Honeywell THX9321 Prestige, THX9421 Prestige Product Information Sheet

PRODUCT DATA
68-0311-03
THX9321 Prestige
®
2.0 and
THX9421 Prestige
®
IAQ
with EIM

APPLICATION

effortless, 7-Day programmable color touchscreen thermostat
that provides control of temperature, humidification,
dehumidification, and ventilation for up to 4 Heat/2 Cool heat
pump systems or up to 3 Heat/2 Cool conventional systems
for residential and commercial applications.

FEATURES

RedLINK™ Compatible
Increase your content and profit per job by including
RedLINK™ accessories that meet your customers comfort
and convenience needs. RedLINK accessories include the
Wireless Outdoor Sensor, Portable Comfort Control (PCC),
Equipment Interface Module (EIM), RedLINK Internet
Gateway, Wireless Indoor Sensor, TrueSTEAM™ humidi-
fier with Wireless Adapter, TrueZONE™ zoning panel with
Wireless Adapter, Vent Boost Remote and Entry/Exit
Remote.
Customizable Service Reminders
Set up to 10 service reminders. Choose from the pre-set
options or customize your own. Reminders based on date
or the outdoor temperature.
Delta T Alerts and Diagnostics
Alerts give customers a sense of security while allowing
you to service or replace the equipment prior to a loss of
heating or cooling. Based on limits you set at installation,
customers can be alerted when their system is not operat-
ing as expected. The system alert will instruct customers to
contact you for assistance. Requires Equipment Interface
Module.
Delta T Installer Test
Save time by viewing Delta T while running a system test to
verify proper operation. Requires Equipment Interface
Module.
Universal Inputs
EIM - S1, S2, S3, S4
Assignable inputs allow you to setup Indoor and Outdoor
Temperature Sensors, Discharge and Return Air Sensors
or Dry Contact Devices. Dry Contact Devices can be used
to trip pre-set or customized alerts on the thermostat home
screen. Requires Equipment Interface Module.
Data Logs
The thermostat stores an Alerts Log, User Interactions Log
and a Performance Log to quickly determine if an issue is
caused by a system error or an accidental user error. Note:
The Performance Log only applies to the THX9421
thermostat.
Selectable for Residential and Light Commercial
Applications
One thermostat does it all to meet the needs of Residential
and Light Commercial applications. Simply select Residen-
tial or Commercial during the installer setup. If Commercial
is selected, the thermostat will use commercial language,
meet building codes and offer 365 day holiday scheduling.
USB Port for Quick Installer Setup
Save time by using a USB stick to upload installer settings,
and service reminders in one simple step.
Selectable Sensors
When paired with a Wireless Indoor Sensor(s) you have
the ability to choose which sensor(s) to use for tempera-
ture, humidification and dehumidification. They can be
used in combination for temperature averaging—or individ-
ually—to condition humidity levels in separate spaces.
THX9321 Prestige
®
2.0
THX9421 Prestige
®
IAQ with EIM
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
68-0311—03 2
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further information,
or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Environmental and Combustion Controls Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
3. http://customer.honeywell.com or http://customer.honeywell.ca
International Sales and Service Offices in all principal cities of the world. Manufacturing in Belgium, Canada, China, Czech
Republic, Germany, Hungary, Italy, Mexico, Netherlands, United Kingdom, and United States.

CONTENTS

Application ........................................... 1
Specifications ...................................... 3
Ordering Information ........................... 2
System Installation .............................. 8
When Installing this Product... ..................... 8
Installing Equipment Interface Module (if used)
10
Wiring 24 Vac Common ................................ 10
Selecting Discharge and Return Air Temperature
Sensor Mounting Locations ......................... 10
Selecting Discharge and Return Air Temperature Sensor
Mounting Locations .............................................. 10
Selecting Return Air Temperature Sensor Mounting Loca-
tion ....................................................................... 11
Selecting Thermostat Location .................... 12
Installing Wallplate ........................................ 12
Power Optional REDLINK™ Accessories ... 14
Linking Thermostat to Equipment Interface Mod-
ule (if used) .................................................... 15
Linking RedLINK™ Accessories ................. 16
Mounting Optional Accessories .................. 70
Alerts and Diagnostics ....................... 87
Delta T Diagnostics ....................................... 87
Before You Set Up Delta T Diagnostics ....... 87
Setting up Alerts and Diagnostics ............... 88
Delta T Alerts ................................................. 90
Delta T Alerts and Utility Saver Switches ... 91
Data Logs ....................................................... 91
Alerts Log ............................................................. 92
User Interactions Log ........................................... 93
Dry Contact Alerts ........................................ 95
Installer Tests ...................................... 68
Using the Equipment Test ............................ 69
Using the Wireless Signal Strength Test .... 69
Indoor Air Quality (IAQ) Control ......... 102
Humidification ............................................... 102
Set up Humidification ........................................... 102
Control Humidification Level ................................ 104
Dehumidification - Residential ..................... 105
Set up Dehumidification With Cooling System ..... 105
Set up Dehumidification With Whole House Dehumidifier
106
Set up Dehumidification Away Mode .................... 108
Control Dehumidification Level ............................. 108
Dehumidification - Commercial ................... 109
Set up Dehumidification With Cooling System ..... 109
Set up Dehumidification With Dehumidifier .......... 110
Control Dehumidification Level ............................. 112
Ventilation ...................................................... 112
Set up Ventilation ................................................. 113
IAQ Reminders ..................................... 116
Customizable Reminders ................... 116
USB Port ............................................... 119
Heat Pump and Backup Heat Operation
100
Portable Comfort Control ................... 129
Remote Indoor Sensors ...................... 130
Commercial Features .......................... 121
Ramp Rates ................................................... 123
Custom Names .............................................. 124
Remote Setback ............................................ 124
Economizer and Time of Day (TOD) Operation
126
Pre-Occupancy Purge ................................... 126
Staging Control ............................................. 97
Optional Accessories .......................... 128
Troubleshooting .................................. 159
Wiring ................................................... 135
EIM Wiring Diagrams .................................... 138
Geothermal Radiant Heat ............................. 100
THX9321 Thermostat Wiring Diagrams ....... 141
THX9321 Thermostat Wiring Diagrams Using Uni-
versal Relays to Control Heating or Cooling 142
Wiring IAQ Equipment or a Heat/Cool Stage to the
Universal Terminals ...................................... 149
Economizer Module Wiring Diagrams ......... 151
Wiring C7089U1006 Outdoor Sensor .......... 153
Wiring guide — Wired Indoor Sensors ........ 154
Regulatory Information ....................... 159
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
3 68-0311—03

