Goodman AWS174CDH Installation Manual

0 (0)

Installation, Operation,

and Maintenance Manual

Pathfinder®

Air-cooled Screw Chillers

Model AWS

170 to 550 Tons (600 to 1935 kW) 60Hz

164 to 604 Tons (575 to 2125 kW) 50Hz HFC-134a Refrigerant

IOM 1202-2

Group: Chiller

Part Number: IOM1202-2

Date: May 2015

 

 

 

Table of Contents

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . 3

Circuit Functions . . . . . . . . . . . . . . . . . . . . .

. 126. . . . .

Installation and Startup . . . . . . . . . . . . . . . . . . . . .

. . . 4

Alarms and Events . . . . . . . . . . . . . . . . . . . . . . . .

. . 137

Lifting and Mounting Information . . . . . . . . . . . . .

. . 16

Using the Controller . . . . . . . . . . . . . . . . . . . . . . . .

. 145

Isolator Information . . . . . . . . . . . . . . . . . . . . . .

. .50.

. Optional Remote User Interface . . . . . . . . . . . .

. .148.

Electrical Information . . . . . . . . . . . . . . . . . . . . . . .

. . 59

Optional Compressor VFD . . . . . . . . . . . . . . . . . . .

. 150

Pressure Drop Data . . . . . . . . . . . . . . . . . . . .

. .82.

. . . Startup and Shutdown . . . . . . . . . . . . . . . . . . . . . .

. 154

Controller Operation . . . . . . . . . . . . . . . .

. .94.

. . System. . . . Maintenance . . . . . . . . . . . . . . . . . . .

. 156. . . .

Sequence of Operation . . . . . . . . . . . . . . . .

.108. . . . .Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 160

Unit Functions . . . . . . . . . . . . . . . . . . . .

.114. . . . . . . .

 

Hazard Identification

DANGER

Dangers indicate a hazardous situation which will result in serious injury or death if not avoided.

WARNING

Warnings indicate potentially hazardous situations which can result in property damage, servere personal injury or death if not avoided.

CAUTION

Cautions indicate potentially hazardous situations which can result in personal injury or equipment damage if not avoided.

Manufactured in an ISO 9001 & ISO 14001 certified facility

©2015 Daikin Applied. Illustrations and data cover the Daikin Applied product at the time of publication and we reserve the right to make changes in design and construction at any time without notice.

IOM 1202-2 • PATHFINDER® MODEL AWS CHILLERS

2

www.DaikinApplied.com

Cut Here

Pre-Start Checklist – Screw Chillers

Must be completed, signed and provided to Daikin Applied at least 2 weeks prior to requested start date.

Job Name

Installation Location

Customer Order Number

Model Number(s)

G.O. Number(s)

Chilled Water

Yes

No

N/A

Initials

Piping Complete

 

 

 

 

Water strainer installed on evaporator entering chilled water piping per IM

 

 

 

 

Water System filled, flushed and vented

 

 

 

 

Pumps installed and operational (rotation checked, strainers cleaned)

 

 

 

 

Controls operational (3-way valves, face/bypass dampers, bypass valves, etc.)

 

 

 

 

Water system operated and tested; flow meets unit design requirements

 

 

 

 

Flow switch installed and wired

 

 

 

 

Vent installed on evaporator

 

 

 

 

Glycol at design %

 

 

 

 

Electrical

Yes

No

N/A

Initials

Building controls operational

 

 

 

 

*Power leads connected to power block or optional disconnect

 

 

 

 

Power leads have been checked for proper phasing and voltage

 

 

 

 

All interlock wiring complete and compliant with Daikin specifications

 

 

 

 

Power applied at least 24 hours before startup

 

 

 

 

Oil heaters energized at least 24 hours before startup

 

 

 

 

Chiller components (EXV Sensors Transducers) installed and wired properly.

 

 

 

 

*Wiring complies with National Electrical Code and local codes (See Notes)

 

 

 

 

Remote EXV wired with shielded cable

 

 

 

 

Miscellaneous

Yes

No

N/A

Initials

Unit control switches all off

 

 

 

 

Remote Evaporator Piping factory reviewed and approved

 

 

 

 

All refrigerant components/piping leak tested, evacuated and charged

 

 

 

 

Thermometers, wells, gauges, control, etc., installed

 

 

 

 

Minimum system load of 80% capacity available for testing/adjusting controls

 

 

 

 

Document Attached: Technical Breakdown from Selection Software

 

 

 

 

Document Attached: Final Order Acknowledgement

 

 

 

 

Document Attached: Remote evaporator piping approval

 

 

 

 

Notes: The most common problems delaying start-up and affecting unit reliability are:

1.Field installed compressor motor power supply leads too small. Questions: Contact the local Daikin sales representative*. State size, number and type of conductors and conduits installed:

a.From Power supply to chiller

*Refer to NEC Article 430-22 (a)

2.Remote Evaporator piping incomplete or incorrect. Provide approved piping diagrams.

3.Items on this list incorrectly acknowledged may result in delayed start and extra expenses incurred for return trips.

Contractor Representative

Daikin Applied Sales Representative

Signed:

 

Signed:

 

Name:

 

Name:

 

Company:

 

Company:

 

Date:

 

Date:

 

Phone/Email:

 

Phone/Email:

 

©2014 Daikin Applied

Form SF01017 P/N 331977001

10OCT2014

Introduction

General Information

Daikin Pathfinder® air-cooled chillers are complete, selfcontained chillers that include the latest in engineered components arranged to provide a compact and efficient unit.

Each unit is completely assembled, factory wired, evacuated, charged, tested and comes complete and ready for installation. Each compressor has an independent refrigeration circuit. Liquid line components included are a manual liquid line shutoff valve, charging port, filter-drier, sight-glass/moisture indicator, and electronic expansion valve. A discharge check valve and discharge shutoff valve are included and a compressor suction shutoff valve is optional. Other features include compressor heaters, evaporator heaters for freeze protection, automatic, one-time pumpdown of each refrigerant circuit upon circuit shutdown, and an advanced fully integrated controller.

Pathfinder® units are available in one of three unit efficiency levels - standard, high, and premium.

Information on the operation of the unit MicroTech®III controller can be found starting on page 94.

Introduction

Remote Evaporator Models

For enhanced application flexibility, Pathfinder® chillers are also available with a remote evaporator option. Information on remote evaporator units can be found in the current installation manual for remote evaporator configurations, available at www.DaikinApplied.com.

Inspections

When the equipment is received, carefully check all items against the bill of lading to verify for a complete shipment. Check all units for damage upon arrival. All shipping damage must be reported to the carrier and a claim must be filed with the carrier. Check the unit name plate before unloading the unit to be sure that it agrees with the power supply available. Physical damage to a unit after shipment is not the responsibility of Daikin.

NOTE: Unit shipping and operating weights are shown in the Lifting and Mounting section beginning on page 16

Nomenclature

 

 

AWS XXX C D S E

 

Model

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit configuration

 

 

 

 

 

 

 

 

 

 

AWS = Air-Cooled World Product Screw Compressor

 

 

 

 

E = Standard packaged

Nominal unit size

 

 

 

 

 

 

 

 

 

 

 

M = Remote Evaporator

 

 

 

 

Unit efficiency

(cataloged size—nominal unit capacity)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S = Standard

Design vintage

 

 

 

 

 

 

 

 

H = High

 

P = Premium

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit compressors

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D = Dual compressors

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T = Triple compressors

Table 1: Operating Limits

Maximum standby ambient temperature

130°F (54.4°C)

 

 

Maximum operating standard ambient temperature

105°F (40.6°C)

 

 

with optional high ambient package

 

Note: some standard efficiency units may not operate fully loaded up to the 125°F maximum ambient temp limit. Some

125°F (52°C)

units offer a reduced RFS option limiting max ambient to 118°F. Contact the Daikin Applied sales office for information.

 

Minimum operating ambient temperature (standard control)

35°F (2°C)

 

 

Minimum operating ambient temperature (with optional low-ambient control)

0°F (-18°C)

 

 

Leaving chilled water temperature [NOTE: 60°F (15.6°C) max with VFD and reduced RFS option]

40°F to 70°F

(4.4°C to 21.1°C)

 

 

 

Leaving chilled fluid temperatures (with anti-freeze) - Unloading is not permitted with fluid leaving temperatures below

20°F to 70°F

30°F (-1°C). [NOTE: 60°F (15.6°C) max with VFD and reduced RFS option]

(-6.7°C to 21.1°C)

Operating chilled water delta-T range

6°F to 18°F

(3.3°C to 10°C)

 

 

 

Maximum evaporator operating inlet fluid temperature

88°F (31.1°C)

 

 

Maximum evaporator non-operating inlet fluid temperature

100°F (38°C)

 

 

 

 

www.DaikinApplied.com

3

IOM 1202-2 • PATHFINDER® MODEL AWS CHILLERS

Installation and Startup

Installation and maintenance are to be performed only by qualified personnel who are familiar with local codes and regulations, and experienced with this type of equipment.

WARNING

Sharp edges and coil surfaces are a potential injury hazard. Avoid contact with them.

Startup by a Daikin Applied service representative is included on all Pathfinder® units sold for installation within the U.S. and Canada and must be performed by them to initiate the standard Limited Product Warranty. Startup by any party other than a Daikin Applied service representative will void the

Limited Product Warranty. Two-week prior notification of startup is required. The contractor should obtain a copy of the Startup Scheduled Request Form from the sales representative or from the nearest Daikin Applied service office.

WARNING

Escaping refrigerant can displace air and cause suffocation. Immediately evacuate and ventilate the equipment area. If the unit is damaged, follow Environmental Protection Agency (EPA) requirements. Do not expose sparks, arcing equipment, open flame or other ignition source to the refrigerant.

Handling

DANGER

Improper lifting or moving of a unit can result in property damage, severe personal injury or death. Follow rigging and moving instructions carefully.

Avoid rough handling shock due to impact or dropping the unit. Do not push or pull the unit. Never allow any part of the unit

to fall during unloading or moving as this can result in serious damage.

To lift the unit, lifting tabs with 3” (76 mm) diameter holes are provided on the base of the unit. All lifting holes must be used when lifting the unit. Spreader bars and cables should

be arranged to prevent damage to the condenser coils or unit cabinet (see Figure 1).

Location

Locate the unit outdoors and provide proper airflow to the condenser. (See page 5 for required clearances.)Using less clearance than shown in Figure 2 can cause discharge

air recirculation to the condenser and could have a significant detrimental effect on unit performance.

