Emerson Fisher 846 Instruction Manual

Instruction Manual
D102005X012
846 Transducer
Fisherr 846 Current-to-Pressure Transducer
March 2015
Contents
1. Introduction
Scope of Manual 2.............................
Description 2.................................
Related Documents 5..........................
Educational Services 6.........................
2. Installation Hazardous Area Classifications and Special
Instructions for Safe‐Use and Installation
in Hazardous Locations 7.....................
CSA 8....................................
FM 8.....................................
ATEX 9...................................
IECEx 10..................................
ATEX/IECEx 10............................
Mounting 11.................................
Pressure Connections 11.......................
Supply Pressure 13.........................
Output Pressure 17........................
Electrical Connections 17.......................
Venting Ports 18..............................
Signal Interruption 18..........................
3. Calibration Standard Performance:
Full Range Input, Direct Action 21.............
Multirange Performance:
Full Range Input, Direct Action 21.............
Standard Performance:
Split Range Input, Direct Action 22.............
4 to 12 mA Input Signal 22..................
12 to 20 mA Input Signal 22.................
Standard Performance:
Full Range Input, Reverse Action 23............
Multirange Performance:
Full Range Input, Reverse Action 23............
Standard Performance:
Split Range Input, Reverse Action 24...........
4 to 12 mA Input Signal 24..................
12 to 20 mA Input Signal 24.................
Transporting the Module Final Assembly 25.......
4. Principle of Operation
Electronic Circuit 26...........................
Magnetic Actuator 27..........................
Pilot Stage 27.................................
Booster Stage 28..............................
Figure 1-1. Fisher 846 Current‐to‐Pressure Transducer
X0234
5. Troubleshooting
Diagnostic Features 29.........................
Stroke Port 29.............................
Remote Pressure Reading (RPR) 29...........
Using a Frequency Counter to read the
RPR Signal 29.........................
In‐service Troubleshooting 30...................
Troubleshooting in the Shop 33.................
6. Maintenance
Module Final Assembly 35......................
Removing the Module Final Assembly 38......
Replacing the Module Final Assembly 39.......
Electronic Circuit Board 40......................
Remote Pressure Reading (RPR) Jumper 40.....
Range Jumper 41..........................
Action 41.................................
Removing the Electronic Circuit Board 41......
Replacing the Electronic Circuit Board 42......
Pilot/Actuator Assembly 42.....................
Action 42.................................
Removing the Pilot/Actuator Assembly 43.....
Replacing the Pilot/Actuator Assembly 44.....
Module Subassembly 44........................
Terminal Compartment 44.....................
Exhaust and Stroke Port Screens 45..............
7. Parts 46....................................
8. Installation Drawings 50......................
www.Fisher.com
846 Transducer
March 2015
Instruction Manual
D102005X012
Section 1 Introduction
Scope of Manual
This instruction manual provides installation, operating, calibration, maintenance, and parts ordering information Fisher 846 current‐to‐pressure transducers. Refer to separate manuals for instructions covering equipment used with the transducers.
Do not install, operate or maintain an 846 current‐to‐pressure transducer without being fully trained and qualified in valve, actuator, and accessory installation, operation, and maintenance. To avoid personal injury or property
damage, it is important to carefully read, understand, and follow all of the contents of this manual, including all safety cautions and warnings. If you have any questions about these instructions, contact your Emerson Process
Management sales office before proceeding.
Description
The 846 current‐to‐pressure transducer, shown in figure 1-1, accepts an electrical input signal and produces a proportional pneumatic output. Typically, 4 to 20 mA is converted to 0.2 to 1.0 bar (3 to 15 psi). Models are available in direct or reverse action and field‐selectable full or split range inputs. Refer to the Calibration section for more information on input/output combinations.
The most common application of the transducer is to receive an electrical signal from a controller and produce a pneumatic output for operating a control valve actuator or positioner. The 846 may also be used to transduce a signal for a pneumatic receiving instrument.
The 846 is an electronic I/P transducer. It has a single electronic circuit board, as shown in figure 1-2. The circuit contains a solid‐state pressure sensor that monitors output pressure and is part of an electronic feedback network. The self‐correcting ability provided by the sensor/circuit combination allows the transducer to produce a very stable and responsive output signal.
All active mechanical and electrical components of the 846 are incorporated into a single, field‐replaceable module called the module final assembly, shown in figure 1-2. The module final assembly contains the electronic circuit board, pilot/actuator assembly, and booster stage. The module final assembly is easily removed by unscrewing the module cover. Its design minimizes parts and reduces the time required for repair and troubleshooting.
