PRODUCT SPECIFICATIONS
11 SEER, 50 HERTZ
4 AND 5 TONS
PC
PACKAGED AIR CONDITIONERS
NOMINAL COOLING CAPACITY:
[13.6 KW TO 16.0 KW]
Standard Features
• Energy-ef cient compressor with internal relief valve
PSC blower motor
Quiet horizontal discharge
• Copper tube/aluminum n coil
Totally enclosed, permanently lubricated condenser
fan motor
Fully charged system
Cabinet Features
Heavy-gauge galvanized-steel cabinet with
attractive Architectural Gray powder-paint nish
Fully insulated blower compartment with
convenient access panels
Louvered condenser coil protection
• Common footprint
Heat Kit Selection
HKR5-12 (12 kW)
HKR5-15 (15 kW)
Above electric heat kits available as
eld-installed options.
The PC50 Packaged Air Conditioner features energy-
ef cient cooling and heating performance in one self-
contained unit. This unit is housed in a heavy-gauge,
galvanized-steel cabinet protected by a high-quality,
UV-resistant powder-paint nish. The PC50 allows for
ground-level or rooftop applications, and is approved for
manufactured or modular homes.
P
RODUCT
S
PECIFICATIONS
2 www.goodmanmfg.com SS-PC50
NOMENCLATURE
Product Category Engineering
P Packaged Unit Major/ Minor Revision
Type Electrical Data
C Air Conditioner 1 208/230 V, 1 Phase, 60 Hz
H Heat Pump 2 220/240 V, 1 Phase, 50 Hz
3 208/230 V, 3 Phase, 60 Hz
Nominal Capacity 4 460 V, 3 Phase, 60 Hz
48 4 Tons 5 380/415 V, 3 Phase, 50 Hz
60 5 Tons
63,4,521
G
A
7,8
P C 048 5
P
RODUCT
S
PECIFICATIONS
SS-PC50 www.goodmanmfg.com 3
SPECIFICATIONS
PC048-5 PC060-5
Cooling Capacity
Total BTU/h 46,400 54,700
Sensible BTU/h 33,300 39,400
SEER / EER 11.9 / 10.2 10.9 / 9.4
Decibels 80 80
Evaporator Motor
Type DD DD
Wheel (D x W) 9 x 8 10 x 8
Nominal Cooling CFM 1,365 1,693
No. of Speeds 2 2
Horsepower - RPM 1/2 - 1075 3/4 - 1075
Evaporator Coil
Face Area (ft²) 6.2 7.0
Rows Deep/ Fins per Inch 4/14 4/14
Filter Size (ft²) (2) 20 x 20 x 1 (2) 20 x 20 x 1
Drain Size (NPT) 3/4” 3/4”
Refrigerant Charge (oz.) 126 125
Condenser Fan / Coil
Horsepower - RPM 1/4 - 1075 1/4 - 1075
Fan Diameter/ # Fan Blades 22 / 4 22 / 4
Face Area (ft²) 17.8 19.1
Rows Deep/ Fins per Inch 2 / 16 2 / 16
Electrical Data
Voltage/Phase/ Frequency 380-415 / 3 / 50
Compressor RLA/LRA 7.4 / 50 10.3 / 65
Indoor Blower FLA 1.4 2.2
Outdoor Fan RLA 0.8 1.2
Total Unit Amps 8.9 11.4
Min. Circuit Ampacity ¹ 11.5 16.3
Max. Overcurrent Protection ² 20 amps 20 amps
Ship Weight (lbs) 400 400
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.