Due to the shape of the condenser coils on Pathfinder® chillers, it is recommended that the unit be oriented so that prevailing winds blow parallel to the unit length, thus minimizing the wind effect on condensing pressure and performance. If low ambient temperature operation is expected, optional louvers should be installed if the unit has no protection against prevailing winds.

Installation and Startup

For pad-mounted units, it is recommended that the unit be raised a few inches with suitable supports such as neoprene waffle vibration pads, located at least under the mounting locations. This will allow water to drain from under the unit and facilitate cleaning under it.

Figure 1: Required Lifting Method

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: 1.Unit with 8 lifting points illustrated above; the number of condenser sections, fans, and lifting points can vary from this diagram.see lifting/mounting drawings beginning on page 16 to identfy the number of lifting points for a specific unit.

2.All rigging points must be used. See weights at lifting points beginning on page 16 for each specific size unit.

3.Crosswise and lengthwise spreader bars must be used to avoid damage to unit.

Mounting Hole Access

The inside of the base rail is open to allow access for securing mounting bolts, etc.

IOM 1202-2 • PATHFINDER® MODEL AWS CHILLERS

4

www.DaikinApplied.com

Installation and Startup

Service Access

Compressors, filter-driers, and manual liquid line shutoff valves are accessible on each side or end of the unit. The evaporator heater is located on the barrel.

The control panels are located on the end of the chiller. The left-hand control box contains the unit and circuit

microprocessors as well as transformers, fuses and terminal. The right-hand panel contains a circuit breaker. A minimum of four feet of clearance is required in front of the panels. The side clearance required for airflow provides sufficient service clearance.

On all Pathfinder® units, the condenser fans and motors can be removed from the top of the unit. The complete fan/motor assembly can be removed for service. The fan blade must be removed for access to wiring terminals at the top of the motor.

DANGER

Disconnect, lockout and tag all power to the unit before servicing condenser fan motors or compressors. Failure to do so can cause bodily injury or death.

Do not block access to the sides or ends of the unit with piping or conduit. These areas must be open for service access.

Do not block access to the control panels with field-mounted disconnect switches.

Clearance Requirements

The clearance requirements shown are a general guideline and cannot account for all scenarios. Such factors as prevailing winds, additional equipment within the space, design outdoor air temperature, and numerous other factors may require more clearance than what is shown.

Figure 2: Guidelines

NOTE: 1 Minimum side clearance between two units is 12 feet (3.7 m). See Case 2 for spacing closer than 12 ft.

2 Minimum clearance on each side is 8 feet (2.4 m) when installed in a pit no deeper than the unit height. Unit must not be installed in a pit or enclosure that is deeper or taller than the height of the unit unless extra clearance is provided per note 4. See Case 5

for performance adjustment factors when installations vary from minimum values.

3 Minimum side clearance to a side wall or building taller than the unit height is 6 feet (1.8 meters), provided no solid wall above 6 feet (1.8 meters) is closer than 12 feet (3.7 meters) to the opposite side of the unit. See Case 1 for performance adjustment factors when installations vary from minimum values.

4 There must be no obstruction of the fan discharge.

Restricted Air Flow

The clearances required for design operation of Pathfinder® air-cooled chillers are described in the previous section. Occasionally, these clearances cannot be maintained due to site restrictions such as units being too close together or a fence or wall restricting airflow, or both. Pathfinder® chillers have several features that may help mitigate the penalties attributable to restricted airflow.

The condenser section is “W” shaped, as shown below. This allows inlet air for these coils to come in from both sides and the bottom. All the coils in one “V” section serve one compressor except for 3 circuit units which use both sides of the “W” shaped condenser coil..

The MicroTech® III control is proactive in response to “offdesign conditions”. In the case of single or compounded influences restricting airflow to the unit, the microprocessor will act to keep the unit running (at reduced capacity), rather than allowing a shut-off on high discharge pressure.

Figure 3: Air Flow

www.DaikinApplied.com

5

IOM 1202-2 • PATHFINDER® MODEL AWS CHILLERS

Installation and Startup

Case 1: Building or Wall on One Side of Unit

The existence of a screening wall or the wall of a building in close proximity to an air-cooled chiller is common in both rooftop and ground level applications. Hot air recirculation on the coils adjoining the wall will increase compressor

discharge pressure, decreasing capacity and increasing power consumption.

When close to a wall, it is desirable to place chillers on the north or east side of them. It is also desirable to have prevailing winds blowing parallel to the unit’s long axis. The worst case is to have wind blowing hot discharge air into the wall.

Figure 4: Case 1 - Unit Adjacent to Wall

Figure 5: Case 1 - Adjustment Factors

Case 2: Two Units Side By Side

Two or more units sited side by side are common. If spaced closer than 12 feet (3.7 meters) it is necessary to adjust the performance of each unit; circuits adjoining each other are affected. If one of the two units also has a wall adjoining it, see Case 1. Add the two adjustment factors together and apply to the unit located between the wall and the other unit.

Mounting units end to end will not necessitate adjusting performance. Do not use pit or solid wall surrounds where the ambient air temperature exceeds 100°F (38°C).

Figure 6: Case 2 - Two Units Side by Side

Figure 7: Case 2 - Adjustment Factors

IOM 1202-2 • PATHFINDER® MODEL AWS CHILLERS

6

www.DaikinApplied.com

Installation and Startup

Case 3: Three or More Units Side By Side

When three or more units are side by side, the outside chillers

(1 and 3 in this case) are influenced by the middle unit only on their inside circuits. Their adjustment factors will be the same as Case 2. All inside units (only number 2 in this case) are influenced on both sides and must be adjusted by the factors shown below.

Figure 8: Case 3 - Three or More Units

Figure 9: Case 3 - Adjustment Factors

Case 4: Open Screening Walls

Decorative screening walls are often used to help conceal a unit either on grade or on a rooftop. Design these walls such that the combination of their open area and distance from the unit do not require performance adjustment. It is assumed that the wall height is equal to or less than the unit height when mounted on its base support. This is usually satisfactory for concealment. If the wall height is greater than the unit height, see Case 5, Pit Installation.

The distance from the sides of the unit to the side walls must be sufficient for service, such as opening control panel doors.

If each side wall is a different distance from the unit, the distances can be averaged providing either wall is not less than 8 feet (2.4 meters) from the unit. For example, do not average 4 feet and 20 feet to equal 12 feet (1 meter and 5 meters to equal 3 meters).

Figure 10: Case 4 - Open Screening Walls

Figure 11: Case 4 - Adjustment Factor

www.DaikinApplied.com

7

IOM 1202-2 • PATHFINDER® MODEL AWS CHILLERS

Installation and Startup

Case 5: Pit/Solid Wall Installation

Pit installations can cause operating problems resulting from recirculation and restriction can both occur. A solid wall surrounding a unit is substantially the same as a pit and the data presented here should be used.

Steel grating is sometimes used to cover a pit to prevent accidental falls or trips into the pit. The grating material and installation design must be strong enough to prevent such accidents, yet provide abundant open area to avoid serious recirculation problems. Have any pit installation reviewed by a Daikin Applied sales representative prior to installation to make sure it has sufficient air-flow characteristics, and approved by the installation design engineer to avoid risk of accident.

Figure 12: Case 5 - Pit Installation

Figure 13: Case 5 - Adjustment Factors

Full Load Capacity Adjustment Factor

 

6..00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D=6 ft

 

 

D=8 ft

 

 

 

 

 

 

 

(1..8m)

 

 

(2..4m)

 

(%)

5..00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Reduction

4..00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3..00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D=10 ft

 

 

 

 

 

 

 

 

 

 

 

2..00

 

 

 

 

 

 

 

 

(3..1m)

 

 

 

 

 

 

 

 

 

 

 

 

1..00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0..00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

10

12

14

 

(2..4)

(3..1)

(3..7)

(4..3)

H - Height of Wall or Building in ft.. (m)

IOM 1202-2 • PATHFINDER® MODEL AWS CHILLERS

8

www.DaikinApplied.com

Installation and Startup

Chilled Water Piping

Figure 14: Typical Piping, Shell and Tube Evaporator

 

VENT

LEAVING FLUID

 

 

3/8” PIPE PLUG

 

 

 

TEMP. SENSOR

 

 

OUTLET

 

 

VIBRATION

 

 

 

 

 

 

 

 

ELIMINATOR

INLET

 

 

 

FLOW

 

 

 

SWITCH

 

 

VALVED

 

 

 

 

PRESSURE

 

 

 

 

GAUGE

 

GATE

 

 

VIBRATION

 

VALVE

 

 

BALANCING

 

 

ELIMINATOR

 

 

VALVE

 

 

 

 

 

DRAIN

WATER

GATE

 

 

 

STRAINER

 

FLOW

 

VALVE

 

 

 

 

PROTECT ALL FIELD PIPING

 

 

 

AGAINST FREEZING

 

FLOW

 

 

 

 

 

CAUTION

To prevent damage to the evaporator and potential chiller failure, a supply strainer is required in the inlet water piping which connects to this evaporator. This strainer must be installed prior to operation of the chilled liquid pumps.

Field installed water piping to the chiller must include:

A cleanable strainer installed at the water inlet to the evaporator to remove debris and impurities before they reach the evaporator. Install cleanable strainer within 5 feet (1500 mm) of pipe length from the evaporator inlet connection and downstream of any welded connections (no welded connections between strainer and evaporator).

AWS-C models require a strainer with perforations no larger than 0.125” (3.2 mm) diameter. See the Inlet Strainer Guidelines on page 10 for more information.

A water flow switch must be installed in the horizontal piping of the supply (evaporator outlet) water line to avoid evaporator freeze-up under low or no flow conditions. The flow switch may be ordered as a factory-installed option, a field-installed kit, or may be supplied and installed in the field. See page 11 for more information.

Purge air from the water system before unit start-up to provide adequate flow through the evaporator.

Adequate piping support, independent from the unit, to eliminate weight and strain on the fittings and connections.

It is recommended that the field installed water piping to the chiller include:

Thermometers at the inlet and outlet connections of the evaporator.

Water pressure gauge connection taps and gauges at

the inlet and outlet connections of the evaporator for measuring water pressure drop.

Shutoff valves are necessary to isolate the unit from the piping during unit servicing.

Minimum bends and changes in elevation to minimize pressure drop.

An expansion tank or regulating valve to maintain adequate water pressure

Vibration eliminators in both the supply and return water lines to reduce transmissions to the building.

