other

115V 0.03A

115V 0.03A

115V 0.53A

115V 0.53A

Maximum Fuse Size

20 AMPS

20 AMPS

20 AMPS

15 AMPS

Max. HACR Breaker

20 AMPS

20 AMPS

20 AMPS

15 AMPS

(USA Only)

 

 

 

 

Max. Circuit Breaker

20 AMPS

20 AMPS

20 AMPS

15 AMPS

(Canada Only)

 

 

 

 

Minimum Circuit

20 AMPS

20 AMPS

20 AMPS

15 AMPS

Ampacity

 

 

 

 

Design Pressure

HI-467PSI

HI-427PSI

HI-467PSI

HI-467PSI

 

LO-250PSI

LO-250PSI

LO-250PSI

LO-250PSI

Refrigerant

404A 2 LB. 4 OZ.

404A 12.3 OZ.

404A

Use only with 404A,

 

 

 

Total Refrigerant

407A, or 407F

 

 

 

Charge with

 

 

 

 

Hoshizaki Remote

 

 

 

 

Condenser Unit

 

 

 

 

URC-5F: 4 LB. 1.2

 

 

 

 

OZ.

 

4. F-1501M_J(-C)

Single Phase

Model Number

F-1501MAJ(-C)

F-1501MWJ(-C)

F-1501MRJ(-C)

AC Supply Voltage

208-230/60/1 (3 wire with

208-230/60/1 (3 wire with

208-230/60/1 (3 wire with

 

neutral)

neutral)

neutral)

Compressor

208-230V 9.3RLA 56LRA

208-230V 9.3RLA 56LRA

208-230V 9.3RLA 56LRA

Gear Motor

115V 5.6FLA 400W

115V 5.6FLA 400W

115V 5.6FLA 400W

Fan Motor

115V 1.0FLA 1/15HP

Cabinet: 115V 0.51FLA 8W

Cabinet: 115V 0.51FLA 8W

 

 

 

 

 

Remote: 115V 3A MAX

Other

115V

0.03A

115V

0.03A

115V

0.03A

Maximum Fuse Size

20 AMPS

20 AMPS

20 AMPS

Max. HACR Breaker

20 AMPS

20 AMPS

20 AMPS

(USA Only)

 

 

 

 

 

 

Max. Circuit Breaker

20 AMPS

20 AMPS

20 AMPS

(Canada Only)

 

 

 

 

 

 

Minimum Circuit

20 AMPS

20 AMPS

20 AMPS

Ampacity

 

 

 

 

 

 

Design Pressure

HI-467PSI LO-250PSI

HI-427PSI LO-250PSI

HI-467PSI LO-250PSI

Refrigerant

404A 2 LB. 5 OZ.

404A 1 LB 4.5 OZ.

404A

 

 

 

 

 

 

Total Refrigerant Charge

 

 

 

 

 

with Hoshizaki Remote

 

 

 

 

 

Condenser Unit URC-14F:

 

 

 

 

 

9 LB. 9 OZ.

8

5. F-2001M_J(-C)

Single Phase

Model Number

F-2001MWJ(-C)

F-2001MRJ(-C)

F-2001MLJ

AC Supply Voltage

208-230/60/1

208-230/60/1

115/60/1

Compressor

240V 10.8RLA 96LRA

240V 10.8RLA 96LRA

– – –

Gear Motor

120V 5.6 FLA 400W

120V 5.6 FLA 400W

120V 5.6 FLA 400W

Cabinet Fan Motor

115V 0.51 FLA 8W

115V 0.51 FLA 8W

115 0.51 FLA 8W

Remote Fan Motor

– – –

120V 3A MAX

 

Other

120V 0.03A

120V 0.03A

120V 0.3A

Maximum Fuse Size

30 AMPS

30 AMPS

15 AMPS

Max. HACR Breaker

30 AMPS

30 AMPS

15 AMPS

(USA Only)

 

 

 

Max. Circuit Breaker

30 AMPS

30 AMPS

15 AMPS

(Canada Only)

 

 

 

Minimum Circuit

30 AMPS

30 AMPS

15 AMPS

Ampacity

 

 

 

Design Pressure

HI-467PSI

HI-467PSI

HI-467PSI

 

LO-290PSI

LO-290PSI

LO-290PSI

Refrigerant

404A 2 LB.

404A

Use only with 404A,

 

 

Total Refrigerant Charge

407A, or 407F

 

 

with Hoshizaki Remote

 

 

 

Condenser Unit

 

 

 

URC-22F: 15 LB. 14 OZ.

