ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®
FCD- LGENSF0014-00
Welcome to the Logix MD+
Welcome to the Flowserve ValveSight® DTM for the Logix MD+ series digital
positioners. This package offers unparalleled functionality for configuring, calibrating,
maintaining and diagnosing control valve operation.
This package follows the standard FDT/DTM conventions. The Frame application
controls the menu bar at the top of the page and the Frame connection tree at the far
left of the frame window.
The DTM application contains a menu tree on the left side showing the available
pages for configuring, calibrating, maintaining and diagnosing control valve operation.
At the top of the DTM window, the device tag is shown, and some basic information
for the actuator and valve that is currently connected to the system.
The bar right below the device information contains two icons, one to toggle the menu
bar on and off and the other to show this help.
At the bottom of the page below the Flowserve logo is an icon indicating the status of
the connection to the field device. If the icon has a green check and the tow plugs
touching it indicates that communications are taking place and the device shown at
the top of the page is online. Two green arrows to the right of the connection symbol
are visible when the DTM is requesting information from the device.
ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®
FCD- LGENSF0014-00
Quick Start Guide
GENERAL INFORMATION
This Document
This document details the installation and functions of the ValveSight® Device Type
Manager (ValveSight DTM) for the Logix® MD+ series of digital positioners including
the Logix 520MD+.
Qualified Personnel
Qualified personnel are people who, on account of their training, experience and
instruction and their knowledge of relevant standards, specifications, accident
prevention regulations and operating conditions, have been authorized by those
responsible for the safety of the plant to perform the necessary work and who can
recognize and avoid possible dangers.
Additionally, product users and maintenance personnel should thoroughly review the
Logix MD+ Series Digital Positioner Instruction, Operation, Maintenance and Safety
Manual prior to installing, operating, or performing maintenance on the valve or
positioner.
System Disclaimer
The installation instructions herein show an example of how to install, navigate, or
commission the ValveSight Logix MD+ DTM in a WINDOWS 7 64 bit operating
system, using the fdtCONTAINER FRAME Application. Any variation of operating
system and/or FRAME application may result in a different procedure to install,
operate, or commission the ValveSight Software.
Terms Concerning Safety
The safety terms DANGER, CAUTION and NOTE are used in these instructions to
highlight particular dangers and/or to provide additional information on aspects that
may not be readily apparent.
To avoid possible injury to personnel or damage to valve parts, DANGER and
CAUTION notes must be strictly followed. Modifying this product, substituting nonfactory parts or using maintenance procedures other than outlined could drastically
affect performance and be hazardous to personnel and equipment, and may void
existing warranties.
NOTE:indicates and provides additional technical information, which may not be very obvious even to qualified personnel.
CAUTION: Indicates that minor personal injury and/or property damage can occur if
proper precautions are not taken.
ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®
FCD- LGENSF0014-00
DANGER: Indicates that death, severe personal injury and/or substantial property
damage can occur if proper precautions are not taken.
Compliance with other, not particularly emphasized notes, with regard to transport,
assembly, operation and maintenance and with regard to technical documentation
(e.g., in the operating instruction, product documentation or on the product itself) is
essential, in order to avoid faults, which in themselves might directly or indirectly
cause severe personal injury or property damage.
ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®
FCD- LGENSF0014-00
DTM Installation
Please log in to the Flowserve FTP Site (ftp://fcdftp) or open the CD to download the
Logix MD+ ValveSight DTM, FdtCONTAINER, or HART COMM DTM Installs. These
installs will allow you to install the ValveSight Logix MD+ DTM, FRAME application,
and COMM DTM respectively.
NOTE: This document will ONLY cover the installation of the Logix 520MD+
ValveSight DTM.
Follow the installation instructions
Frame and COMM DTM Install
If you do not have the FRAME Application or the HART Communication DTM
installed, check the two boxes below and follow the installation instruction for both
Frame and Communication DTM, else uncheck the already installed component.
Runtime Libraries
The ValveSight installation will check to see if the computer already has the
necessary Microsoft Libraries, else it will prompt you to install the Libraries. Select
ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®
Create a Field Network
HART Modem
• If the modem is a serial port, move on to the next step
• The USB Modem requires that you install the driver for it. Make sure you
remember what slot you put the USB Driver, in case you unplug and plug in a
different slot you will need to install the driver for the different slot.
• Right Click on My Computer and select Manage.
• Click on Device Manager and select Ports
• Check what port the modem was installed
FCD- LGENSF0014-00
Create a Field Network
The remainder of the Quick Start Guide will give instructions on how to create a Field
Network using the fdtCONTAINER FRAME Application.