Flush the system water piping thoroughly before making connections to the unit evaporator.

Piping insulation, including a vapor barrier, helps prevent condensation and reduces heat loss.

Regular water analysis and chemical water treatment for the evaporator loop is recommended immediately at equipment start-up.

Chilled Water Pump

It is important that the chilled water pumps be wired to, and controlled by, the chiller controller. The chiller controller has the capability to selectively start pump A or B or automatically alternate pump selection and also has standby operation capability. The controller will energize the pump whenever at least one circuit on the chiller is enabled to run, whether there is a call for cooling or not. This helps ensure proper unit startup sequence. The pump will also be turned on when the water temperature goes below the Freeze Setpoint for longer than

a specified time to help prevent evaporator freeze-up. Wiring connection points are shown in Figure 56 on page 60.

www.DaikinApplied.com

9

IOM 1202-2 • PATHFINDER® MODEL AWS CHILLERS

Installation and Startup

CAUTION

Adding glycol or draining the system is the recommended method of freeze protection. If the chiller does not have the ability to control the pumps and the water system is not drained in temperatures below freezing, catastrophic evaporator failure may occur. Adding glycol or draining the system is the recommended method of freeze protection. If the chiller does not have the ability to control the pumps and the water system is not drained in temperatures below freezing, catastrophic evaporator failure may occur.

Failure to allow pump control by the chiller controller may cause the following problems:

1.If any device other than the chiller attempts to start the chiller without first starting the pump, the chiller will lock out on the No Flow alarm and require manual reset.

2.If the chiller evaporator water temperature drops below the “Freeze setpoint” the chiller will attempt to start the water pumps to avoid evaporator freeze. If the chiller does not have the ability to start the pumps, the chiller will alarm due to lack of water flow.

3.If the chiller does not have the ability to control the pumps and the water system is not to be drained in temperatures below freezing, the chiller may be subject to catastrophic evaporator failure due to freezing. The freeze rating of the evaporator is based on the immersion heater and pump operation. The immersion heater itself may not be able to properly protect the evaporator from freezing without circulation of water.

Inlet Strainer Guidelines

An inlet water strainer kit must be installed in the chilled water piping before the evaporator inlet. Two paths are available to meet this requirement:

1.A field-installed kit shipped-loose with the unit is available for all unit sizes and consists of:

Y-type area strainer with 304 stainless steel perforated basket, Victaulic pipe connections and strainer cap [a strainer with perforations no larger than 0.125” (3.2 mm) diameter for AWS-C models].

Extension pipe with two Schrader fittings that can be used for a pressure gauge and thermal dispersion flow switch. The pipe provides sufficient clearance from the evaporator for strainer basket removal.

½-inch blowdown valve

Two grooved clamps

The strainer is sized per Table 2 and has the pressure drop shown in the Strainer Pressure Drop graph. Connection sizes are given in the Pressure Drop Data section on page 82.

2.A field-supplied strainer that meets specification and installation requirements of this manual.

Table 2: Strainer Sizing Data

Strainer

Strainer Plus

Strainer

Pipe Length

Weight

Size (in.)

(in.)

(lbs)

 

 

 

 

6

30.5

72

8

36.0

125

 

 

 

10

43.0

205

 

 

 

Figure 15: Strainer Pressure Drop

Installing Inlet Strainer (Field-installed Kit)

The extension pipe is located adjacent to the evaporator with the strainer then mounted to it. The strainer must be mounted per manufacturer’s instruction with the arrows in the direction of flow; inlet and outlet are noted along with the arrows.

Use one Victaulic clamp to mount the extension pipe to the evaporator and the second to mount the strainer to the pipe.

The clamps to mount the field piping to the strainer are field supplied. The piping and strainer must be supported to prevent any stress on the evaporator nozzle.

The extension pipe has two Schrader fittings that can be used as desired. The ball valve can be installed in the strainer basket cover as a blow-down valve.

System Water Volume

All chilled water systems need adequate time to recognize a load change, respond to that load change and stabilize, without undesirable short cycling of the compressors or loss of control. In air conditioning systems, the potential for short cycling usually exists when the building load falls below the minimum chiller plant capacity or on close-coupled systems with very small water volumes.

Some of the things the designer should consider when looking at water volume are the minimum cooling load, the minimum chiller plant capacity during the low load period and the desired cycle time for the compressors.

Assuming that there are no sudden load changes and that the chiller plant has reasonable turndown, a rule of thumb of

IOM 1202-2 • PATHFINDER® MODEL AWS CHILLERS

10

www.DaikinApplied.com

Installation and Startup

“gallons of water volume equal to two to three times the chilled water gpm flow rate” is often used. Refer to AG 31-003 for method of calculating “Minimum Chilled Water Volume”.

A properly designed storage tank may be added if the system components do not provide sufficient water volume.

Variable Speed Pumping

Variable water flow involves reducing the water flow through the evaporator as the load decreases. Daikin chillers are designed for this duty, provided that the rate of change in water flow is slow, and the minimum and maximum flow rates for the evaporator are not exceeded.

The recommended maximum change in water flow is 10 percent of the change per minute. For example, if the maximum (design) flow is 200 gpm and the flow is reduced to a minimum of 140 gpm, the change in flow is 60 gpm, so the maximum change per minute would be 10% of 60, or 6 gpm per minute. It would take ten minutes to change the flow through the entire range.

The water flow through the evaporator must remain between the minimum and maximum values listed, beginning on page 82. Note that units with variable chilled water flow can tolerate lower minimum flows than constant flow systems. If flow drops below the minimum allowable, large reductions in heat transfer can occur. Unit set point “Variable Evap Flow”

must be set to “Yes”, if the chill water flow is variable. If the flow exceeds the maximum rate, excessive pressure drop and tube erosion can occur.

Evaporator Freeze Protection

Pathfinder® chillers are equipped with thermostatically controlled evaporator heaters that help protect against freezeup down to -20°F (-28°C). The immersion heater itself may not be able to properly protect the evaporator from freezing without circulation of water, and it is important that the chilled water pumps are wired to, and controlled by, the chiller’s controller. Additionally, use at least one of the following procedures during periods of sub-freezing temperatures:

1.Add a concentration of a glycol anti-freeze with a freeze point 10°F below the lowest expected temperature. This will result in decreased capacity and increased pressure drop. Do not use automotive grade antifreezes as they contain inhibitors harmful to chilled water systems. Use only glycols specifically designated for use in building cooling systems.

2.Drain the water from outdoor equipment and piping and blow the chiller tubes dry from the chiller. Do not energize the chiller heater when water is drained from the vessel.

NOTE: The heaters come from the factory connected to the control power circuit. The control power can be rewired in the field to a separate 115V supply (do not wire directly to the heater). See the field wiring diagram on page 60. If this is done, it should power the entire control circuit. Mark the disconnect switch clearly to avoid accidental deactivation of the heater during freezing temperatures. Exposed chilled water

piping also requires protection. If the evaporator is drained for winter freeze protection, the heaters must be de-energized to prevent heater burnout.

Table 3: Freeze Protection

 

% Volume Glycol Concentration Required

Temp.

 

 

 

 

For Freeze Protection

For Burst Protection

°F (°C)

 

 

 

 

Ethylene

Propylene

Ethylene

Propylene

 

Glycol

Glycol

Glycol

Glycol

 

 

 

 

 

20 (6.7)

16

18

11

12

 

 

 

 

 

10 (-12.2)

25

29

17

20

 

 

 

 

 

0 (-17.8)

33

36

22

24

 

 

 

 

 

-10 (-23.3)

39

42

26

28

-20 (-28.9)

44

46

30

30

 

 

 

 

 

-30 (-34.4)

48

50

30

33

-40 (-40.0)

52

54

30

35

 

 

 

 

 

-50 (-45.6)

56

57

30

35

 

 

 

 

 

-60 (-51.1)

60

60

30

35

Notes:

“Freeze protection” maintains the solution in a

 

pumpable, usable liquid state. “Burst protection”

 

prevents pipes from rupturing, but solution may be in

 

a gel state and not pumpable. In most applications,

 

“burst” protection is sufficient; concentrations over

 

30% Ethylene Glycol or 35% Propylene Glycol will

 

result in efficiency and capacity losses with negligible

 

protection increases and are not recommended.

 

These values are examples only and cannot be

 

appropriate to every situation. Generally, for an

 

extended margin of protection, select a temperature

 

at least 15°F lower than the expected lowest ambient

 

temperature. Inhibitor levels should be adjusted for

 

solutions less than 25% glycol.

 

Glycol of less than 25% concentration is not

 

recommended, unless inhibitors are adjusted,

 

because of the potential for bacterial growth and loss

 

of efficiency.

Flow Switch

A flow switch must be included in the chilled water system to prove that there is adequate water flow before the unit can start. It also serves to shut down the unit in the event that water flow is interrupted in order to guard against evaporator freeze-up.

A factory-mounted, solid state, thermal dispersion flow switch is available as an option.

A field-installed and wired version for remote evaporators is also available as a kit (Accessory part number 332688401).

A paddle-type flow switch for field mounting and wiring is also available as a kit (Accessory part number 017503300). It is adaptable to pipe sizes from 1” (25mm) to 8” (203mm).

Installation should be per manufacturer’s instructions included with the switch. There is also a set of normally closed contacts on the switch that can be used for an indicator light or an alarm

www.DaikinApplied.com

11

IOM 1202-2 • PATHFINDER® MODEL AWS CHILLERS

Installation and Startup

to indicate when a “no flow” condition exists. Flow switches should be calibrated to shut off the unit when operatred below the minimum listed flow rate for the unit listed in the Pressure

Drop section beginning on page 82. The minimum required pipe diameter before and after the switch is 1 1/4” (32 mm).

Figure 16: Flow Switch Diagram

Refrigerant Charge

All packaged units are designed for use with R-134a and are shipped with a full operating charge. The operating charge for each unit is shown in the Physical Data Tables in the current catalog, available at www.DaikinApplied.com.

Glycol Solutions

When using glycol anti-freeze solutions, the chiller’s capacity, glycol solution flow rate, and pressure drop through the evaporator can be calculated using the following:

Note: The procedure below does not specify the type of glycol. Use the derate factors found in Table 4 or Table 5 for corrections when using glycol.

1.Capacity - Cooling capacity is reduced from that with plain water. To find the reduced value, multiply the chiller’s water system tonnage by the capacity correction factor to find the chiller’s capacity when using glycol.

