Flowserve Logix 510si Installation, Operation & Maintenance Instructions Manual

Page 1
1
Logix 510si Digital Positioner
This product meets the requirements of
ADK041400E - 04.03
Page 2
2
Table of Content Page
1 General Information ................................................................................ 3
3 Logix 510si Overview .............................................................................. 5
5 Principle of Operation ............................................................................. 6
8.1 Logix 510si Local Interface Operation ........................................ 8
8.2 Operation of Configuration Dipswitch Setup .............................. 8
8.3 Setup of the Cal Dipswitches ...................................................... 9
8.4 Quick-Cal Operation .................................................................... 10
8.5 Local Control of Valve Position................................................... 10
8.6 Factory Reset .............................................................................. 10
8.7 Loop Calibration ......................................................................... 10
9 Error Codes .............................................................................................. 12
10 Version Number checking ....................................................................... 14
11 Trouble Shooting ..................................................................................... 15
Page 3
3
1 USING FLOWSERVE VALVES, ACTUATORS
AND ACCESSORIES CORRECTLY
1.1 Using
The following instructions are designed to assist in unpacking, installing and performing maintenance as required on FLOWSERVE products. Product users and maintenance personnel should thoroughly review this bulletin prior to installing, operating or perform­ing any maintenance.
In most cases FLOWSERVE valves, actuators and accessories are designed for specific applications (e.g. with regard to medium, pressure, temperature). For this reason they should not be used in other ap­plications without first contacting the manufacturer.
1.2 Terms concerning safety
The safety terms DANGER, WARNING, CAUTION and NOTE are used in these instructions to highlight par-
ticular dangers and/or to provide additional informa­tion on aspects that may not be readily apparent.
DANGER:
indicates that death, severe personal in­jury and/or substantial property damage will occur if proper precautions are not taken.
WARNING:
indicates that death, severe personal in­jury and/or substantial property damage can occur if proper precautions are not taken.
CAUTION:
indicates that minor personal injury and/ or property damage can occur if proper precautions are not taken.
NOTE:
indicates and provides additional technical information, which may not be very obvious even to qualified personnel.
Compliance with other, not particularly emphasised notes, with regard to transport, assembly, operation and maintenance and with regard to technical docu­mentation (e.g. in the operating instruction, product documentation or on the product itself) is essential, in order to avoid faults, which in themselves might directly or indirectly cause severe personal injury or property damage.
1.3 Protective clothing
FLOWSERVE products are often used in problematic applications (e.g. extremely high pressures, danger­ous, toxic or corrosive mediums). In particular valves with bellows seals point to such applications. When performing service, inspection or repair operations always ensure, that the valve and actuator are de­pressurised and that the valve has been cleaned and is free from harmful substances. In such cases pay particular attention to personal protection (protective clothing, gloves, glasses etc.).
1.4 Qualified personnel
Qualified personnel are people who, on account of their training, experience and instruction and their knowledge of relevant standards, specifications, ac­cident prevention regulations and operating condi­tions, have been authorised by those responsible for the safety of the plant to perform the necessary work and who can recognise and avoid possible dangers.
1.5 Installation DANGER:
Before installation check the order-no, se­rial-no. and/or the tag-no. to ensure that the valve/ actuator is correct for the intended application.
Do not insulate extensions that are provided for hot or cold services.
Pipelines must be correctly aligned to ensure that the valve is not fitted under tension.
Fire protection must be provided by the user.
STOP!
Page 4
4
1.6 Spare parts
Use only FLOWSERVE original spare parts. FLOWSERVE cannot accept responsibility for any damages that occur from using spare parts or fastening materials from other manufactures. If FLOWSERVE products (especially sealing materials) have been on store for longer periods check these for corrosion or deterioration before using these products. Fire protection for FLOWSERVE products must be provided by the end user.
1.7 Service / repair
To avoid possible injury to personnel or damage to products, safety terms must be strictly adhered to. Modifying this product, substituting nonfactory parts, or using maintenance procedures other than outlined in this instruction could drastically affect performance and be hazardous to personnel and equipment, and may void existing warranties. Between actuator and valve there are moving parts. To avoid injury FLOWSERVE provides pinch-point-protection in the form of cover plates, especially where side-mounted positioners are fitted. If these plates are removed for inspection, service or repair special attention is required. After completing work the cover plates must be refitted.
Apart from the operating instructions and the obligatory accident prevention directives valid in the country of use, all recognised regulations for safety and good engineering practices must be followed.
WARNING:
Before products are returned to FLOWSERVE for repair or service FLOWSERVE must be provided with a certificate which confirms that the product has been decontaminated and is clean. FLOWSERVE will not accept deliveries if a certificate has not been provided (a form can be obtained from FLOWSERVE).