The terminal compartment and module compartment are separated by a sealed compartment wall. This multi‐compartment housing also protects the electronics from contaminants and moisture in the supply air.
Specifications
WARNING
This product is intended for a specific range of pressures, temperatures, and other application specifications. Applying different pressure, temperature and other service conditions could result in a malfunction of the product, property damage or personal injury.
Specifications for the 846 transducer are listed in table 1-1.
2
Instruction Manual
D102005X012
Table 1-1. Specifications
846 Transducer
March 2015
Input Signal
Standard Performance:
4 to 20 mA DC, 4 to 12 mA DC, or 12 to 20 mA DC. Field adjustable split ranging.
Multirange Performance:
4 to 20 mA DC. Consult factory for split range input.
Equivalent Circuit
See figure 1-3
Output Signal
(1)
Standard Performance:
(Consult factory for split range output)
Direct Action (Minimum span of 6 psi)
Typical outputs: 0.2 to 1.0 bar (3 to 15 psi). Rangeability between 0.1 and 1.2 bar (1 and 18 psi)
Reverse Action (Minimum span of 11 psi)
Typical outputs: 1.0 to 0.2 bar (15 to 3 psi) Rangeability between 1.2 and 0.1 bar (18 and 1 psi)
Multirange Performance: Direct Action (Minimum span of 6 psi)
Typical outputs: 0.2 to 1.9 bar (3 to 27 psi), 0.4 to 2 bar (6 to 30 psi), and 0.3 to 1.7 bar (5 to 25 psi) Rangeability between 0.03 and 2.3 bar (0.5 and 33 psi)
Reverse Action (Minimum span of 11 psi)
Typical outputs: 1.9 to 0.2 bar (27 to 3 psi), 2 to
0.4 bar (30 to 6 psi), and 1.7 to 0.3 bar (25 to 5 psi) Rangeability between 2.3 and 0.03 bar (33 and
0.5 psi)
Supply Pressure
(2)
Standard Performance: 1.2 to 1.6 bar (18 to 24 psi) Multirange Performance:
0.2 bar (3 psi)
(3)
greater than the maximum
calibrated output pressure Maximum: 2.4 bar (35 psi)
Supply Pressure Medium
Clean, dry air
Per ISA Standard 7.0.01
A maximum 40 micrometer particle size in the air system is acceptable. Further filtration down to 5 micrometer particle size is recommended. Lubricant
-Continued-
content is not to exceed 1 ppm weight (w/w) or volume (v/v) basis. Condensation in the air supply should be minimized
Per ISO 8573-1
Maximum particle density size: Class 7 Oil content: Class 3 Pressure Dew Point: Class 3 or at least 10°C less than
the lowest ambient temperature expected
Output Air Capacity
(4)
Standard: 6.4 m3/hr (240 scfh) at 1.4 bar (20 psi) supply pressure
3
Multirange: 9.7 m
/hr (360 scfh) at 2.5 bar
(35 psig) supply pressure
Maximum Steady‐State Air Consumption
(4)
0.3 m3/hr (12 scfh) at 1.4 bar (20 psi) supply pressure
Temperature Limits
(2)
Operating: -40 to 85_C (-40 to 185_F) Storage :-40 to 93_C (-40 to 200_F)
Humidity Limits
0 to 100% condensing relative humidity
Performance
(5)
Note: The performance of all 846 I/Ps is verified using computer automated manufacturing systems to ensure that every unit shipped meets its performance specifications.
Linearity, Hysteresis, and Repeatability: $0.3% of span.
Temperature Effect (total effect including zero and span): $0.07%/_C (0.045%/_F) of span
Vibration Effect: $0.3% of span per g during the
following conditions: 5 to 15 Hz at 4 mm constant displacement 15 to 150 Hz at 2 g. 150 to 2000 Hz at 1 g. per SAMA Standard PMC 31.1, Sec. 5.3, Condition 3, Steady State
Shock Effect: $0.5% of span, when tested per SAMA Standard PMC 31.1, Sec. 5.4.
Supply Pressure Effect: Negligible
3
846 Transducer
March 2015
Table 1-1. Specifications (continued)
Instruction Manual
D102005X012
Performance (continued)
(5)
Electromagnetic Interference (EMI): Tested per IEC 61326‐1 (Edition 1.1). Meets emission levels for Class A equipment (industrial locations) and Class B equipment (domestic locations). Meets immunity requirements for industrial locations (Table A.1 in the IEC specification document). Immunity performance is shown in table 1-2.
