AEG-Electrolux EXH09HX1WI User Manual

0 (0)

www.electrolux.com

www.electrolux.dk

www.electrolux.fi

www.electrolux.no

www.electrolux.se

installation manual Installationsvejledning Asennusohje Installasjonshåndbok Installationsmanual

Heatpump

Varmepumpe

Ilmapumppu

Varmepumpe

Värmepump

TINS-B117JBRZ

EXH09HX1WI/EXH09HX1WE

EXH12HX1WI/EXH12HX1WE

installation manual Installationsvejledning Asennusohje Installasjonshåndbok Installationsmanual

Heatpump

Varmepumpe

Ilmapumppu

Varmepumpe

Värmepump

EXH09HX1WI/EXH09HX1WE

EXH12HX1WI/EXH12HX1WE

2 electrolux

Heatpump

Important! Carefully read and follow these instructions for smooth and trouble-free installation.

Accessories

Caution! This room Heatpump uses new refrigerant R410A.

1.Keep any open ends of pipes be sealed with a cap, etc. until connected with the equipment.

2.Exercise great care when performing piping installation so as water, dust, etc. will not enter into the piping and equipment.

3.Pipes connected to the indoor and outdoor units must be used new. (This Heatpump using R410A incurs pressure higher compared with R22, it is necessary to choose adequate materials.)

4.Use only R410A refrigerant when charging additional refrigerant to the equipment. Never add lubricating oil to the equipment in any case.

5.In order to prevent any other refrigerant from being charged accidentally, the service port diameter of the 3-way valve has been changed. (1/2” UNF screw)

 

Items

Q'ty

Application

1

Mounting plate

1

To mount the indoor unit on the wall.

2

Wall plug

8

To fix the mounting plate with the long screws. To fix the

 

 

 

remote control with the special screw.

3

Long screw

7

To fix the mounting plate with the wall plugs.

4

Remote control

1

To control remotely.

5

Dry battery

2

For the remote control. AAA batteries.

6

Special screw

1

To mount the remote control on the wall.

7

Short screw

1

To fix the CORD HOLDER.

electrolux 3

 

Items

Q'ty

Application

8

Cord holder

1

To secure the electrical cable.

9

Manuals

1

Installation manual

INSTALL

OPER

 

1

Operation manual

10 Air purifying filter

2

To remove dust and tobacco smoke from the air.

 

 

 

Notes on locations

Important! Keep the following points in mind and get the customer's approval.

Indoor unit

1.Keep the air outlet clear of any obstacle so that outgoing air flows smoothly in the entire room.

2.Make a drain hose hole for easy drainage.

3.Provide sufficient space on both sides and above the unit.

4.The air filters should be easily taken in and out.

5.Keep TV set, radio and the like 1 m or more away from the unit and the remote control.

6.Keep the air inlet clear of obstacles that could block incoming air.

7.The remote control may not function properly in a room equipped with an electronic simultaneous-start or rapidstart fluorescent lighting.

8.Select a location that does not cause loud operation noise and extreme vibrations.

Outdoor unit

1.Place the outdoor unit on a stable base.

2.Provided sufficient space around the unit. It should also be well ventilated.

3.The unit should not be exposed to strong wind nor splashed with rain water.

4.Water drain from the unit should be let out without problem. Lay a drain hose if required. In cold regions, installation of the drain pipe is not advisable as freezing could result.

5.Keep TV set, radio and the like 1 m or more away from the unit.

6.Avoid locations exposed to machine oil vapor, salty air (facing the seashore, for example), hot spring vapor sulfur gas,

etc. Such location can cause breakdown.

7.Also, avoid locations exposed to muddy water (along a road, for example) or where the unit can be tampered with.

8.Select a location where the outgoing air or operating noise cannot annoy others.

9.Install the unit on a stable base not to allow louder noise.

10.Keep the air outlet opening free of any obstacle. This could affect the performance of the unit and create loud noises.

Piping

1.Piping length should be 1m or more in order to decrease vibration propagated from the outdoor unit.

2.If piping length exceeds 10m, add 20g of refrigerant per 1m.

3.When the outdoor unit is placed at a higher level than the indoor units, provide a trap near the hose’s lead-in port.