1.8 Storage
In most cases FLOWSERVE products are manufactured from stainless steel. Products not manufactured from stainless steel are provided with an epoxy resin coating. This means that FLOWSERVE products are well protected from corrosion. Nevertheless FLOWSERVE products must be stored adequately in a clean, dry environment. Plastic caps are fitted to protect the flange faces to prevent the ingress of foreign materials. These caps should not be removed until the valve is actually mounted into the system.
STOP!
1.9 Valve and actuator variations
These instructions cannot claim to cover all details of all possible product variations, nor in particular can they provide information for every possible example of installation, operation or maintenance. This means that the instructions normally include only the directions to be followed by qualified personal where the product is being used for is defined purpose. If there are any uncertainties in this respect particularly in the event of missing product-related information, clarification must be obtained via the appropriate FLOWSERVE sales office.
2 UNPACKING
Each delivery includes a packing slip. When unpacking, check all delivered valves and accessories using this packing slip.
Report transport damage to the carrier immediately.
In case of discrepancies, contact your nearest FLOWSERVE location.
Page 5
5
Shipping weights (incl. mounting kit)
Linearity < ± 1,0% Resolution < 0,3% Repeatability < 0,5% Deadband < 0,5%
Operating Temperature Standard -20 – ˚80 C
-4 – 178 ˚F
Low -40 – 80 ˚C
-40 – 178 ˚F
Transport and Storage -40 – 80 ˚C Temperature -40 – 178 ˚F
Operating Humidity 0 – 100% non-condensing Intrinsic Safety Logix 510 - 04
ATEX II 1G EEX ia II C T6
3 LOGIX 510si OVERVIEW
The Logix 510si is a two-wire, 4-20 mA input digital valve positioner. The Logix 510si positioner controls single-acting actuators with linear and rotary mount­ings. The Logix 510si is completely powered by the 4-20 mA input signal. The minimum input signal re­quired to function is 3,6 mA.
Since the positioner is insensitive to supply pressure changes and can handle supply pressures from 1,5 to 6 barg (22 to 87 psig), a supply regulator is usu­ally not required; however, in applications where the supply pressure is higher than the maximum actua-
tor pressure rating a supply regulator is required to lower the pressure to the actuator’s maximum rating (not to be confused with operating range). A coa­lescing air filter is recommended for all applications due to the close tolerances in the positioner. Optional analog feedback system as well as limit switch unit and a directly attachable double acting module com­plete the Logix 510si positioner accessories.
NOTE:
The air supply must conform to ISA 7.0.01or IEC 770 (a dew point at least 10 ˚C / 18 ˚F below ambient temperature, particle size below five microns – one micron recommended – and oil content not to exceed one part per million).
4 SPECIFICATIONS
Input Signal Range 4 - 20 mA
Compliance Voltage 6,0 VDC (analog)
Voltage Supply (maximum) 30 VDC Minimum Required 3,6 mA
Operating Current
Table 1: Input Signal
Feedback Shaft 0° to 90° normal Rotation 0° to 40° minimum
Table 2: Stroke Output
Supply Air Quality Free from moisture, oil and
dust per IEC 770 and ISA-7.0.01 Input Pressure Range 1,5 to 6,0 bar (22 – 87 psi) Air Consumption 0,08 Nm3/h @ 1,5 bar
(steady state) 0,047 SCFM @ 22 psi
0,120 Nm3/h @ 6,0 bar
0,071 SCFM @ 87 psi
Table 3: Supply Air
Output Pressure 0 - 100 % of supply air Range pressure
Output Flow Capacity 2,4 Nm3/h @ 1,5 bar (input @ pressure) 1,41 SCFM @ 22 psi
7,0 Nm3/h @ 6,0 bar
4,12 SCFM @ 90 psi
Table 4: Output Signal
Housing Material Cast aluminum,
powder-painted Soft Goods Nitrile Weight 1,2 kg (2,7 lbs)
Table 7: Physical Specifications
Table 6: Environmental Conditions
Table 5: Performance
Characteristics (typical)
Specification Logix 510 with pressure gauges 1,6 kg
without pressure gauges 1,2 kg
Table 8: Shipping weights
Page 6
6
Figure 1: Logix 510si Principle of Operation
5 PRINCIPLE OF OPERATION
The Logix 510si positioner is a digital positioner with various options. The positioner consists of three main modules:
