3D Connexion mD4000-b User Manual

INSTALLATION INSTRUCTIONS
MD4000 SERIES SOLID STATE
DUAL UNIT LEAD/LAG CONTROLLER
for use with H-Series
Wall Mount Air Conditioners
with F & G Spyder™ Economizers only
Bard Manufacturing Company, Inc. Bryan, Ohio 43506
Since 1914...Moving ahead, just as planned.
Manual No.: 2100-574 Supersedes: NEW File: Vol. III Tab 19 Date: 07-05-12
Manual 2100-574 Page 1 of 23
CONTENTS
Getting Other Information and publications 3 MD4000 General Information
Shipping Damage....................................................4
General ...................................................................4
Theory of Operation ................................................4
 ControllerCertications ...........................................4
Specications/Features for MD4000 Series Controller
MD4000 Controller ..................................................5
Mounting the Controller
Installation Instructions............................................5
Temperature Sensors
Two Optional Sensor Inputs ....................................5
Temperature Sensor Logic
Using Multiple Sensors ...........................................5
Basic MD4000 Controller Input/Output Specs.
MD4000 Controller Connections .............................6
Located in the MD4000 panel Box
Unit #1 & Unit #2 Terminal Block .............................6
Specications/Features for Alarm Boards
MD4000-B & -BC w/Controller Alarms ....................7
Low Voltage Field Wiring
Circuitry in the MD4000...........................................7
Controller Grounding
Earth ground ...........................................................7
Controller power-Up
Time Delay on Power-Up ........................................7
Fire Suppression Circuit
Disabling the MD4000 .............................................8
Staging Delay periods
Stages 1 - 4 .............................................................8
Blower Operation
Various Blower Options ...........................................8
Advance (Swap) Lead/Lag Unit Feature
Manual Switching of Units .......................................8
Accelerate Timer Feature
Testing the Timer Function ......................................8
General programming Overview
Buttons & Function ..................................................9
Heating Sequence of Operation ............................10
Specications Opt. Remote Comm. Board
CB4000 Communications Board ......................11-12
Controller Wiring
Refer to Connection Diagram................................13
Security (Locking) Feature
Locking and Unlocking the MD4000 .....................13
Generator Run / Economizer Shutdown Feature
Standby Generator Disable Operation ..................13
Backup DC power Connection
Input Connections Available ..................................13
Economizer Failure Alarm .....................................16
Dirty Filter Alarm ....................................................16
2-Compressor Run Alarm ......................................16
Alarm Wiring ...........................................................16
2nd Stage Cooling Alarm .......................................17
Refrigerant pressure Alarms .................................17
Spyder Economizer Displays ................................17
Emergency Ventilation Sequence .........................17
programming Instructions .....................................20
Figures
— — — MD4000 Flow Chart ................................10
Figure 1 Controller Connections 1-Stage (H**A/L ....
Series) A/C w/ECONWMT Econ. .............14
Figure 2 Controller Connections 1-Stage (H**A/L ... Series) A/C w/ ECONWMT Econ. & w/Alarm
Board & CB4000 Comm. Board .............15
— — — Alarm LED Display Board ........................16
Figure 3 Alarm Board Connections for Normally ......
Closed "NC" Open-On-Alarm Strategy ....18
Figure 4 Alarm Board Connections for Normally Open
"NO" Close-On-Alarm Strategy ................................19
— — — MD4000 Label .........................................21
Figure 5 Parts List Description Diagram ................22
Tables
Controller Prog. Features & Defaults ........9
Table 1 Hook-Up Diagram Selection ....................14
Table Parts List .................................................23
Manual 2100-574 Page 2 of 23
Getting Other Information and Publications
These publications can help you install the air
conditioner or heat pump. You can usually nd these
at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
Standard for the Installation ............... ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air Heating .........ANSI/NFPA 90B
and Air Conditioning Systems
FOr mOre InFOrmatIOn, cOntact these PublIshers:
ACCA Air Conditioning Contractors of America 1712 New Hampshire Avenue, NW Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
ANSI American National Standards Institute 11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
ASHRAE American Society of Heating, Refrigerating, and Air Conditioning Engineers, Inc. 1791 Tullie Circle, N.E.
Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
BARD Bard Manufacturing Company, Inc. 1914 Randolph Drive
Bryan, OH 43506 Telephone: (419) 636-1194 Fax: (419) 636-2640
Manual 2100-574 Page 3 of 23
** ImPOrtant **
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians. Please read entire manual before proceeding.
shIPPInG DamaGe
The MD4000 is equipped with the B alarm board. Form C dry contact alarm relays are used, offering
both NO and NC switching to meet the user’s specic alarm protocol, providing complete exibility to meet
any user's requirements. All alarm actuations are individually indicated on the controller front panel.
There is an Ethernet based remote communication
option that can be either factory or eld installed. See
section on Communication Module.
Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
General
These instructions explain the operation, installation and troubleshooting of the MD4000 Series controller.
All internal wiring is complete. Only attach low
voltage eld wiring to designated terminal strips.
The MD4000 is for use with units with economizers. Each unit should be sized to handle the total load of the
structure if 100% redundancy is required. The MD4000 controller is suitable for both 50 and 60
HZ operation. See Controller Programmable Features and Default Settings.
theOrY OF OPeratIOn
The controller is used to control two wall mount air conditioners from one control system. It provides total redundancy for the structure and equal wear on both units. It must be used with units with economizers and both units be equipped alike.
cOntrOller certIFIcatIOns
The MD4000 main controller board, alarm board, optional communication module, and remote sensors have undergone extensive testing for immunity and emissions. This system is FCC-compliant, in accordance with CE requirements, and meets the following standards:
MD4000 Series
Master Controller
This device complies with FCC Rule Part 15, Subpart B, Class A. Operation is subject to the following two conditions:
1. This device may not cause harmful interference
2. This device must accept any interference received, including that which may cause undesired operation.
This device complies with CE Standards EN55011/ EN50081 and EN55024 for ISM Equipment, Class A.
This ISM device also complies with Canadian ICES – 001.
Bard Manufacturing Company, Inc.
Bryan, OH 43506
The MD4000 controller is congured for alternative
(lead/lag/lead/lag) sequence, which is default setting. The MD4000 works in conjunction with the Economizer
Logic Modules to provide room temperature control based on the DC amp load that the building is using.
The Economizer Logic Modules, in the air conditioner, control the cooling stages and functions. The MD4000 controls the heating stages, lead lag operation and alarming operation for the system.
Manual 2100-574 Page 4 of 23
sPecIFIcatIOns/Features FOr mD4000-b cOntrOller
MD4000 Basic Controller
•Input power: 18-32 VAC, 60/50Hz, power is supplied from
A/C #1 and/or A/C #2
•Isolation circuitry: no line or low voltage phasing required
•Backup power: connection for -24 VDC or -48 VDC (-20 to
-56V) maintains microprocessor operation, front panel indication & alarm relay operation during commercial power outages.
•Digital display: 4-character LCD
•Temperature display: F or C
•HVAC outputs: Form A (NO) relays (1A @ 24 VAC)
•Cooling control stages:
2 for each A/C unit (4 total)
•Heating Control stages:
1 for each A/C unit
•Operating temperature range: 0 to 120F (-18 to 49C)
•Storage temperature range: -20 to 140F (-29 to 60C)
•Temperature accuracy: +/- 1F from 60-85F (16-30C) +/- 1% outside 60-85F
•Lead/lag changeover time: 0 to 30 days
•Timing accuracy: +/- 1%
•Inter-stage time delay: 10 seconds between stages
•On-Off differential: 2F (1C) is standard, 4F (3C) when
“excessive cycling” mode is enabled
•Comfort setting, Heating 68F(20C), for 1 hour
•Dead band (difference between cooling and heating set
points): 2F to 40F (1.1C to 22.2C)
•Fire/smoke interface: standard NC circuit jumper, remove
for connection to building system control, shuts down both A/C units immediately
•Memory: EEPROM for set point and changeable
parameters (maintains settings on power loss)
•Space temperature sensors: 1 local is standard, will accept up
to 2 optional 25' remote sensors, Bard part number 8612-023. When multiple sensors are used, temperatures are averaged
•Controller Enclosure: 20-gauge pre-painted steel, 9.25"W x 20.875"H x 3.00"D, hinged cover, twenty four (24) .875"
diameter electrical knockouts
•LEDs for basic controller: Lead unit, Heating Stages 1 – 4
•Six (6) Push-button controls: On/Off switch-Change lead
unit-Increase & Decrease set points-Program/Save-Comfort.
mOuntInG the cOntrOller
Included in the controller carton is the controller and installation instructions.