SPECIFICATIONS

Thermostat Description:
Electrical Ratings for:
Equipment Interface Module and the THX9321 Prestige 2.0
Thermostat
NOTE: To find what terminals are available on the Equip-
ment Interface Module and the Prestige Thermo-
stats, see “Terminal Designations” below the
table.
Terminal Designations:
Equipment Interface Module: R, RC, RH, C, W-O/B,
W2-AUX 1, W3-AUX 2, Y, Y2, G, A-L/A, U1 U1, U2 U2,
U3 U3, S1 S1, S2 S2, S3 S3, S4 S4, A, B, C, D
THX9421 Thermostat: R, C
THX9321 Thermostat: R, RC, C, W-O/B, W2-AUX/E, Y,
Y2, G, A-L/A, K, U1 U1, U2 U2
Power Consumption of THX9421/THX9321:
Full brightness = 3.0 VA
1/2 brightness = 2.1 VA
Backlight off = 1.9 VA
RedLINK Communication:
Frequency: 900 Mhz frequency range
Re-Sync Time: RedLINK devices re-establish communication
within 6 minutes after AC power resumes.
Temperature Setting Range:
Heating: 40 to 90 °F (4.5 to 32 °C).
Cooling: 50 to 99 °F (10 to 37 °C).
Temperature Sensor Accuracy: ± 1.5 °F at 70 °F (0.75 °C at
21.0 °C)
Humidification Setting Range:
10% to 60% RH.
Dehumidification Setting Range:
40% to 80% RH.
Humidity Display Range:
0% to 99%.
Humidity Sensor Accuracy: ± 5% RH from 30% to 50% RH
at 75 °F (24 °C).
Cool Indication:
Prestige 2.0 and Prestige IAQ 2.0 displays “Cool On” when the
thermostat turns the cooling on.
Heat Indication:
Prestige 2.0 and Prestige IAQ 2.0 displays “Heat On” when the
thermostat turns the heating on.
Auxiliary Heat Indication:
Prestige 2.0 and Prestige IAQ 2.0 displays “Auxiliary Heat On”
when the thermostat turns the auxiliary heat on.
Interstage Differential:
Comfort: The thermostat keeps the indoor temperature within 1
degree of the setpoint (droop less control). The thermostat
turns on stage 2 when the capacity on stage 1 reaches
90%.
When the interstage differential is set to 1.0 or higher, the ther-
mostat stages the equipment based on how far the indoor
temperature is from the setpoint (ISU 3030 to 3090). See
page 31 for more information.
Clock Accuracy: ± 1 minute per month at 77 °F (25 °C). ± 2
minutes per month over the operating ambient temperature
range.
Mounting Means:
Thermostat mounts directly on the wall in the living space
using mounting screws and anchors provided. Fits a hori-
zontal 2 x 4 in. junction box.
Equipment Interface Module (EIM) mounts on HVAC equip-
ment or on a wall in the equipment room.
Feature Description
Powering method Common wire only
System types (up to
4 heat/2 cool heat
pump and up to 3
heat/2 cool
conventional)
Gas, oil or electric heat with air
conditioning
Warm air, hot water, high-efficiency
furnaces, heat pumps, steam and
gravity
Cool only
Changeover Manual or Auto changeover selectable
System setting Em Heat-Heat-Off-Cool-Auto
Fan setting Auto-On-Circ-Follow Schedule
Ter minal
Volt ag e
(50/60 Hz)
Max. Current
Rating
W - O/B 18 to 30 VAC and
750 mVDC
1.00A
Y (cooling) 18 to 30 VAC 1.00A
G (fan) 18 to 30 VAC 0.50A
W2 - Aux 1 (heating) 18 to 30 VAC 0.60A
W3 - Aux 2 (heating) 18 to 30 VAC 0.60A
Y2 (cooling) 18 to 30 VAC 0.60A
A-L/A (Output) 18 to 30 VAC 1.00A
U1, U1
U2, U2
U3, U3
18 to 30 VAC 0.50A
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
68-0311—03 4
Fig. 1. Dimensions of THX9421 Prestige IAQ thermostat in
in. (mm).
Fig. 2. Dimensions of THX9421 Prestige IAQ cover plates
in in. (mm).
Fig. 3. Dimensions of THX9321 Prestige
®
2.0 thermostat in
in. (mm).
Fig. 4. Dimensions of THX9321 Prestige 2.0 cover plate in
in. (mm).
Fig. 5. Dimensions of Equipment Interface Module in in.
(mm).
M34630
3-5/16 (84)
3-1/2
(89)
4-1/2 (115)
7/8
(22)
M34262
1-25/32
(46)
5-33/64
(140)
2-1/8
(54)
4-21/64
(110)
1-25/32
(46)
6-7/8
(175)
2-1/8
(54)
5
(127)
M33329A
6-13/16 (173)
3-5/16 (84)
1-7/16
(36)
3-7/8
(99)
M33330
3-19/64 (84)
7-29/32 (201)
5-1/2
(140)
M33331
4-53/64 (123)
8-7/8
(225)
9-11/32
(237)
1-19/32
(41)
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
5 68-0311—03
Table 1. Prestige Kits.
Kit
Part Number
Included in Kit
Part Number Description
Prestige IAQ Kit
YTHX9421R5101WW
THX9421R5021WW Thermostat - White Front, White Side
THM5421R1021 Equipment Interface Module
C7089R1013 Wireless Outdoor Sensor
50062329-001 Discharge/Return Sensors (Qty. 2)
Prestige IAQ Kit
YTHX9421R5101BB
THX9421R5021BB Thermostat - Black Front, Black Side
THM5421R1021 Equipment Interface Module
C7089R1013 Wireless Outdoor Sensor
50062329-001 Discharge/Return Sensors (Qty. 2)
Prestige IAQ Kit
YTHX9421R5101SG
THX9421R5021SG Thermostat - Silver Front, Gray Side
THM5421R1021 Equipment Interface Module
C7089R1013 Wireless Outdoor Sensor
50062329-001 Discharge/Return Sensors (Qty. 2)
Prestige IAQ Kit
YTHX9421R5101WG
THX9421R5021WG Thermostat - White Front, Gray Side
THM5421R1021 Equipment Interface Module
C7089R1013 Wireless Outdoor Sensor
50062329-001 Discharge/Return Sensors (Qty. 2)
Prestige IAQ Kit
YTHX9421R5085WW
THX9421R5021WW Thermostat - White Front, White Side
THM5421R1021 Equipment Interface Module
50062329-001 Discharge/Return Sensors (Qty. 2)
Prestige IAQ Kit
YTHX9421R5085BB
THX9421R5021BB Thermostat - Black Front, Black Side
THM5421R1021 Equipment Interface Module
50062329-001 Discharge/Return Sensors (Qty. 2)
Prestige IAQ Kit
YTHX9421R5085SG
THX9421R5021SG Thermostat - Silver Front, Gray Side
THM5421R1021 Equipment Interface Module
50062329-001 Discharge/Return Sensors (Qty. 2)
Prestige IAQ Kit
YTHX9421R5085WG
THX9421R5021WG Thermostat - White Front, Gray Side
THM5421R1021 Equipment Interface Module
50062329-001 Discharge/Return Sensors (Qty. 2)
Prestige 2.0 Kit
YTHX9321R5061
THX9321R5030 Thermostat
REM5000R1001 Portable Comfort Control
C7089R1013 Wireless Outdoor Sensor
Prestige 2.0 Kit
YTHX9321R5079
THX9321R5030 Thermostat
C7089R1013 Wireless Outdoor Sensor
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
68-0311—03 6
Table 2. Thermostat Replacement Parts and Accessories.
Product Part Number
Operating
Ambient
Temperature
Operating