Device Catalog
Double click on the FDT Container, which is the M&M • Frame to open it. You will see
a widow on the right of the page called “Device Catalog”. At the bottom of the page,
click on Update. This should allow the Frame to identify both the COMM DTM and the
ValveSight DTM.
ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®
Select the “LogixMD+”
FCD- LGENSF0014-00
Optional: Save the project to your desktop or somewhere easy to remember. This will
save you time so you do not have to create a field network in the future.
Starting the ValveSight MD+ DTM
To launch the ValveSight DTM, ensure the modem is connected to a device and the
device is powered on.
Right click on the “HART Channel 0> LogixMD+” and select “Go Online”
ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®
FCD- LGENSF0014-00
Double click the “HART Channel 0> LogixMD+”, or right click and select Online
Parameter
Troubleshooting
If communications is not established:
1. Verify the HART modem is functional. Some HART modems will report a positive
self-check, but still be non-functional.
2. If another primary master is connected in the system, use a communication DTM
other than the M&M fdtCONTAINER. This communication DTM does not support a
primary master other than itself.
ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®
FCD- LGENSF0014-00
DANGER: Using certain features of the DTM can result in valve movement and the
inability to operate the valve until the operation is complete. Notify proper personnel
that the valve may stroke, and make sure the valve is properly isolated before
proceeding.
ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®
FCD- LGENSF0014-00
Basic Dashboard
The Basic Dashboard is a high level view of the status of the positioner. It is the main view
of the ValveSight® DTM.
Status Area
The Active Indicator area shows the status of the most relevant active indicator. The color
of the "LED light" corresponds to the Active Indicator and the first color of the blink code
sequence on the positioner. Generally green indicates no immediate issues. Yellow
indicates a developing issue. Red indicates the ability to control may be compromised. A
detailed list of the indicators is given in the Alarm Congfiguraion - Alarm Annunicator page.
The Command Source field indicates weather the positioner is being controlled by digital or
an analog (4-20 mA) command source.
Command and Position
This area contains a graphical representations of the valve command and position. The
blue bar tracks the final command value (after adjustments for characterization curves).
The green position bar indicates the current measured position of the valve. The smaller
pointers show the settings of the travel alert settings (these can be changed on the Travel
Alerts page located under Alarms/Alerts). Grayed out zones at the top or bottom of the
graphs indicate the settings of soft travel limits.
ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®
FCD- LGENSF0014-00
Input Source
Select the analog or digital control mode. In analog mode, the positioner will position the
valve according to the 4-20 mA supplied current. In digital mode, the positioner will position
according to the value entered in the Digital Input field.
Pressure
Supply, port A and port B pressures are seen in this box. If the Supply Pressure field is
yellow or red, there is a problem with the supply pressure to the positioner. The fields in the
Pressure box are only active if the positioner is upgraded to have Advanced or Pro
diagnostics.
ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®
FCD- LGENSF0014-00
Ambient Temperature
The temperature and relative humidity inside the positioner are shown here. The units for
temperature can be changed in the Positioner Configuration - Units page.
Dip Switch Configuration
The box shows the current configuration of the DIP switches on the front of the positioner.
These switches should be set on the positioner before calibration. The configuration that is
set by the DIP switches can be overridden in the software using the DTM. (See the
Basic/Local Interface page of the DTM). If this is the case, an X will be shown in the box to
the right of the item. Be careful when changing the configuration in software because
performing a position calibration (Quick-Cal) will reset the configuration according to the
physical DIP switch settings. See you instructions for the positioner for a detailed
explanation of the switches.
HART Status
Communication with the DTM is displayed here. The Transmit field displays a data packet
transmitted to the positioner. The Receive field shows data packets received from the
positioner. These are constantly updating. If they appear static, there may be a problem
with communications.
ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®
FCD- LGENSF0014-00
Advanced Dashboard
The Dashboard view is the main diagnostic view of the ValveSight® DTM. Generally, the
color green signifies a healthy condition, yellow signifies some degradation has taken
place, and red signifies a problem that needs to be addressed right away. You can identify
problems right away by observing any red areas on this page.
Status Area
The Active Indicator area shows the status of the most relevant active indicator. The color
of the "LED light" corresponds to the Active Indicator and the first color of the blink code
sequence on the positioner. Generally green indicates no immediate issues. Yellow
indicates a developing issue. Red indicates the ability to control may be compromised. A
detailed list of the indicators is given in the Alarm Congfiguraion - Alarm Annunicator page.
The Command Source field indicates weather the positioner is being controlled by digital or
an analog (4-20 mA) command source.