2.Flow - To determine flow (or Delta-T) knowing Delta-T (or flow) and capacity:

GPM = (24) (tons) (flow factor)

Delta T

3.Pressure drop - To determine pressure drop through the evaporator when using glycol, enter the water pressure drop curve at the water flow rate. Multiply the water pressure drop found there by the “PD” factor to obtain corrected glycol pressure drop.

4.Power - To determine glycol system kW, multiply the water system kW by the factor designated “Power”.

Test coolant with a clean, accurate glycol solution hydrometer (similar to that found in service stations) or refractometer

to determine the freezing point. Obtain percent glycol from the freezing point table below. On glycol applications, the

supplier normally recommends that a minimum of 25% solution by weight be used for protection against corrosion or that additional inhibitors should be employed.

CAUTION

Do not use automotive grade antifreeze. Industrial grade glycols must be used. Automotive antifreeze contains inhibitors that will cause plating on the copper tubes within the chiller evaporator. The type and handling of glycol used must be consistent with local codes.

Performance Adjustment Factors

AWS chillers are designed to operate with leaving anti-freeze solution temperatures per software range limits. Consult the local Daikin Applied sales office for performance outside these temperatures. Leaving chilled fluid temperatures below

40°F (4.4°C) result in evaporating temperatures at or below the freezing point of water and a glycol solution is required. MicroTech® III control inhibits compressor unloading at leaving fluid temperatures below 30°F (-1°C).

Low fluid temperatures or high equipment room humidity may require optional double evaporator insulation. The system designer should determine its necessity. The use of glycol will reduce the performance of the unit depending on its concentration. Take this into consideration during initial system design. On glycol applications, the supplier typically recommends that a minimum of 25% solution by weight be used for protection against corrosion, or additional inhibitors will be required.

Table 4: Ethylene Glycol Correction Factors

%

Freeze Point

Capacity

Power

Flow

PD

E..G

oF

oC

 

 

 

 

10

26

-3.3

0.996

0.998

1.036

1.097

 

 

 

 

 

 

 

20

18

-7.8

0.988

0.994

1.061

1.219

 

 

 

 

 

 

 

30

7

-13.9

0.979

0.991

1.092

1.352

 

 

 

 

 

 

 

40

-7

-21.7

0.969

0.986

1.132

1.532

 

 

 

 

 

 

 

50

-28

-33.3

0.958

0.981

1.182

1.748

 

 

 

 

 

 

 

Table 5: Propylene Glycol Correction Factors

%

Freeze Point

Capacity

Power

Flow

PD

P..G

oF

oC

 

 

 

 

10

26

-3.3

0.991

0.996

1.016

1.092

 

 

 

 

 

 

 

20

19

-7.2

0.981

0.991

1.032

1.195

 

 

 

 

 

 

 

30

9

-12.8

0.966

0.985

1.056

1.345

 

 

 

 

 

 

 

40

-5

-20.6

0.947

0.977

1.092

1.544

 

 

 

 

 

 

 

50

-27

-32.8

0.932

0.969

1.14

1.906

IOM 1202-2 • PATHFINDER® MODEL AWS CHILLERS

12

www.DaikinApplied.com

Installation and Startup

Electrical Connections

All wiring must be done in accordance with applicable local and national codes. Pathfinder® units can be ordered with either standard multi-point power or optional single point power connections and with various disconnect and circuit breaker options. Wiring within the unit is sized in accordance with the U.S.A. National Electrical Code. Field-supplied disconnect switches are required if not factory-supplied with the unit.

Table 6: Electric Power Connection Option

Multi-Point

Single-Point

Power Connection

Power Connection

Standard:

Optional:

Disconnect switch per circuit,

one power block, compressor

no compressor isolation

isolation circuit breakers

circuit breakers

 

Optional:

Optional:

High short circuit current

one disconnect switch

rated panel with disconnect

replacing the power block,

switch and no isolation circuit

compressor isolation circuit

breakers

breakers

 

Optional:

 

High short circuit current

 

rated panel with disconnect

 

switch and compressor

 

isolation circuit breakers

NOTE: Disconnect switches are molded case construction with lockable through-the-door handles. They can be used to remove the unit/circuit from the power system.

The individual compressor isolation circuit breakers for each circuit isolate the compressor and do not have through-the-door handles. They are operable only after the panel doors are opened.

The high short circuit rated panel means that a short circuit current up to the ratings shown below will be contained in the panel. There is a short period of time when the circuit breaker will short circuit before opening a circuit that can damage downstream components. In other words, the enclosure is stronger than a standard enclosure. It has a high interrupt rated disconnect switch.

The factory-mounted control power transformer is protected by fuses. Condenser fans are protected and isolated by circuit breakers.

Table 7: Interrupt Ratings (kAmps)

Voltage

Standard Short Circuit

High Short Circuit

Rated Panel

Rated Panel

 

208-230V / 60Hz

10kA

100kA

 

 

 

380V / 60Hz

10kA

65kA

 

 

 

460V / 60Hz

10kA

65kA

575V / 60Hz

5kA

25kA

 

 

 

400V / 50Hz

10kA

65kA

 

 

 

Disconnecting means are addressed by Article 440 of the U.S.A. National Electrical Code (NEC), which requires “disconnecting means capable of disconnecting air conditioning and refrigerating equipment including motor-compressors,

and controllers from the circuit feeder.” Select and locate the disconnect switch per the NEC guidelines. Maximum

recommended fuse sizes are given in the electrical data tables of this catalog for help in sizing the disconnect.

Terminals are provided in a unit control panel for optional field hookup of the control circuit to a separate fused 115-volt power supply in lieu of the standard factory installed control transformer.

RapidRestore® Options

This option does not require field installation. Exception: Field supplied inputs are required in the case of a backup unit being started after the power interruption rather than restarting the primary unit. A field supplied control (normally a BAS) must turn off the Backup Chiller connection on the primary chiller and turn on the connection on the backup chiller at the time of switching. See the unit Field Wiring Diagram on page 60 for the Backup Unit connection point (terminals #61 and #62).

Economizer Components

The chiller may or may not have economizers depending on design capacity requirements. An economizer is a well-proven device to increase a refrigerant circuit’s capacity and efficiency.

Warm liquid from the condenser is fed into the economizer where it is cooled by flashing off liquid also from the condenser. The flash gas is piped to a compressor interstage point.

Lowering the liquid refrigerant temperature to the evaporator decreases its enthalpy (heat content) and results in a greater amount of heat absorption from the chilled water.

Figure 17: Economizer Components

www.DaikinApplied.com

13

IOM 1202-2 • PATHFINDER® MODEL AWS CHILLERS

CHILLERS AWS MODEL ®PATHFINDER • 2-1202 IOM

14

com.DaikinApplied.www

 

 

 

 

 

 

 

RANSDUCERSUCTION

 

 

 

AWS PACKAGE CHILLER

 

 

 

 

T

 

 

 

WITH ECONOMIZER

 

 

 

 

 

 

 

 

331994701 REV. 0D

 

 

 

 

 

 

 

 

SCHRADER

 

 

 

 

 

 

CONDENSER

AIR

VALVE

 

 

 

 

 

 

FLOW

(HEADER)

 

 

CHECK

 

BUTTERFLY

ASSEMBLY

 

 

 

 

OIL PRESS.

 

VALVE

 

 

 

 

 

VALVE

 

 

 

DISCHARGE

DISCHARGE

SHUT-OFF

TRANSDUCER

(OPTIONAL)

 

 

TUBING

TRANSDUCER

VALVE

 

WITH SCHRADER

 

 

 

 

 

 

 

VALVE

 

 

BALL

CHARGING

OUTSIDE AIR

RELIEF

 

VALVE

 

VALVE

VALVE

SCHRADER

TEMPERATURE

 

 

 

 

(WAA)

 

 

 

 

VALVE

DISCHARGE

 

 

 

 

 

 

 

 

 

TEMP. SENSOR

F3/F4

 

 

 

 

 

COMPRESSOR

LIQUID

 

AIR

 

 

 

BALL

SCHRADER

LIQUID

 

CHECK

 

 

FLOW

 

 

 

VALVE

VALVE

INJECTION STRAINER

SOLENOID

VALVE

 

TUBING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TUBING

VALVE

 

 

 

 

 

ECONOMIZER FLASH GAS TO COMPRESSOR INTERSTAGE

 

 

 

SCHRADER

SCHRADER

 

 

 

 

 

 

 

 

SUCTION

 

VALVE

 

 

 

 

 

 

 

 

VALVE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TUBING

 

 

 

 

 

 

 

 

 

 

 

FILTER

SCHRADER SIGHT

SOLENOID

 

 

 

 

 

Note: Provide 20-mesh strainer

VALVE

 

 

 

 

 

DRYER

CHARGING

GLASS

VALVE

 

 

 

 

 

at evaporator inlet

 

 

 

 

 

 

 

 

 

 

VALVE

 

 

 

 

 

 

 

 

 

 

 

 

 

TGE

 

 

 

WATER OUT

 

WATER IN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EXPANSION

 

 

 

 

(WOE)

(WIE)

 

 

 

 

 

VALVE

 

 

 

 

 

 

 

 

 

 

 

 

 

TEMP. SENSOR

TEMP. SENSOR

 

 

 

 

 

 

 

 

 

 

 

 

ECONOMIZER

SOLENOID

SCHRADER

EXPANSION CHARGING

DX EVAPORATOR

RELIEF

SUCTION

 

 

VALVE

 

 

 

(OPTIONAL)

VALVE

VALVE

VALVE

 

 

 

VALVE

TEMP. SENSOR

Shown Circuit One Circuit, Economizer with Schematic Piping 18: Figure

tartupS and nstallationI

com.DaikinApplied.www

15

CHILLERS AWS MODEL ®PATHFINDER • 2-1202 IOM

CONDENSER

ASSEMBLY

BALL CHARGING

VALVE VALVE

SCHRADER

VALVE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SCHRADER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FLOW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VALVE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LIQUID

TUBING

FILTER CHARGING SIGHT SCHRADER SOLENOID DRYER VALVE GLASS VALVE VALVE

(OPTIONAL)

AWS PACKAGE CHILLER 331994701 REV. 0D

 

SCHRADER

 

 

AIR

VALVE

 

 

(HEADER)

 

 

FLOW

 

 

 

 

 

 

DISCHARGE

DISCHARGE

 

 

TUBING

TRANSDUCER

SHUT-OFF

 

 

 

 

 

 

VALVE

 

RANSDUCERSUCTION

 

OIL PRESS.