1. The microprocessor-based electronic control module includes direct local user interface switches
2. The piezo valve-based electro-pneumatic con verter module
3. The infinite resolution valve position sensor.
The basic positioner operation is best understood by referring to Figure 1. The complete control circuit is powered by the two-wire, 4-20 mA command signal. The analog 4-20 mA command is passed to the mi­croprocessor, where it is compared to the measured valve stem position. The control algorithm in the proc­essor performs control calculations and produces an output command to the piezo valve, which drives the pneumatic amplifier. The position of the pilot valve in the pneumatic amplifier is measured and relayed to the inner loop control circuit. This two-stage control provides for more responsive and tighter control than is possible with a single stage control algorithm. The pneumatic amplifier controls the airflow to the actua­tor. The change of pressure and volume of the air in the actuator causes the valve to stroke. As the valve ap
6 TUBING POSITIONER TO ACTUATOR
After mounting has been completed, tube the positioner to the actuator using the appropriate com­pression fitting connectors:
Air connections: 1/4” NPT (standard air connec­tion)
Auxiliary power: Pressurized air or permissible gases, free of moisture and dust in according with IEC 770 or ISA 7.0.01.
Pressure range: 1,5 – 6,0 bar (22 – 87 psi) For connecting the air piping, the following notes
should be observed:
1. The positioner passageways are equipped with filters, which remove medium and coarse size dirt from the pressurized air. If necessary, they are easily accessible for cleaning.
2. Supply air should meet IEC 770 or ISA 7.0.01 requirements. A coalescing filter should be installed in front of the supply air connection Z. Now connect the air supply to the filter, which is connected to the Logix 500 Series positioner.
3. With a maximum supply pressure of 6 bar (87 psi) a regulator is not required.
4. With an operating pressure of more than 6 bar (87 psi), a reducing regulator is required. The flow capacity of the regulator must be larger than the air consumption of the positioner (7 Nm3/h @ 6 bar / 4,12 scfm @ 87 psi).
Local User Interface
4 – 20 mA
Inner Loop
Piezo Control
Stroke
Inner Loop
Position Feedback
1 Digital Control Circuit
2 Electro-pneumatic Converter Module
3 Valve Position Sensor
Filter / Regulator
for Supply Air
1.5 – 6.0 bar (22 – 87 psi)
Air Supply
-
Micro-
Processor
Gain
Pressure Regulator
Piezo Valve
Pneumatic
Amplifier
Control Valve
+
4 – 20 mA
Input
Output
(0ptional)
Page 7
7
Compliance Voltage (Figure 9) Output compliance voltage refers to the voltage limit the cur-
rent source can provide. A current loop system consists of the current source, wiring resistance, barrier resistance (if present), and the Logix 510 impedance. The Logix 510 re­quires that the current loop system allow for a 6,0 VDC drop across the positioner at maximum loop current.
CAUTION: Never connect a voltage source directly across the positioner terminals. This could cause per­manent circuit board damage.
In order to determine if the loop will support the Logix 510, perform the following calculation:
Voltage = Compliance Voltage (@Current
MAX
)
- Current
MAX
*(R
barrier
+ R
wire
)
The calculated voltage must be greater than 6.0 VDC in order to support the Logix 510.
Example: DCS Compliance Voltage = 19 V
R
barrier
= 300
R
wire
= 25
CURRENT
MAX
= 20 mA
Voltage = 19 V - 0,020 A*(300 Ω + 25 Ω)
= 12,5 V
The voltage 12,5 V is greater than the required 6.0 V; there­fore, this system will support the Logix 510si. The Logix 510si has an input resistance equivalent to 300 at a 20 mA input current.
5. Connect the outlet connector Y of the positioner to the actuator with tubing, independent of the action (direct or reverse).
7 WIRING AND GROUNDING GUIDELINES
Electrical connections: signal cable with cable pas-
sage (NPT, PG13,5, or M20 x 1,5) to terminals 2 x 2,5 mm
Input signal: 4 – 20 mA NOTE:
Observe the minimum requirements of volt­age and equivalent electrical load: 6,0 VDC / 300 Ω / at 20 mA
The performance is ensured only for a minimum input cur­rent of 3,6 mA.
For wiring, the following notes should be observed:
NOTE: The input loop current signal to the Logix 510si should be in shielded cable. Shields must be tied to a ground at only one end of the cable to provide a place for environmental electrical noise to be removed from the cable. In general, shield wire should be connected at the source. (Figure 8)
Connect the 4-20 mA current source to terminals +11 and -12 (Figure 8).
Grounding Screw
The grounding screw, located inside the positioner cover, should be used to provide the unit with an adequate and reli­able earth ground reference. This ground should be tied to the same ground as the electrical conduit. Additionally, the electrical conduit should be earth grounded at both ends of its run. The grounded screw must not be used to terminate signal shield wires.
