Flowserve NRS 2-40 User Manual

NRS 2-40
Installation Instructions 810371-02
Level Switch Type NRS 2-40
1
Contents
Page
Important Notes
Usage to the intended purpose .......................................................................................7
Safety note / Danger.......................................................................................................7
Explanatory Notes
Scope of supply ..............................................................................................................8
System description .........................................................................................................8
Function ..........................................................................................................................8
Technical data .................................................................................................................9
Installation
Example of installation ................................................................................................. 29
Wiring
Wiring diagram ......................................................................................................3, 4, 11
Basic Adjustment
CAN bus........................................................................................................................12
Node ID .........................................................................................................................12
First / second control equipment ..................................................................................12
Factory setting ..............................................................................................................13
Commissioning
Control range ................................................................................................................ 14
Establish control range............................................................................................15, 16
Establish switchpoints within adjusted control range ....................................................16
Establish switchpoints ........................................................................................... 16 – 19
Operation
Normal operation ..........................................................................................................19
Alarm ............................................................................................................................. 19
High-level alarm ............................................................................................................19
Low-level alarm ............................................................................................................. 19
Relay test high/low (
System Malfunctions
Systematic fault finding procedure ................................................................................21
Analysis of system malfunctions 1 – 4 ....................................................................22–24
Operation Malfunctions
Fault-finding list for troubleshooting ........................................................................ 25, 26
Annex
Factory set default node IDs .........................................................................................27
Assigning / changing node IDs ................................................................................27, 28
Declaration of conformity .............................................................................................. 29
2
MAX/MIN) level .................................................................................20
Wiring Diagram
Relay Relay Relay Relay
1234
Fill/
MAX
discharge control
MIN
Seite
Paired cable
Paired cable
Fig. 1
Control terminal URB 1
*) CEP = central earthing point
Level switch NRS 2-40
CEP*)
Power supply CAN data line
Terminating resistor 120
Fig. 2
Controller . . .
Potentiometer
Terminating resistor
ΩΩ
120
ΩΩ
Level electrodes NRG 26-40
Terminating resistor 120
optional output for actual value 4-20 mA
Electrodes ...
3
Wiring Diagram
Discharge control –
Pump OFF at low level (MIN)
Pump contactor
Paired cable
Paired cable
Fig. 3
Potentiometer
Terminating resistor
ΩΩ
120
ΩΩ
Fill control – Pump OFF at high level (MAX)
Paired cable
Paired cable
Fig. 4
Potentiometer
Terminating resistor
ΩΩ
120
ΩΩ
optional output for actual value 4-20 mA
Pump contactor
optional output for actual value 4-20 mA
4
Parts Drawing
1
Fig. 5
A
A B
3567
4
2
Fig. 6
5
Key
1
Indicator LEDs
Discharge control Fill control
LED 1 – switchpoint 1
LED 2 – switchpoint 2
LED 3 – switchpoint 3
LED 4 – switchpoint 4
2
LED “Bus status”
3
LED “Power”
4
Enter button / test mode
5
Decrease button
6
Increase button
7
Program button
8
Code switch, 10 poles
A
Terminal strip
B
Screws for terminal strip
High-level alarm High-level alarm
Pump ON Pump OFF
PUMP OFF Pump ON
Low-level alarm Low-level alarm
6
Important Notes
Usage for the intended purpose
Use level switch NRS 2-40 in conjunction with level electrode NRG 26-40 only for liquid level monitoring and control.
Safety notes
The equipment must only be installed by qualified staff. Qualified staff are those persons who – through adequate training in electrical
engineering, the use and application of safety equipment in accordance with regulations concerning electrical safety systems, and first aid & accident prevention – have achieved a recognised level of competence appropriate to the installation and commissioning of this device.
Danger
The terminal strip of the NRS 2-40 is live during operation. This presents the danger of electric shock. Cut off power supply before fixing or removing the cover.
7
Explanatory Notes
Scope of supply
NRS 2-40
1 Level switch type NRS 2-40 (plug-in unit in plastic case with box terminals) 1 Terminating resistor 120 1 Operating manual
Description
Use level switch type NRS 2-40 in combination with level electrode type NRG 26-40 for level monitoring. The level switch has the following functions:
Four liquid levels with one switchpoint each.
High-level alarm, low-level alarm, pump ON, pump OFF, with one switchpoint each.
Continuous level monitoring within control band defined by two preset limits.