Leak Sensitivity
3
4.8 m
/hr (180 scfh) downstream leakage.
(4)
: Less than 1.0% of span for up to
Overpressure Effect: Less than 0.25% of span for
misapplication of up to 7.0 bar (100 psi) supply pressure for less than 5 minutes to the input port.
Reverse Polarity Protection:
No damage occurs from reversal of normal supply current (4 to 20 mA) or from misapplication of up to 100 mA.
Connections
Supply Air, Output Signal, and Output Gauge: 1/4‐18 NPT internal connection Electrical: 1/2‐14 NPT internal conduit connection
Adjustments
Zero and Span: screwdriver adjustments located in terminal compartment.
Remote Pressure Reading (RPR) Jumper selectable, ON or OFF, if unit includes option
Frequency Range: 0 to 10,000 Hz Amplitude: 0.4 to 1.0 V
p‐p
Required Operating Voltage with Remote pressure Reading Off
Min. 6.0 V (at 4 mA) Max. 7.2 V (at 20 mA)
Required Operating Voltage with Remote Pressure Reading On
Min 6.4 V (at 4 mA) Max. 8.2 V (at 20 mA)
-continued-
Electrical Classification
Hazardous area:
CSA C/US—Intrinsically Safe, Explosion-proof,
Non-Incendive
FM—Intrinsically Safe, Explosion-proof, Non-Incendive
ATEX—Intrinsically Safe, Flameproof, Type n
IECEx—Intrinsically Safe, Flameproof
Refer to Hazardous Area Classifications and Special Instructions for “Safe Use” and Installation in Hazardous Locations in Section 2 for additional information
Electrical Housing:
Tropicalization (Fungus test per MIL-STD-810)
CSA C/US—Type 4X
FM—Type 4X
ATEX—IP66
IECEx—IP66
(6)
(6)
Other Classifications/Certifications
INMETRO—National Institute of Metrology, Quality, and Technology (Brazil)
KGS—Korea Gas Safety Corporation (South Korea)
NEPSI— National Supervision and Inspection Centre
for Explosion Protection and Safety of Instrumentation (China)
Contact your Emerson Process Management sales
office for classification/certification specific
information
Construction Materials
Housing: Low‐copper aluminum with polyurethane paint, or 316 stainless steel O‐Rings: Nitrile, except silicone for sensor O‐rings.
Options
Fisher 67CFR filter regulator, supply and output gauges or tire valve remote pressure reading, module cover with multiple stroke ports, stainless steel housing, or stainless steel mounting bracket.
Weight
Aluminum: 2.9 kg (6.5 lb) excluding options Stainless Steel: 6.7 kg (14.8 lb) excluding options
4
Instruction Manual
D102005X012
Table 1-1. Specifications (continued)
846 Transducer
March 2015
Declaration of SEP
Fisher Controls International LLC declares this product to be in compliance with Article 3 paragraph 3 of the Pressure Equipment Directive (PED) 97 / 23 / EC. It was designed and manufactured in accordance
NOTE: Specialized instrument terms are defined in ANSI/ISA Standard 51.1 - Process Instrument Terminology.
1. Metric calibration also available.
2. The pressure/temperature limits in this document, and any applicable standard or code limitation should not be exceeded.
3. 0.14 bar (2 psi) for a 2.3 bar (33 psi) output.
4. Normal m
5. Reference Conditions: 4.0 to 20 mA DC input, 0.2 to 1.0 bar (3 to 15 psi) output, and 1.4 bar (20 psi) supply pressure.
6. ATEX and IECEx Flameproof — IP66 per CSA Letter of Attestation.
3
/hr—Normal cubic meters per hour (0_C and 1.01325 bar, absolute). Scfh—Standard cubic feet per hour (60_F and 14.7 psia).
with Sound Engineering Practice (SEP) and cannot bear the CE marking related to PED compliance.
However, the product may bear the CE marking to indicate compliance with other applicable European Community Directives.
