Goodman GSX16S421AA, GSX16S361AA, GSX16S301AA, GSX16S181AA, GSX16S241AA Installation Manual

...
4 (2)
CONDENSING UNIT
AIR CONDITIONING INSTALLATION & SERVICE REFERENCE
© 2005-2013, 2017-2018 Goodman Manufacturing Company, L.P. 5151 San Felipe, Suite 500, Houston, TX 77056 www.goodmanmfg.com -or- www.amana-hac.com P/N: IO-258T Date: January 2018
Important Safety Instructions
The following symbols and labels are used throughout this manual to indicate immediate or potential safety hazards. It is the owner’s and installer’s responsibility to read and comply with all safety information and instructions accompanying these symbols. Failure to heed safety information increases the risk of personal injury, property damage, and/or product damage.
HIGH VOLTAGE!
Disconnect ALL power before servicing. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.
O
NLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL ADJUST, SERVICE OR REPAIR (HEREINAFTER EQUIPMENT SPECIFIED IN THIS MANUAL SHOULD SERVICE THE EQUIPMENT FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE PROCEDURES THIS UNIT, YOU ASSUME RESPONSIBILITY FOR ANY INJURY OR PROPERTY DAMAGE WHICH MAY RESULT JURISDICTIONS THAT REQUIRE ONE OR MORE LICENSES TO SERVICE THE EQUIPMENT SPECIFIED IN THIS MANUAL, ONLY LICENSED PERSONNEL SHOULD SERVICE THE EQUIPMENT
MPROPER INSTALLATION, ADJUSTMENT, SERVICING OR REPAIR
I
OF THE EQUIPMENT SPECIFIED IN THIS MANUAL, OR ATTEMPTING TO INSTALL, ADJUST, SERVICE OR REPAIR THE EQUIPMENT SPECIFIED IN THIS MANUAL WITHOUT PROPER TRAINING MAY RESULT IN PRODUCT DAMAGE, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH
. THE
,
, “
SERVICE
MANUFACTURER WILL NOT BE RESPONSIBLE
. IF
. IN
ADDITION, IN
.
”)
THE
YOU SERVICE
.
Codes & Regulations
This product is designed and manufactured to comply with national codes. Installation in accordance with such codes and/or prevailing local codes/regulations is the responsibility of the installer. The manufacturer assumes no responsibility for equipment installed in violation of any codes or regula­tions. Rated performance is achieved after 72 hours of operation.Rated performance is delivered at the specified air­flow. See outdoor unit specification sheet for split system mod­els or product specification sheet for packaged and light com­mercial models. Specification sheets can be found at
www.goodmanmfg.com for Goodman® brand products or www.amana-hac.com for Amana® brand products. Within ei-
ther website, please select the residential or commercial prod­ucts menu and then select the submenu for the type of prod­uct to be installed, such as air conditioners or heat pumps, to access a list of product pages that each contain links to that model’s specification sheet.
The United States Environmental Protection Agency (EPA) has issued various regulations regarding the introduc­tion and disposal of refrigerants. Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines. Should you have any
questions please contact the local office of the EPA. If replacing a condensing unit or air handler, the system must
be manufacturer approved and Air Conditioning, Heating and Refrigeration Institute (AHRI) matched. NOTE: Installation of unmatched systems is strongly discouraged.
Outdoor units are approved for operation above 55°F in cool­ing mode. Operation below 55°F requires the use of an ap­proved low ambient kit.
Shipping Inspection
Always keep the unit upright; laying the unit on its side or top may cause equipment damage. Shipping damage, and subse­quent investigation is the responsibility of the carrier. Verify the model number, specifications, electrical characteristics, and accessories are correct prior to installation. The distribu­tor or manufacturer will not accept claims from dealers for trans­portation damage or installation of incorrectly shipped units.
is a registered trademark of Maytag Corporation or its related companies and is used
under license to Goodman Company, L.P., Houston, TX. All rights reserved.
Damage to the unit caused by operating the unit in a structure that is not complete (either as part of new construction or renovation) is not covered under the warranty.
Installation Clearances
Special consideration must be given to location of the con­densing unit(s) in regard to structures, obstructions, other units, and any/all other factors that may interfere with air circulation. Where possible, the top of the unit should be completely unob­structed; however, if vertical conditions require placement be­neath an obstruction there should be a minimum of 60
inches between the top of the unit and the obstruction(s).
The specified dimensions meet requirements for air circula­tion only. Consult all appropriate regulatory codes prior to determining final clearances.
Another important consideration in selecting a location for the unit(s) is the angle to obstructions. Either side adjacent the valves can be placed toward the structure provided the side away from the structure maintains minimum service clearance. Corner installations are strongly discouraged.
NOT
RECOMMENDED
B B B
AA AAA
AA
C
AA
C
B
AA
OK!
OK!
OK!
OK!