T

 

BUTTERFLY

TRANSDUCER

 

VALVE

WITH SCHRADER

(OPTIONAL)

VALVE

 

 

 

RELIEF

 

 

VALVE

 

 

DISCHARGE

F3/F4

OUTSIDE AIR

TEMP. SENSOR

TEMPERATURE

 

COMPRESSOR

(WAA)

 

 

LIQUID

 

 

SUCTION

INJECTION

 

 

TUBING

 

 

TUBING

BALL

SCHRADER

STRAINER

SOLENOID

VALVE

VALVE

 

VALVE

 

 

 

 

Note: Provide 20-mesh strainer

 

 

WATER OUT

 

at evaporator inlet

 

 

 

WATER IN

 

 

 

 

 

 

 

 

(WOE)

 

(WIE)

 

 

 

TEMP. SENSOR

TEMP. SENSOR

 

EXPANSION

CHARGING

DX EVAPORATOR

RELIEF

SUCTION

VALVE

VALVE

 

 

VALVE

TEMP. SENSOR

Shown Circuit One Circuit, Economizer without Schematic Piping 19: Figure

tartupS and nstallationI

Lifting and Mounting Information

Lifting and Mounting Information

Figure 20: 10 Fan Non-VFD Models

5820

 

 

 

 

229.1

 

 

 

 

 

 

4910

 

 

 

 

193.3

 

 

 

 

4791

 

 

 

 

188.6

2100

 

 

 

 

 

 

 

 

82.7

600

 

 

 

 

 

 

 

 

23.6

 

 

 

 

431

 

 

 

 

17.0

M5

L3

M3

M1

L1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BOX

 

 

 

 

2225

 

 

 

 

 

 

 

 

 

 

 

 

CONTROL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

87.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

190

 

 

M6

L4

 

 

 

 

M4

 

 

M2

L2

AWS 10 FAN DIM. DWG

7.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

330973501

0A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS DIMENSIONAL DATA - WEIGHTS IN LBS.

 

 

LIFTING WEIGHT FOR EACH POINT LB

MOUNTING LOADS FOR EACH POINT LB

UNIT SIZE

VOLTAGE

HZ.

STARTER

SHIPPING OPERATING COPPER # OF

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

WEIGHT

WEIGHT

FIN ADD FANS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS164CDS

400V - 50HZ

WYE DELTA

12535

12778

 

 

3843

3825

2439

2428

2670

2658

2255

2245

1478

1472

AWS190CDS

380-575V - 60HZ SOLID STATE

12829

13072

1786

10

4015

3997

2414

2403

2805

2792

2324

2313

1422

1415

 

208-575V - 60HZ

WYE DELTA

12535

12778

 

 

3843

3825

2439

2428

2670

2658

2255

2245

1478

1472

 

AWS DIMENSIONAL DATA - WEIGHTS IN KG.

 

 

LIFTING WEIGHT FOR EACH POINT KG

MOUNTING LOADS FOR EACH POINT KG

UNIT SIZE

VOLTAGE

HZ.

STARTER

SHIPPING OPERATING COPPER # OF

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

WEIGHT

WEIGHT

FIN ADD FANS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS164CDS

400V - 50HZ

WYE DELTA

5686

5796

 

 

1743

1735

1106

1101

1211

1206

1023

1018

670

668

AWS190CDS

380-575V - 60HZ SOLID STATE

5819

5929

810

10

1821

1813

1095

1090

1272

1266

1054

1049

645

642

 

208-575V - 60HZ

WYE DELTA

5686

5796

 

 

1743

1735

1106

1101

1211

1206

1023

1018

670

668

IOM 1202-2 • PATHFINDER® MODEL AWS CHILLERS

16

www.DaikinApplied.com

Goodman AWS174CDH Installation  Manual

Lifting and Mounting Information

Figure 21: 12 Fan Non-VFD Models

 

AWS 12 FAN DIM. DWG

330973502 0A

 

 

5820

 

 

 

 

229.1

4910

 

 

 

 

 

 

 

 

193.3

 

 

 

 

4791

 

 

 

 

188.6

 

2100

 

 

 

 

 

 

 

 

82.7

600

 

 

 

 

 

 

 

 

23.6

 

 

 

 

431

 

 

 

 

17.0

M5

L3

M3

M1

L1

2225

87.6

190

7.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BOX

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONTROL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M6

L4

 

 

 

 

 

M4

 

 

 

M2

L2

 

 

 

AWS DIMENSIONAL DATA - WEIGHTS IN LBS.

 

 

LIFTING WEIGHT FOR EACH POINT LB

MOUNTING LOADS FOR EACH POINT LB

UNIT SIZE

VOLTAGE

HZ.

STARTER

SHIPPING OPERATING COPPER # OF

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

WEIGHT

WEIGHT

FIN ADD FANS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS174CDH

400V - 50HZ

WYE DELTA

13174

13357

 

 

3823

3805

2779

2767

2598

2586

2314

2303

1782

1773

AWS184CDS

400V - 50HZ

WYE DELTA

13290

13503

 

 

4154

3968

2643

2525

2876

2747

2431

2323

1599

1527

AWS204CDS

400V - 50HZ

WYE DELTA

13789

14032

 

 

4283

4264

2627

2615

2982

2969

2488

2477

1562

1555

AWS210CDH

380-575V - 60HZ SOLID STATE

13470

13653

 

 

3999

3981

2751

2739

2737

2724

2383

2373

1722

1714

208-575V - 60HZ

WYE DELTA

13174

13357

 

 

3823

3805

2779

2767

2598

2586

2314

2303

1782

1773

 

 

 

 

380-575V - 60HZ SOLID STATE

13575

13788

1786

12

4320

4126

2623

2506

3005

2871

2498

2387

1548

1479

AWS210CDS

208-230V - 60HZ

WYE DELTA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V - 60HZ

WYE DELTA

13290

13503

 

 

4154

3968

2643

2525

2876

2747

2431

2323

1599

1527

 

380-575V - 60HZ SOLID STATE

14092

14335

 

 

4459

4439

2603

2591

3121

3106

2558

2547

1505

1498

AWS225CDS

208-230V - 60HZ

WYE DELTA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V - 60HZ

WYE DELTA

13789

14032

 

 

4283

4264

2627

2615

2982

2969

2488

2477

1562

1555

 

AWS DIMENSIONAL DATA - WEIGHTS IN KG.

 

 

LIFTING WEIGHT FOR EACH POINT KG

MOUNTING LOADS FOR EACH POINT KG

UNIT SIZE

VOLTAGE

HZ.

STARTER

SHIPPING OPERATING COPPER # OF

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

WEIGHT

WEIGHT

FIN ADD FANS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS174CDH

400V - 50HZ

WYE DELTA

5976

6059

 

 

1734

1726

1261

1255

1179

1173

1050

1045

808

804

AWS184CDS

400V - 50HZ

WYE DELTA

6028

6125

 

 

1884

1800

1199

1145

1304

1246

1103

1054

725

693

AWS204CDS

400V - 50HZ

WYE DELTA

6255

6365

 

 

1943

1934

1192

1186

1353

1347

1129

1123

708

705

AWS210CDH

380-575V - 60HZ SOLID STATE

6110

6193

 

 

1814

1806

1248

1242

1241

1236

1081

1076

781

778

208-575V - 60HZ

WYE DELTA

5976

6059

 

 

1734

1726

1261

1255

1179

1173

1050

1045

808

804

 

 

 

 

380-575V - 60HZ SOLID STATE

6158

6254

810

12

1960

1872

1190

1137

1363

1302

1133

1083

702

671

AWS210CDS

208-230V - 60HZ

WYE DELTA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V - 60HZ

WYE DELTA

6028

6125

 

 

1884

1800

1199

1145

1304

1246

1103

1054

725

693

 

380-575V - 60HZ SOLID STATE

6392

6502

 

 

2023

2014

1181

1175

1416

1409

1160

1155

683

680

AWS225CDS

208-230V - 60HZ

WYE DELTA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V - 60HZ

WYE DELTA

6255

6365

 

 

1943

1934

1192

1186

1353

1347

1129

1123

708

705

www.DaikinApplied.com

17

IOM 1202-2 • PATHFINDER® MODEL AWS CHILLERS

Lifting and Mounting Information

Figure 22: 14 Fan Non-VFD Models

 

 

 

 

 

 

431

17.0

 

 

CONTROLBOX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

600

23.6

 

 

L1

 

 

L2

 

 

 

 

 

 

 

 

 

 

 

M1

 

 

M2

 

 

 

 

 

 

2100

82.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M3

 

 

M4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4791

188.6

 

 

 

 

 

 

 

 

AWS 14 FAN DIM. DWG

330973503 0A

 

 

4910

193.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L3

 

 

L4

 

 

 

6310

248.4

 

 

 

 

 

 

M5

 

 

M6

 

 

6720

264.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M7

 

 

M8

 

 

 

 

 

 

 

 

 

 

 

 

 

100

3.9

 

 

 

 

 

 

 

 

 

66

2.6

 

2225

87.6

190

7.5

 

IOM 1202-2 • PATHFINDER® MODEL AWS CHILLERS

18

 

 

 

www.DaikinApplied.com

com.DaikinApplied.www

19

CHILLERS AWS MODEL ®PATHFINDER • 2-1202 IOM

 

AWS 14 FAN DIM. DWG

330973503

0A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS DIMENSIONAL DATA - WEIGHTS IN LBS.

 

 

 

LIFTING WEIGHT FOR EACH POINT LB

 

MOUNTING LOADS FOR EACH POINT LB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT SIZE

VOLTAGE

HZ.