Table 1-2. EMC Immunity Performance Criteria
Port Phenomenon Basic Standard Test Level Performance Criteria
Electrostatic discharge (ESD) IEC 61000‐4‐2
Enclosure
I/O signal/control
Specification limit = ±1% of span
1. A = No degradation during testing. B = Temporary degradation during testing, but is self‐recovering.
Radiated EM field IEC 61000‐4‐3
Burst (fast transients) IEC 61000‐4‐4 1 kV A Surge IEC 61000‐4‐5 1 kV (line to ground only, each) B
Conducted RF IEC 61000‐4‐6
4 kV contact 8 kV air
80 to 1000 MHz @ 10V/m with 1 kHz AM at 80% 1400 to 2000 MHz @ 3V/m with 1kHz AM at 80% 2000 to 2700 MHz @ 1V/m with 1kHz AM at 80%
150 kHz to 8 MHz at 3 Vrms B 8 MHz to 80 MHz at 3 Vrms A
(1)
A
A
Related Documents
This section lists other documents containing information related to the 846 transducer. These documents include:
DINMETRO Hazardous Area Approvals for Fisher 846 Current-to-Pressure Transducers Instruction Manual
(D103623X012)
DNEPSI Hazardous Area Approvals for Fisher 846 Current-to-Pressure Transducers Instruction Manual
(D103618X012)
All documents are available from your Emerson Process Management sales office. Also visit our website at www.Fisher.com.
5
846 Transducer
March 2015
Instruction Manual
D102005X012
Figure 1-2. Transducer Modular Construction
TERMINAL COMPARTMENT COVER
TERMINAL BLOCK
MODULE HOUSING
ELECTRONIC CIRCUIT BOARD
MODULE FINAL ASSEMBLY
Figure 1-3. Equivalent Circuit
846
6 V DC
50 OHM S
POWER SUPPLY
NOTE: THE 846 IS NOT A CONSTANT RESISTOR IN SERIES WITH AN INDUCTOR. IT IS BETTER MODELED IN THE LOOP AS A 50 OHM RESISTOR IN SERIES WITH A 6‐VOLT DC VOLTAGE DROP WITH NEGLIGIBLE INDUCTANCE.
A6325
MODULE COVER
A6643
Educational Services
For information on available courses for the 846 current‐to‐pressure transducer, as well as a variety of other products, contact:
Emerson Process Management Educational Services - Registration Phone: +1-641-754-3771 or +1-800-338-8158 Email: education@emerson.com http://www.emersonprocess.com/education
6
Instruction Manual
D102005X012
846 Transducer
March 2015
Section 2 Installation22
WARNING
To avoid personal injury or property damage from the sudden release of pressure or air:
D Always wear protective clothing, gloves, and eyewear when performing any installation operations.
D Disconnect any operating lines providing air pressure, electric power, or a control signal to the actuator. Be sure the
actuator cannot suddenly open or close the valve.
D Use bypass valves or completely shut off the process to isolate the valve from process pressure. Relieve process pressure
on both sides of the valve.
D Use lock‐out procedures to be sure that the above measures stay in effect while you work on the equipment.
D Check with your process or safety engineer for any additional measures that must be taken to protect against process
media.
This section presents information on installing the 846 current‐to‐pressure transducer. Figures 2-1, 2-2, 2-3, and 2-5 can be used as references for instructions contained in this section.
When a control valve is ordered with a 846 transducer specified to be mounted on the actuator, the factory‐mounted transducer is connected to the actuator with the necessary tubing and calibrated to the specifications on the order.
If the transducer is purchased separately for mounting on a control valve already in service, all the necessary mounting parts are furnished, if ordered. This includes the appropriate bracket for attaching the unit to an actuator boss (with tapped holes) or for attaching it to the diaphragm casing.
If preferred, mounting parts can be supplied for mounting the transducer on a 51 mm (2‐inch) diameter pipestand, a flat surface, or a bulkhead.
Transducers also can be ordered separately for mounting on a control valve assembly already in service. The transducer may be ordered with or without mounting parts. Mounting parts include the appropriate bracket and bolts for attaching the unit to an actuator boss (with tapped holes) or for attaching it to the diaphragm casing.
Hazardous Area Classifications and Special Instructions for “Safe Use” and Installation in Hazardous Locations
Certain nameplates may carry more than one approval, and each approval may have unique installation/wiring requirements and/or conditions of “safe use”. These special instructions for “safe use” are in addition to, and may override, the standard installation procedures. Special instructions are listed by approval.
Note
This information supplements the nameplate markings affixed to the product.
Always refer to the nameplate itself to identify the appropriate certification. Contact your Emerson Process Management sales
office for approval/certification information not listed here.
7
846 Transducer
March 2015
Instruction Manual
D102005X012
WARNING
Failure to follow these conditions of safe‐use could result in personal injury or property damage from fire or explosion, and area re‐classification.