OK!
OK!
Safe Refrigerant Handling
While these items will not cover every conceivable situation, they should serve as a useful guide.
Refrigerants are heavier than air. They can "push out" the oxygen in your lungs or in any enclosed space. To avoid possible difficulty in breathing or death:
Never purge refrigerant into an enclosed room or
space. By law, all refrigerants must be reclaimed.
If an indoor leak is suspected, thoroughly ventilate the
area before beginning work.
• Liquid refrigerant can be very cold. To avoid possible frostbite or blindness, avoid contact and wear gloves and goggles. If liquid refrigerant does contact your skin or eyes, seek medical help immediately.
• Always follow EP A regulations. Never burn refrigerant, as poisonous gas will be produced.
A
Model Type A B C AA Residential
Light Commercia l
AA
Minim um Airf low Clearance
10" 10" 18" 20" 12" 12" 18" 24"
AA
CC
This unit can be located at ground floor level or on flat roofs. At ground floor level, the unit must be on a solid, level founda­tion that will not shift or settle. To reduce the possibility of sound transmission, the foundation slab should not be in con­tact with or be an integral part of the building foundation. En­sure the foundation is sufficient to support the unit. A con­crete slab raised above ground level provides a suitable base.
Rooftop Inst allations
If it is necessary to install this unit on a roof structure, ensure the roof structure can support the weight and that proper con­sideration is given to the weather-tight integrity of the roof. Since the unit can vibrate during operation, sound vibration transmis­sion should be considered when installing the unit. Vibration absorbing pads or springs can be installed between the con­densing unit legs or frame and the roof mounting assembly to reduce noise vibration.
T o avoid possible injury, explosion or death, practice safe handling of refr ig erants.
To av oi d po s sible explosion: Never apply flame or steam to a refrigerant cylinder.
If you must heat a cylinder for faster charging, partially imm erse it in wa rm water.
Never fill a cylinder more than 80% full of liquid re-
frigerant.
• Never add anything other than R-22 to an R-22 cy­ linder or R-410A to an R-410A cylinder. The service equipment used must be listed or certified for the type of refrigerant used.
• Store cylinders in a cool, dry place. Never use a cy­ linder as a platform or a roller.
To avoid possible explosion, use only returnable (not disposable) service cylinders when removing refrig­erant from a system.
• Ensure the cylinder is free of damage which could lead to a leak or explosion.
• Ensure the hydrostatic test date does not exceed 5 years.
• Ensure the pressure rating meets or exceeds 400 psig. When in doubt, do not use cylinder.
Refrigerant Lines
CAUTION
The compressor POE oil for R-410A units is extremely susceptible to moisture absorption and could cause compressor failure. Do not leave system open to atmos­phere any longer than necessary for installation.
Use only refrigerant grade (dehydrated and sealed) copper tubing to connect the condensing unit with the indoor evapo­rator. After cutting the tubing, install plugs to keep refrigerant tubing clean and dry prior to and during installation. Tubing should always be cut square keeping ends round and free from burrs. Clean the tubing to prevent contamination.
2
Do NOT let refrigerant lines come in direct contact with plumb­ing, ductwork, floor joists, wall studs, floors, and walls. When running refrigerant lines through a foundation or wall, openings should allow for sound and vibration absorbing material to be placed or installed between tubing and foundation. Any gap between foundation or wall and refrigerant lines should be filled with a pliable silicon-based caulk, RTV or a vibration damping material. Avoid suspending refrigerant tubing from joists and studs with rigid wire or straps that would come in contact with the tubing. Use an insulated or suspension type hanger. Keep both lines separate and always insulate the suction line.
These sizes are recommended for line lengths of 79 feet or less to obtain optimum performance. For alternate line sizing options or runs of more than 79 feet, refer to Remote Cooling Service Manual or TP-107 Long Line Set Application R-410A or contact your distributor for assistance.
RECOMMENDED INTERCONNECTING TUBING (Ft)
Cond
Unit
Tons Suct Liq Suct Liq Suct Liq
0-24 25-49 50-79*
Line Di ameter (I n. OD )
1 1/2 5/8 1/4 3/4 3/8 3/4 3/8
2 5/81/43/43/83/43/8
2 1/2 5/8 1/4 3/4 3/8 7/8 3/8
3 3/4 3/8 7/8 3/8 1 1/8 3/8
3 1/2 7/8 3/8 1 1/8 3/8 1 1/8 3/8
4 7/ 8 3/8 1 1/8 3/8 1 1/8 3/8 5 7/ 8 3/8 1 1/8 3/8 1 1/8 3/8
* Lines greater than 79 feet in length or vertical elevation changes more than 50 feet
Service Manual or contact your distributor for assistance.
refer to the Remote Cool ing
Insulation is necessary to prevent condensation from forming and dropping from the suction line. Armflex (or satisfactory equivalent) with 3/8” min. wall thickness is recommended. In severe conditions (hot, high humidity areas) 1/2” insulation may be required. Insulation must be installed in a manner which protects tubing from damage and contamination.