STARTER

SHIPPING

OPERATING

COPPER

# OF

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

M7

 

M8

WEIGHT

WEIGHT

 

FIN ADD

FANS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS204CDH

400V 50HZ

WYE DELTA

 

14740

14863

 

 

 

3983

3770

3589

3398

2976

2818

2420

2291

1379

1305

860

 

814

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS224-234CDS

400V 50HZ

WYE DELTA

 

14714

14887

 

 

 

4141

4122

3233

3218

3073

3059

2444

2433

1266

1260

679

 

676

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS224CDH

400V 50HZ

WYE DELTA

 

15420

15523

 

 

 

4092

4092

3619

3619

3048

3048

2471

2471

1390

1390

852

 

852

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V 60HZ

SOLID STATE

 

15042

15165

 

 

 

4168

3928

3576

3370

3103

2924

2503

2359

1380

1301

821

 

774

 

 

 

 

 

 

 

 

 

AWS230CDH

208-230V 60HZ

WYE DELTA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V 60HZ

WYE DELTA

 

14740

14863

 

 

 

3983

3770

3589

3398

2976

2818

2420

2291

1379

1305

860

 

814

 

 

 

 

 

 

 

2084

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V 60HZ

SOLID STATE

 

15015

15188

 

4313

4294

3212

3197

3190

3175

2519

2508

1264

1258

638

 

635

 

 

 

 

 

 

 

 

 

AWS250-260CDS

208-230V 60HZ

WYE DELTA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V 60HZ

WYE DELTA

 

14714

14887

 

 

 

4141

4122

3233

3218

3073

3059

2444

2433

1266

1260

679

 

676

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V 60HZ

SOLID STATE

 

15722

15825

 

 

 

4277

4258

3601

3585

3175

3160

2554

2542

1391

1385

811

 

808

 

 

 

 

 

 

 

 

 

AWS250CDH

208-230V 60HZ

WYE DELTA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V 60HZ

WYE DELTA

 

15420

15523

 

 

 

4092

4092

3619

3619

3048

3048

2471

2471

1390

1390

852

 

852

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS DIMENSIONAL DATA - WEIGHTS IN KG.

 

 

 

LIFTING WEIGHT FOR EACH POINT KG

 

MOUNTING LOADS FOR EACH POINT LB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT SIZE

VOLTAGE

HZ.

STARTER

SHIPPING

OPERATING

COPPER

# OF

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

M7

 

M8

WEIGHT

WEIGHT

 

FIN ADD

FANS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS204CDH

400V 50HZ

WYE DELTA

 

6686

6742

 

 

 

1807

1710

1628

1541

1350

1278

1098

1039

625

592

390

 

369

AWS224-234CDS

400V 50HZ

WYE DELTA

 

6674

6753

 

 

 

1878

1870

1467

1460

1394

1387

1108

1103

574

571

308

 

306

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS224CDH

400V 50HZ

WYE DELTA

 

6995

7041

 

 

 

1856

1856

1641

1641

1383

1383

1121

1121

631

631

386

 

386

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V 60HZ

SOLID STATE

 

6823

6879

 

 

 

1891

1782

1622

1529

1407

1326

1135

1070

626

590

372

 

351

 

 

 

 

 

 

 

 

 

AWS230CDH

208-230V 60HZ

WYE DELTA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V 60HZ

WYE DELTA

 

6686

6742

 

 

 

1807

1710

1628

1541

1350

1278

1098

1039

625

592

390

 

369

 

 

 

 

 

 

 

945

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V 60HZ

SOLID STATE

 

6811

6889

 

1956

1948

1457

1450

1447

1440

1143

1138

573

571

290

 

288

 

 

 

 

 

 

 

 

 

AWS250-260CDS

208-230V 60HZ

WYE DELTA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V 60HZ

WYE DELTA

 

6674

6753

 

 

 

1878

1870

1467

1460

1394

1387

1108

1103

574

571

308

 

306

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V 60HZ

SOLID STATE

 

7131

7178

 

 

 

1940

1931

1634

1626

1440

1433

1158

1153

631

628

368

 

366

 

 

 

 

 

 

 

 

 

AWS250CDH

208-230V 60HZ

WYE DELTA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V 60HZ

WYE DELTA

 

6995

7041

 

 

 

1856

1856

1641

1641

1383

1383

1121

1121

631

631

386

 

386

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(continued) Models VFD-Non Fan 14 23: Figure

nformationI ountingM and iftingL

 

 

 

 

 

 

 

 

 

 

 

 

 

Lifting and Mounting Information

Figure 24: 16 Fan Non-VFD Models

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

431

17.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONTROLBOX

 

 

 

 

 

 

 

 

600

23.6

 

L1

 

 

 

L2

 

 

 

 

 

 

 

 

 

 

M1

 

 

 

M2

 

 

 

 

 

 

2100

82.7

 

 

 

 

 

 

 

 

 

 

 

 

2381

93.7

 

 

 

M3

 

 

 

M4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L4

 

 

 

 

 

 

 

 

 

 

L3

 

 

 

 

 

0A

 

 

4791

188.6

 

 

 

 

 

 

 

 

 

 

330973504

 

4910

193.3

 

 

 

 

 

 

 

 

 

 

 

DWG

 

 

 

 

 

 

 

 

L5

 

 

 

L6

 

DIM.

 

 

 

 

 

 

 

 

M5

 

 

 

M6

 

AWS 16 FAN

 

6791 267.4

 

 

 

 

 

 

 

 

 

 

 

 

 

7210

283.9

 

 

 

 

 

 

 

 

 

 

190

7.5

 

 

 

 

 

 

 

 

 

L7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L8

 

7620

300.0

 

 

 

 

 

 

 

M7

 

100

3.9

M8

 

 

 

 

 

 

 

 

66

2.6

2225

87.6

 

 

 

IOM 1202-2 • PATHFINDER® MODEL AWS CHILLERS

20

 

 

 

www.DaikinApplied.com

com.DaikinApplied.www

21

CHILLERS AWS MODEL ®PATHFINDER • 2-1202 IOM

 

 

 

 

 

 

 

AWS 16 FAN DIM. DWG

330973504 0A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS DIMENSIONAL DATA - WEIGHTS IN LBS.

 

 

 

LIFTING WEIGHT FOR EACH POINT LB

 

 

MOUNTING LOADS FOR EACH POINT LB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT SIZE

VOLTAGE

HZ.

STARTER

SHIPPING

OPERATING

COPPER

# OF

L1

L2

L3

L4

L5

L6

 

L7

L8

M1

M2

M3

M4

M5

M6

M7

M8

WEIGHT

WEIGHT

FIN ADD

FANS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS194CDP

400V - 50HZ

WYE DELTA

16057

16909

 

 

2648

2636

2256

2246

1772

1764

 

1370

1364

2813

2800

2477

2466

1849

1841

1335

1329

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS240CDP

380-575V

- 60HZ

SOLID STATE

16358

17210

 

 

2766

2754

2325

2314

1779

1771

 

1327

1321

2926

2912

2554

2542

1857

1849

1287

1282

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208-575V

- 60HZ

WYE DELTA

16057

16909

 

 

2648

2636

2256

2246

1772

1764

 

1370

1364

2813

2800

2477

2466

1849

1841

1335

1329

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS244-264CDH

400V - 50HZ

WYE DELTA

16793

17160

 

 

3048

3034

2467

2455

1749

1741

 

1153

1147

3103

3089

2642

2630

1780

1772

1074

1069

AWS264CDS

400V - 50HZ

WYE DELTA

16741

17188

 

 

3294

3176

2578

2486

1693

1632

 

958

924

3344

3224

2785

2685

1739

1677

883

851

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V

- 60HZ

SOLID STATE

17094

17461

 

 

3158

3158

2529

2529

1752

1752

 

1108

1108

3206

3206

2711

2711

1786

1786

1028

1028

 

 

 

 

 

 

 

 

AWS280-300CDH

208-575V

- 60HZ

WYE DELTA

 

 

2372

16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V

- 60HZ

WYE DELTA

16793

17160

 

 

3048

3034

2467

2455

1749

1741

 

1153

1147

3103

3089

2642

2630

1780

1772

1074

1069

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS284CDS

400V - 50HZ

WYE DELTA

17432

17869

 

 

3426

3426

2658

2658

1709

1709

 

922

922

3465

3465

2870

2870

1756

1756

843

843

AWS290CDS

380-575V

- 60HZ

SOLID STATE

17044

17491

 

 

3414

3292

2648

2553

1701

1640

 

915

882

3457

3333

2862

2760

1749

1686

837

807

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V

- 60HZ

WYE DELTA

16741

17188

 

 

3294

3176

2578

2486

1693

1632

 

958

924

3344

3224

2785

2685

1739

1677

883

851

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS310CDS

380-575V

- 60HZ

SOLID STATE

17724

18161

 

 

3547

3531

2730

2718

1721

1713

 

883

879

3580

3563

2950

2936

1769

1761

803

799

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V

- 60HZ

WYE DELTA

17432

17869

 

 

3426

3426

2658

2658

1709

1709

 

922

922

3465

3465

2870

2870

1756

1756

843

843

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS DIMENSIONAL DATA - WEIGHTS IN KG.

 

 

 

LIFTING WEIGHT FOR EACH POINT KG

 

 

MOUNTING LOADS FOR EACH POINT KG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT SIZE

VOLTAGE

HZ.

STARTER

SHIPPING

OPERATING

COPPER

# OF

L1

L2

L3

L4

L5

L6

 

L7

L8

M1

M2

M3

M4

M5

M6

M7

M8

WEIGHT

WEIGHT

FIN ADD

FANS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS194CDP

400V - 50HZ

WYE DELTA

7283

7670

 

 

1201

1196

1023

1019

804

800

 

621

619

1276

1270

1124

1119

839

835

605

603

AWS240CDP

380-575V

- 60HZ

SOLID STATE

7420

7806

 

 

1255

1249

1055

1050

807

803

 

602

599

1327

1321

1158

1153

843

839

584

581

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208-575V

- 60HZ

WYE DELTA

7283

7670

 

 

1201

1196

1023

1019

804

800

 

621

619

1276

1270

1124

1119

839

835

605

603

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS244-264CDH

400V - 50HZ

WYE DELTA

7617

7784

 

 

1382

1376

1119

1114

793

790

 

523

520

1407

1401

1199

1193

807

804

487

485

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS264CDS

400V - 50HZ

WYE DELTA

7594

7796

 

 

1494

1441

1169

1127

768

740

 

435

419

1517

1462

1263

1218

789

761

401

386

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V

- 60HZ

SOLID STATE

7754

7920

 

 

1432

1432

1147

1147

795

795

 

502

502

1454

1454

1230

1230

810

810

466

466

 

 

 

 

 

 

 

 

AWS280-300CDH

208-575V

- 60HZ

WYE DELTA

1076

16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V

- 60HZ

WYE DELTA

7617

7784

 

 

1382

1376

1119

1114

793

790

 

523

520

1407

1401

1199

1193

807

804

487

485

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS284CDS

400V - 50HZ

WYE DELTA

7907

8105

 

 

1554

1554

1206

1206

775

775

 

418

418

1572

1572

1302

1302

796

796

383

383

AWS290CDS

380-575V

- 60HZ

SOLID STATE

7731

7934

 