Relative Humidity
Shipping
Temperature
Physical Dimensions in in.
(mm) Color(s)
Thermostat THX9421R5021WW 32 to 120 °F
(0 to 48.9 °C)
5% to 90%
Non-Condensing
-20 to 120 °F
(-28.9 to 48.9 °C)
4-1/2 x 3-1/2 x 7/8
(115 x 88 x 22)
Front-White,
Side-White
THX9421R5021BB 32 to 120 °F
(0 to 48.9 °C)
5% to 90%
Non-Condensing
-20 to 120 °F
(-28.9 to 48.9 °C)
4-1/2 x 3-1/2 x 7/8
(115 x 88 x 22)
Front-Black,
Side-Black
THX9421R5021SG 32 to 120 °F
(0 to 48.9 °C)
5% to 90%
Non-Condensing
-20 to 120 °F
(-28.9 to 48.9 °C)
4-1/2 x 3-1/2 x 7/8
(115 x 88 x 22)
Front-Silver,
Side-Gray
THX9421R5021WG 32 to 120 °F
(0 to 48.9 °C)
5% to 90%
Non-Condensing
-20 to 120 °F
(-28.9 to 48.9 °C)
4-1/2 x 3-1/2 x 7/8
(115 x 88 x 22)
Front-White,
Side-Gray
THX9321R5030 32 to 120 °F
(0 to 48.9 °C)
5% to 90%
Non-Condensing
-20 to 120 °F
(-28.9 to 48.9 °C)
6-13/16 x 3-7/8 x 1-7/16
(173 x 99 x 36)
Arctic
White
Equipment Interface
Module
YTHM5421R1010*
THM5421R1021
-40 to 165 °F
(-40 to 73.9 °C)
5% to 95%
Non-Condensing
-20 to 165 °F
(-28.9 to 73.9 °C)
9-11/32 x 4-53/64 x 1-19/32
(237 x 123 x 41)
Gray
Wireless Adapter
(For TrueZONE,
TrueSTEAM or
extend wireless
range of EIM)
THM4000R1000 -40 to 165 °F
(-40 to 73.9 °C)
5% to 95%
Non-Condensing
-20 to 165 °F
(-28.9 to 73.9 °C)
5-9/16 x 4-3/8 x 1-1/4
(141 x 112 x 32)
Gray
RedLINK Internet
Gateway
THM6000R1002 32 to 120 °F
(0 to 48.9 °C)
5% to 95%
Non-Condensing
-20 to 120 °F
(-28.9 to 48.9 °C)
6 x 4-7/8 x 2-1/2
(152 x 124 x 64)
Black
Portable Comfort
Control
REM5000R1001 32 to 120 °F
(0 to 48.9 °C)
5% to 90%
Non-Condensing
-20 to 120 °F
(-28.9 to 48.9 °C)
6-1/4 x 3-1/8 x 1-5/8
(158 x 80 x 38)
Arctic White
Gray
Wireless Entry/Exit
Remote
REM1000R1003 32 to 120 °F
(0 to 48.9 °C)
5% to 90%
Non-Condensing
-20 to 120 °F
(-28.9 to 48.9 °C)
3-15/16 x 1-15/16 x 5/8
(101 x 50 x 16)
Arctic White
Wireless Vent and
Filter Boost Remote
HVC20A1000 32 to 120 °F
(0 to 48.9 °C)
5% to 90%
Non-Condensing
-20 to 120 °F
(-28.9 to 48.9 °C)
3-15/16 x 1-15/16 x 5/8
(101 x 50 x 16)
Arctic White
Wireless Outdoor
Sensor
C7089R1013 -40 to 140 °F
(-40 to 60 °C)
0% to 100%
Condensing
-40 to 120 °F
(-40 to 48.9 °C)
5 x 3-1/2 x 1-11/16
(127 x 89 x 43)
Gray
Wireless Indoor
Sensor
C7189R1004 0 to 120 °F
(-17.8 to 48.9 °C)
For optimal
Battery Life:
35 to 114 °F
(1.7 to 45.6 °C)
5% to 90%
Non-Condensing
-20 to 120 °F
(-28.9 to 48.9 °C)
2-7/8 x 1-7/8 x 15/16
(74 x 48 x 24)
Arctic White
Wired Outdoor
Sensor
(10K ohm Negative
Temperature
Coefficient)
C7089U1006 -40 to 120 °F
(-40 to 48.9 °C)
5% to 95%
Non-Condensing
-40 to 130 °F
(-40 to 54.4 °C)
1-1/2 (38) - -
Wired Wall Mount
Indoor Sensor
(10K ohm Negative
Temperature
Coefficient)
C7189U1005 45 to 88 °F
(7 to 32 °C)
5% to 95%
Non-Condensing
-20 to 120 °F
(-28.9 to 48.9 °C)
2-9/32 x 1-1/2 x 11/16
(58 x 38 x 18)
Premier
White
Wired Wall Mount
Indoor Sensor
(20K ohm Negative
Temperature
Coefficient)
TR21 45 to 99 °F
(7 to 37 °C)
5% to 95%
Non-Condensing
-40 to 150 °F
(-40 to 65.5 °C)
4-9/16 x 3 x 7/8
(116 x 76.5 x 22)
White
Wired Wall Mount
Indoor Sensor
(10K ohm Negative
Temperature
Coefficient)
TR21-A 45 to 99 °F
(7 to 37 °C)
5% to 95%
Non-Condensing
-40 to 150 °F
(-40 to 65.5 °C)
4-9/16 x 3 x 7/8
(116 x 76.5 x 22)
White
Wired Flush Mount
Indoor Sensor
(20K ohm Negative
Temperature
Coefficient)
C7772A1004 45 to 99 °F
(7 to 37 °C)
5% to 95%
Non-Condensing
-40 to 150 °F
(-40 to 65.5 °C)
4-1/2 x 2-3/4 x 5/16
(114 x 70 x 8)
Brushed
Stainless
Steel
Wired Flush Mount
Indoor Sensor
(20K ohm Negative
Temperature
Coefficient)
C7772A1012 45 to 99 °F
(7 to 37 °C)
5% to 95%
Non-Condensing
-40 to 150 °F
(-40 to 65.5 °C)
4-1/2 x 2-3/4 x 5/16
(114 x 70 x 8)
Brushed
Stainless
Steel
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
7 68-0311—03
* Prestige IAQ Kits and YTHM5421R1010 Kit include 50062329-001 Discharge/Return Air Sensors. Replacement Discharge/
Return Air Sensor part number is C7735A1000.
Discharge or Return
Air Sensor
(10K ohm Negative
Temperature
Coefficient)
C7735A1000* 0 to 200 °F
(- 17.8 to 93.3 °C)
- - -20 to 120 °F
(-28.9 to 48.9 °C)
Probe:
3-3/4 x 1/4 (77 x 6.4)
Cap Diameter:
2-7/16 (62)
Gray
Discharge or Return
Air Sensor
(20K ohm Negative
Temperature
Coefficient)
C7041 - - - - - - 4-3/16 x 2-5/16 x 1-11/16
(107 x 59 x 43)
- -
Discharge or Return
Air Sensor
(20K ohm Negative
Temperature
Coefficient)
C7770A1006 45 to 99 °F
(7 to 37 °C)
5% to 95%
Non-Condensing
-40 to 150 °F
(-40 to 65.5 °C)
Probe: 6 x 1/4
(152 x 6.4)
- -
Occupancy Sensor
for Remote Setback
(Requires an
Equipment Interface
Module)
WSK-24 Receiver:
- 5 to 140 °F
(-21 to 60 °C)
Door Sensor:
-4 to 140 °F
(-20 to 60 °C)
PIR Sensor:
-4 to 104 °F
(-20 to 40 °C)
- - - - Receiver:
3.6 x 3.4 x 1.2
(91.4 x 86.4 x 30.5)
Door Sensor:
1.4 x 2.3 x 0.6
(35.8 x 57.6 x 15.2)
PIR Sensor:
2.8 x 3.9 x 1.1
(71 x 100 x 28)
White
THX9421
Coverplate
(covers marks left
by old thermostats)
THP2400A1027W
(Includes 2 cover
plates)
- - - - - - Small = 5-33/64 x 4-21/64
(140 x 110), Large = 6-7/8 x
5 (175 x 127)
White
THX9421
Coverplate
(covers marks left
by old thermostats)
THP2400A1027B
(Includes 2 cover
plates)
- - - - - - Small = 5-33/64 x 4-21/64
(140 x 110), Large = 6-7/8 x
5 (175 x 127)
Black
THX9421
Coverplate
(covers marks left
by old thermostats)
THP2400A1027G
(Includes 2 cover
plates)
- - - - - - Small = 5-33/64 x 4-21/64
(140 x 110), Large = 6-7/8 x
5 (175 x 127)
Gray
THX9321
Coverplate
(covers marks left
by old thermostats)
50028399-001 - - - - - - 7-29/32 x 5-1/2 (201 x 140) White
Wire Saver Module THP9045A1023 -40 to 163 °F
(-40 to 73 °C)
5% to 90%
Non-Condensing
-40 to 185 °F
(-40 to 85 °C)
- - Gray
Table 2. Thermostat Replacement Parts and Accessories. (Continued)
Product Part Number
Operating
Ambient
Temperature
Operating
Relative Humidity
Shipping
Temperature
Physical Dimensions in in.
(mm) Color(s)
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
68-0311—03 8