1

A

B

B

2

3

A)Max. piping length 15m

B)Max. level difference 7m

1Indoor unit

2Outdoor unit

3Trap

AEG-Electrolux EXH09HX1WI User Manual

4 electrolux

Locations of indoor and outdoor unit

min. 50

min. 50

min. 50

 

 

min. 70

 

4

min. 50

min. 100

min. 200

min. 200

Length unit: mm

Provide as much installation space as possible for efficient functioning.

Notes on drain hose

The drain hose can be connected at either side of the indoor unit.

The unit has been shipped with the drain hose connected at left (viewed from the back of the unit) and the drain cap applied at right.

2

1

4. Reconnect the drain hose to the right and insert the drain cap to the left.

Fully insert the drain hose until it stops and use the screw that was previously removed in STEP (1) to secure the hose holder to the drain pan.

Insert a hexagon socket screw key (4mm diagonal) into the drain cap, and press it fully.

1 1 2

3

2

3

4

4

3

 

4

5

 

 

4

1Screw

2Hose holder

3Drain hose

4Drain cap

5Hexagon socket screw key

Caution! After replacing, make sure that both the drain hose and drain cap are firmly inserted.

Outdoor unit mounting screw holes

1

Drain hose

540

2

Drain cap

 

Reposition the drain hose and drain cap as

 

required.

 

1.

Remove the fixed screw in the hose

 

 

holder at the end of the drain hose.

 

2.

Hold the end of the drain hose, and pull it

 

 

out.

 

3.

Pull out the drain cap.

 

299

Opening/closing open panel

To open, hold the left and right bottom corners of the panel and lift it up.

electrolux 5

Placing the mounting plate and making a tube hole

Important! Fix the mounting plate horizontally.

To close, press-fit the arrow-marked points.

Detaching the front panel

For servicing, for example, detach the front panel in the following steps. Be sure to disconnect the power cord from the wall outlet or turn off the circuit breaker.

1.Remove the air filter.

2.Unscrew the 2 screws of the front panel.

3.Open the vertical adjustment louver by hand.

4.Remove the front panel.

Slightly open the lower part of the front panel, and extract the 5 hooks along the upper surface for disassembly.

5.To set the panel back into position, press-fit it at the bottom first and then press its top.

3 4

 

1

 

2

1

3

2

 

1Screw

2Vertical adjustment louver

3Air filter

5

860

 

 

 

4

175

 

125

 

 

I

 

J

 

 

 

 

30

E

 

 

 

E

 

 

D

 

 

 

 

I

 

J

292

5

D

 

 

F

 

A

 

 

 

 

45

 

 

115

 

108

 

 

 

 

 

 

F

 

 

 

 

1

2

A3

 

 

1.Referring to the figure above, mark the location for the wall plugs and the tube hole.

Length unit: mm

1Center of wall hole: Leftward piping.

2Outline of indoor unit

3Center of wall hole: Backward piping

4Ceiling

5unit size

2.Drill diameter 6.5mm, depth 32mm holes and fit the wall plug.

6,5 mm

32 mm

2

3.Secure mounting plate and check the stiffness. Refer to figure at right for fixing hole locations on mounting plate. Fix mounting plate to wall at 7 points. Recommended fixing holes are marked in circle around the hole.

6 electrolux

2

1

3

4. Drill a piping hole with 70mm diameter concrete drill or a hole saw with a 5mm down ward slant to the outside.

1 2

3 4

5 mm

5

1Indoor

2Outdoor

3Cut with a saw

4Cap (Downward to outdoor)

5Sleeve

5.Set the sleeve and caps.

Setting up the indoor unit

Piping route

For directions 1 and 3, cut out the specific zone without leaving any sharp edge. (Keep the cut-out plate for possible future use.)

3

1 2

3

2

1

1Cut the plate along notch

2Cut-out

3Notch

Mounting the indoor unit

If the wall is 250 mm or thicker, connect the pipes first.

1.For rear exit piping, pass the auxiliary pipe and the drain hose through the piping hole, and hook the unit onto the mounting plate.