 

1549

1493

1201

1158

771

744

 

415

400

1568

1512

1298

1252

793

765

380

366

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V

- 60HZ

WYE DELTA

7594

7796

 

 

1494

1441

1169

1127

768

740

 

435

419

1517

1462

1263

1218

789

761

401

386

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS310CDS

380-575V

- 60HZ

SOLID STATE

8039

8238

 

 

1609

1602

1239

1233

781

777

 

401

399

1624

1616

1338

1332

802

799

364

362

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V

- 60HZ

WYE DELTA

7907

8105

 

 

1554

1554

1206

1206

775

775

 

418

418

1572

1572

1302

1302

796

796

383

383

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(continued) Models VFD-Non Fan 16 25: Figure

nformationI ountingM and iftingL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Lifting and Mounting Information

Figure 26: 18 Fan Non-VFD Models

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

600

23.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONTROLBOX

 

 

 

 

 

 

 

 

 

 

431

17.0

L1

 

 

 

L2

 

 

 

 

 

 

 

 

 

 

 

M1

 

 

 

M2

 

 

 

 

 

 

 

2100

82.7

 

 

 

 

 

 

 

 

 

 

 

 

 

2381

93.7

 

 

 

M3

 

 

 

M4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L4

 

 

 

 

 

 

 

 

 

 

 

L3

 

 

 

 

 

 

 

 

 

4791

188.6

 

 

 

 

 

 

 

 

 

 

0A

 

 

4910

193.3

 

 

 

 

 

 

 

 

 

 

 

330973505

 

 

 

 

 

 

 

 

 

M5 L5

 

 

 

M6 L6

 

DIM. DWG

 

7484

294.6

 

 

 

 

 

 

 

 

 

 

 

 

AWS 18 FAN

 

 

 

 

 

 

 

 

 

 

 

 

 

190

7.5

 

8110

319.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L8

 

8520

335.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M7

 

100

3.9

M8

 

 

 

 

 

 

 

 

 

66

2.6

 

2225

87.6

 

 

 

IOM 1202-2 • PATHFINDER® MODEL AWS CHILLERS

22

 

 

 

www.DaikinApplied.com

com.DaikinApplied.www

23

CHILLERS AWS MODEL ®PATHFINDER • 2-1202 IOM

 

 

 

AWS 18 FAN DIM. DWG

330973505 0A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS DIMENSIONAL DATA - WEIGHTS IN LBS.

 

 

 

LIFTING WEIGHT FOR EACH POINT LB

MOUNTING LOADS FOR EACH POINT LB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT SIZE

VOLTAGE

HZ.

STARTER

SHIPPING

OPERATING

COPPER

# OF

L1

L2

L3

L4

L5

L6

L7

L8

M1

M2

M3

M4

M5

M6

M7

M8

WEIGHT

WEIGHT

FIN ADD

FANS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS214CDP

400V - 50HZ

WYE DELTA

17527

18329

 

 

 

2826

2737

2476

2398

2043

1979

1559

1510

3009

2914

2702

2617

2127

2060

1473

1427

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS244CDP

400V - 50HZ

WYE DELTA

19237

20420

 

 

 

3006

3006

2655

2655

2221

2221

1736

1736

3257

3257

2940

2940

2345

2345

1668

1668

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V

- 60HZ

SOLID STATE

17829

18631

 

 

 

2944

2839

2550

2459

2063

1989

1519

1465

3121

3009

2784

2684

2151

2074

1430

1379

 

 

 

 

 

 

 

 

AWS265CDP

208-230V

- 60HZ

WYE DELTA

2679

 

18

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V

- 60HZ

WYE DELTA

17527

18329

 

2826

2737

2476

2398

2043

1979

1559

1510

3009

2914

2702

2617

2127

2060

1473

1427

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V

- 60HZ

SOLID STATE

19539

20722

 

 

 

3115

3115

2723

2723

2237

2237

1694

1694

3361

3361

3014

3014

2363

2363

1622

1622

 

 

 

 

 

 

 

 

AWS290CDP

208-230V

- 60HZ

WYE DELTA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V

- 60HZ

WYE DELTA

19237

20420

 

 

 

3006

3006

2655

2655

2221

2221

1736

1736

3257

3257

2940

2940

2345

2345

1668

1668

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS DIMENSIONAL DATA - WEIGHTS IN KG.

 

 

 

LIFTING WEIGHT FOR EACH POINT KG

MOUNTING LOADS FOR EACH POINT KG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT SIZE

VOLTAGE

HZ.

SHIPPING

SHIPPING

OPERATING

COPPER

# OF

L1

L2

L3

L4

L5

L6

L7

L8

M1

M2

M3

M4

M5

M6

M7

M8

WEIGHT

WEIGHT

WEIGHT

FIN ADD

FANS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS214CDP

400V - 50HZ

WYE DELTA

7950

8314

 

 

 

1282

1241

1123

1088

927

898

707

685

1365

1322

1226

1187

965

935

668

647

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS244CDP

400V - 50HZ

WYE DELTA

8726

9262

 

 

 

1363

1363

1204

1204

1008

1008

788

788

1477

1477

1333

1333

1064

1064

757

757

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V

- 60HZ

SOLID STATE

8087

8451

 

 

 

1336

1288

1157

1115

936

902

689

664

1416

1365

1263

1217

976

941

649

625

 

 

 

 

 

 

 

 

AWS265CDP

208-230V

- 60HZ

WYE DELTA

1215

 

18

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V

- 60HZ

WYE DELTA

7950

8314

 

1282

1241

1123

1088

927

898

707

685

1365

1322

1226

1187

965

935

668

647

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V

- 60HZ

SOLID STATE

8863

9399

 

 

 

1413

1413

1235

1235

1015

1015

769

769

1525

1525

1367

1367

1072

1072

736

736

 

 

 

 

 

 

 

 

AWS290CDP

208-230V

- 60HZ

WYE DELTA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V

- 60HZ

WYE DELTA

8726

9262

 

 

 

1363

1363

1204

1204

1008

1008

788

788

1477

1477

1333

1333

1064

1064

757

757

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(continued) Models VFD-Non Fan 18 27: Figure

nformationI ountingM and iftingL

 

 

 

 

 

 

 

 

 

 

 

 

 

Lifting and Mounting Information

Figure 28: 20 Fan Non-VFD Models

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

431

17.0

CONTROLBOX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

600

23.6

 

 

L1

 

 

L2

 

 

 

 

 

 

 

 

 

 

M1

 

 

M2

 

 

 

 

 

2100

82.7

 

 

 

 

 

 

 

 

 

 

 

2381

93.7

 

 

 

 

M3

 

 

M4

 

 

 

 

 

 

 

 

 

 

L3

 

 

L4

 

 

 

 

 

 

 

 

 

 

 

 

 

0A

 

 

4910

193.3

 

 

 

 

 

 

 

 

 

330973506

 

 

 

 

 

 

 

 

 

M5

 

 

M6

DWG

 

 

5961 234.7

 

 

 

 

 

 

L5

 

 

 

DIM.

 

 

 

 

 

 

 

 

 

 

 

L6

FAN

 

 

 

 

 

 

 

 

 

 

 

 

AWS 20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8384

330.1

 

 

 

 

66

2.6

 

190

7.5

 

9010

354.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L7

 

 

 

9421

370.9

 

 

 

 

 

 

 

 

 

 

 

L8

 

 

 

 

 

 

 

 

 

 

M7

 

100

3.9

 

 

 

 

 

 

 

 

 

 

 

 

 

M8

 

 

 

 

 

 

 

 

 

 

 

2225

87.6

 

IOM 1202-2 • PATHFINDER® MODEL AWS CHILLERS

24

www.DaikinApplied.com

com.DaikinApplied.www

25

CHILLERS AWS MODEL ®PATHFINDER • 2-1202 IOM

 

 

 

 

 

 

AWS 20 FAN DIM. DWG

330973506

0A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS DIMENSIONAL DATA - WEIGHTS IN LBS.

 

 

 

LIFTING WEIGHT FOR EACH POINT LB

MOUNTING LOADS FOR EACH POINT LB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT SIZE

VOLTAGE

HZ.

STARTER

SHIPPING

OPERATING

COPPER

# OF

L1

L2

 

L3

 

L4

L5

L6

L7

L8

M1

M2

M3

M4

M5

M6

M7

M8

WEIGHT

 

WEIGHT

FIN ADD

FANS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS264-284CDP

400V - 50HZ

WYE DELTA

20124

 

21257

 

 

 

3278

3278

2893

2893

2185

2185

1706

1706

3223

3223

2984

2984

2537

2537

1884

1884

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS294CDH

400V - 50HZ

WYE DELTA

19139

 

19461

 

 

 

3463

3338

2944

2838

1991

1920

1347

1298

3256

3139

2927

2822

2312

2229

1414

1363

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V

- 60HZ

SOLID STATE

20426

 

21559

 

 

 

3385

3385

2965

2965

2193

2193

1671

1671

3321

3321

3057

3057

2562

2562

1839

1839

 

 

 

 

 

 

 

 

 

AWS310-330CDP

208-230V

- 60HZ

WYE DELTA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V

- 60HZ

WYE DELTA

20124

 

21257

 

 

 

3278

3278

2893

2893

2185

2185

1706

1706

3223

3223

2984

2984

2537

2537

1884

1884

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS314CDH

400V - 50HZ

WYE DELTA

19846

 

20143

 

 

 

3592

3592

3031

3031

1999

1999

1301

1301

3367

3367

3009

3009

2338

2338

1358

1358

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS314-334CDS

400V - 50HZ

WYE DELTA

19164

 

19501

2968

 

20

3558

3558

2970

2970

1892

1892

1162

1162

3337

3337

2958

2958

2247

2247

1209

1209

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS330CDH

460-575V

- 60HZ

SOLID STATE

19442

 

19764

 

 

 

3573

3445

3018

2910

1998

1927

1308

1262

3355

3235

3001

2893

2337

2253

1369

1320

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V

- 60HZ

WYE DELTA

19139

 

19461

 

 

 

3463

3338

2944

2838

1991

1920

1347

1298

3256

3139

2927

2822

2312

2229

1414

1363

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS350-375CDS

460-575V

- 60HZ

SOLID STATE

19466

 

19803

 

 

 

3666

3666

3043

3043

1899

1899

1124

1124

3434

3434

3030

3030

2272

2272

1166

1166

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V

- 60HZ

WYE DELTA

19164

 

19501

 

 

 

3558

3558

2970

2970

1892

1892

1162

1162

3337

3337

2958

2958

2247

2247

1209

1209

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS350CDH

460-575V

- 60HZ

SOLID STATE

20147

 

20444

 

 

 

3699

3699

3102

3102

2007

2007

1266

1266

3462

3462

3080

3080

2363

2363

1317

1317

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V

- 60HZ

WYE DELTA

19846

 

20143

 

 

 

3592

3592

3031

3031

1999

1999

1301

1301

3367

3367

3009

3009

2338

2338

1358

1358

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS DIMENSIONAL DATA - WEIGHTS IN KG.