The controller should be installed on a vertical wall
approximately four (4) feet above the oor-away from drafts &
outside doors or windows. Four (4) mounting holes are provided
for mounting to the wall and 7/8" holes for conduit connections
are provided in both the base, sides & top of the controller.
If the differential is greater than 12F then the controller will check to determine the on-board sensor is reading a temperature that is between the SP (set-point) plus 12F and the SP minus the DB (dead-band) minus 12F. If it is the on-board sensor will become the valid sensor reading and the controller will ignore the local sensor reading. If it is not then the controller will still use the local sensor reading. This is to add additional level of operational capability in the rare event the local sensor fails. If the controller is operating in this mode it is indicated by the
lower left decimal point ashing in the display. Note: for purposes of testing when the local sensor is manually driven higher or lower by applying warm or cool water
to the probe the on-board sensor is inhibited for the rst
30-minutes following power up, or when power is cycled off and back on.
The controller is designed to accept 1 or 2 additional sensors and those have 25-foot leads. The Bard part number for the optional sensor with 25-foot leads is 8612-023. These can be installed as required in the
structure to address hot spots, barriers to airow, etc.
It is recommended that the sensor lead wires be installed in conduit for protective purposes.
The highest reading of any connected sensor will be used for high temperature alarm and the lowest reading sensor will be used for low temperature alarm.
Note: All sensors are polarity sensitive. the copper lead must connect to terminal CU, and the silver lead to AG. Sensors are solid state, not RtD. Use only sensors supplied by Bard. Sensor leads can be extended up to 200 feet. Use 18-gauge twisted pair with soldered connections.
temPerature sensOr lOGIc
The standard local (LSEn) sensor monitors the temperature at the controller location. If this is the only sensor connected, it will control the temperature read-out, the space (building) temperature, and also be used for Low and High Temperature alarm functions.
If one or more REMOtE sensors are installed and connected (Rem 1 or Rem 2), the temperature read-out will display and the building will be controlled to an average of all connected sensors. If there is more than 10F difference from the highest to the lowest connected sensor, the actual control will be governed by the hottest sensor for cooling and the coldest sensor for heating.
If multiple temperature sensors are used, the High and Low temperature alarms will be governed by the average of the connected sensors.
temPerature sensOrs
The standard (local) temperature sensor has 12" leads and
comes installed from the factory. A secondary sensor is located internally on the main
controller board and serves as a reference and back-up
sensor to the local sensor. Any differential of +/- 12F
between the on-board and local sensor will cause the controller to use the local sensor as its point of reference.
Manual 2100-574 Page 5 of 23
basIc mD4000 cOntrOller InPut/OutPut sPecIFIcatIOns
mD4000 cOntrOller cOnnectIOns
Located on Main Controller Board
Unit #1 C – 24VAC common
R – 24VAC hot G – fan (Form A, NO) W – heat (Form A, NO) Unit #2 C – 24VAC common R – 24VAC hot G – fan (Form A, NO) W – heat (Form A, NO) F1-F2 Fire/smoke interface Shipped with jumper installed (a) 48Vdc Back-up power input
-24Vdc or –48Vdc
-20V to –56V range Local Main sensor, 12-inch leads CU – copper, AG – silver Polarity sensitive Rem 1 Optional remote indoor sensor CU – copper, AG – silver Polarity sensitive Rem 2 Optional remote indoor sensor CU – copper, AG – silver Polarity sensitive H1-H2 Humidity controller input Requires optional controller Field installed Advance Input used to remotely toggle lead/lag change
(a) These connections require either jumper or Normally Closed (NC) relay contact at the Fire/Smoke and Generator interface for Controller to function.
Note: All alarm and output relays are dry contacts rated
1A @ 24 VAC.
Note: All alarm relay outputs have 10-second delay before issuing to protect against nuisance alarm signals.
NOTE:
Sensors are
solid state,
not RTD.