SYSTEM INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to follow the
instructions can damage the product or cause a hazard-
ous condition.
2. Check the ratings given in the instructions to make sure
the product is suitable for your application.
3. Installer must be a trained, experienced service
technician.
4. After completing installation, use these instructions to
verify the product operation.

Finding Your Password (Date Code)

You will need the thermostat password to:
Make changes to the Installer Setup.
Setup Diagnostics.
Perform an Installer Test.
View Data Logs.
Add, remove, rename or view connected RedLINK
accessories.
Reset the thermostat to Factory Default settings.
The password (Date Code) is located on the back of the
thermostat. It can also be found by following these steps:
1. Touch Menu.
2. Select Dealer Information.
Fig. 6. Finding thermostat password.
Fig. 7. Finding thermostat password.
1324
1324
Password
(Date Code)
Dealer Informaon
OK
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
9 68-0311—03

INSTALLATION OPTIONS

The THX9321 Prestige
®
2.0 thermostat is wired directly to the equipment. The THX9421 Prestige
®
IAQ thermostat is used with the
Equipment Interface Module or with a TrueZONE Wireless Adapter.
If using the Equipment Interface Module, see “Installing Equipment Interface Module (if used)” beginning on page 10.
If using a TrueZONE wireless adapter, follow the installation instructions that came with the TrueZONE, and go to “Selecting
Thermostat Location” beginning on page 12.
Guidelines for Installing RedLINK
Devices
When installing more than one Thermostat and Equip-
ment Interface Module, mount the Equipment Interface
Modules at least 2 feet apart for best RedLINK perfor-
mance. No minimum distance is required between the
Thermostats if the Thermostat is linked to an Equip-
ment Interface Module.
When the Thermostat is wired directly to the equipment
(No Equipment Interface Module and No TrueZONE
Wireless Adapter), mount the Thermostats at least 2
feet apart for best RedLINK performance.
To determine if a RedLINK device will communicate
properly in the installed location, during the connection
process, press and quickly release the connect button
on the RedLINK device at the desired mounting loca-
tion. If the RedLINK device connects, then it will work
reliably during normal operation. If the RedLINK device
does NOT connect, try a new location. During the con-
nection process, the signal is sent at low power and
during normal operation the signal is sent at high
power.
To connect a RedLINK device, make sure to press and
quickly release the connect button on the RedLINK
device. Press and holding the connect button down too
long will not allow the device to connect.
If you link the Thermostat to the TrueZONE Wireless
Adapter, you will NOT be able to do the following: con-
trol humidification, dehumidification or ventilation, setup
a program schedule remotely from a computer, smart
phone or tablet, work with the Wireless Indoor Sensor,
Entry / Exit Remote or the Vent and Filter Boost
Remote. To use these features, wire the Thermostat
directly to the zone panel or use an Equipment Inter-
face Module.
If you are using a RedLINK device from a previous
installation, you must reset the device first before you
re-connect it to the new Thermostat/Equipment Inter-
face Module. See page 134 for more information.
TM
TM
OR
THX9421 THERMOSTAT –
2 WIRES FOR POWER
RedLINK TO EQUIPMENT INTERFACE MODULE
RedLINK TO TrueZONE WIRELESS ADAPTER
THX9421 THERMOSTAT
2 WIRES FOR POWER
THX9321 THERMOSTAT
WIRED DIRECTLY TO EQUIPMENT
OR
MCR34631
W
I
R
E
D
D
I
R
E
C
T
L
Y
T
O
E
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
68-0311—03 10
Installing Equipment Interface
Module (if used)
If no Equipment Interface Module is used, skip to “Selecting
Thermostat Location” beginning on page 12.
NOTE: If an EIM is mounted inside a metal cabinet, such
as a commercial rooftop unit, it is recommended
to use a THM4000R1000 Wireless Adapter for
extended wireless range. Mount the Wireless
Adapter outside the metal cabinet and connect to
the ABCD terminals at the EIM. The Wireless
Adapter functions as a remote antenna for the
EIM. After it is wired to the EIM, it automatically
takes over as the antenna for RedLINK communi-
cation. For best RedLINK performance, avoid
mounting the Wireless Adapter above the roof
deck or outside the exterior walls.
NOTE: If you install more than one thermostat and EIM,
the EIMs must be at least 2 feet apart for best
RedLINK performance.
Fig. 8.
CAUTION
Electrical Hazard.
Can cause electrical shock or equipment damage.
Disconnect power before wiring.
The Equipment Interface Module (EIM) can be mounted
vertically on the HVAC equipment or on a wall in the equipment
room.
1. Mount the EIM near the HVAC equipment or on the
equipment itself. Use screws and anchors as appropriate
for the mounting surface..
2. To wire the EIM, strip 1/4” insulation, then insert wires
(see Fig. 9). For wiring diagrams, see “Wiring” beginning
on page 135.
Fig. 9.

Wiring 24 Vac Common

Single-Transformer System—Connect the common side of
the transformer to the C screw terminal of the EIM. Leave
the metal jumper wires in place between R, RC, and RH.
Two-Transformer System—Connect the common side of the
cooling transformer to the C screw terminal of the EIM.
Remove the metal jumper wire between RC and RH.
Connect the hot side of heating transformer to RH and leave
the jumper wire between R and RC and connect the hot
side of cooling transformer to R or RC.
Selecting Discharge and Return Air
Temperature Sensor Mounting
Locations
Refer to the guidelines below and Fig. 10–14 for mounting
locations of the Discharge and Return Air Temperature
Sensors.
Selecting Discharge Air Temperature
Sensor Mounting Location
1. Mount the Discharge Air Temperature Sensor on the
supply duct in a location where the air is mixed well.
Mount the Discharge Air Temperature Sensor out of sight
of the A-Coil/Heat Exchanger when possible. See Fig.
10.
2. When possible, mount the Discharge Air Temperature
Sensor upstream of a Steam Humidifier, a Fan Powered
Humidifier or a Dehumidifier that is ducted to the supply.
See Fig. 11–12.
3. If space does not allow a Discharge Air Temperature
Sensor upstream of a Steam Humidifier or Fan Powered
Humidifier, mount the Discharge Air Temperature Sensor
downstream of the Humidifier. See Fig. 11. When setting
the Delta T Limits (see “Set Delta T Limits” on page 90),
be sure to consider the affect that the humidifier has on
Delta T.
4. If a Bypass Humidifier is installed, mount the Discharge
Air Temperature Sensor downstream of the Bypass
Humidifier. See Fig. 13–14.
EIM
A
B
C
D
WIRELESS
ADAPTER
CONNECT
POWER
THM4000R
CONNECTED
WIRELESS SETUP
MCR32389
R
C
Y
Y2
G
L
W
O/B
W2
AUX1
W3
AUX2
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
11 68-0311—03
Selecting Return Air Temperature
Sensor Mounting Location
1. Install the Return Air Temperature Sensor on the return
duct in a location where the air is mixed well. Mount the
Return Air Temperature Sensor downstream of a Bypass
Humidifier, Dehumidifier or Ventilator. See Fig. 10–14.
Fig. 10.
Fig. 11.
Fig. 12.
Fig. 13.
MOUNT DISCHARGE
SENSOR HERE
M33074
HEAT
EXCHANGER
BLOWER
VENTILATOR
OR
DEHUMIDIF IER
MOUNT RETURN
SENSOR HERE
DOWNSTREAM OF
VENTILATOR OR
DEHUMIDIFIER
A-COIL
M33075A
HEAT
EXCHANGER
BLOWER
STEAM OR
FAN
POWERED
HUMIDIFIER
ALTERNATE MOUNTING LOCATION FOR DISCHARGE
SENSOR. WHEN SETTING THE LIMITS, BE SURE TO
CONSIDER THE AFFECT THAT THE HUMIDIFIER HAS
ON DELTA T.
MOUNT RETURN
SENSOR HERE
DOWNSTREAM OF
VENTILATOR OR
DEHUMIDIFIER
MOUNT
DISCHARGE
SENSOR HERE
ABOVE CENTER
OF A-COIL
UPSTREAM OF
STEAM OR FAN
POWERED
HUMIDIFIER
VENTILATOR
OR
DEHUMIDIF IER
M33076A
HEAT
EXCHANGER
BLOWER
MOUNT RETURN
SENSOR HERE
DOWNSTREAM OF
DEHUMIDIFIER
ALTERNATE MOUNTING LOCATION FOR DISCHARGE
SENSOR. WHEN SETTING THE LIMITS, BE SURE
TO CONSIDER THE AFFECT THAT THE DEHUMIDIFIER
HAS ON DELTA T.
MOUNT
DISCHARGE
SENSOR HERE
ABOVE CENTER
OF A-COIL
UPSTREAM OF
DEHUMIDIFIER
DEHUMIDIF IER
MOUNT RETURN
SENSOR HERE
MOUNT DOWNSTREAM
OF BYPASS HUMIDIFIER,
DEHUMIDIFIER OR
VENTILATOR
HEAT
EXCHANGER
BLOWER
VENTILATOR
OR
DEHUMIDIF IER
MOUNT
DISCHARGE
SENSOR HERE
MOUNT
DOWNSTREAM
OF BYPASS
HUMIDIFIER
BYPASS
HUMIDIFIER
M33078A
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
68-0311—03 12
Fig. 14.
Installing Discharge and Return Air
Temperature Sensors
Use the following steps to mount the Discharge/Return Air
Sensors:
1. Attach plastic cover to the sensor probe.
2. Drill 1/4-inch hole for the sensor probe and mount it to
the ductwork with enclosed screws (see Fig. 15).
3. Connect wires to S1, S2, S3, or S4 terminals at the EIM.
4. Setup the S1, S2, S3, or S4 terminals in the Installer
Setup at the thermostat.
Fig. 15. Mounting Discharge/Return Air Sensor.

Selecting Thermostat Location

Install the thermostat about 5 ft. (1.5m) above the floor in an area
with good air circulation at average temperature. See Fig. 16.
Fig. 16. Selecting thermostat location.
Do not install the thermostat where it can be affected by:
Drafts or dead spots behind doors and in corners.
Hot or cold air from ducts.
Radiant heat from sun or appliances.
Concealed pipes and chimneys.
Unheated (uncooled) areas such as an outside wall behind
the thermostat.