 

 

 

LIFTING WEIGHT FOR EACH POINT KG

MOUNTING LOADS FOR EACH POINT KG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT SIZE

VOLTAGE

HZ.

STARTER

SHIPPING

OPERATING

COPPER

# OF

L1

L2

 

L3

 

L4

L5

L6

L7

L8

M1

M2

M3

M4

M5

M6

M7

M8

WEIGHT

 

WEIGHT

FIN ADD

FANS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS264-284CDP

400V - 50HZ

WYE DELTA

9128

 

9642

 

 

 

1487

1487

1312

1312

991

991

774

774

1462

1462

1354

1354

1151

1151

855

855

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS294CDH

400V - 50HZ

WYE DELTA

8682

 

8827

 

 

 

1571

1514

1335

1287

903

871

611

589

1477

1424

1328

1280

1049

1011

641

618

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V

- 60HZ

SOLID STATE

9265

 

9779

 

 

 

1535

1535

1345

1345

995

995

758

758

1506

1506

1387

1387

1162

1162

834

834

 

 

 

 

 

 

 

 

 

AWS310-330CDP

208-230V

- 60HZ

WYE DELTA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V

- 60HZ

WYE DELTA

9128

 

9642

 

 

 

1487

1487

1312

1312

991

991

774

774

1462

1462

1354

1354

1151

1151

855

855

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS314CDH

400V - 50HZ

WYE DELTA

9002

 

9137

 

 

 

1630

1630

1375

1375

907

907

590

590

1527

1527

1365

1365

1060

1060

616

616

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS314-334CDS

400V - 50HZ

WYE DELTA

8693

 

8846

1346

 

20

1614

1614

1347

1347

858

858

527

527

1514

1514

1342

1342

1019

1019

549

549

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS330CDH

460-575V

- 60HZ

SOLID STATE

8819

 

8965

 

 

 

1621

1563

1369

1320

906

874

594

572

1522

1467

1361

1312

1060

1022

621

599

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V

- 60HZ

WYE DELTA

8682

 

8827

 

 

 

1571

1514

1335

1287

903

871

611

589

1477

1424

1328

1280

1049

1011

641

618

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS350-375CDS

460-575V

- 60HZ

SOLID STATE

8830

 

8983

 

 

 

1663

1663

1380

1380

861

861

510

510

1558

1558

1374

1374

1030

1030

529

529

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V

- 60HZ

WYE DELTA

8693

 

8846

 

 

 

1614

1614

1347

1347

858

858

527

527

1514

1514

1342

1342

1019

1019

549

549

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS350CDH

460-575V

- 60HZ

SOLID STATE

9139

 

9273

 

 

 

1678

1678

1407

1407

910

910

574

574

1571

1571

1397

1397

1072

1072

597

597

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V

- 60HZ

WYE DELTA

9002

 

9137

 

 

 

1630

1630

1375

1375

907

907

590

590

1527

1527

1365

1365

1060

1060

616

616

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(continued) Models VFD-Non Fan 20 29: Figure

nformationI ountingM and iftingL

 

 

 

 

 

 

 

 

 

 

 

 

 

Lifting and Mounting Information

Figure 30: 22 Fan Non-VFD Models

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

431

17.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONTROLBOX

 

 

 

 

 

 

 

 

600

23.6

L1

 

 

L2

 

 

 

 

 

 

 

 

 

 

M1

 

 

M2

 

 

 

 

 

 

 

2100

82.7

 

 

 

 

 

 

 

 

 

 

 

2381

93.7

 

 

M3

 

 

M4

 

 

 

 

 

 

 

 

 

 

 

 

 

L4

 

 

 

 

 

 

 

 

 

 

L3

 

 

 

 

 

 

 

 

5401

212.6

 

 

 

 

 

 

 

 

0A

 

 

6000

236.2

 

 

 

 

 

 

 

 

 

330973507

 

 

 

 

 

 

 

 

L5

 

 

L6

 

DWG

 

 

 

 

 

 

 

 

M5

 

 

M6

 

22 FAN DIM.

 

8384

330.1

 

 

 

 

 

 

 

 

 

 

AWS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9110

358.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L7

 

 

L8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M7

 

 

M8

 

10720

422.0

 

 

 

 

 

 

 

 

 

 

190

7.5

 

 

 

 

 

 

 

 

66

2.6

 

100

3.9

 

 

 

 

 

 

 

 

 

 

 

2225

87.6

 

 

IOM 1202-2 • PATHFINDER® MODEL AWS CHILLERS

26

 

 

www.DaikinApplied.com

com.DaikinApplied.www

27

CHILLERS AWS MODEL ®PATHFINDER • 2-1202 IOM

 

 

 

AWS 22 FAN DIM. DWG

330973507 0A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS DIMENSIONAL DATA - WEIGHTS IN LBS.

 

 

 

 

LIFTING WEIGHT FOR EACH POINT LB

 

 

MOUNTING LOADS FOR EACH POINT LB

 

UNIT SIZE

VOLTAGE

HZ.

STARTER

SHIPPING

OPERATING

COPPER

# OF

L1

 

L2

L3

L4

L5

L6

L7

L8

M1

M2

M3

M4

M5

M6

M7

M8

WEIGHT

WEIGHT

 

FIN ADD

FANS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS314CDP

400V - 50HZ

WYE DELTA

22264

23357

 

 

 

3162

 

3063

2987

2893

2715

2629

2446

2369

3577

3465

3339

3234

2721

2635

2228

2157

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS344CDH

400V - 50HZ

WYE DELTA

21312

21563

 

 

 

3266

 

3251

2953

2940

2469

2458

1991

1982

3498

3482

3188

3174

2382

2371

1738

1730

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS365CDP

460-575V - 60HZ

SOLID STATE

22566

23659

 

3256

22

3271

 

3168

3058

2962

2730

2644

2405

2329

3682

3566

3418

3311

2733

2647

2186

2117

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V - 60HZ

WYE DELTA

22264

23357

 

3162

 

3063

2987

2893

2715

2629

2446

2369

3577

3465

3339

3234

2721

2635

2228

2157

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS390CDH

460-575V - 60HZ

SOLID STATE

21613

21864

 

 

 

3371

 

3356

3023

3009

2485

2473

1952

1944

3598

3581

3263

3249

2394

2384

1701

1694

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V - 60HZ

WYE DELTA

21312

21563

 

 

 

3266

 

3251

2953

2940

2469

2458

1991

1982

3498

3482

3188

3174

2382

2371

1738

1730

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS DIMENSIONAL DATA - WEIGHTS IN KG.

 

 

 

 

LIFTING WEIGHT FOR EACH POINT KG

 

 

MOUNTING LOADS FOR EACH POINT KG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT SIZE

VOLTAGE

HZ.

STARTER

SHIPPING

OPERATING

COPPER

# OF

L1

 

L2

L3

L4

L5

L6

L7

L8

M1

M2

M3

M4

M5

M6

M7

M8

WEIGHT

WEIGHT

 

FIN ADD

FANS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS314CDP

400V - 50HZ

WYE DELTA

10099

10595

 

 

 

1434

 

1389

1355

1312

1231

1193

1109

1075

1623

1572

1515

1467

1234

1195

1010

979

AWS344CDH

400V - 50HZ

WYE DELTA

9667

9781

 

 

 

1481

 

1475

1340

1334

1120

1115

903

899

1587

1580

1446

1439

1080

1075

789

785

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS365CDP

460-575V - 60HZ

SOLID STATE

10236

10732

 

1477

22

1484

 

1437

1387

1344

1238

1199

1091

1056

1670

1618

1550

1502

1240

1201

992

960

380-575V - 60HZ

WYE DELTA

10099

10595

 

1434

 

1389

1355

1312

1231

1193

1109

1075

1623

1572

1515

1467

1234

1195

1010

979

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS390CDH

460-575V - 60HZ

SOLID STATE

9804

9917

 

 

 

1529

 

1522

1371

1365

1127

1122

886

882

1632

1624

1480

1474

1086

1081

772

768

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-575V - 60HZ

WYE DELTA

9667

9781

 

 

 

1481

 

1475

1340

1334

1120

1115

903

899

1587

1580

1446

1439

1080

1075

789

785

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(continued) Models VFD-Non Fan 22 31: Figure

nformationI ountingM and iftingL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Lifting and Mounting Information

Figure 32: 24 Fan 2-Circuit Non-VFD Models

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONTROLBOX

 

 

 

 

 

 

 

 

600

23.6

431

17.0

L1

 

L2

 

 

 

 

 

 

 

 

 

 

 

 

M1

 

M2

 

 

 

 

 

 

 

2100

82.7

 

 

 

 

 

 

 

 

 

 

 

 

2381

93.7

 

 

 

 

M3

 

M4

 

 

 

 

 

 

 

 

 

 

 

 

L3

 

L4

 

 

 

 

 

5401

212.6

 

 

 

 

 

 

 

 

 

 

 

 

5949

234.2

 

 

 

 

 

 

 

 

 

0A

 

 

 

 

 

 

 

 

 

 

 

M5 L5

 

M6 L6

330973508

 

 

 

8147 320.8

 

 

 

 

 

 

 

 

 

 

DIM. DWG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AWS 24 FAN

 

 

 

 

 

 

 

 

 

 

 

M7

 

M8

 

 

 

9962

392.2

 

 

 

 

 

 

 

 

 

 

 

 

10499

413.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L7

 

L8

 

 

 

 

 

 

 

 

 

 

 

 

M9

 

M10

 

11620

457.5

 

 

 

 

 

 

 

 

 

 

100

3.9

 

 

 

 

 

 

 

 

 

 

 

66

2.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

190

7.5

 

 

 

 

 

 

 

 

 

 

 

2225

87.6

 

 

IOM 1202-2 • PATHFINDER® MODEL AWS CHILLERS

28

 

www.DaikinApplied.com

Loading...
+ 142 hidden pages