CSA
Intrinsically Safe, Explosion-proof, Non-Incendive
No special conditions for safe use.
Refer to table 2-1 for approval information.
Table 2-1. Hazardous Area Classifications for Canada—cCSAus
Certification Body Certification Obtained Entity Rating Temperature Code
Vmax = 30 VDC Imax = 100 mA Ci = 0.016 mF Li = 20 mH
- - - T4 (Tamb 60_C)
T4 (Tamb ≤ 60_C)
CSA
Ex ia Intrinsically Safe  Class I Division 1 Groups A,B,C,D T4  per drawing GE59146 (see figure 8-1)
XP Explosion-proof  Class I Division 1 Groups C,D DIP Dust Ignition-proof  Class II III Division I Groups E,F,G T4 NI Non-incendive  Class I, Division 2, Groups A,B,C,D T4
FM
Special Conditions of Use
Intrinsically Safe, Explosion-proof, Non-Incendive
1. The apparatus enclosure contains aluminum and is considered to constitute a potential risk of ignition by impact or friction. Care must be taken into account during installation and use to prevent impact or friction.
Refer to table 2-2 for additional approval information.
Table 2-2. Hazardous Area Classification for United Stated—FM
Certification Body Certification Obtained Entity Rating Temperature Code
Vmax = 30 VDC Imax = 100 mA Pmax = 1.0 W Ci = 0.016 mF Li = 20 mH
- - - T4 (Tamb ≤ 60_C)
T4 (Tamb ≤ 60_C)
FM
IS Intrinsically Safe  Class I, II, III Division 1 Groups A,B,C,D,E,F,G  per drawing GE59147 (see figure 8-2)
XP Explosion-proof  Class I Division 1 Groups B,C,D DIP Dust Ignition-proof  Class II, III Division I Groups EFG NI Non-incendive  Class I Division 2 Groups A,B,C,D
8
Instruction Manual
D102005X012
846 Transducer
March 2015
ATEX
Special Conditions for Safe Use
Intrinsically Safe
This equipment is intrinsically safe and can be used in potentially explosive atmospheres.
The apparatus must be only connected to a certified associated intrinsically safe equipment and this combination must be compatible as regards intrinsic safety rules.
The electrical parameters of certified equipment which can be connected to the sensor must not exceed one of these following values:
U
≤ 30 V
0
I
≤ 100 mA
0
P
≤ 1.0 W
0
Ambient temperature: -40_C to +80_C
Flameproof
Refer to page 10.
Type n
No special conditions for safe use.
Refer to table 2-3 for additional approval information.
Table 2-3. Hazardous Area Classifications—ATEX
Certificate Certification Obtained Entity Rating Temperature Code
Intrinsically Safe II 1 GD Gas Ex ia IIC T4,T5 Ga Dust Ex ia IIIC IP66 Da T90_C (Tamb ≤ 80_C) Ex ia IIIC IP66 Da T50_C (Tamb ≤ 40_C)
Flameproof
ATEX
II 2 G Gas Ex d IIB T5/T6 Gb
Type n II 3 GD Gas Ex nA IIC T5/T6 Gc Dust Ex tc IIIC T88_C T Ex tc IIIC T77_C T
500 500
Dc IP66 Dc IP66
Ui = 30 VDC Ii = 100 mA Pi = 1.0 W Ci = 8 nF Li = 20 mH
- - -
- - -
T4 (Tamb ≤ 80_C) T5 (Tamb ≤ 40_C)
T5 (Tamb ≤ 80_C) T6 (Tamb ≤ 65_C)
T5 (Tamb ≤ 85_C) T6 (Tamb ≤ 74_C)
9
846 Transducer
March 2015
IECEx
Special Conditions for Safe Use
Intrinsically Safe
No special conditions for safe use.
Flameproof
See below.
Refer to table 2-4 for additional approval information.
Table 2-4. Hazardous Area Classifications—IECEx
Certificate Certification Obtained Entity Rating Temperature Code
Intrinsically Safe Gas Ex ia IIC T4/T5 Ga
IECEx
Flameproof Gas Ex d IIB T5/T6 Gb
Ui = 40 VDC Ii = 200 mA Pi = 1.0 W Ci = 8 nF Li = 20 mH
- - -
Instruction Manual
D102005X012
T4 (Tamb ≤ 80_C) T5 (Tamb ≤ 40_C)
T5 (Tamb ≤ 80_C) T6 (Tamb ≤ 65_C)
ATEX/IECEx
Special Conditions for Safe Use
Flameproof
1. The equipment incorporates flameproof joints which have a maximum gap less than that stated in EN 60079‐1. The user shall refer to the manufacturer's installation, operation, and maintenance document for guidance.