2.Push the unit and apply the bottom hooking points to the mounting plate's support. (Take this step after cabling between the indoor and outdoor units.)

3.Pull the bottom of the unit to check that the unit is fixed in place.

1

1

1 Taping

Detaching the unit from the mounting plate

Push the “ “ marks at the bottom of the indoor unit and pull the bottom of the unit. When the hooks are released from the mounting plate, support the bottom of the unit and lift the unit upwards.

Horizontal Piping

1.Reverse the positions of the drain hose and drain cap. Refer to Notes on drain hose.

2

1

1Drain cap

2Drain hose

2.Connect the pipes and coil tape around the pipes and electrical cable.

electrolux 7

1

 

2

1Unit

2Piping holder

3.Store the pipes within the back cavity of the unit, and secure the pipes by attaching the piping holder. (Refer to steps a) and b) as shown below.)

a)Insert the top of the piping holder into the square opening.

4

3

2

1

1Unit

2Tape

3Piping holder

4Insert

b)Hook the bottom of piping holder to the unit.

8 electrolux

2

1

1Unit

2Hook

4.Coil tape around the drain hose together with the pipes and electrical cable.

5.Hook the unit onto the mounting plate.

Connecting the electrical cable to the indoor unit

1.Process the end of the electrical cable for the indoor side.

Use a copper cable. (Cross-section area 2mm² or more)

Use a cable which is not lighter than polychloroprene sheathed flexible cord (design 245 IEC 57).

40mm

8mm

3

N 1 2

 

1

 

8

7

2

 

1Earth wire

2Electrical cable

3Terminal board

4.Fix the cable with the accompanying cord holder and the short screw.

5.Close the open panel.

Connecting the drain hose

Indoor unit

1.Connect a drain hose.

2.Tape over the connecting part.

ø 18mm

1

1 Drain hose

2.Open the open panel by about 70°.

3.Connect the electrical cable.

Be very careful not to confuse the terminal connections. Wrong cabling may damage the internal control circuit.

The markings on the indoor unit’s terminal board must match with those of the outdoor unit.

Be sure to lay the drain hose downward for smooth drainflow.

2 1

1No trap allowed

2Not to rise

Be careful not to allow the drain hose to rise, form a trap or leave its end in water, as shown below.

electrolux 9

on a high-rise building, for example. For this purpose, employ a "T tube joint" (PVCmade, commercially available) halfway in the hose.

2

1

1

2

3

1Not running wavy

2No trap allowed

3Not left in water

Coil thermal insulation around a drain hose extension, if running in the room.

It is recommended to add an "intermediate air vent" when the drain hose is extended horizontally, or an "anti-back-flow air vent" when the hose is exposed to high winds

Flare nut tightening torque

 

Tube size

Liquid side

 

1/4"

Gas side

 

3/8"

 

 

 

Flaring the pipe end

1.Cutting with a pipe cutter Cut at a right angle.

1To drainage pit

2Air vent (T tube joint)

Connecting the refrigerant pipes

Use pipes with thickness 0.8mm.

Connect the pipes for the indoor unit first and then for the outdoor unit.

Bend the pipes carefully as not to damage them.

Do not over tighten the tubes; it may be deformed or damaged.

Use a torque wrench, when possible. See the table below for the flare nut tightening torque.

Torque

16±2N·m (1.6±0.2kgf·m)

38±4N·m (3.8±0.4kgf·m)

Allow no cuttings in the pipe.

3.Putting in the flare nut

4.Flaring

Flare processing dimensions (A) differ according to the type of flare tool.

2. Deburring

10 electrolux

A

R410A tool: 0-0.5mm

Conventional tool: 1.0-1.5mm

5.Checking

To be flared perfectly circular. Flare nut not missing.

Connecting the pipes

1.Tighten the flare nuts by hand for the first 3-4 turns.

2.Use two wrenches to tighten up the pipes.

2

1Flare body

2Flare nut

3.Wind coating tape around refrigerant pipes together with drain hose and electrical cable for general.

1Coating tape

Lay the drain hose below the pipes.

The thermal insulation should cover both the GAS and LIQUID pipes as

shown below. As insulation, use polyethylene foam 6 mm or thicker.