Where possible, drain as much residual compressor oil from existing systems, lines, and traps; pay close attention to low areas where oil may collect. NOTE: If changing refrigerant types, ensure the indoor coil and metering device is compat­ible with the type of refrigerant being used; otherwise, the in­door coil must be replaced.
Burying Refrigerant Lines
If burying refrigerant lines can not be avoided, use the following checklist.
1. Insulate liquid and suction lines separately.
2. Enclose all underground portions of the refrigerant lines in waterproof material (conduit or pipe) sealing the ends where tubing enters/exits the enclosure.
3. If the lines must pass under or through a concrete slab, ensure lines are adequately protected and sealed.
Refrigerant Line Connections
IMPORTANT
To avoid overheating the service valve, TXV valve, or filter drier while brazing, wrap the component with a wet rag, or use a thermal heat trap compound. Be sure to follow the manufacturer’s instruction when using the heat trap compound. Note: Remove Schrader valves from service valves before brazing tubes to the valves. Use a brazing alloy of 2% minimum silver content. Do not use flux.
Torch heat required to braze tubes of various sizes is proportional to the size of the tube. Tubes of smaller size require less heat to bring the tube to brazing temperature before adding brazing alloy. Applying too much heat to any tube can melt the tube. Service personnel must use the appropriate heat level for the size of the tube being brazed. Note: The use of a heat shield when brazing is recommended to avoid burning the serial plate or the finish on the unit.
1. The ends of the refrigerant lines must be cut square, de­burred, cleaned, and be round and free from nicks or dents. Any other condition increases the chance of a refrigerant leak.
3
2. “Sweep” the refrigerant line with nitrogen or inert gas during brazing to prevent the formation of copper-oxide inside the refrigerant lines. The POE oils used in R­410A applications will clean any copper-oxide present from the inside of the refrigerant lines and spread it throughout the system. This may cause a blockage or failure of the metering device.
3. After brazing, quench the joints with water or a wet cloth to prevent overheating of the service valve.
4. Ensure the filter drier paint finish is intact after brazing. If the paint of the steel filter drier has been burned or chipped, repaint or treat with a rust preventative. This is especially important on suction line filter driers which are continu­ally wet when the unit is operating.
NOTE: Be careful not to kink or dent refrigerant lines. Kinked or dented lines will cause poor performance or compressor damage.
Do NOT make final refrigerant line connection until plugs are removed from refrigerant tubing.
NOTE: Before brazing, verify indoor piston size by checking the piston kit chart packaged with indoor unit.
Leak Testing (Nitrogen or Nitrogen-Traced)
System Evacuation
Condensing unit liquid and suction valves are closed to con­tain the charge within the unit. The unit is shipped with the valve stems closed and caps installed. Do not open valves
until the system is evacuated.
WARNING
REFRIGERANT UNDER PRESSURE!
Failure to follow proper procedures may cause proper ty damag e , pe rsonal injury or de a th.
NOTE: Scroll compressors should never be used to evacuate
or pump down a heat pump or air conditioning system.
CAUTION
Prolonged operation at suction pressures less than 20 psig for more than 5 seconds will result in overheating of the scrolls and permanent damage to the scroll tips, drive bearings and internal seal.
1. Connect the vacuum pump with 250 micron capability to the service valves.
2. Evacuate the system to 250 microns or less using suc­tion and liquid service valves. Using both valves is nec­essary as some compressors create a mechanical seal separating the sides of the system.
WARNING
To avoid the risk of fire or explosion, never use oxygen, high pressure air or flammable gases for leak testing of a refrigeration system.
WARNING
To avoid possible explosion, the line from the nitrogen cylinder must include a pressure regulator and a pressure relief valve. The pressure relief valve must be set to open at no more than 150 psig.
Pressure test the system using dry nitrogen and soapy water to locate leaks. If you wish to use a leak detector, charge the system to 10 psi using the appropriate refrigerant then use nitrogen to finish charging the system to working pressure then apply the detector to suspect areas. If leaks are found, repair them. After repair, repeat the pressure test. If no leaks exist, proceed to system evacuation.
3. Close pump valve and hold vacuum for 10 minutes. Typi­cally pressure will rise during this period.
If the pressure rises to 1000 microns or less and remains
steady the system is considered leak-free; proceed to startup.
5000 4500 4000 3500
MICRONS
3000
IN
2500
ACUUM
2000
V
1500 1000
500
0 1 2 3 4 5 6 7 8 9
CONDENSIBLES OR SMALL LEAK PRESENT
NO LEAKS NO CONDENSIBLES
MINUTES
LEAK(S) PRESENT
10
4
Loading...
+ 8 hidden pages