2. The cable entry device used shall be certified Ex d IIB or Ex d IIC.
3. The user shall ensure that the maximum system pressure does not exceed 35 psi.
4. Refer to figures 2-2 and 2-3 for proper bolting engagement length for ATEX and IECEx flameproof units.
5. A cable entry hole is provided for the accommodation of a flameproof cable entry device, with or without the interposition of a flameproof thread adaptor.
For ATEX certified versions of 846 transducers—the cable entry device and thread adapter shall be suitable for the equipment, the cable and the conditions of use and shall be certified as Equipment (not a Component) under an EC Type Examination Certificate to Directive 94/9/EC. Refer to table 2-3 for additional approval information.
For IECEx certified versions of 846 transducers—the cable entry device and thread adapter shall be suitable for the equipment, the cable and the conditions of use and shall be certified as Equipment (not a Component). Refer to table 2-4 for additional approval information.
10
Instruction Manual
D102005X012
846 Transducer
March 2015
Mounting
WARNING
This unit will vent to the atmosphere through the stroke port in the module cover and the exhaust port, located under the nameplate. Do not remote vent this unit.
The transducer is designed for mounting on a control valve, 51 mm (2‐inch) diameter pipestand, wall, or panel. Figures 2-2, 2-3, 2-4, and 2-5 show recommended mounting configurations. The mounting positions shown allow any moisture buildup in the terminal compartment to drain to the signal wire conduit entrance. Any moisture in the pilot stage area will be expelled through the stroke port without affecting pilot stage operation. In applications with excessive moisture in the supply air, vertical mounting allows the most effective drainage through the stroke port.
CAUTION
Do not mount the transducer with the terminal compartment cover on the bottom as moisture, or any corrosive elements in the plant atmosphere, may accumulate in the terminal compartment or pilot stage, resulting in transducer malfunction.
Mounting is accomplished with an optional universal mounting bracket. Before mounting the transducer, note the following recommendations:
D Ensure that all bolts are fully tightened. The recommended torque is 22 NSm (16 lbfSft).
D Bolts that connect to the transducer and to a valve actuator should have the lock washer placed directly beneath the
bolt head and the flat washer placed between the lock washer and bracket. All other bolts should have the lock washer next to the nut, and the flat washer placed between the lock washer and bracket.
D Do not mount the transducer in a location where foreign material may cover the stroke port or exhaust port. See the
descriptions of the stroke port and exhaust port later in this section.
Pressure Connections
As shown in figure 2-1, all pressure connections are 1/4‐18 NPT internal connections. Use 9.5 mm (3/8‐inch) outside diameter tubing for the supply and output connections.
11
846 Transducer
March 2015
Instruction Manual
D102005X012
Figure 2-1. Typical Dimensions and Connection Locations (Aluminum Construction Shown)
129
(5.07)
119
STROKE PORT
(4.68)
MODULE COVER WITH
MULTIPLE PORTS
NAMEPLATE
MOUNTING BOLT HOLES 5/16‐18 (3)
EXHAUST PORT UNDERNEATH NAMEPLATE
59
(2.31)
CONDUIT CONNECTION 1/2 ‐ 14 NPT
OUTPUT PORT 1/4 ‐ 18 NPT
35
(1.38)
29
(1.13)
29
(1.16)
COVER REMOVAL
OUTPUT GAUGE PORT 1/4‐18 NPT
TEST PINS
WIRING CONNECTION
NOTE:
REFER TO FIGURE 2-5 FOR TRANSDUCER DIMENSIONS WITH ATEX / IECEx FLAMEPROOF CERTIFICATIONS
B2473‐1
POSITIVE NEGATIVE INTERNAL GROUND
110
(4.33)
102
(4.00)
O‐RING GROOVE FOR FILTER REGULATOR
SUPPLY PORT 1/4‐18 NPT
5/16‐18 (2)
mm
(INCHES)
12
Instruction Manual
D102005X012
846 Transducer
March 2015
Supply Pressure
WARNING
Severe personal injury or property damage may occur from process instability if the instrument supply medium is not clean, dry air. While use and regular maintenance of a filter that removes particles larger than 40 micrometers in diameter will suffice in most applications, check with an Emerson Process Management field office and industry instrument air quality standards if you are unsure about the proper amount or method of air filtration or filter maintenance.