2

5

3

4

1Gas

2Insulation

3Liquid

4Drain hose

5Electrical cable

OK

OK

OK

1

1

1

2

2

2

3

3

3

1Gas

2Liquid

3Insulation

Air removal

Use an adapter for preventing vacuum pump oil from flowing back to the gauge manifold hose.

ON/OFF operation of the vacuum pump should be made by the adapter switch.

1.Remove both valve shaft caps of the 2 and 3-way valves.

2.Remove the service port cap of the 3- way valve.

3.Connect the gauge manifold hose to the service port and the vacuum pump.

Be sure that the hose end to be connected to the service port has a valve core pusher.

4.Open the gauge manifold valve and operate the vacuum pump for 10-15 minutes.

Make sure the compound gauge reads -76cmHg.

5.Close the gauge manifold valve.

6.Turn off the vacuum pump.

7.Fully open the 2-way valve with hexagon socket screw key. (diagonally 4 mm) Turn all the way up to contact.

8.Fully open the 3-way valve with hexagon socket screw key. Turn all the way up to contact.

9.Disconnect the gauge manifold hose from the service port.

10.Replace the service port cap and both

valve shaft caps tightly.

Use a gauge manifold and hoses exclusive for R410A.

After air removal, check the tube connections for gas leak using a leakage detector or soapy water. Regarding leakage detector, use high-sensitivity type designed specially for R410A.

 

11

 

3

 

2

7

3

1

9

 

1

 

10

 

1

 

10

electrolux 11

1Valve shaft cap

2Hexagon socket screw key

32 - way valve

4Service port cap

5Vacuum pump

6Vacuum pump adapter

7Gauge manifold

8Compound gauge

9Valve shaft cap

103 - way valve

11Indoor unit

10

7

8

8

Lo Hi

9

4

1

10

5

 

 

 

 

 

6

4

 

5 4

 

 

 

 

6

Valve shaft cap tightening torque

 

Pipe size

 

Width

Torque

Liquid side

 

1/4"

 

22mm

24±3N·m (2.4

 

 

 

 

 

±0.3kgf·m)

Gas side

 

3/8"

 

22mm

24±3N·m (2.4

 

 

 

 

 

±0.3kgf·m)

Service port cap tightening torque

Torque

11±1N·m (1.1±0.1kgf·m)

Pump down

(Pump down is adopted in the case of unit removal for re-installation, abandonment, repair etc.)

Pump down is to collect the refrigerant into the outdoor unit by control of the 2 and 3- way valves and the compressor.

1.Stop the Heatpump operation.

2.Remove both valve shaft caps of the 2 and 3-way valves.

3.Run the Heatpump at cooling test run mode (Refer to TEST RUN). If pump down is performed at normal cooling operation, the protection system may engage and stop the operation.

4.After 5~10 minutes, fully close the 2-way valve by turning the hexagon socket screw key clockwise.

5.After 2~3 minutes, immediately close the 3-way valve fully.

12 electrolux

6.Stop the test run operation.

7.Replace both valve shaft caps tightly.

8.Disconnect both refrigerant pipes.

Do not perform the pump down when at heating mode. The refrigerant will not be collected.

Connecting the electrical cable to the outdoor unit

1.Process the end of the electrical cable for the outdoor unit.

40mm

8mm

2.Remove the control box cover.

3.Remove the cable holder and connect the cable.

Be sure that the terminal connections are as specified.

4.Fix the electrical cable sheath with the cable holder and the screw.

5.Double-check that the cable is securely in place.

6.Place the control box cover back in the reverse order.

1

N 1 2

2

 

3

6

4

1Earth wire

2Terminal board

3Cable holder

4Electrical cable

5Control box cover

6Screw

Caution!

Use the specified electrical cable. Make sure the cable is secured in place and that the terminals are free of any excess force from the cable. Otherwise overheating or fire may result.

Dress the cable so that the control box cover, the cord holder and cable holder are not loose. Double-check that the cover is tight in position. Otherwise overheating, fire or electric shock may result.

Be sure to put the cable leads deep into the terminal board and tighten up the screws. Poor contact can cause overheating or fire, or malfunction.