 

6. F-2001MRJ3

Three Phase

Model Number

F-2001MRJ3

AC Supply Voltage

208-230/60/3

Compressor

240V 9.0RLA 75LRA

Gear Motor

120V 5.6 FLA 400W

Cabinet Fan Motor

115V 0.51 FLA 8W

Remote Fan Motor

120V 3A MAX

Other

120V 0.03A

Maximum Fuse Size

20 AMPS

Max. HACR Breaker

20 AMPS

(USA Only)

 

Max. Circuit Breaker

20 AMPS

(Canada Only)

 

Minimum Circuit

20 AMPS

Ampacity

 

Design Pressure

HI-467PSI

 

LO-290PSI

Refrigerant

404A

 

Total Refrigerant Charge

 

with Hoshizaki Remote

 

Condenser Unit

 

URC-22F: 15 LB. 14 OZ.

9

7. FD-650M_J-C

 

Single Phase

 

Model Number

FD-650MAJ-C

FD-650MWJ-C

FD-650MRJ-C

AC Supply Voltage

115/60/1

115/60/1

115/60/1

Compressor

115V 7.9RLA 54.5LRA

115V 5.5RLA 50LRA

115V 5.5RLA 50LRA

Gear Motor

120V 2.3FLA 1/4HP

120V 2.3FLA 1/4HP

120V 2.3FLA 1/4HP

Fan Motor

115V 1.0FLA 1/15HP (each)

-

120V 3A MAX (Fan in URC)

Other

115-120V 0.3A

115-120V 0.3A

115-120V 0.3A

Maximum Fuse Size

20 AMPS

20 AMPS

20 AMPS

Max. HACR Breaker

20 AMPS

20 AMPS

20 AMPS

(USA Only)

 

 

 

Max. Circuit Breaker

20 AMPS

20 AMPS

20 AMPS

(Canada Only)

 

 

 

Minimum Circuit

20 AMPS

20 AMPS

20 AMPS

Ampacity

 

 

 

Design Pressure

HI-427PSI LO-230PSI

HI-427PSI LO-230PSI

HI-427PSI LO-230PSI

Refrigerant

404A 12.4 OZ.

404A 15.0 OZ.

404A

 

 

 

Total Refrigerant Charge

 

 

 

with Hoshizaki Remote

 

 

 

Condenser Unit URC-5F:

 

 

 

4 LB. 1.2 OZ.

8. FD-1002M_J(-C)

Single Phase

Model Number

FD-1002MAJ-C

FD-1002MRJ-C

AC Supply Voltage

115/60/1

115/60/1

Compressor

115V

11.2RLA 93LRA

115V

11.2RLA 93LRA

Gear Motor

115V

3.0FLA 200W

115V

3.0FLA 200W

Fan Motor

115V

1.0FLA 1/15HP

115V

3A MAX (Fan in URC)

Other

115V

0.03A

115V

0.53A

Maximum Fuse Size

20 AMPS

20 AMPS

Max. HACR Breaker

20 AMPS

20 AMPS

(USA Only)

 

 

 

 

Max. Circuit Breaker

20 AMPS

20 AMPS

(Canada Only)

 

 

 

 

Minimum Circuit

20 AMPS

20 AMPS

Ampacity

 

 

 

 

Design Pressure

HI - 467PSI LO - 250PSI

HI - 467PSI LO - 250PSI

Refrigerant

404A 2 LB. 4.1 OZ.

404A

 

 

 

 

Total Refrigerant Charge

 

 

 

with Hoshizaki Remote

 

 

 

Condenser Unit URC-5F:

 

 

 

4 LB. 1.2 OZ.

10

B. Dimensions/Connections

1. Air-Cooled Models (MAJ(-C))

Units: mm [in.]

 

Side

 

 

 

 

 

 

 

 

 

Model Shown: F-801MAJ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F-450MAJ(-C)

F-801MAJ(-C)

F-1501MAJ(-C)

FD-650MAJ-C

 

 

 

 

 

F-1002MAJ(-C)

F-2001MAJ(-C)

FD-1002MAJ-C

 

A

560

[22]

560

[22]

768 [30-1/4]

560

[22]

 

B

556

[21-7/8]

556

[21-7/8]

756

[29-3/4]

556

[21-7/8]

 

C

395

[15-9/16]

395

[15-9/16]

602

[23-3/4]

395

[15-9/16]

 

D

558

[21-15/16]

659

[25-15/16]

874 [34-3/8]

659

[25-15/16]

 

E

499

[19-11/16]

599

[23-9/16]

817 [32-1/8]

599

[23-9/16]

 

F

476 [18-11/16]

575

[22-5/8]

731

[28-13/16]

575

[22-5/8]