Actual-value output 4-20 mA (optional)
Contact multiplication by connecting in parallel a second level switch NRS 2-40 without optional actual value output.
The level data are transmitted via CAN-bus from the electrode NRG 26-40 to the level switch.
Function
At regular intervals the level electrode type NRG 26-40 sends a data telegram to the level switch NRS 2-40. The data transfer is effected by means of a CAN bus according to DIN ISO 11898. The transferred measuring data are then evaluated and assigned to the manually adjusted switchpoints. To guarantee the correct functioning and safety of the system the data transmitting cycle is constantly monitored by the level switch. When the CAN bus line is interrupted the level switch sends a visual signal to indicate a malfunction and the relays 1 and 4 will be instantaneously de-energized (alarm position).
Additional functions, e.g. (de)-energizing delay times of the output relays (1 to 25 sec.) can be adjusted with the control terminal and display unit URB 1.
8
Technical data
Type approval no.
NRS 2-40: TÜV · WR · 98-399
Input / Output
Interface for CAN bus to DIN ISO 11898 using CANopen
Output – voltage supply for electrodes
Power supply 24 V DC, short-circuit protected Analogue output 4– 20 mA, load 500 for display of actual value (optional). 4 volt-free relay contacts. Max. contact rating with switching voltages of 24 V AC, 115 V AC and 230 V AC: 4 A resistive, 0.75 A inductive at cos ϕ 0.5 Max. contact rating with a switching voltage of 24 V DC: 4 A. Contact material: silver, hard-gold plated
Interference suppression
Provide contactor with an external RC combination (100 Ω / 47nF)
Relay de-energizing delay
Output “MIN”, “MAX” 3 s
Indicators and adjustors
1 red LED for switchpoint “High level” (MAX) 1 red LED for switchpoint “Low level” (MIN) 2 green LEDs for switchpoints “PUMP ON” and “PUM OFF” 1 green LED “Power” 1 red LED “Bus fault” 1 ten-pole code switch for node ID and baud rate settings 4 pushbuttons
Supply voltage
230 V ± 10 %, 50/60 Hz 115 V ± 10 %, 50/60 Hz (option)
Power consumption
10 VA
Protection
Case: IP 40 to DIN ISO 60529 Terminal strip: IP 20 to DIN ISO 60529
Admissible ambient temperature
0 °C to 55 °C
Enclosure material
Front panel: polycarbonate, grey Case: polycarbonate, black
Weight
Approx. 0.8 kg
9
Installation
NRS 2-40
Installation on mounting rail
1. Clip level switch onto mounting rail 35x 15 mm (DIN EN 50022).
2. Align level switch, fig. 14, fig. 15
Tool
Screwdriver (5.5/100)
Wiring
Note that screened multi-core twisted-pair control cable is required, e. g. UNITRONIC
®
BUS CAN 2 x 2 x ... 2 or RE-2YCYV-fl 2 x 2 x ...
2
.
The baud rate (data transfer rate) dictates the cable length between the bus nodes and the total power consumption of the measuring sensors dictates the conductor size.
8S9S01SetarduaBhtgnelelbaC
FFO NO FFO s/tiBk052 m521
gnittesyrotcaF
NONOFFOs/tiBk521m0525.0x2x2
FFOFFONOs/tiBk001m53357.0x2x2
NOFFONOs/tiBk05m005
FFONONOs/tiBk02m0001
NONONOs/tiBk01m0001
sriapforebmuN
2
mm[ezisrotcudnocdna
]
43.0x2x2
notnedneped,tseuqerno
noitarugifnocsub
The baud rate is set via a code switch. Reduce baud rate if cable is longer than specified in the table. Make sure that all bus nodes have the same settings.
To protect the switching contacts fuse circuit with 2.5 A (anti-surge fuse) or according to TRD regulations (1.0 A for 72 hrs operation).
When a max. cable length of 1000 m is desired, make sure to modify the baud rate accordingly. Refer to page 27 and 28 for more details.
Wiring diagram
See wiring diagrams on pages 3 and 4.
UNITRONIC® is a registered trademark of LAPP Kabelwerke GmbH, Stuttgart
10
Wiring – continued –
Attention
Wire equipment in series. Star-type wiring is not permitted.
Interlink screens of control cables such that electrical continuity is ensured and connect them once to the central earthing point (CEP).
To protect the switching contacts fuse circuit with T 2.5 A or according to TRD regulations (1.0 A for 72 hrs.).