Installing Wallplate

CAUTION
Electrical Hazard.
Can cause electrical shock or equipment damage.
Disconnect power before wiring.
The thermostat can be mounted horizontally on the wall or on a
4 in. x 2 in. (101.6 mm x 50.8 mm) wiring box.
1. Separate wallplate from thermostat.
Fig. 17. Separate wallplate from thermostat (THX9421).
2. Position and level the wallplate (for appearance only).
3. Use a pencil to mark the mounting holes.
MOUNT RETURN
SENSOR HERE
MOUNT DOWNSTREAM
OF BYPASS HUMIDIFIER,
DEHUMIDIFIER OR
VENTILATOR
HEAT
EXCHANGER
BLOWER
VENTILATOR
OR
DEHUMIDIF IER
MOUNT
DISCHARGE
SENSOR HERE
BYPASS
HUMIDIFIER
M33079A
M32995
5 FEET
[1.5 METERS]
YES
NO
NO
NO
M19925
1324
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
13 68-0311—03
4. Remove the wallplate from the wall and, if drywall, drill
two 3/16-in. holes in the wall, as marked. For firmer
material such as plaster, drill two 7/32-in. holes. Gently
tap anchors (provided) into the drilled holes until flush
with the wall.
5. Position the wallplate over the holes, pulling wires
through the wiring opening. See Fig. 18.
6. Insert the mounting screws into the holes and tighten.
Fig. 18. Mounting wallplate (THX9421).
Insert Coin Cell Battery in Thermostat
Place coin cell battery in thermostat. Be sure to follow polarity
markings on thermostat. See Fig. 19.
NOTE: Coin cell battery saves time and date during a
power loss.
Fig. 19. Insert coin cell battery (THX9421)
THX9421 Installation
INSTALLATION WITH EQUIPMENT INTERFACE MODULE
(EIM)
1. Wire to C and R terminals of the EIM or to a separate 24
volt transformer (not provided). See Fig. 20.
2. Snap thermostat onto wallplate after wiring is complete.
INSTALLATION WITH TRUEZONE WIRELESS ADAPTER
1. Wire to C and R terminals of the TrueZONE panel or to a
separate 24 volt transformer (not provided). See Fig. 20.
2. Snap thermostat onto wallplate after wiring is complete.
THX9321 Installation
THERMOSTAT WIRED DIRECTLY TO THE HVAC
EQUIPMENT OR ZONE PANEL
1. Refer to “THX9321 Thermostat Wiring Diagrams” begin-
ning on page 141.
2. Snap thermostat onto wallplate after wiring is complete.
INSTALLATION WITH EQUIPMENT INTERFACE MODULE
(EIM)
1. Connect power and common from the EIM to the Rc and
C terminals at the thermostat or use a separate 24 volt
transformer (not provided) to power the thermostat.
2. Snap thermostat onto wallplate after wiring is complete.
NOTE: Note: When the THX9321 thermostat is used with
an EIM, the relays in the thermostat do not func-
tion.
INSTALLATION WITH TRUEZONE WIRELESS ADAPTER
1. Connect power and common from the TrueZONE panel
to the Rc and C terminals at the thermostat or use a sep-
arate 24 volt transformer (not provided) to power the
thermostat.
2. Snap thermostat onto wallplate after wiring is complete.
NOTE: When the THX9321 thermostat is used with a
TrueZONE Wireless Adapter, the relays in the
thermostat do not function.
Fig. 20. Inserting wires in thermostat terminal screws
(THX9421).
MCR34688
R
C
1324
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
68-0311—03 14
Mount Thermostat on Wallplate
Align thermostat to wallplate and snap into place. See Fig. 19.
Fig. 21. Mount thermostat (THX9421).
POWER OPTIONAL REDLINK™
ACCESSORIES
1. Install batteries or power the optional RedLINK accesso-
ries.
2. If no RedLINK accessories are used, skip to “Linking
Thermostat to Equipment Interface Module (if used)”
beginning on page 15.
3. If no RedLINK accessories are used and there is no EIM
or TrueZONE Wireless Adapter, skip to “Completing Ini-
tial Setup” beginning on page 17.
Outdoor Air Sensor
1. Install 2 fresh AA lithium batteries.
Fig. 22.
Portable Comfort Control
1. Install 3 fresh AA alkaline batteries.
Fig. 23.
Indoor Air Sensor
1. Install 2 fresh AAA alkaline batteries.
Fig. 24.
RedLINK™ Internet Gateway
1. Connect power cord to an electrical outlet not controlled
by a wall switch.
2. Connect ethernet cable to router and the RedLINK Inter-
net Gateway.
Fig. 25.
R
C
MCR32937
MCR32939
MCR32938
M32940
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
15 68-0311—03
TrueSTEAM
1. Wire and power TrueSTEAM.
2. Connect the ABCD terminals between TrueSTEAM and
the THM4000 Wireless Adapter.
3. Adjust the DIP Switches on TrueSTEAM as follows when
using the Wireless Adapter:
DIP3: UP
DIP4: UP
DIP5: DOWN
Fig. 26. Powering TrueSTEAM wireless adapter.
Entry/Exit Remote or Vent Boost Remote
1. Remove the cover.
2. Insert the CR2450 coin cell battery (included) into the
slot at the bottom of the remote. See polarity marking on
the remote.
Fig. 27. Installing Entry/Exit Remote or Vent Boost Remote
battery.
3. The LED will briefly flash green. If it flashes red, battery
is not good.

PERFORMING INITIAL SETUP

Initial setup options define the type of system you are installing:
Residential or commercial
Non-zoned or zoned
Used with or without an Equipment Interface Module
(THM5421)
Used with or without the TrueZONE Wireless Adapter
(THM4000)
1. Follow prompts on the screen to select the appropriate
options.
Fig. 28.
NOTE: If you are connecting the thermostat to the True-
ZONE Wireless Adapter (THM4000), refer to the
TrueZONE instructions to link the thermostat and
RedLINK accessories.
Linking Thermostat to Equipment
Interface Module (if used)
1. Press and quickly release the CONNECT button on the
EIM. Make sure the Connected light is flashing green.
Fig. 29. EIM CONNECT button.
NOTE: If the Connected light does NOT flash green,
another system may be in the listening mode.
Please exit the listening mode at the other system
and then try again.
Green flashing: In Listening Mode. System is ready
to add RedLINK devices.
Green steady: RedLINK devices are communicating.
Red: RedLINK device(s) not communicating. Check
EIM and RedLINK devices.
THM4000R1000
TrueSTEAM
MCR31476
6
543
2
ON
OFF
1
MCR33269
Next
CONNECT
CONNECTED
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
68-0311—03 16
2. Follow the prompts on the thermostat screen until you
reach the Wireless Setup screen. See Fig. 30.
Fig. 30.
3. While the Connected light is flashing green on the EIM,
press Next on the thermostat. After a short delay, the
screen will display Device Connected.
Fig. 31.
4. Press Next, as directed on screen, to link RedLINK
accessories.

Linking RedLINK™ Accessories

Fig. 32. Connect RedLINK accessories.
1. When you see the prompt Do you have RedLINK
accessories to connect? touch Yes or No.
a. If you select No, continue to step 5.
b. If you select Yes, you will be prompted to Press Con-
nect on New Accessories. Continue to step 2.
NOTE: Accessories must be at least 2 feet away from the
thermostat or EIM during the linking process.
2. While the Add Device screen is displayed (listening
mode), press and quickly release the CONNECT button
on each new RedLINK accessory.
NOTE: For locations of CONNECT buttons on
RedLINK accessories, see “Locating the Con-
nect Buttons on RedLINK Accessories” begin-
ning on page 18.
Fig. 33. Thermostat in listening mode.
3. After a short delay (up to 20 seconds), check the thermo-
stat to confirm the connection of each RedLINK acces-
sory.
Fig. 34. Thermostat in listening mode.
4. Touch Done at the thermostat after all new RedLINK
accessories are connected.
NOTE: The thermostat displays a countdown timer
while in the listening mode. If it detects no activ-
ity for 15 minutes, it exits the listening mode.
Next
Next
Done
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
17 68-0311—03