Figure 2: Wiring Diagram
Table 9: Connection Table
Connection Description
+11 Input+ 4..20 mA
-12 Input- 4..20 mA
+31* Output+ 4..20 mA
-31* Output– 4..20 mA
+41* Limit switch 1+
-42* Limit switch 1-
+51* Limit switch 2+
-52* Limit switch 2­Y Pneumatic output signal (outlet) Z Air supply
* 0ptional
PIEZO RELAY
POT.
LS1
LS2
Internal Housing EARTH Terminal
Limit Switch 1
Limit Switch2
4-20 mA Signal
Connect Shield at Source Ground
-
+
4-20 mA Current Source
Shielded Cable
Y
Z
Page 8
8
Electromagnetic Compatibility
The Logix 510si digital positioner has been designed to operate correctly in electromagnetic (EM) fields found in typical industrial environments. Care should be taken to prevent the positioner from being used in environments with excessively high EM field strengths (greater than 10 V/m). Portable EM devices such as hand-held two-way radios should not be used within 30 cm of the device.
Ensure proper wiring and shielding techniques of the control lines, and route control lines away from elec­tromagnetic sources that may cause unwanted noise. An electromagnetic line filter can be used to further eliminate noise (FLOWSERVE Part Number
10156843). In the event of a severe electrostatic discharge near
the positioner, the device should be inspected to ensure correct operability. It may be necessary to recalibrate the Logix 510si positioner to restore operation.
8STARTUP
8.1 Logix 510si Local Interface Operation
The Logix 510si local user interface allows the user to fully configure the operation of the positioner, tune the response, and calibrate the positioner. The Local interface consists of a quick calibration button for automatic zero and span setting, along with two jog buttons for manually spanning the positioner, or for local Jogging of the valve. There is also a switch block containing 8 switches. Five of the switches are for basic configuration settings, three are for calibration options There is also a rotary selector switch for ad­justing the positioner gain settings. A 4-20 current loop calibration button is accessed through a hole in the cover next to the bottom dipswitch. For indica­tion of the operational status or alarm conditions there are 3 LEDs on the local user interface. This docu­ment describes the setting and use of the Logix 510si user interface.
8.2 Initial DIP Switch Setting
Before placing the unit in service, set the dipswitches in the Configuration and Cal boxes to the desired control options. For a detailed description of each dipswitch setting, see sections 1&2.
NOTE:
The switch settings in the Configuration box
are activated only by pressing the Quick-Cal button.
Operation of Configuration Dipswitch Setup -The first 5 Dip Switches are for basic configuration.
a. Air Action - This must be set to match the configura-
tion of the valve/actuator mechanical tubing connec­tion and spring location since these determine the air action of the system.
ATO (air-to-open)- Selecting ATO if increasing output pressure from the positioner is tubed so it will cause the valve to open.
ATC (air-to-close)- Selecting ATC if increasing output pressure from the positioner is tubed so it will cause the valve to close.
b. Signal at Closed - Normally this will be set to 4 mA
for an Air-to-open actuator, and 20 mA for an Air-to­close actuator configuration.
Selecting 4 mA will make the valve fully closed when the signal is 4mA and fully open when the signal is 20 mA.
Selecting 20 mA will make the valve fully closed when the signal is 20 mA and fully open when the signal is 4 mA.
c. Characteristic
Select Linear if the actuator position should be directly proportional to the input signal.
The =% option will characterize the actuator response to the input signal based on a stan­dard 30:1 equal percent rangability curve.
d. Tight Shutoff
Select On to have the positioner fully saturate the actuator closed at a signal less than 1%.
Setting the switch in the Off position disables this feature.
e. Auto Tune -This switch controls whether the posi-
tioner will auto tune itself every time the quick cal button is pressed
Figure 3: Compliance Voltage
12.0 VDC
510
6.0 si
Page 9
9
•On enables an automatic tuning feature that will automatically determine the positioner gain set­tings every time a “Quick-Cal” is performed. The gain settings can be modified after a cali­bration by adjusting the rotary “Gain” switch.
Note:
there is a small black arrow indicating the
selection. The slot does not indicate the chosen gain.
If the rotary “Gain” selector switch is set to “E” with the auto tune switch on, a Flowserve stan­dard response tuning set will be calculated and used.
If the rotary “Gain” selector switch is set to “D”, “C”, “B”, or “A” with the auto tune switch on, progressively lower gain settings will be calcu­lated and used.
If the rotary “Gain” selector switch is set to “F”, “G”, or “H” with the auto tune switch on, progressively higher gain settings will be calcu­lated and used.
Off forces the positioner to use one of the factory preset tuning sets determined by the rotary “Gain” selector switch. Settings “A” through “H” are progressively higher gain pre defined tuning sets.