Power cabling

Prepare a dedicated power supply circuit. For the connections, see below.

Supply power

220-240V, single-phase

Circuit breaker

10A (EXH09HX1WI)

 

15A (EXH12HX1WI)

 

 

1A

2B

3 C

 

 

electrolux 13

 

 

 

 

Power supply cable

Power supply

A

Blue

Neutral

B

Brown

Live

C

Green/yellow-striped

Ground

 

 

 

The appliance shall be installed in accordance with national wiring regulations. Wrong connection can cause overheating or fire.

Fit a disconnect switch, having a contact separation of at least 3mm in all poles, to the electricity power line.

Earth leakage breaker

Provide an earth leakage breaker in order to protect against electric shock in case of leak.

Use the current-activated, high-sensitivity, high-speed type breaker with a rated sensitivity current of below 30 mA and an operating time of below 0.1 second.

Hanging the remote control

1.Fit the special screw to the wall with the wall plug.

2.Hang the remote control to the screw head.

1.Open the cover.

2.Insert the batteries.

3.Close the cover.

If after battery replacement the control fails to function, take out the batteries. Wait for more than 30 seconds and put them in again.

Test run

1.Open the open panel to see the control section.

2.Start the operation with the remote control.

3.Press the “AUX” button on the unit for 5 seconds or more.

2 6

1

1 Remote control rear side

Loading the batteries

Slide the cover in the direction of the arrow.

A beep sound is heard and the OPERATION lamp starts flashing. Now the system is in the cooling test run mode.

4. To put the system in the heating test run mode, start the cooling operation and select the heating mode on the remote control.

14 electrolux

5.Make sure the system runs well, and press the AUX button again to stop the operation.

Explanation to Customer

Explain to the customer how to use and maintain the system, referring to the operation manual.

Ask the customer to carefully read the operation manual.

When the system has been set up, hand the installation manual to the customer.

Important! Important points to explain

Whipping sound :

The system adjusts itself, by expansion or shrinkage, according to great temperature fluctuations.

Running liquid sound :

The refrigerant runs in the system, generating such sound. (For details, refer to the accompanying operation manual.)

electrolux 15

Varmepumpe

Vigtigt Læs denne vejledning grundigt. Den sikrer, at installationen forløber glat og uden problemer.

Tilbehør

Bemærk Denne varmepumpe til rumopvarmning anvender et nyt kølemiddel, R410A.

1.Evt. åbne slangeender skal proppes til, indtil de sluttes til enheden.

2.Vær meget omhyggelig, når rørføringen udføres, så der ikke kommer vand, støv og lign. ind i rør og anlæg.

3.Der skal anvendes nye rør til tilslutningerne på udeog indeenheden. (Da varmepumpen bruger R410A som kølemiddel, udsættes den for højere driftstryk end med R22, og det skal der tages højde for ved materialevalget).

4.Brug kun R410A-kølemiddel, når der efterfyldes kølemiddel på anlægget. Smør aldrig anlægget med smøreolie.

5.Diameteren på 3-vejsventilens driftsindgang er ændret for at sikre, at der ikke utilsigtet kan påfyldes et andet kølemiddel. (1/2" UNF-skrue)

 

Betegnelse

Antal

Anvendelse

1

Monteringsplade

1

Til vægmontering af indeenhed.

2

Rawlplug

8

Til fastgørelse af monteringspladen med de lange skruer.

 

 

 

Til fastgørelse af fjernbetjening med specialskrue.

3

Lang skrue

7

Til fastgørelse af monteringspladen med rawlpluggene.

4

Fjernbetjening

1

Til fjernstyret betjening.

5

Batteri

2

Til fjernbetjeningen. AAA-batterier.

6

Specialskrue

1

Til vægmontering af fjernbetjening.

7 Kort skrue

1

Til fastgørelse af KABELKLEMME.

16 electrolux

 

 

 

Betegnelse

Antal

8

Kabelklemme

1

9

Vejledninger

1

INSTALL

OPER

 

 

 

 

1

10 Luftrensningsfilter

2

Anvendelse

Til fastgørelse af netkablet.

Installationsvejledning

Betjeningsvejledning

Til at fjerne støv og tobak fra luften.