Completing Initial Setup

5. Finish the setup by selecting the desired options. Touch
Done after you select the last option you want to change.
See “Installer Options” beginning on page 21 for a full
listing of setup options.
Fig. 35. Scheduling options.
6. The thermostat now displays its Home screen and the
thermostat setup is complete.
Fig. 36. Thermostat home screen.
Adding RedLINK Accessories to the
Thermostat
If you want to add RedLINK accessories after the thermostat
has been setup, follow these steps.
1. Touch Menu.
2. Select Installer Options.
Fig. 37.
3. Enter password (date code) and touch Done. See “Find-
ing Your Password (Date Code) to Access Installer
Options” beginning on page 20 for more information.
Fig. 38.
4. Select Wireless Device Manager.
Fig. 39.
5. Select Add Device to display the Add Device screen. The
thermostat is now in listening mode.
Fig. 40.
NOTE: Accessories must be at least 2 feet away from the
thermostat or EIM during the linking process.
Installer Opons
Done
Wireless Device Manager
Add Device
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
68-0311—03 18
6. Press and quickly release the CONNECT button on each
new RedLINK accessory.
NOTE: For locations of CONNECT buttons on
RedLINK accessories, see “Locating the Con-
nect Buttons on RedLINK Accessories” begin-
ning on page 18.
Fig. 41. Thermostat in listening mode.
7. After a short delay (up to 20 seconds), check thermostat
to confirm the connection of each RedLINK accessory.
8. Touch Done at the thermostat after all new RedLINK
accessories are connected.
Fig. 42. Thermostat in listening mode.
NOTE: Thermostat displays a count-down timer while in
the listening mode. If it detects no activity for 15
minutes, it exits listening mode.
Locating the Connect Buttons on
RedLINK Accessories
Wireless Outdoor Sensor
1. Press and quickly release the CONNECT button on the
Wireless Outdoor Sensor. After a short delay (up to 15
seconds), the thermostat will display “Wireless Outdoor
Sensor added.
Fig. 43. Wireless outdoor sensor connect button.
Portable Comfort Control
1. Press CONNECT on the Portable Comfort Control dis-
play screen.
Fig. 44. Portable Comfort Control connect button.
2. Press DONE on the Portable Comfort Control when it
displays “Connected.
3. Press “No” at the next screen to save and exit, or press
“Yes” if you need to connect additional thermostats to the
Portable Comfort Control. See Fig. 45.
NOTE: The Portable Comfort Control can control up to 16
thermostats.
Fig. 45. Connect additional thermostats to Portable
Comfort Control.
4. Follow the same linking procedure as above to connect
additional thermostats.
Done
MCR28847A
MCR32942
CONNECT
WIRELESS SETUP
NOYES
CONNECT MORE?
M28482
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
19 68-0311—03
ERROR MESSAGES:
E1 29: Incompatible device cannot be connected.
E1 34: Low RF signal. Move device to a different location and
try again.
E1 38: Make sure the thermostat, EIM, or TrueZONE Wireless
Adapter is in Wireless Setup mode, and the Portable Comfort
Control is at least 2 feet away (600 mm).
NOTE: The linking procedure will time out if there is no
keypress for 30 minutes. To begin again, press
and hold in the lower right corner of the screen
until the display changes (about 3 seconds). See
Fig. 46.
Fig. 46. Restarting the linking process.
RedLINK Internet Gateway
1. Press and quickly release the button on the bottom of the
Internet Gateway. After a short delay, the RedLINK sta-
tus light will glow steady green.
Fig. 47. RedLINK Internet Gateway connect button.
NOTE: The Internet Gateway must be registered online
before use at www.mytotalconnectcomfort.com.
Enter the MAC ID and MAC CRC numbers located
on the bottom of the Internet Gateway. For addi-
tional information, see instructions provided with
the device.
TrueSTEAM
1. Press and quickly release the CONNECT button on
THM4000 Wireless Adapter. After a short delay, the
CONNECTED status light will glow steady green.
Fig. 48. Connect button on TrueSTEAM wireless adapter.
Wireless Indoor Sensor
1. Press and quickly release the CONNECT button. After a
short delay, the status light (see Fig. 49) will glow green
for 15 seconds. If the status light turns red, the sensor
did not link with the thermostat.
Fig. 49. Wireless indoor sensor connect button and status
light.
NOTE: In normal operation, the status light remains off.
If it begins flashing red, batteries are low (power
will be depleted after 2–3 weeks).
2. If you are installing more than 1 wireless indoor sensor,
give each sensor a name as you install it. Press Name
Device, as shown in Fig. 50.
Fig. 50.
Press and hold
the blank space
(or arrow may be
present)
MCR32943
THM4000R1000
TrueSTEAM
MCRXXXXX
MCR32934
MCR32935
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
68-0311—03 20
3. Type the sensor name and press Done. The sensor
names are used when selecting which sensor to use for
temperature, humidification, and dehumidification con-
trol.
Fig. 51.
NOTE: If you link more than 1 wireless indoor sensor,
and forget to name them, you will be prompted
to name each wireless indoor sensor after you
exit wireless setup. See Fig. 52.
Fig. 52.
Linking Entry/Exit Remote or Vent Boost
Remote
1. Press and quickly release the CONNECT button.
Fig. 53. Connect button and status light on Entry/Exit
Remote or Vent Boost Remote.
2. After a short delay, the status light will glow green for 15
seconds. If the status light turns red, the remote did not
link with the thermostat for the connection process.
NOTE: The thermostat can work with up to 3 Entry/Exit
remotes. Each Entry/Exit remote can control up to
16 thermostats.
NOTE: The thermostat can work with up to 6 Vent Boost
remotes.
Finding Your Password (Date Code)
to Access Installer Options
You will need the thermostat password to:
Make changes to the Installer Setup.
Setup Diagnostics.
Perform an Installer Test.
View Data Logs.
Add, remove, rename or view connected RedLINK
accessories.
Reset the thermostat to Factory Default settings.
The password (Date Code) is located on the back of the
thermostat.
Fig. 54. Finding thermostat password.
The password (Date Code) can also be found by following
these steps:
1. Touch Menu.
2. Select Dealer Information.
Fig. 55. Finding thermostat password.
1324
1324
Password
(Date Code)
Dealer Informaon
OK
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
21 68-0311—03

Installer Options

The following options are available when you access Installer
Options. For more information on each, press Help on the
thermostat or see Table 3.
Fig. 56. Installer Options screen.
NOTE: You can use the thermostat USB port to download
all Installer Setup settings, including your com-
pany name and contact information. You can
upload this data to each thermostat you install, to
save time.