8.3 Setup of the Cal Dipswitches - The last 3 Dip Switches are for calibration configuration.
a. Quick calibration operating mode.
Select Auto if the valve/actuator assembly has
an internal stop in the open and closed posi­tions. In Auto mode the positioner will fully
close the valve and register the 0% position and then open the valve to the stop to register the 100% position when performing a self-calibra­tion. See detailed instructions in section 10.4 on how to perform an auto positioner calibra­tion.
Select Jog if the valve/actuator assembly has no calibration stop in the open position and or if you want to manually set the closed posi­tion. In the Jog mode the positioner waits for the user to set the open and closed positions
using the Jog buttons labeled with the ∆ and arrows. See the detailed instructions in section
10.4 on how to perform a manual calibration using the “Jog” buttons.
b. Stability Switch – This switch adjusts the position
control algorithm of the positioner for use with low friction control valves or high friction automated valves.
Placing the switch to the left optimizes the re­sponse for low friction, high performance con­trol valves. This setting provides for optimum response times when used with most low fric­tion control valves.
Placing the switch to the right optimizes the response for valves and actuators with high friction levels. This setting slightly slows the response and will normally stop limit cycling
that can occur on high friction valves.
Figure 4: Logix 510si Local Interface
Configuration Switches
Gain selector
4-20 mA Input
Optional 4-20,mA Feedback
Terminals for Optional Limit Switches
Jog Calibrate Buttons
LED Status Lights
Quick-Cal Switch
Calibration Switches
Page 10
10
WARNING:
During the Quick-Cal operation the valve
may stroke unexpectedly. Notify proper personnel that the valve will stroke, and make sure the valve is properly isolated.
c. Loop Calibration- this setting determines whether
the input or output is calibrated when a loop calibra­tion is initialized.
An Input loop calibration, requiring an external current source, will be started when the Loop calibration button is pressed with a small object with the switch in the Input position. See the detailed instructions in section 8.7.1 on how to perform an Input calibration using the Loop calibration button.
An Output (optional) loop calibration, requiring an external current meter and power source, will be started when the Loop calibration but­ton is pressed with a small object with the switch in the Output position. See the detailed instruc­tions in section 8.7.2 on how to perform an Output calibration using the Loop calibration button.
WARNING:
During the Quick-Cal operation the valve
may stroke unexpectedly. Notify proper personnel that the valve will stroke, and make sure the valve is properly isolated.
8.4 QUICK-CAL Operation
The QUICK-CAL button is used to locally initiate a cali­bration of the positioner. Pressing and holding the QUICK-CAL button for approximately 3 seconds will initiate the calibration. The settings of all the con­figuration switches are read and the operation of the positioner adjusted accordingly. A QUICK-CAL can be aborted at any time by briefly pressing the QUICK­CAL button and the previous settings will be retained. If the Quick calibration switch (be careful not to confuse with the QUICK-CAL button) is set to Auto and the valve/actuator assembly has the necessary inter­nal stops the calibration will complete automatically. While the calibration is in progress you will notice a series of different lights flashing indicating the calibra­tion progress. When the lights return to a sequence that starts with a green light the calibration is com­plete. (see the appendix for an explanation of the various light sequences)
WARNING:
When operating using local control of the
valve, the valve will not respond to external commands. Notify proper personnel that the valve will not respond to remote command changes, and make sure the valve is properly isolated.
If the Quick calibration switch is set to Jog, the LED’s will initially flash in a sequence of Y-R-R-G (yellow­red-red-green) which indicates that the user must use the jog keys to manually position the valve to 100%. When the valve is approximately at the position de­sired for 100% open, press both the ∆ and buttons simultaneously to proceed to the next step. (Note
that the Logix 510si is only setting internal gain and direction of rotation parameters at this point the ac­tual span is set after the zero is set.) The valve will then moved closed and flash a Y-G-G-R sequence, al­lowing the user to adjust the valve position to 0% us­ing the jog buttons. When the stem is properly posi­tioned press both the ∆ and ∇ buttons simultaneously again to register the 0% position and to proceed. The valve will then stroke back to the 100% open position and the calibration the LED’s will flash in a sequence of Y-R-R-G again and wait for the user to make final adjustments. When the 100% is correct press both the and buttons simultaneously to continue. No more user actions are required while the calibration process automatically finishes. When the lights return to a sequence that starts with a green light the cali­bration is complete. (see the appendix for an expla­nation of the various light sequences)
Note:
It is recommended that the first time a Logix 510si is installed on a new actuator that a second QUICK-CAL be performed.
WARNING:
When operating using local control of the
valve, the valve will not respond to external commands. Notify proper personnel that the valve will not respond to remote command changes, and make sure the valve is properly isolated.