If two or more system components are connected in a CAN bus network, the first and last equipment have to be provided with a terminating resistor of 120 Ω. Fig. 2
The CAN bus network must not be interrupted while operating. Any interruption will result in
If the level controller must be replaced, remove terminal strip Fig. 6.
Before removing the CAN-bus line from the terminal strip disconnect all relevant system components.
Note
Connect screen only to designated terminals.
The loop resistance must be under 10 Ω.
The rated voltage is stated on the name plate.
When switching off inductive loads, voltage spikes are produced that may impair the operation of control and measuring systems. Inductive loads should therefore be provided with commercial arc suppressor RC combinations.
In spite of correct wiring H.F. interference caused by the installation may lead to system breakdowns and malfunction messages. If necessary refer to the “Fault finding list for troubleshooting” on pages 25 and 26.
HIGH/LOW level alarm!
A
Tool
Screwdriver for slotted screws, size 2.5, completely insulated according to
VDE 0680.
11
Basic Adjustments
CAN Bus
All level and conductivity controllers and associated electrodes are interconnected by means of a CAN bus using the CANopen protocol. Every item of equipment features an electronic address (Node ID). The four-core bus cable serves as power supply and data highway for high-speed data exchange. The CAN address (Node ID) can be set between 1 and 123.
The NRS 2-40 is configured at our works and ready for service with other GESTRA system components without having to set the node ID.
If several systems of the same kind are to communicate in one CAN bus network, be sure to assign one node ID for each individual system component. Refer to pages 27 and 28 for more details.
Node ID
First and second control equipment
It is possible to operate the level switch NRS 2-40 together with a second level switch NRS 2-40 when 8 instead of only 4 switchpoints are required. The second level switch is termed “second control equipment” and must be ordered separately.
The NRS 2-40 can also be operated together with the level controller NRR 2-40 as “second control equipment”.
The standard equipment NRS 2-40 is termed “first control equipment 1”. Be sure to assign different node IDs for NRS 2-40 (first control equipment),
additional NRS 2-40 (second control equipment) and NRR 2-40 (controller)!
The name plate of the NRS 2-40 is marked “Control equipment 1” or “Control equipment 2”.
12
Basic Adjustments – continued –
Factory setting
The level switch features the following factory set default values:
Baud rate: 250 kb/s
Control equipment: 1
Node ID: 039
Control equipment: 2
Node ID: 040
Switchpoint 1: 80%
Switchpoint 2: 60%
Switchpoint 3: 40%
Switchpoint 4: 20%
80% 60 % 40% 20%
Relay with energizing delay switchpoint 1: 1s
Relay with energizing delay switchpoint 2: 1s
Relay with energizing delay switchpoint 3: 1s
Relay with energizing delay switchpoint 4: 1s
Relay with de-energizing delay switchpoint 1: 3s
Relay with de-energizing delay switchpoint 2: 1s
Relay with de-energizing delay switchpoint 3: 1s
Relay with de-energizing delay switchpoint 4: 3s
100 %
Fig. 7
13
Commissioning
NRS 2-40
Apply power to the unit. The four indicator LEDs flash rapidly.
The LED “Power” lights up. The system test cycle takes about 2 sec.
Control Range
1
Desired control range [mm]
2
Max. control range
Establish the control range for your level monitoring
1
37
application.
2
Fig. 8
26
Indicator LEDs flash rapidly
LED “Power” illuminated
NRG 26-40
1
Lower control range limit
14
Commissioning – continued –
Establish control range
Press button for 3 sec. Lower the liquid level in the vessel until the
lower limit of the control range is reached.
1
Use button if you want to establish the upper limit of the desired control range first.
If two control devices are used only one has to be adjusted.
Press button briefly.
Note:
In the event of a system malfunction, the LED(s) “Bus status” and/or “Power” will be flashing rapidly when in program mode. Quit program mode and analyse the system malfunction (see pages 22 – 24).
Press button briefly. The lower limit of the control range is
now saved.
LEDs illuminated LEDs flash slowly
3 sec.
LEDs flash LEDs flash slowly
briefly
LEDs illuminated LEDs flash slowly
LED “Power”
briefly
Press button briefly. Raise liquid level until the upper limit of
the desired control range is reached.
1
Press button briefly.
LEDs illuminated LEDs flash slowly
briefly
LEDs flash LEDs flash slowly
briefly
15
Commissioning – continued –
Establish control range – continued –
Press button twice briefly. The upper limit of the desired control
range is now saved. The NRS 2-40 is back in operating
mode.