Command and Position
This area contains a graphical representations of the valve command and position. The
blue pointer tracks the final command value after adjustments for characterization curves,
Soft Limits, and Tight Shut Off. The green position bar indicates the current measured
position of the valve. The smaller pointers show the settings of the travel alert settings
(these can be changed on the Travel Alerts page located under Alarms/Alerts). Grayed out
ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®
FCD- LGENSF0014-00
zones at the top or bottom of the graphs indicate the settings of Soft Limits. The command
chart also displays the settings for travel limits and position Tight Shut Off (Minimum
Position Cut Off (MPC)) limits. If the positioner has been configured for Tight Shut Off this
will show up in the field below the position bar. The Pressure Lock field indicates if the
positioner is locked on a steady command by controlling the pressures, or tracking a
moving command signal.
Input Source
The command source can be changed to analog or digital mode. In analog mode, the
positioner will position the valve according to the 4-20 mA supplied current. In digital mode,
the positioner will position the valve according to the value entered in the Digital Input field.
HART Status
The status of HART communication with the DTM is displayed here. The Transmit field
displays a data packet transmitted to the positioner. The Receive field shows data packets
received from the positioner. These are constantly updating. If they appear static, there
may be a problem with communications.
ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®
FCD- LGENSF0014-00
Health Status
The Health Status box has health indication bars for Valve, Position, Actuator, and Control
which are displayed in 4 bar graphs in the center of the dashboard. These are powerful,
visual diagnostic tools. Information from all of the diagnostic indications are rolled up into
these health bars. As the graphs turn color (from green to yellow to red) they indicate
developing issues. The health of the four key components of a control valve can be
identified quickly by looking at the color of the bar. If the bars only show green then
everything is operating within normal limits and no further action is required. If the bar is
partially yellow it is pointing out a degraded condition. The further the bar goes to the right
the more serious the degradation. If the bar is red then action should be taken immediately
because the ability to control may be compromised. To learn more about any of the 4
health areas, click the double arrows () button at the end of the bar. This leads to the
detailed health status page for that particular item.
NOTE: Health Status bars are only available with the Advanced ValveSight® license
viewing positioners with Advanced or Pro diagnostics. See the licensing and upgrade
pages under Positioner Configuration in the DTM for more information.
Dip Switch Configuration
The box shows the current configuration of the DIP switches on the front of the positioner.
These switches should be set on the positioner before calibration. The configuration that is
set by the DIP switches can be overridden in the software using the DTM. (See the
Basic/Local Interface page of the DTM). If this is the case, an X will be shown in the box to
the right of the item. Be careful when changing the configuration in software because
performing a position calibration (Quick-Cal) will reset the configuration according to the
physical DIP switch settings. See you instructions for the positioner for a detailed
explanation of the switches.
ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®
FCD- LGENSF0014-00
Pressure
Pressure values are shown here. The units for pressure can be changed in the Positioner
Configuration - Units page. The pressure gages for Port 1 and Port 2 read directly from the
pressure sensors in the positioner. For single acting configurations, the Port 2 gage is not
be active. Should the DTM view a device with no pressure sensors, all 3 gauges will be
inactive. Pressure sensors are calibrated in the factory. A pressure calibration is not
required unless there has been sever pressure or thermal stress on the positioner. See the
Calibration - Sensor Calibration page.
NOTE: Pressure gauges are only available while viewing positioners with Advanced or Pro
diagnostics. See the Positioner Upgrade page under Positioner Configuration in the DTM
for more information.
Temperature
This gage shows the temperature on the circuit board in the positioner. The units for
temperature can be changed in the Positioner Configuration - Units page.
ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®
FCD- LGENSF0014-00
Humidity
This gage shows the Humidity on the circuit board inside the positioner. Since the
positioner should be run with a dry air supply, this value should be near zero most of the
time. Elevated humidity inside the positioner may significantly shorten the life of the
positioner. Sensor accuracy is +/-10% RH. The sensors are calibrated in the factory. No
other calibration is required.
ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®
FCD- LGENSF0014-00
Annunciator Panels
Annunciator Panels allow quick viewing of the current state and history of diagnostic
indicators and allows masking of alarms, warnings and alerts. This selection automatically
redirects to the Alarms Annunciator page.
ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®
FCD- LGENSF0014-00
Alarms Annunciator
The Alarm Annunciator page displays the status of all
diagnostic indicators. The status is shown in by the indicator "light". The checkboxes allow
masking of indicators.
Status Area
The Active Indicator area shows the status of the most relevant active indicator. The color
of the "LED light" corresponds to the Active Indicator and the first color of the blink code
sequence on the positioner. Generally green indicates no immediate issues. Yellow
indicates a developing issue. Red indicates the ability to control may be compromised. A
detailed list of the indicators is given below. The Command Source field indicates weather
the positioner is being controlled by digital or an analog (4-20 mA) command source.
ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®
Legend
Each indicator group box may contain the following components:
•An "LED light" indicates health status. Warning and alarm limits (set by the
user in many cases) determine the conditions when the color will turn from
green to yellow to red. The most sever of the indicators on this page will be
shown in the health bar on the Dashboard.
•Dark Greencircle indicates a healthy condition where no attention is
needed.
• Light Green indicates an occurrence of a normal activity that does
not affect the health of the valve system.
• Yellow circle indicates that an active warning, alert or mode is
present.
• Red circle indicates that an active alarm or state is present that
could seriously limit the operation of the valve.
•Graycircle indicates that the feature or condition is not available
because the configuration of the hardware or software does not support
it.
• A checkbox indicates the masked status. Check to mask. If a particular
indicator is masked, it will not be shown in the active indicator field at the top
of each screen, affect the status of the health bars on the main dashboard, be
sent in command 48, or be seen on the blinking LEDs on the positioner. It
will however continue to show on this page.
FCD- LGENSF0014-00
Cycles & Travel Status
Valve Cycles
•Definition: The valve cycle limit has been exceeded.
ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®
•Implications: Each cycle represents two reversals of the direction of
valve movement. The cycle counting criterion and count limit are set by
the user to track the usage of the valve.
•Possible Solutions: Follow routine procedures for maintenance when
the limit is reached such as checking the packing tightness, and
checking linkages for wear, misalignment, and tightness. After
maintenance, reset the cycle accumulator.
Valve Travel
•Definition: The total accumulated valve travel limit has been
exceeded.
•Implications: The travel is accumulated in both directions. The travel
counting criterion and limit are set by the user to track the usage of the
valve.
•Possible Solutions: Follow routine procedures for maintenance when
the limit is reached such as checking the packing tightness, and
checking linkages for wear, misalignment, and tightness. After
maintenance, reset the travel accumulator.
Actuator Cycles
• Definition: The actuator cycle limit has been exceeded.
• Implications: Each cycle represents two reversals of the direction of
valve movement. The cycle counting criterion and count limit are set by
the user to track the usage of the valve.
•Possible Solutions: Follow routine procedures for maintenance when
the limit is reached such as checking the actuator seals and
lubrication. After maintenance, reset the travel accumulator.
Actuator Travel
•Definition: The total accumulated actuator travel limit has been
exceeded.
•Implications: The travel is accumulated in both directions. The travel
counting criterion and limit are set by the user to track the usage of the
valve.
•Possible Solutions: Follow routine procedures for maintenance when
the limit is reached such as checking the actuator seals and
lubrication. After maintenance, reset the travel accumulator.
Bellows Cycles
• Definition: The bellows cycle limit has been exceeded.
• Implications: The bellows may be reaching the end of its fatigue
life. Each cycle represents two reversals of the direction of bellows
movement. The cycle counting criterion and count limit are set by the
user to track the usage of the valve.
•Possible Solutions: Follow routine procedures for maintenance when
the limit is reached such as checking bellows for cracking or
leaking. After maintenance, reset the cycle accumulator.
Bellows Travel
• Definition: The bellows cycle limit has been exceeded.
ValveSight™ Diagnostics DTM Manual for Logix MD+ Positioner with HART®
•Implications: The bellows may be reaching the end of its fatigue
life. Each cycle represents two reversals of the direction of valve
movement. The cycle counting criterion and count limit are set by the
user to track the usage of the valve.
•Possible Solutions: Follow routine procedures for maintenance when
the limit is reached such as checking bellows for cracking or
leaking. After maintenance, reset the cycle accumulator.
Pilot Cycle
•Definition: The pilot relay cycle limit set by the user has been
exceeded.
•Implications: The pilot relay cycles indicate the activity level of the pilot
relay as it maintains a valve’s position. Excessive cycles can contribute
to a worn relay which can lead to high air consumption.
•Possible Solutions: Inspect for high air consumption and signs of
wear.
Pilot Travel
•Definition: The total accumulated pilot relay travel (% of full relay span)
set by the user has been exceeded.
•Implications: The pilot relay travel indicates the activity level of the
relay as it maintains a valve’s position. Excessive travel can contribute
to a worn pilot relay which can lead to high air consumption.
•Possible Solutions: Inspect for high air consumption and signs of
wear.
Feedback Loop Status
FCD- LGENSF0014-00
Position Deviation
• Definition: The device is not controlling at the set point.
• Implications: The difference between the command and the actual
position has been greater than the user-set limit for longer than a userset time.
•Possible Solutions: Review active alarms and warnings to find root
causes of this alarm. The deviation settings can be changed in the
Valve Health page of the DTM.
Position Sensor Fail
•Definition: The feedback arm may be disconnected from the valve
assembly.
•Implications: The feedback arm may be disconnected from the valve
assembly or the sensor has failed.