8.5 Local control of valve position-Can be done from the user interface by holding both jog buttons while then simultaneously pressing the quick cal button for 3 seconds. When in this mode the position can be adjusted using the ∆ and buttons. While in this mode the LED’s will flash a YGRR (yellow-green-red-red) sequence. To exit the local control mode and return to normal operation, briefly press the quick-Cal button.
8.6 Factory reset - Hold Quick cal button while applying power and all of the internal variables including cali­bration will be reset to factory defaults. The positioner must be re-calibrated after a factory reset.
8.7 Loop Calibration – Using a small pointed object push and hold, the Loop Calibration button through the small hole on the electronic cover for 3 seconds to initiate calibration of either the 4-20 mA input or output current loop as selected by the bottom Dip switch.
8.7.1 Input loop calibration - Note that the valve will be locked at its position when an input loop calibration is initiated until the calibration is completed. If a loop calibration is started with the Input loop selected on the Loop calibration Dip switch, the LED’s will flash a sequence of Y-G-G-Y indicating that it is waiting for the minimum signal to be input to the positioner on terminals +11 and –12 from an external 4-20 mA current source. Normally this will be 4 mA, but if split range operation is required use the minimum current for the desired operating range. When the minimum signal value is set at the desired value, press the and buttons simultaneously to proceed to the next step. The LED’s will now flash a sequence of Y-G-Y-R
STOP!
STOP!
STOP!
Page 11
11
indicating that it is waiting for the maximum signal to be input to the positioner. Normally this will be 20 mA, but if split range operation is required use the maximum current for the desired range. When the maximum signal value set at the desired value, press the and buttons simultaneously to set the span. The LED’s then will flash a sequence of Y-Y-G-G indicating that the calibration is complete. The signal can now be adjusted to the desired output value without affecting the valve position. Press the and buttons simultaneously to put the unit back in operation. Note that the input calibration correlates the signal to 0% and 100% signal it does not affect the position calibration all since that calibration is done separately with the Quick-Cal button.
8.7.2 Output loop calibration (optional) - If a loop calibra- tion is started with the Output loop selected on the Loop calibration Dip switch, the LED’s will flash a sequence of Y-G-G-G indicating that it is waiting for the 0% signal to be adjusted using the and buttons for the output current loop on positioner on terminals +31 and –32. (Note that the loop must be externally powered with a voltage between 12VDC and 40VDC and a current meter used to measure the current in the loop). Normally this will be 4 mA, but if split range operation is required adjust to the minimum current for the desired range. When the 0% signal value is set at the desired value, press the ∆ and buttons simultaneously to proceed to the next step. The LED’s will now flash a sequence of Y-R-G-Y indicating that it is waiting for the 100% signal to be adjusted using the and buttons for the output current loop. Normally the 100% setting will be 20 mA, but if split range operation is required adjust to the maximum current for the desired range. When the 100% signal value set at the desired value press the and ∇ buttons simultaneously to complete the calibration.
Page 12
12
Logix 510si Status Condition Codes
Colors Identifier Indication and resolution G - - - Any sequence starting with a Green light flashing first is a normal operating mode and indicates that there
are no internal problems. GGGG 1 No errors, alerts, or warnings. GGGY 2 MPC active - The command is below the 1% command limit for tight shutoff feature. This is a normal
condition for a closed valve. To clear the condition, adjust the command signal above the specified MPC
value, or disable the feature by moving the Tight Shutoff switch to the off position and recalibrating. GGYR 3 LED test mode, Initializing - This sequence should only be visible for 3 sequences when
powering up the unit.
9 STATUS CODES
Page 13
13
Colors Identifier Indication and resolution Y - - - Any sequence starting with a yellow light indicates that the unit is in a special calibration or test mode, or that
there was a calibration problem.
YYYR 4 Command minimum saturated - Calibration error indicating that the 4-20 mA signal corresponding to the
minimum command was too low. Adjust the signal to higher range and re-do the calibration. This error may be cleared by briefly pushing the quick-cal button, which will force the positioner to use the parameters from the last good calibration.
YYRR 5 Command span - Calibration error indicating that the 4-20 mA signal was below the minimum calibration span.
The minimum calibration span is 3.0 mA. This error may be cleared by briefly pushing the quick-cal button, which will force the positioner to use the parameters from the last good calibration or if the ∆ and ∇ buttons are pressed simultaneously the calibrated span will be used even though it is less than the recommended range.
YYRY 6 Command maximum saturated - Calibration error indicating that the 4-20 mA signal corresponding the
maximum command was too high. Adjust the signal a lower range and re-do the calibration. This error may be cleared by briefly pushing the quick-cal button, which will force the positioner to use the parameters from the last good calibration.