The supply medium must be clean, dry air that meets the requirements of ISA Standard 7.0.01 or ISO 8573-1. An output span of 0.2 to 1.0 bar (3 to 15 psi) requires a nominal supply pressure of 1.4 bar (20 psi) and a flow capacity not less than 6.4 normal m
For multirange performance units with higher output spans, the supply pressure should be at least 0.2 bar (3 psi) greater than the maximum calibrated output pressure.
The air supply line can be connected to the 1/4‐18 NPT supply port, or to the supply port of a filter‐regulator mounted directly to the transducer. Figures 2-2, 2-3, 2-4, and 2-5 show the installation options.
3
/hr (240 scfh).
Figure 2-2. Typical Dimensions with Fisher 67CFR Filter/Regulator and Gauges
215 COVER REMOVAL CLEARANCE
NOTE: 1 THE MOUNTING POSITIONS SHOWN ALLOW ANY MOISTURE BUILDUP IN THE TERMINAL COMPARTMENT TO DRAIN TO THE SIGNAL WIRE CONDUIT ENTRANCE. DO NOT MOUNT THE TRANSDUCER WITH THE TERMINAL COMPARTMENT COVER ON THE BOTTOM; MOISTURE MAY ACCUMULATE IN THE TERMINAL COMPARTMENT OR PILOT STAGE, PREVENTING PROPER TRANSDUCER OPERATION. THE VERTICAL MOUNT IS MOST EFFECTIVE FOR MOISTURE DRAINAGE IN WET APPLICATIONS.
14B7361‐D A6626-3
67
(2.62)
78
(3.08)
156
(6.15)
(8.48)
CENTERLINE OF ACTUATOR
YOKE MOUNTED
6
(0.25)
FOR PROPER MOISTURE DRAINAGE THIS END MUST BE UP
191
(7.51)
MODULE COVER REMOVAL CLEARANCE
1
13
(0.50)
FOR ATEX/IECEx FLAMEPROOF UNITS: BOLT ENGAGEMENT NOT TO EXCEED
137
12.9 mm (0.51 INCHES).
(5.38)
5/16‐18 BOLTS
mm
(INCH)
13
846 Transducer
March 2015
Figure 2-3. Typical Transducer Mounting with Universal Mounting Bracket
Instruction Manual
D102005X012
ADDITIONAL ADAPTER PLATE PART NUMBER 03311‐0318‐0001 REQUIRED FOR I/P WITH STAINLESS STEEL HOUSING
U BOLT
5/16‐18 x 5/8 BOLTS
ADAPTER PLATE (SEE DETAIL “B”)
(1.61)
VERTICAL MOUNT
MOUNTING BRACKET (SEE DETAIL “A”)
FOR PROPER MOISTURE DRAINAGE, THIS END MUST BE UP
5/16‐18 HEX NUT (4 PLACES)
41
3
2‐INCH PIPESTAND MOUNTING
FOR ATEX/IECEx FLAMEPROOF UNITS: BOLT ENGAGEMENT NOT TO EXCEED 8.8 mm (0.35 INCHES). 5/16‐18 BOLT HOLES
1
MOUNTING BRACKET (SEE DETAIL “A”)
ADAPTER PLATE (SEE DETAIL “B”)
FOR ATEX/IECEx FLAMEPROOF UNITS: BOLT ENGAGEMENT NOT TO EXCEED
8.1 mm (0.32 INCHES). 5/16‐18 BOLT HOLES
2
HORIZONTAL MOUNT
FOR PROPER MOISTURE DRAINAGE, THE I/P MUST BE MOUNTED ON TOP OF THE PIPE
ADDITIONAL ADAPTER PLATE PART NUMBER 03311‐0318‐0001 REQUIRED FOR I/P WITH STAINLESS STEEL HOUSING
5/16‐18 x 3/4 BOLTS (4 PLACES)
5/16‐18 x 3/4 BOLTS (4 PLACES)
MOUNTING BRACKET (SEE DETAIL “A”)
FOR PROPER MOISTURE DRAINAGE, THIS END MUST BE UP
1
1
GE06214 SHT 3
BOLT HOLES FOR STAINLESS
STEEL CONSTRUCTION
(COVERLOCK SHOWN)
GE06214 SHT 2
BOLT HOLES FOR ALUMINUM
CONSTRUCTION (COVERLOCK SHOWN)
NOTES: 1 THE MOUNTING POSITIONS SHOWN ALLOW ANY MOISTURE BUILDUP IN THE TERMINAL COMPARTMENT TO DRAIN TO THE SIGNAL WIRE CONDUIT ENTRANCE. DO NOT MOUNT THE TRANSDUCER WITH THE TERMINAL COMPARTMENT COVER ON THE BOTTOM; MOISTURE MAY ACCUMULATE IN THE TERMINAL COMPARTMENT OR PILOT STAGE, PREVENTING PROPER TRANSDUCER OPERATION. THE VERTICAL MOUNT IS MOST EFFECTIVE FOR MOISTURE DRAINAGE IN WET APPLICATIONS. 2 IF MOUNTED ON HORIZONTAL PIPE, THE I/P MUST BE ON TOP OF THE PIPE FOR PROPER MOISTURE DRAINAGE. 3 THIS DIMENSION IS 44 (1.74) FOR STAINLESS STEEL HOUSING.