Making Changes to Installer Setup

Follow these steps to set system options after initial
installation.
NOTE: Use a USB device to save set up time. See “USB
Port” beginning on page 119 for more informa-
tion.
1. Touch Menu.
2. Select Installer Options.
Fig. 57.
3. Enter password (Date Code) and touch Done. See “Find-
ing Your Password (Date Code) to Access Installer
Options” beginning on page 20 for more information.
Fig. 58.
4. Select Create Setup.
Fig. 59.
5. Follow prompts on the screen to select the desired setup
options. See Table 4 for Installer Setup options.
Table 3. Installer Options.
Menu Item Description
Create Setup Press CREATE SETUP to set all system
settings one by one.
View/Edit
Current Setup
Press VIEW/EDIT CURRENT SETUP to
select a specific function and make quick
changes
Set Up
Diagnostics
Press SET UP DIAGNOSTICS to set up
and test Delta T diagnostics.
Installer Test Press INSTALLER TEST to quickly
determine if the heat, cool, fan and
thermostat are operating properly. Minimum
off timers are ignored during the test
Data Logs Press DATA LOGS to view the Alerts Log,
User Interactions Log, and Performance
Logs.
Wireless Device
Manager
Press WIRELESS DEVICE MANAGER to
add, remove, rename, or view the
connected wireless accessories.
Advanced
Options
Press ADVANCED OPTIONS to setup the
thermostat using a USB device or to restore
the thermostat to the factory default
settings.
NOTE: If the THX9321 has been setup
WITHOUT an Equipment Interface Module
or the TrueZONE Wireless Adapter and you
would like to add one, you must reset the
thermostat back to factory defaults.
Installer Opons
Done
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
68-0311—03 22
Table 4. Installer Setup (ISU) Table.
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes
1000 Language
English
Français
Español
English Both No
1010 Application
Residential
Commercial
Residential Both No
1020 Zone Number
1-16
1 Both No This ISU is only displayed on a thermostat
that is controlling a zone panel through the
THM4000 Wireless Adapter.
1030 Device Name
[Enter Device Name]
Thermostat Both No The Portable Comfort Control remote and
Web Interface displays the name of the
thermostat that you enter on this screen.
1030 Display on Home
Screen
No
Yes
(select check box)
No Commercial No Thermostat location (name) can be
displayed on the home screen. This feature
is typically used when multiple
thermostat's are mounted in a manager's
office or equipment room. This allows you
to quickly identify which thermostat is in
control of a specific zone or area.
1040 Scheduling Options
Non-Programmable
Programmable
Programmable Both No
1050 Temperature
Indication Scale
Fahrenheit
Celsius
Fahrenheit Both No
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
23 68-0311—03
1060 Outdoor Air Sensor
No
Yes
No Both No This ISU automatically defaults to Yes
when a Wireless Outdoor Sensor is
connected.
An Outdoor Sensor is required to set the
following ISUs:
ISU 3120 Outdoor Temperature Lockouts
(Compressor Lockout and Backup Heat
Lockout)
ISU 4050 Outdoor Temperature used with
Minimum Heat Recovery Ramp Rate
ISU 4060 Outdoor Temperature used with
Maximum Heat Recovery Ramp Rate
ISU 4070 Outdoor Temperature used with
Minimum Cool Recovery Ramp Rate
ISU 4080 Outdoor Temperature used with
Maximum Cool Recovery Ramp Rate
ISU 8050 Humidification - Window
Protection
ISU 10130 Ventilation Low Temperature
Lockout
ISU 10130 Ventilation High Temperature
Lockout
ISU 10130 Ventilation High Dew Point
Lockout (requires Wireless Outdoor
Sensor)
ISU 13070 Allow Heat Delta T Diagnostics
when Outdoor Temperature is [Out. Temp.
Range]
ISU 13080 Allow Heat Delta T Diagnostics
when Outdoor Humidity is [Out. Humidity
Range]
ISU 13110 Allow Backup Heat Delta T Diag.
when Outdoor Temperature is [Out. Temp.
Range]
ISU 13120 Allow Backup Heat Delta T
Diagnostics when Outdoor Humidity is
[Out. Humidity Range]
ISU 13150 Allow Cool Delta T Diagnostics
when Outdoor Temperature is [Out. Temp.
Range]
ISU 13160 Allow Cool Delta T Diagnostics
when Outdoor Temperature is [Out.
Humidity Range]
2000 Heating System
Type
Conventional Forced Air Heat
Heat Pump
Radiant Heat
Other
None (Cool Only)
Conventional
Forced Air Heat
Both No
Table 4. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
68-0311—03 24
2010 Heating Equipment
Type
Conventional Forced Air Heat:
Standard Efficiency Gas Forced Air
High Efficiency Gas Forced Air
Oil Forced Air
Electric Forced Air
Hot Water Fan Coil
Other
Heat Pump:
Air to Air Heat Pump
Geothermal Heat Pump
Geothermal Radiant Heat
Radiant Heat:
Hot Water Radiant Heat
Geothermal Radiant Heat
Steam
Other
Other:
Gravity
Other
Default varies
based on
previous
selections
Both No Cycle Rate and Fan Operation automatically
default to the correct settings based on the
equipment type selected.
This ISU is not displayed when ISU 2000
Heating System Type is set to None (Cool
Only).
See “Geothermal Radiant Heat” beginning
on page 100.
2030 What Terminals are
Wired to Radiant
Heat?
None
U1
U2
U3
Default varies
based on
previous
selections
Both No This ISU is only displayed when ISU 2010
Heating Equipment Type is Geothermal
Radiant Heat.
Geothermal Radiant Heat must be wired to
a universal terminal (U1, U2, or U3).
U1, U2 and U3 are normally open dry
contacts when configured for a stage of
Heat. U1, U2 and U3 require power from
the system transformer or a separate
transformer.
U3 is only available on the Equipment
Interface Module (EIM).
2040 What Terminals are
Wired to Radiant
Heat - Stage 2?
None
U1
U2
U3
Default varies
based on
previous
selections
Both No This ISU is only displayed when ISU 2010
Heating Equipment Type is Geothermal
Radiant Heat.
Geothermal Radiant Heat must be wired to
a universal terminal (U1, U2, or U3).
U1, U2 and U3 are normally open dry
contacts when configured for a stage of
Heat. U1, U2 and U3 require power from
the system transformer or a separate
transformer.
U3 is only available on the Equipment
Interface Module (EIM).
Table 4. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
25 68-0311—03
2050 Geothermal Forced
Air System
None
Used for Cooling Only
Used for Heating and Cooling
Used for
Heating and
Cooling
Both No This thermostat has the capability of
controlling Geothermal Radiant Heat,
Geothermal Forced Air and Backup Heat.
If this thermostat is not controlling the
Geothermal Forced Air System, select
None. This setting is typically used if the
thermostat is only controlling Geothermal
Radiant Heat.
If this thermostat is using the Geothermal
Forced Air System for cooling and not for
heating, select Used for Cooling Only.
If this thermostat is using the Geothermal
Forced Air System for both heating and
cooling, select Used for Heating and
Cooling.
2060 Reversing Valve
O/B
O (O/B on Cool)
B (O/B on Heat)
O/B on Cool Both No Only displayed if the equipment type is Air
to Air Heat Pump, Geothermal Heat Pump
or Geothermal Radiant Heat.
2070 Cool Stages /
Compressor
Stages
1-4
1 if ISU 1010 is
Residential
2 if ISU 1010 is
Commercial
Both No Conventional:
Cool Stage 3 and 4 are only available if ISU
1010 is Commercial.
Cool Stage 3 and 4 must be wired to a
universal terminal (U1, U2 or U3).
Heat Pumps:
Maximum of 2 Compressor Stages for heat
pump systems.
2020,
2070
Heat Stages /
Backup Heat
Stages
1 - 3
Default is 1
stage if ISU
1010
Application is
Residential
Default is 2
stages if ISU
1010
Application is
Commercial
Both No Maximum of 3 Heat Stages for
conventional systems.
Maximum of 2 Backup Heat Stages for
systems with more than 1 heating
equipment type.
2080 What Terminals are
Wired to Cool -
Stage 3?
None
U1
U2
U3
Default varies
based on
previous
selections
Commercial No Cool Stage 3 is only available if ISU 1010 is
Commercial.
Cool Stage 3 must be wired to a universal
terminal (U1, U2 or U3).
U1, U2 and U3 are normally open dry
contacts when configured for a stage of
Cool. U1, U2 and U3 require power from a
system transformer or a separate
transformer.
U3 is only available on the Equipment
Interface Module (EIM).
Table 4. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
68-0311—03 26
2090 What Terminals are
Wired to Cool -
Stage 4?
None
U1
U2
U3
Default varies
based on
previous
selections
Commercial No Cool Stage 4 is only available if ISU 1010 is
Commercial.
Cool Stage 4 must be wired to a universal
terminal (U1, U2 or U3).
U1, U2 and U3 are normally open dry
contacts when configured for a stage of
Cool. U1, U2 and U3 require power from a
system transformer or a separate
transformer.
U3 is only available on the Equipment
Interface Module (EIM).
2100 What Terminals are
Wired to Heat -
Stage 3?
None
U1
U2
U3
Default varies
based on
previous
selections
Both No THX9321 Thermostat Only:
This ISU is only displayed on the THX9321
thermostat when it is wired directly to the
equipment (Equipment Interface Module is
NOT used).
Heat Stage 3 must be wired to a universal
terminal (U1 or U2).
U1 and U2 are normally open dry contacts
when configured for a stage of Heat. U1
and U2 require power from a system
transformer or a separate transformer.
2110 Fan Operation in
Heat
No Fan
Equipment Controls Fan
Thermostat Controls Fan
Thermostat
Controls Fan
Both No This ISU is only displayed when ISU 2010
Heating Equipment Type is Electric Forced
Air, Hot Water Fan Coil or Other.
The thermostat automatically defaults to
Equipment Controls Fan when ISU 2010
Heating Equipment Type is Standard
Efficiency Gas Forced Air, High Efficiency
Gas Forced Air or Oil Forced Air.
No Fan is only displayed when ISU 2010
Heating Equipment Type is Other.
2120 Backup Heat Type