YYGG 7 Calibration complete - Indicates that a 4-20 command calibration is complete. This pause allows the signal to be adjusted
without affecting the valve position. Press the and buttons simultaneously to put the unit back in operation.
YRRR 8 Feedback span - The range of motion of the position feedback arm was too small. Check for loose linkages
and/or adjust the feedback pin to a position closer to the follower arm pivot to create a larger angle of rotation. Also check the air supply to make sure the system is properly connected. This error may be cleared by briefly pushing the quick-cal button, which will force the positioner to use the parameters from the last good calibration or if the ∆ and ∇ buttons are pressed simultaneously the calibrated span will be used even though it is less than the recommended range.
YRRY 9 Feedback 100 saturated - Calibration error indicating that the position sensor was out of range during the
calibration. To correct the condition, adjust the positioner mounting, linkage or feedback potentiometer to move the position sensor back into range then restart the calibration. This error may be cleared by briefly pushing the quick-cal button, which will force the positioner to use the parameters from the last good calibration.
YRRG 10 Waiting for 100% position JOG set point from User - only used during Jog calibration see explanation in
Quick-Cal section of main document for operation.
YRYY 11 Feedback no-motion during calibration - Indicates that there was no motion of the actuator based on the
current stroke time configuration. Check linkages and air supply to make sure the system is properly connected. If the time out occurred because the actuator is very large then simply retry the Quick cal and the positioner will automatically adjust for a larger actuator by doubling the time allowed for movement. This error may be cleared by briefly pushing the quick-cal button, which will force the positioner to use the parameters from the last good calibration.
YRYG 12 Setting IL offset (during Stroke calibration) - An automatic step in the calibration process that is done with
the valve a 50% position. This must be completed for proper operation.
YRYR 13 Feedback 0 saturated - Calibration error indicating that the position sensor was out of range during the
calibration. To correct the condition, adjust the positioner mounting, linkage or feedback potentiometer to move the position sensor back into range then restart the calibration. This error may be cleared by briefly pushing the quick-cal button, which will force the positioner to use the parameters from the last good calibration.
YRGG 14 Stroke Calibration in Progress - Calibration sequence started using the local Quick- Cal button. It may be
cancelled by briefly pushing the quick-cal button.
YRGY 15 Unable to set IL offset during QUICK-CAL – This may occur on very large or small actuators on the first
calibration attempt. The Logix 510 will automatically adjust parameters for future calibrations. To Continue briefly push the quick-cal button to acknowledge and restart Quick-Cal.
YRGR 16 Feedback unstable during calibration - Check for loose linkages or loose positioner sensor. This error may
be cleared by briefly pushing the quick-cal button, which will force the positioner to use the parameters from
the last good calibration. YGGG 17 4-20 mA output O% - Waiting for the user to adjust the 0% 4-20 mA output during calibration. YGGY 18 4-20 mA input O% - Waiting for 0% 4-20 mA command input during command calibration. YGGR 19 Jog O% - Waiting for 0% position JOG set point from User - only used during Jog calibration see explanation
in Quick-Cal section of main document for operation YGYY 20 4-20 mA output 10O% - Waiting for the user to adjust the 100% 4-20 mA output during calibration. YGYR 21 4-20 mA input 10O% - Waiting for 100% 4-20 mA command input during command calibration. YGRY 22 Analog output span too small - The span must be calibrated to a range greater than 3.0 mA. This error may
be cleared by briefly pushing the quick-cal button, which will force the positioner to use the parameters from
the last good calibration or if the ∆ and ∇ buttons are pressed simultaneously the calibrated span will be used
even though it is less than the recommended range. YGRR 23 JOG Control Mode - the unit has been placed in a local override mode where the valve can only be stroked using
the two local jog buttons. It may be cancelled by briefly pushing the quick-cal button.
Logix 510si Status Condition Codes
Page 14
14
Troubleshooting Logix 510si Digital Positioners
Failure Probable Cause Corrective action
No LED is blinking 1. Current source below 3.6 mA 1. Verify current source is outputting at
least 3,6 mA
2. Incorrect wiring polarity 2. Check wiring for correct polarity Unit does not respond 1.Error occurred during calibration 1. Correct calibration error. Recalibrate to analog commands Valve position reading is 1. Stroke not calibrated 1. Recalibrate not what is expected 2. Stem position sensor mounting 2. 2.Orient sensor properly
is off 180 degrees Position is driven fully 1. Stroke not calibrated 1. Calibrate valve stroke open or closed and will 2. Inner-loop hall sensor not connected 2. Verify hardware connections not respond to command 3. Wrong air action set on DIP switch 3. Check ATO (Air-to-open) and ATC
(Air-to-Close) settings. Recalibrate
4. Actuator tubing backward 4. Verify ATO/ATC actuator tubing
5. Electro-pneumatic converter 5. Replace electro-pneumatic converter
malfunctioning Sticking or hunting 1. Contamination of the electro- 1. Check air supply for proper filtering operation of the positioner pneumatic converter. and meeting ISA specifcations ISA-7.0.01
2. Control tuning parameters not 2. Lower gain switch settings
11 TROUBLE SHOOTING
Logix 510si Status Condition Codes
Colors Identifier Indication and resolution R - - - Any sequence starting with a red light indicates that there is an operational problem with the unit.