Use Bard
sensors only.
lOcateD In the mD4000 Panel bOx
Unit #1 terminal Block
R – 24VAC hot from Unit C – 24VAC common from Unit Y – Compressor Signal to Unit F – A – Compressor Signal from Economizer 4 – Dirty Filter Alarm from Unit 5 – Dirty Filter Alarm from Unit 6 – Signal Common for F 8 – Economizer Fail from Unit 9 – Economizer Fail from Unit 10 – Emergency Vent Output to Economizer 41 – To Unit 2, 43 42 – To Unit 2, 44 43 – To Unit 2, 41 44 – To Unit 2, 42 45 – To Unit 2, 45 DCA Input 46 – To Unit 2, 46 DCA Input 47 – To Unit 1 Display 48 – To Unit 1 Display
Unit #2 terminal Block R – 24VAC hot from Unit
C – 24VAC common from Unit Y – Compressor Signal to Unit F – A – Compressor Signal from Economizer 4 – Dirty Filter Alarm from Unit 5 – Dirty Filter Alarm from Unit 6 – Signal Common for F 8 – Economizer Fail from Unit 9 – Economizer Fail from Unit 10 – Emergency Vent Output to Economizer
41 – To Unit 1, 43
42 – To Unit 1, 44 43 – To Unit 1, 41 44 – To Unit 1, 42 45 – To Unit 1, 45 DCA Input 46 – To Unit 1, 46 DCA Input 47 – To Unit 2 Display
48 – To Unit 2 Display
Gen Run/Econ Shutdown terminal Block(a)
Economizer Fail terminal Block
Economizer Shutdown Output to Economizer
Economizer Shutdown Output to Economizer
Gen Run Input
Alarm Output
Alarm relays can be wired for NO (close on alarm) or NC (open on alarm) strategy. Alarm relays can be used individually if there are enough available building alarm points, or can be arranged into smaller groups or even a single group so that all alarm capabilities can be utilized. When multiple alarms are grouped together and issued as a single alarm there will be no
off-site indication of which specic problem may have occurred, only that one of the alarms in the group has been triggered.
The individual alarm problem will be displayed on the LED display on face of the controller.
Manual 2100-574 Page 6 of 23
sPecIFIcatIOns/Features FOr mD4000-b & -bc cOntrOller alarms
Inputs
Lockout 1 2, 3 – input from HVAC #1 Lockout 2 2, 3 – input from HVAC #2
Outputs
Smoke/Fire Form C (SPDT) Lockout 1 Form C (SPDT) Refrigerant alarm HVAC #1 Lockout 2 Form C (SPDT) Refrigerant alarm HVAC #2 Power Loss 1 Form C (SPDT) Power loss HVAC #1 Power Loss 2 Form C (SPDT) Power loss HVAC #2 Low Temp Form C (SPDT) Low temperature alarm High Temp 1 Form C (SPDT) High temperature alarm #1 High Temp 2 Form C (SPDT) High temperature alarm #2 Controller Form C (SPDT) Controller failure alarm Econ 1 E, F - Form A (NO) See note (b) Econ 2 E, F - Form A (NO) See note (b) 2nd Stage (c) Form C (SPDT) 2
(b) Make these connections to terminals E & F in HVAC 1 and 2 respectively if desired to have economizers open for emergency ventilation at High Temp Alarm #2 setpoint condition.
(c) For units with 2-stage compressors, 2nd stage cooling alarm activates on cooling Stage 3 initiation.
2nd Compressor Form A (NC) Dirty Filter Form A (NC)
4, 5 – Input from Unit Economizer Fail Form A (NC)
8, 9 – Input from Unit
nd
-stage cooling alarm
lOW vOltaGe FIelD WIrInG
The MD4000 is powered from the air conditioners that it is controlling, 24 VAC (18-32V) low voltage only.
Circuitry in the MD4000 isolates the power supplies of the two air conditioners so that no back feeds or phasing problems can occur. Additionally, if one air conditioner loses power, the MD4000 and the other air conditioner are unaffected and will continue to operate normally.
Connect the low voltage eld wiring from each unit per the low voltage eld wiring diagrams in Section on
“Controller Wiring”. NOTE: Maximum of 18-gauge control wiring should be used. Using heavier gauge wiring can create excessive stress on the control board as door is opened and closed. Create a wiring loop so the door can open and close without stressing terminal blocks.
cOntrOller GrOunDInG
A reliable earth ground must be connected in addition to any grounding from conduit. Grounding lugs are supplied for this purpose.
cOntrOller POWer-uP
Whenever power is rst applied to the controller, there
is a twenty (20) second time-delay prior to any function (other than display) becoming active. This time-delay is in effect if the controller On/Off button is used when 24VAC from air conditioners is present, and also if controller is in “ON” position and 24VAC from air conditioners is removed and then restored.
Manual 2100-574 Page 7 of 23
Loading...
+ 16 hidden pages