None
Standard Efficiency Gas Forced Air
High Efficiency Gas Forced Air
Oil Forced Air
Electric Forced Air
Hot Water Fan Coil
Hot Water Radiant Heat
Other
None Both No This ISU is only displayed when ISU 2010
Heating Equipment Type is Hot Water
Radiant Heat, Steam, Hot Water Fan Coil,
Electric Forced Air or Other.
The list of Backup Heat Types will vary
based on the type of primary heat selected
at ISU 2010 Heating Equipment Type.
When ISU 2010 Heating Equipment Type is
Hot Water Radiant Heat, the thermostat
keeps the Hot Water Radiant Heat on when
it calls for Backup Heat.
When ISU 2010 Heating Equipment Type is
Steam, the thermostat keeps the Steam
Heat on when it calls for Backup Heat.
When ISU 2010 Heating Equipment Type is
Hot Water Fan Coil, Electric Forced Air or
Other, you can select how the backup
operates. See ISU 2150 Backup Heat
Operation.
Table 4. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
27 68-0311—03
2130 Backup Heat
Stages
0 - 2
1 Both No This ISU is only displayed when a backup
heat source is selected at ISU 2120 Backup
Heat Type.
Maximum of 2 Backup Heat stages.
2140 What Terminals are
Wired to Backup
Heat?
None
U1
U2
Default varies
based on
previous
selections
Both No THX9321 Thermostat Only:
This ISU is only displayed on the THX9321
thermostat when it is wired directly to the
equipment (Equipment Interface Module is
NOT used).
The thermostat can support up to 3
conventional heat stages. When there are a
total of 3 conventional heat stages, the last
stage of heat must be wired to U1 or U2.
U1 and U2 are normally open dry contacts
when configured for a stage of Heat. U1
and U2 require power from a system
transformer or a separate transformer.
2150 Backup Heat
Operation
NOT Allowed to Run with Primary
Heat
Allowed to Run with Primary Heat
NOT allowed to
run with
Primary Heat
Both No This ISU is only displayed when ISU 2010
Heating Equipment Type is Hot Water Fan
Coil, Electric Forced Air or Other.
When ISU 2010 Heating Equipment Type is
Hot Water Fan Coil, Electric Forced Air or
Other, you can select how the Backup Heat
operates. The thermostat can be setup to
keep the primary heat source on when it
calls for Backup Heat or the thermostat can
be setup to turn off the primary heat source
when it calls for Backup Heat.
When ISU 2010 Heating Equipment Type is
Hot Water Radiant Heat, the thermostat
keeps the Hot Water Radiant Heat on when
it calls for Backup Heat.
When ISU 2010 Heating Equipment Type is
Steam, the thermostat keeps the Steam
Heat on when it calls for Backup Heat.
2160 Backup Heat Fan
Operation
No Fan
Equipment Controls Fan
Thermostat Controls Fan
Thermostat
Controls Fan
Both No This ISU is only displayed for conventional
systems when ISU 2120 Backup Heat Type
is Electric Forced Air, Hot Water Fan Coil
or Other.
Backup Heat Fan Operation automatically
defaults to Equipment Controls Fan when
ISU 2120 Backup Heat Type is Standard
Efficiency Gas Forced Air, High Efficiency
Gas Forced Air or Oil Forced Air.
No Fan is only displayed when ISU 2120
Backup Heat Type is Other.
Table 4. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
68-0311—03 28
2170 What Terminals are
Wired to Backup
Heat - Stage 2?
None
U1
U2
Default varies
based on
previous
selections
Both No THX9321 Thermostat Only:
This ISU is only displayed on the THX9321
thermostat when it is wired directly to the
equipment (Equipment Interface Module is
NOT used).
The thermostat can support up to 2 backup
heat stages for heat pump applications.
When there are 2 backup heat stages,
backup heat stage 2 must be wired to U1 or
U2.
U1 and U2 are normally open dry contacts
when configured for a stage of Heat. U1
and U2 require power from a system
transformer or a separate transformer.
2180 Backup Heat Type
Electric Forced Air
Standard Efficiency Gas Forced Air
High Efficiency Gas Forced Air
Oil Forced Air
Hot Water Fan Coil
Hot Water Radiant Heat
Other
Electric Forced
Air
Both No This ISU is only displayed when ISU 2010
Heating Equipment Type is Air to Air Heat
Pump, Geothermal Heat Pump or
Geothermal Radiant Heat and there is at
least one stage of backup heat.
See “Heat Pump and Backup Heat
Operation” beginning on page 100.
2190 External Fossil Fuel
Kit
Thermostat Controls Backup Heat
External Fossil Fuel Kit Controls
Backup Heat
Thermostat
Controls
Backup Heat
Both No This ISU is only displayed when ISU 2010
Heating Equipment Type is Air to Air Heat
Pump, Geothermal Heat Pump or
Geothermal Radiant Heat and ISU 2180
Backup Heat Type is Standard Efficiency
Gas Forced Air, High Efficiency Gas
Forced Air or Oil Forced Air.
2200 Backup Heat
Operation
NOT allowed to Run with Heat
Pump
Allowed to Run with Heat Pump
Default varies
based on
previous
selections
Both No This ISU is only displayed when ISU 2010
Heating Equipment Type is Air to Air Heat
Pump, Geothermal Heat Pump or
Geothermal Radiant Heat and ISU 2180
Backup Heat Type is Hot Water Fan Coil or
Other.
Not Allowed to Run with Heat Pump: The
thermostat turns off the heat pump when it
calls for backup heat.
Allowed to Run with Heat Pump: The
thermostat keeps the heat pump on when it
calls for backup heat.
Table 4. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
29 68-0311—03
2210 Backup Heat Fan
Operation
No Fan
Equipment Controls Fan
Thermostat Controls Fan
Default varies
based on
previous
selections
Both No This ISU is only displayed for heat pumps
when ISU 2180 Backup Heat Type is Other.
Backup Heat Fan Operation:
Electric Forced Air: Thermostat Controls
Fan
Standard Efficiency Gas Forced Air:
Equipment Controls Fan
High Efficiency Gas Forced Air: Equipment
Controls Fan
Oil Forced Air: Equipment Controls Fan
Hot Water Fan Coil: Thermostat Controls
Fan
Hot Water Radiant Heat: Not Applicable
2220 A-L/A Terminal
Setup
None
Time Of Day
Economizer
Heat Pump Failure Indication
None Commercial No This ISU is only displayed when ISU 1010
Application is Commercial.
Note: When the thermostat is setup for
Residential, the L/A terminal operates as
described under “Heat Pump Failure
Indication.” The L/A terminal requires no
setup for residential applications.
None: The A-L/A terminal is not used.
Time of Day: The A-L/A terminal is
energized during Occupied periods and
when the user overrides the temperature.
The terminal is de-energized during
Unoccupied periods and in Standby mode.
Economizer: The thermostat controls an
economizer module to provide ventilation
during Occupied periods and free cooling
when outdoor conditions are favorable. The
A-L/A terminal is energized during
Occupied periods and during a call for
cooling in Unoccupied periods. See
“Economizer and Time of Day (TOD)
Operation” beginning on page 126.
Notes: The economizer module determines
when outdoor conditions are favorable for
free cooling. Delta T Diagnostics is not
available when the thermostat is setup for
an Economizer.
Heat Pump Failure Indication: When 24
volts is detected on the L/A terminal
(compressor monitor), the thermostat
displays a message to alert the user when
the heat pump requires service. The L/A
terminal sends a continuous output to a
zone panel when the thermostat is set to
Emergency Heat mode. The zone panel will
not turn on the heat pump when a zone is
set to Emergency Heat mode.
Table 4. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
68-0311—03 30
3000 Changeover
Manual
Automatic
Manual:
if ISU 1010 is
Residential
Automatic:
if ISU 1010 is
Commercial
Both No Manual: The user must select heating or
cooling as needed to maintain the desired
indoor temperature.
Automatic: The user has the option to
select Auto for the system setting. In Auto
mode, the thermostat controls heating and
cooling equipment as needed to maintain
the desired indoor temperature.
3000 Deadband
2° F to 9° F (in 1° F increments)
3° F Both No This ISU is only displayed when ISU 3000
is set to Automatic.
Deadband is the minimum separation
between heat and cool settings when the
thermostat is setup for Auto Changeover.
For example, if the deadband is set to 3° F
and the cool setpoint is 75° F, the warmest
heat setpoint allowed would be 72° F. If the
heat setpoint is adjusted above 72° F, it will
automatically adjust the cooling setpoint
higher to maintain the 3° F deadband.
When ISU 9070 (Dehumidification - Over
Cooling Limit) or ISU 9100 (High Humidity
Comfort Reset Setting) is set to 1, 2, 3, 4 or
5° F, the thermostat will not show the full
Deadband range. For example, if you set a
Deadband of 3° F and an Over Cooling
Limit of 2° F, the minimum Deadband that
you can select will be 5 F. This prevents the
heating system from turning on when the
thermostat over cools to reach the
dehumidification setting.
3010 Temperature
Control Options
Basic Options
Advanced Options
Advanced Options + PID Settings
Basic Options Both No Basic Options: The Installer Setup displays
basic temperature control options which
include Backup Heat Differential, Backup
Heat Upstage Timer and Outdoor
Temperature Lockouts. Note: Outdoor
Temperature Lockouts only apply to Heat
Pump applications.
Advanced Options: The Installer Setup
displays both Basic and Advanced Options.
Advanced temperature control options
include Finish With High Cool Stage, Finish
With High Heat Stage, Temperature
Differential settings between all stages and
Cycle Rate settings per stage.
Advanced Options+PID Settings: The
Installer Setup displays both Basic and
Advanced Options including PID settings
which allow you to adjust the integral,
derivative and throttling range.
Table 4. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes
Loading...
+ 130 hidden pages