14B7332 19B9484‐B E0786
14
32
(1.25)
WALL/PANEL MOUNTING
(ALUMINUM HOUSING)
mm (INCH)
Instruction Manual
D102005X012
Figure 2-3. Typical Transducer Mounting with Universal Mounting Bracket (continued)
846 Transducer
March 2015
4 X 10 (0.375)
(1.18)
5 X 10 (0.375)
U‐BOLT SLOTS 19 (0.75)
30
29
(1.13)
38
(1.50)
(3.50)
29
(1.16)
(2.312)
59
89
(.89)
23
89
(3.50)
FOR ALUMINUM HOUSING, ALIGN 3 HOLES WITH I/P HOUSING
DETAIL “A” MOUNTING BRACKET
29
(1.125
57
(2.25)
U‐BOLT SLOTS 19 (0.75)
FOR STAINLESS STEEL HOUSING, ALIGN 4 HOLES WITH I/P HOUSING
38
(1.50)
29
(1.125
57
(2.25)
2 X 10 (0.375)
03311-0318
4 X 5 (0.188)
2 X 10 (0.375)
DETAIL “B” ADAPTER PLATE
4 X 5 (0.188)
mm (INCH)
ADDITIONAL ADAPTOR PLATE (PART NUMBER 03311‐0318‐0001)
NOTES:
1. ATTACH THE BRACKET SHOWN IN DETAIL “A” TO THE TRANSDUCER
2. ATTACH THE ADAPTER PLATE SHOWN IN DETAIL “B” TO THE VALVE OR PIPE.
3. CONNECT THE TWO PIECES.
34B4990‐C 34B5000‐B E0787
REQUIRED FOR I/P WITH STAINLESS STEEL HOUSING
The mounting boss for the air supply connection contains two 5/16‐18 UNC tapped holes that are 2‐1/4 inches apart. The tapped holes allow direct connection (integral mount) of a 67CFR filter‐regulator, if desired. When the filter‐regulator is factory mounted, the mounting hardware consists of two 5/16‐18 x 3‐1/2 inch stainless steel bolts and one O‐ring. When the filter‐regulator is field mounted, the mounting hardware consists of two 5/16‐18 x 3‐1/2 inch stainless steel bolts, two spacers (which may or may not be required) and two O‐rings (of which only one will fit correctly into the housing O‐ring groove and the other may be discarded). This is due to the fact that the current housing has been slightly modified from its original design, hence, the additional hardware (if needed) when field mounting the 67CFR filter‐regulator.
15
846 Transducer
March 2015
Figure 2-4. Typical Transducer Dimensions with Gauges
OUTPUT GAGE
FILTER‐ REGULATOR
SUPPLY GAGE
Instruction Manual
D102005X012
81
(3.2)
14B7332‐D E0776
49
(1.92)
72
(2.83)
67CFR 14‐18 NPT SUPPLY CONN
9
(0.36)
Figure 2-5. Transducer Dimensions with ATEX / IECEx Flameproof Certifications
EXTERNAL EARTHING CONNECTION, SST TERMINAL CLAMP AND SLOTTED M5 SCREW AND SPLIT RING WASHER
TERMINAL COMPARTMENT COVER
3.62 (92)
COVER LOCK
1/4‐18 NPT OUTLET CONN PLUGGED WHEN GAUGE NOT FURNISHED
162
(6.38)
mm
(INCH)
16
B2465
INTERNAL HEX DRIVE ROUND HEAD SCREW (3 mm)
4.75
(121)
HOUSING
129
(5.07)
MODULE COVER
121
(4.75)
mm
(INCH)
Loading...
+ 36 hidden pages