Bemærkninger om placering

Vigtigt Husk på følgende, og spørg kunden om lov.

Indeenhed

1.Hold luftudblæsningen fri for forhindringer, så den udgående luft uhindret kan sendes rundt i hele rummet.

2.Lav et hul til afløbsslange, for nem aftapning.

3.Sørg for, at der er god plads på begge sider og over enheden.

4.Det skal være let at komme til at tage luftfiltrene ud og sætte dem i.

5.Hold tv-apparat, radio og lign. mindst 1 meter fra enheden og fjernbetjeningen.

6.Sørg for, at der ikke står noget i vejen for luftindsugningen, så indtaget blokeres.

7.Hvis der findes lamper med fluorescerende lys i rummet, virker fjernbetjeningen muligvis ikke, som den skal.

8.Vælg en placering, der ikke giver kraftige støjgener og vibrationer under drift.

Udeenhed

1.Sæt udeenheden på et stabilt underlag.

2.Sørg for god plads rundt om enheden. Der skal også være god lufttilførsel.

3.Enheden må ikke udsættes for kraftig blæst eller sprøjt fra regnvand.

4.Det skal være let at komme til enhedens vandafløb. Læg evt. en afløbsslange. I kolde egne frarådes det at installere et afløbsrør, da det vil kunne fryse til.

5.Hold en afstand på mindst 1 meter til tvapparat, radio og lign.

6.Undgå placeringer, hvor enheden udsættes for dampe fra motorolie, saltholdig luft (f.eks. ved kysten), svovlgas fra varme kilder og lign. På sådanne placeringer kan enheden bryde sammen.

7.Undgå også placeringer, hvor enheden udsættes for mudret vand (f.eks. langs en vej), eller hvor nogen kan komme til at pille ved den.

8.Vælg en placering, hvor udblæsningsluft eller driftsstøj ikke kan genere naboer.

9.Installer enheden på et stabilt underlag, der ikke forstærker støjen.

10.Hold luftudblæsningen fri for forhindringer af enhver art. De vil kunne påvirke enhedens ydelse og give kraftig støj.

Rørføring

1.Rørlængden skal mindst være 1 meter for at mindske de vibrationer, der forplanter sig fra udeenheden.

2.Hvis rørlængden er over 10 meter, tilsættes 20 g kølemiddel pr. løbende meter.

3.Hvis udeenheden placeres højere end indeenhederne, skal der være en vandlås tæt ved slangens indføringsåbning.

1

A

B

B

2

3

A)Maks. rørlængde: 15 meter

B)Maks. niveauforskel: 7 meter

1Indeenhed

2Udeenhed

3Vandlås

Placering af indeog udeenhed

min. 50

min. 50

min. 50

 

 

min. 70

 

4

min. 50

min. 100

min. 200

min. 200

Længdeenhed: mm

Sørg for at give installationen så meget plads som muligt for at sikre effektiv funktion.

Bemærkninger om afløbsslange

Afløbsslangen kan tilsluttes på begge sider af indeenheden.

Enheden leveres med afløbsslangen tilsluttet til venstre (set fra enhedens bagside) og med afløbsproppen til højre.

2

1

1Afløbsslange

2Afløbsprop

Omplacér afløbsslange og afløbsprop, hvis det er nødvendigt.

1.Fjern den faste skrue i slangeholderen i enden af afløbsslangen.

2.Hold fast i enden af afløbsslangen, og træk den ud.

3.Træk afløbsproppen ud.

electrolux 17

4. Tilslut afløbsslangen til højre, og sæt afløbsproppen i på venstre side.

Sæt afløbsslangen så langt ind, som den kan komme, og spænd slangeholderen fast på bundkarret med den skrue, der blev taget ud under TRIN (1).

Sæt en unbrakonøgle (4 mm diameter) i afløbsproppen, og tryk den helt ind.

1 1 2

3

2

3

4

4

3

 

4

5

 

 

4

1Skrue

2Slangeholder

3Afløbsslange

4Afløbsprop

5Unbrakonøgle

Bemærk Kontroller efter montering af afløbsslange og afløbsprop, at de sidder helt fast.