 

G

169 [6-11/16]

169 [6-5/8]

165 [6-1/2]

169 [6-5/8]

 

H

22

[7/8]

24 [15/16]

25

[1]

 

24

[15/16]

 

I

42

[1-5/8]

35 [1-3/8]

44

[1-3/4]

37

[1-1/2]

 

J

64

[2-1/2]

67 [2-5/8]

87

[3-7/16]

64

[2-1/2]

 

K

672

[26-7/16]

675

[26-9/16]

676 [26-5/8]

587

[23-182]

 

L

695

[27-3/8]

692

[27-1/4]

699

[27-1/2]

607

[24]

 

M

260

[10-3/16]

-------

323

[12-11/16]

280

[11]

 

N

28

[1-1/8]

-------

30

[1-3/16]

28

[1-1/8]

 

O

370

[14-1/2]

-------

330

[13]

324

[12-11/16]

 

P

104 [4-1/8]

-------

113 [4-1/2]

106 [4-3/16]

 

NOTICE

Allow 6" (15 cm) clearance at rear and sides for proper air circulation and ease of maintenance and/or service should they be required. Allow 24" (61 cm) clearance at top to allow for removal of the auger.

The dispenser unit/ice storage bin opening must accommodate the bottom opening as in the illustration.

Rear

Model Shown: F-801MAJ

Bottom

F-801 and F-1002

Model Shown: F-801MAJ

Bottom

F-450, F-1501,

FD-650, and FD-1002

Model Shown: FD-650MAJ-C

11

2. Water-Cooled Models (MWJ(-C))

Units: mm [in.]

Side

Model Shown: F-801MWJ

F-801MWJ(-C) F-1501MWJ(-C) FD-650MWJ-C F-1002MWJ(-C) F-2001MWJ(-C)

A

560

[22]

768 [30-1/4]

560

[22]

B

550

[21-5/8]

756

[29-3/4]

550

[21-5/8]

C

395

[15-9/16]

602

[23-3/4]

395

[15-9/16]

D

659

[25-15/16]

874 [34-3/8]

659

[25-15/16]

E

599

[23-9/16]

817

[32-1/8]

599

[23-5/8]

F

575

[22-5/8]

731

[28-13/16]

575

[22-5/8]

G

169 [6-5/8]

165

[6-1/2]

169 [6-5/8]

H

24

[15/16]

25 [1]

23

[7/8]

I

41

[1-5/8]

44 [1-3/4]

43

[1-3/4]

J

67

[2-5/8]

87 [3-7/16]

62

[2-1/2]

K

185 [7-5/16]

371

[14-5/8]

235

[9-1/4]

L

145 [5-11/16]

139

[5-1/2]

95

[3-3/4]

M 80

[3-1/8]

127

[5]

83

[3-1/4]

N

675

[26-9/16]

676

[26-5/8]

587

[23-1/8]

O

695

[27-3/8]

699

[27-1/2]

607

[24]

Q

-------

323

[12-11/16]

280

[11]

R

-------

30 [1-3/16]

28

[1-1/8]

S

-------

330

[13]

324

[12-11/16]

T

-------

113 [4-1/2]

106 [4-3/16]

NOTICE

Allow 6" (15 cm) clearance at rear and sides for proper air circulation and ease of maintenance and/or service should they be required. Allow

24" (61 cm) clearance at top to allow for removal of the auger.

The dispenser unit/ice storage bin opening must accommodate the bottom opening as in the illustration.

Rear

Model Shown: F-801MWJ

Bottom

F-801 and F-1002

Model Shown: F-801MWJ

Bottom

F-1501 and FD-650

Model Shown: FD-650MWJ-C

12

3. Remote Models (MRJ/3(-C))

Units: mm [in.]

Side

Model Shown: FD-650MRJ-C

 

F-1002MRJ(-C)

F-1501MRJ(-C)

FD-650MRJ-C

 

 

 

 

 

 

 

FD-1002MRJ-C

 

 

 

 

 

 

 

F-2001MRJ/3(-C)

A

560

[22]

768 [30-1/4]

560

[22]

B

556

[21-7/8]

756

[29-3/4]

556

[21-7/8]

C

395

[15-9/16]

602

[23-3/4]

395

[15-1/2]

D

659

[25-15/16]

874 [34-3/8]

659

[26]

E

599

[23-9/16]

817 [32-1/8]

599

[23-5/8]

F

575

[22-5/8]

731

[28-13/16]

575

[22-5/8]

G

169 [6-5/8]

165 [6-1/2]

169 [6-5/8]

H

24

[15/16]

25

[1]

23

[7/8]