RRYY 24 Bad electronic assembly - replace. RGRR 25 Position Deviation – Indicates that he position has exceeded a fixed 20% error between command and
position for a period of time 5 times longer than the recorded stroke time. This error is usually seen when the positioner is first mounted and powered up before a stroke calibration has been done. If the positioner is properly calibrated, the air supply is correct, and the linkage is properly adjusted this error normally indicates that there is a mechanical problem in the positioner, actuator, or valve that is preventing the valve from stroking properly. If a regulated air supply connected to the actuator properly strokes the valve this
indicates a bad positioner and should be replaced if a calibration does not clear the error.
10 Version number checking- The version number of the embedded code may be checked at any time except during a
calibration by holding down the button. This will not alter the operation of the unit other than to change the blink sequence to 3 blinks indicating the major version number. Holding the button will give the minor version number without affecting operation. The version codes are interpreted by adding up the numbers assigned according to the following table:
Color First blink value Second blink value Third blink value
Green 0 0 0 Yellow 9 3 1 Red 18 6 2
For example if holding the ∆ button gave a G-G-R code, and holding the ∇ button gave a Y-Y-G code then the resulting version number would be (0+0+2).(9+3+0) or version 2.12.
Page 15
15
12 SPARE PART KITS
Item No. Description Part-No.
1 Cover Assembly Yellow
White
Black 2a PC Board Assembly H10114000 2b PC Board Assembly with analog feedback H10114001
3 Repair kit for Logix 500-Relay Module Assembly H10011500 4 Repair kit for Potentiometer Assembly H10011600 5 Position Feedback Assembly H194500003 8 Follower Arm Assembly Max. stroke 65 mm H194512001
Max. stroke 110 mm H194512002
Item No. Description Part-No.
IEC 534 part 6 (Valtek 2000, Kämmer KA, Kämmer KP, and standard NAMUR linear valves) H192685001 – Rotary VDI/VDE 3845 (DIN ISO 5211) H194984001
Item No. Description Part-No.
–2 gauge set, 6 bar / 4 bar, brass, nickel plated H179379013 –2 gauge set, 6 bar / 4 bar, stainless steel H179379015
Mounting Kits
Gauge Kits
Page 16
16
All data subject to change without notice
©04.2002 Flowserve Corporation. Flowserve and Kämmer are trademarks of Flowserve Corporation
Regional Headquarters Flowserve Flowserve Flowserve
Manderscheidstr. 19 1350 N. Mt. Springs Prkwy. 12 Tuas Avenue 20 45141 Essen Springville, UT 84663 Germany USA Republic of Singapore 638824 Telephone: +49 (0) 201 8919 5 Telephone: +1 801 489 8611 Telephone: +65 862 3332 Facsimile: +49 (0) 201 8919 662 Facsimile: +1 801 489 3719 Facsimile: +65 862 4940
Main Sales Offices (Europe, Middle East, Africa)
Flowserve Flowserve Flowserve Flowserve
von-Braun-Straße 19a 12, av. du Québec Station Road Allee du Quartz 1 48681 Ahaus 91965, Courtaboeuf Cedex Pershore, Worcestershire CH-2300 La-Chaux-de Fonds Germany France England WR102BZ Switzerland Telephone: +49 (0) 2561 6860 Telephone: +33 (0) 1 60 923 251 Telephone: +44 (0) 1386 55 45 51 Telephone: +41 (0) 32 925 9700 Facsimile: +49 (0) 2561 68648 Facsimile: +33 (0) 1 60 923 299 Facsimile: +44 (0) 1386 55 49 68 Facsimile: +41 (0) 32 926 5422
Flowserve Flowserve
Units 1 and 2 C/O Saleh & Abdulaziz Abahsain 26, Imvuba Road, Sebenza Ext 6 P.O. Box 209 Edenvale, Gauteng Edenglen 1613 Al Khobar 31952 South Africa Saudi Arabia Telephone: +27 11 609 2094 Telephone: 9663 857 3442 Facsimile: +27 11 609 3735 Facsimile: 9663 859 5284
Loading...