Establish switchpoints within the adjusted control range
1
Switchpoint 1
2
Switchpoint 2
3
Switchpoint 3
4
Switchpoint 4
5
Adjusted control range
1 2 3 4
NRG 26-40
5
twice briefly
Fig. 9
Establish switchpoints
Press button briefly. Raise or lower the liquid level in the
vessel until the desired value is reached. Use button if you want to establish a
different switchpoint first.
16
LED illuminated LEDs flash slowly
briefly
Commissioning – continued –
Establish control range – continued –
Press button briefly. Lower or raise liquid level until
switchpoint 4 within the adjusted control range is reached.
Note:
In the event of a system malfunction the LED(s) “Bus status” and/or “Power” will be flashing rapidly.
Press button briefly. Switchpoint 4 is now saved.
Press button briefly. Switchpoint 3 is now active.
LED illuminated LEDs flash slowly
briefly
LED illuminated LEDs flash slowly
briefly
LED illuminated LEDs flash slowly
briefly
Press button briefly. Raise liquid level until switchpoint 3
within the adjusted control range is reached.
Press button briefly. Switchpoint 3 is now saved.
LED flashes LEDs flash slowly
briefly
LED illuminated LEDs flash slowly
briefly
17
Commissioning – continued –
Establish control range – continued –
Press button briefly. Switchpoint 2 is now active.
Press button briefly. Raise liquid level until switchpoint 2
within the adjusted control range is reached.
Press button briefly. Switchpoint 2 is saved.
LED illuminated LEDs flash slowly
briefly
LED illuminated LEDs flash slowly
briefly
LED illuminated LEDs flash slowly
briefly
Press button briefly. Switchpoint 1 is now active.
Press button briefly. Raise liquid level until switchpoint 1
within the adjusted control range is reached.
18
LED illuminated LEDs flash slowly
briefly
LED illuminated LEDs flash slowly
briefly
Commissioning – continued –
Establish control range – continued –
Press button twice briefly. Switchpoint 1 is saved. The NRS 2-40 is again in operating
mode.
Operation
Normal operation
Normal operation – switching controller is working.
All LEDs go out as soon as the setpoint is reached.
The LED “Power” is illuminated.
Alarm
There are two alarm conditions:
High-level alarm
Low-level alarm
LED illuminated
twice briefly
LEDs go out upon reaching the setpoint
LED “Power” illuminated
High-level alarm
LED 1 changes after the de-energizing delay from rapid flashing to lighting.
Low-level alarm
LED 4 changes after the de-energizing delay from rapid flashing to lighting.
illuminatedflashes
flashes illuminated
19
Operation – continued –
Relay test high/low level alarm (MIN/MAX)
Press button briefly. The test mode is active for 5 seconds.
LEDs illuminated
briefly
Hold down button .
LED 4 goes out
LED 4 goes out. A low-level alarm is simulated for
switchpoint 4.
Hold down button .
LED 1 goes out
LED 1 goes out. A high-level alarm is simulated for
switchpoint 1.
System Malfunctions
There are four types of system malfunctions that might occur in the level electrode and the level switch:
Max. admissible temperature in electrode terminal box exceeded
No or faulty communication between switching controller and electrode
Fault in CAN bus
Failure of 24 V power supply unit built in level controller NRS 2-40
20
Danger
The terminal strip of the NRS 2-40 is live during operation. This presents the danger of electric shock. Cut off power supply before mounting or removing the equipment.
System Malfunctions – continued –
Systematic Malfunction Analysis
The sources of malfunctions occurring in CAN bus systems operating with several bus-based stations must be analysed systematically since faulty components or incorrect settings can give rise to negative interactions with intact bus devices in the CAN bus system. These unwanted interactions can cause error messages in fully functional bus devices, which will make fault detection even more difficult.
We recommend the following systematic fault finding procedure:
Step 1 (Start)
Detach terminal strips in all sensing units of bus nodes.
Level electrode Conductivity electrode Pressure sensor Temperature sensor
Check
Use fault-finding list to correct fault(s).
Final test: have all faults been eliminated?
System Malfunction
Use fault-finding list to identify the fault(s).
Cut off power supply to the equipment.
Step 2
Plug in terminal strips of the bus nodes e. g.
NRS ...
and
NRG ...
Step 3
Apply mains voltage to bus nodes e. g.