Skruehuller til montering af udeenhed

540

299

18 electrolux

Åbne/lukke adgangspanel

Panelet åbnes ved at holde i nederste højre og venstre hjørne og løfte det op.

Placering af monteringsplade og hul til rørføring

Vigtigt Fastgør monteringspladen vandret.

Panelet lukkes ved at trykke det på plads på de steder, der er markeret med pile.

 

5

 

 

860

 

175

 

125

I

 

J

 

 

E

 

D

 

I

 

J

 

D

 

F

 

A

115

 

108

 

 

F

 

 

1

2

A3

45 30

E

292

4

5

Aftagning af frontpanel

Til service og lign. afmonteres frontpanelet som beskrevet nedenfor. Sørg for at tage stikket ud af kontakten eller afbryde på ejendommens el-tavle.

1.Fjern luftfilteret.

2.Skru de 2 skruer i frontpanelet ud.

3.Åbn med hånden spjældet til lodret justering.

4.Fjern frontpanelet.

Åbn frontpanelets nederste kant lidt, og træk de 5 kroge langs overkanten ud, så panelet kan tages af.

5.Panelet monteres igen ved at først at trykke det på plads langs underkanten og derefter trykke foroven.

3 4

 

1

 

2

1

3

2

 

1Skrue

2Spjæld til lodret justering

3Luftfilter

1.Markér placeringen af rawlpluggene og hullet til rørføringen som vist på ovenstående tegning.

Længdeenhed: mm

1Centrum, hul i væg: Rørføring til venstre.

2Omrids, indeenhed

3Centrum, hul i væg: Rørføring bagud

4Maks.

5enhedens størrelse

2.Bordiameter 6,5 mm, 32 mm dybe huller. Sæt rawlplugs i.

6,5 mm

32 mm

2

3.Spænd monteringspladen fast, og mærk efter, at den ikke giver sig. Hullernes placering på monteringspladen er vist på tegningen til højre. Fastgør monteringspladen i væggen i 7 punkter. Anbefalede monteringshuller er markeret med en cirkel om hullet.

electrolux 19

2

1

3

4. Bor hul til rørgennemføring med et 70 mm murbor eller en hulsav, med 5 mm fald mod ydersiden.

1 2

3 4

5 mm

5

1Inde

2Ude

3Skær til med sav

4Prop (med fald udefter)

5Muffe

5.Påsæt muffe og propper.

Opsætning af indeenhed

Rørføring

Til retningerne 1 og 3 udskæres det pågældende område uden skarpe kanter. (Gem det afskårne stykke til evt. senere brug).

3

1 2

3

2

1

1Skær pladen langs rillen

2Afskæring

3Rille

Montering af indeenhed

Hvis væggen er 250 mm tyk eller derover, tilsluttes rørene først.

1.Ved afgang bagtil sættes forlængerrøret og afløbsslangen gennem rørgennemføringen, og enheden hægtes på monteringspladen.

2.Tryk på enheden, og sæt den fast på monteringspladen ved at klemme den ind over krogene nederst på monteringspladen. (Det gøres først, når ledningsføringen mellem indeog udeenhed er færdig).

3.Træk i underkanten af enheden for at sikre, at den sidder helt fast.

20 electrolux

1

1

1 Bevikling

Afmontering af enhed fra monteringspladen

Tryk på " "-markeringerne nederst på indeenheden, og træk i enhedens underkant. Når krogene slipper monteringspladen, understøttes enheden nedefra og løftes opad.

Vandret rørføring

1.Byt om på placeringen af afløbsslange og afløbsprop. Se under Bemærkninger til afløbsslange.

2

1

1Afløbsprop

2Afløbsslange

2.Tilslut rørene, og vikl tape rundt om rørene og elkablet.

1

 

2

1Enhed

2Rørholder

3.Gem rørene i hulrummet bag i enheden, og sæt dem fast med rørholderen. (Se trin

a)og b) nedenfor).

a)Sæt toppen af rørholderen ind i det firkantede hul.

4

3

2

1

1Enhed

2Tape

3Rørholder

4Hul

b)Hægt nederste ende i underkanten af enheden.

Loading...
+ 48 hidden pages