I

35

[1-3/8]

44

[1-3/4]

43

[1-3/4]

J

65

[2-1/2]

87

[3-7/16]

62

[2-1/2]

K

434

[17-1/16]

524

[20-5/8]

434

[17-1/8]

L

40

[1-9/16]

92

[3-5/8]

70

[2-3/4]

M

100 [3-15/16]

154 [6]

60

[2-3/8]

N

70

[2-3/4]

70

[2-3/4]

70

[2-3/4]

O

673

[26-1/2]

676 [26-5/8]

587

[23-1/8]

P

708

[27-3/4]

699

[27-1/2]

607

[23-13/16]

Q

-------

323

[12-11/16]

280

[11]

R

-------

30

[1-3/16]

28

[1-1/8]

S

-------

330

[13]

324

[12-11/16]

T

-------

113 [4-1/2]

106 [4-3/16]

NOTICE

Allow 6" (15 cm) clearance at rear and sides for proper air circulation and ease of maintenance and/or service should they be required. Allow

24" (61 cm) clearance at top to allow for removal of the auger.

The dispenser unit/ice storage bin opening must accommodate the bottom opening as in the illustration.

Rear

Model Shown: FD-650MRJ-C

Bottom

F-1002

Model Shown: FD-650MRJ-C

Bottom

F-1501,

FD-650, and FD-1002

Model Shown: FD-650MRJ-C

13

4. Low Side, Parallel Rack System Models (MLJ)

Units: mm [in.]

 

 

Side

 

 

Rear

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F-2001MLJ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F-1002MLJ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bottom

 

 

F-1002MLJ

 

F-2001MLJ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

560

[22]

 

768

[30-1/4]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

555

[21-7/8]

 

762

[30]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

395

[15-9/16]

 

602 [23-11/16]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D

658

[25-7/8]

 

874 [34-7/16]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E

598

[23-1/2]

 

817

[32-3/16]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F

575

[22-5/8]

 

705 [27-3/4]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

G

169 [6-5/8]

 

165

[6-1/2]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

24

[15/16]

 

24

[15/16]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I

35

[1-3/8]

 

43

[1-11/16]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J

64

[2-1/2]

 

75

[2-15/16]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K

434 [17-1/16]

 

524 [20-5/8]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L

40 [1-9/16]

 

92 [3-5/8]

 

 

 

 

 

 

 

 

 

 

 

F-1002MLJ

 

M

60

[2-3/8]

 

62

[2-7/16]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bottom

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTICE

• Allow 6" (15 cm) clearance at rear and sides for proper air circulation and ease of maintenance and/or service should they be required. Allow 24" (61 cm) clearance at top to allow for removal of the auger.

• The dispenser unit/ice storage bin

F-2001MLJ

opening must accommodate the

 

bottom opening as in the illustration.

 

14

Hoshizaki F2001MLJ, F1501MRJC, F2001MWJ, F1002MWJ, FD1002MRJC User Manual

5. Remote Condenser Unit URC-5F

(use with F-1002MRJ(-C), FD-650MRJ-C, FD-1002MRJ-C)

Units: mm [in.]

NOTICE

Allow 24" (61 cm) clearance at front and rear for proper air circulation and ease of maintenance and/or service should they be required.

 

URC-5F Heat of Rejection

Icemaker

AT 90°F (32°C)

Model

WT 70°F (21°C)

F-1002MRJ

7,660 BTU/hr

F-1002MRJ-C

7,840 BTU/hr

FD-650MRJ-C

4,900 BTU/hr

FD-1002MRJ-C

8,900 BTU/hr

Top

Rear

6.Remote Condenser Unit URC-14F (use with F-1501MRJ(-C))

NOTICE

Allow 24" (61 cm) clearance at front and rear for proper air circulation and ease of maintenance and/or service should they be required.

 

URC-14F Heat of Rejection

Icemaker

AT 90°F (32°C)

Model

WT 70°F (21°C)

F-1501MRJ

13,194 BTU/hr

F-1501MRJ-C

 

Units: mm [in.]

Top

Rear

15

7.Remote Condenser Unit URC-22F (use with F-2001MRJ/3(-C))

NOTICE

Allow 24" (61 cm) clearance at front and rear for proper air circulation and ease of maintenance and/or service should they be required.

Units: mm [in.]

Top

 

URC-22F Heat of Rejection

 

AT 90°F (32°C)

Icemaker Model

WT 70°F (21°C)

F-2001MRJ

16,475 BTU/hr

F-2001MRJ-C

17,690 BTU/hr

F-2001MRJ3

16,890 BTU/hr

Rear

16

Loading...