NRS ...
and
NRG ...
Check next system
System O.K.
Detach terminal strips between bus nodes e. g.
NRS ...
and
NRG ...
21
System Malfunctions – continued –
System malfunction 1
The four indicator LEDs flash slowly. High/low-level alarm
LEDs flash slowly
Fault: Remedy:
The max. admissible temperature in the electrode terminal box is exceeded. Insulate electrode flange to protect the equipment against heat radiation.
As soon as the temperature drops below the max. admissible limit the equipment automatically returns to normal operation.
System malfunction 2
LEDs flash rapidly
The four indicator LEDs flash rapidly. High/low-level alarm
Fault: Remedy:
Fault: Remedy:
The CAN bus line between the nodes is interrupted. Check wiring and terminals. Restart system
Incorrect node ID(s). Set correct nodes ID(s), referring to section “Basic Adjustments” or “Annex”.
Disconnect the system from its power supply. After 5 sec. apply power and restart system.
22
System Malfunctions – continued –
System malfunction 3
LED “Bus status” flashes slowly.
LED flashes slowly
Fault: Remedy:
Malfunction in CAN bus. Restart system.
LED “Bus status” flashes slowly. High/low-level alarm
Fault: Remedy:
Data transfer in CAN bus interrupted. The bus cables have to be correctly connected according to the wiring diagram (observe polarity!). Make sure that all end-of-line nodes are provided with 120 terminating resistors, referring to the wiring diagram.
Disconnect the system from its power supply. After 5 sec. apply power and restart system.
Fault: Remedy:
The baud rate of one or more nodes is not set correctly. Check baud rate settings of all bus nodes. The baud rates must be identical. Refer to section “Annex” for more details.
Disconnect the system from its power supply. After 5 sec. apply power and restart system.
Fault:
The overall length of the bus cable does not correspond to the selected baud rate.
Remedy:
Change baud rate settings of all nodes according to the indications specified in “Annex”.
Disconnect the system from its power supply. After 5 sec. apply power and restart system.
LED flashes slowly
23
System Malfunctions – continued –
System malfunction 4
LED “Power” flashes slowly.
LED flashes slowly
Fault:
Remedy:
Fault: Remedy:
The power supply unit (PSU) is overloaded and may be misused for other components. Check load of power supply unit. Be sure to use the PSU only for the voltage supply of bus-based network components.
Disconnect the system from its power supply. After 5 sec. apply power and restart system.
Power supply unit defective. Replace power supply unit.
24
Malfunctions
Danger
The terminal strip of the NRS 2-40 is live during operation. This presents the danger of electric shock. Cut off power supply before mounting or removing the equipment.
Fault-finding list for troubleshooting
Device fails to work – indication of malfunction
Fault:
Remedy:
Device fails to work – no function
Fault: Remedy:
Device does not work properly
Fault:
Remedy:
Fault Remedy
In spite of correct wiring and commissioning of the equipment an interference signal is indicated. The interference signal is caused by H. F. interferences coming from the installation. For interference suppression of the voltage supply we supply ferrite rings, stock code 147253. The 230 V supply lines should be looped through the ferrite ring five to ten times. If several controllers are used in the system, they can be fed from the interference suppressed supply lines. For the intererence suppression of the bus line we supply hinged-shell ferrite rings, stock code 147254. The hinged-shell ferrite rings are clamped onto the bus line close to the terminal strip of the controller. Restart system after installation.
LED “Power” does not light up. Apply power. Connect the equipment properly, referring to wiring diagrams.
Incorrect function at analogue output. The following actual value indicator shows incorrect values. Correct the switchpoint settings and the control range settings of the electrode.
: Switchpoints and actual value indication drift continuously towards 100 %.
: Deposits have accumulated on the electrode rod. Remove the level
electrode and clean the electrode rod.
Fault
: A high-level alarm is raised although the liquid level is below high level.
Remedy
Fault Remedy
: Deposits have accumulated on the electrode rod.
Clean the electrode rod. Defective electrode insulation. Replace level electrode.
: Liquid level below switchpoint “LOW LEVEL”, device fails to switch.
: Check installation of level electrode and vent hole in the protection tube.
If an external measuring pot is used make sure to open the isolating valves.
25
Malfunctions – continued –
Fault-finding list for troubleshooting– continued –
Fault
: “HIGH-LEVEL” switchpoint exceeded – no indication.
Remedy:
If faults occur that are not listed above or cannot be corrected, please contact our service centre or authorized agency in your country.
Level switch defective. Replace equipment.
26
Annex
Danger
The terminal strip of the NRS 2-40 is live during operation. This presents the danger of electric shock. Cut off power supply before mounting or removing the equipment.
Factory set default node IDs
Switching controller
The individual node IDs must be manually adjusted on the equipment. Please observe the installation instructions of the device in question.
Assigning/ changing node ID
If several systems of the same kind are to communicate in one CAN bus network, be sure to assign one node ID for each individual system component (e. g. controller).
Detach terminal strips in order to change the code switch setting .
Attention
Do not assign the same node ID twice within the CAN bus network.
A 8
Level electrode
Fig. 10
8
27
Annex – continued –
Node ID S1 S2 S3
ON ON ON
OFFS4 OFFS5
S6
ON
OFFS7
Fig. 11 (Factory setting)
S8
OFF
S9 S0
ON
ONON
16 32 64
OFF
OFF 125 kBit/s
ON
ON
OFF 1000 m
ON ONON
Fig. 13 (Factory setting 250 kBit/s)
ON ON ON
39
1 2
S1 S2
4 8
S4
S7
Fig. 12 (Example)
Baud rate
Cable length
250 kBit/s
100 kBit/sOFFOFF 335 m
50 kBit/sOFF 20 kBit/s 50 kBit/s
Node ID
OFF
ON
OFFS3
ON
OFFS5 OFFS6
ON
125 m
250 m
500 m
1000 m
74
1 2 4
8 16 32
64
28
Annex – continued –
Declaration of conformity
We hereby declare that the equipment NRS 2-40 conforms to the following European guidelines:
LV guideline 73/23/eec version 93/68/eec
EMC guideline 89/336/eec version 93/68/eec
which are based on the following harmonised standards:
LV standard DIN EN 50178
EMC standard DIN EN 50 081-2, DIN EN 61 000-6-2
This declaration is no longer valid if modifications are made to the equipment without consultation with us.
Bremen, 23
Head of the Design Dept.
Uwe Bledschun
(Academically qualified engineer)
Key
Terminal strips
A
Supporting rail 35 x 15 to DIN EN 50022
C
rd
GESTRA GmbH
July 2002
Quality Assurance Manager
(Academically qualified engineer)
Lars Bohl
29
Example of Installation
A
Fig. 14
A
100
C
73
118
Fig. 15
30
20 20
For your notes
31
GESTRA Gesellschaften · GESTRA Companies · Sociétés GESTRA · Sociedades Gestra · Società GESTRA
Vertretungen weltweit · Agencies all over the world · Représentations dans le monde entier · Representaciones en todo el mundo · Agenzie in tutto il mondo
Great Britain Flowserve Flow Control (UK) Ltd.
Burrel Road, Haywards Heath West Sussex RH 16 1TL Tel. 00 44 14 44 / 31 44 00 Fax 00 44 14 44 / 31 45 40 E-mail: sales@flowserve.com
France Flowserve Flow Control S.A.S.
10 Avenue du Centaure, BP 8263 F-95801 CERGY PONTOISE CEDEX Tél. 0 03 31 /3443 26 60 Fax 00331/34432687 E-mail: gnation@flowserve.com
España GESTRA ESPAÑOLA S.A.
Luis Cabrera, 86-88 E-28002 Madrid Tel. 00 3491 /5 152032 Fax 003491/4136747; 5152036 E-mail: gestra@gestra.es
Italia
Flowserve S.p. A
Divisione Italgestra Via Prealpi, 30 – 20032 Cormano (MI) Tel. 00 3902 /66 3251 Fax 00 39 02/ 66 32 55 60 E-mail: info@italgestra.it
Portugal
Flowserve Portuguesa, Lda.
Av. Dr. Antunes Guimarães, 1159 Porto 4100-082 Tel. 0035122/6198770 Fax 003 51 22 /6 10 7575 E-mail: gestra@gestra.pt
®
GESTRA GmbH
P. O. Box 10 54 60, D-28054 Bremen, Münchener Str. 77, D-28215 Bremen Telephone +49 (0) 421 35 03 - 0, Fax +49 (0) 421 35 03 - 393 E-Mail gestra.gmbh@flowserve.com, Internet www.gestra.de
A Unit of Flowserve Corporation
810371-02/903 · ©2000 GESTRA GmbH · Bremen · Printed in Germany
32
Loading...