Zircon LC1, LC2 Installation & Operating Manual

LC1 & 2
Fire Alarm Panel
6\VWHPLQVWDOODWLRQRSHUDWLQJPDLQWHQDQFH
LQVWUXFWLRQV
ZIRCONLC1
One Zone Conventional Fire Panel
ZIRCONLC2
Two Zone Conventional Fire Panel
For Technical advice & Servicing contact -
+44 (0) 1268 56 3256
This publication is issued to provide outline information only and is not deemed to form part of any offer or contract
Our policy is one of continual improvement and we reserve the right to vary details without prior notice.
61640610 issue 5
INSTALLATION INFORMATION
General Installation of this product must be carried out using the information given in this leaflet by a qualified electrician.
BEFORE INSTALLATION ENSURE THE ELECTRICAL SUPPLY IS ISOLATED.
Installation of this product must be carried out using the methods and equipment specified in BS5839 Pt1 and EN54.
Consult the supplier if the equipment is to be installed in an environment where the ambient temperature regularly exceeds 30 ºC (86 ºF)
Mounting location considerations
The fire alarm control panel should be mounted near to a permanent, low fire risk, Entry / Exit, for easy access by the Emergency Services. The panel should not be mounted in direct sunlight, or in a place where the ambient temperature is above 30
o
C (86oF)
Mains must not be capable of being accidentally disconnected and the isolating switch should clearly state :
FIRE ALARM - DO NOT SWITCH OFF
Anti static precautions should be taken when installing the panel
FIGURE 1
-
Top cover removed for clarity
1 MOUNTING INSTRUCTIONS
1.1 In order to minimise the installation time, it is strongly recommended, that the following procedure is followed.
1.2 Remove plastic fascia by removing the two screws from the top plastic cover.
1.3 Disconnect the two secondary transformer wires from the terminals marked ‘AC~’ on the PCB. These are located on the right-hand side of the fire panel.
1.4 Remove the two screws that hold the bottom plastic cover in place, then lift away from fire panel housing. Store cover assembly in a safe place to prevent damage during initial installation. Note:
DO NOT REMOVE THE PCB FROM THE
PLASTIC MOULDING.
1.5 Using the back box as a Drill template, mark through fixing positions, prepare the fixing holes, and fit onto wall using an appropriate mounting system. Ensure the back box is not contaminated with drilling debris, e.g. brick dust, as this can adversely affect the electronic circuitry.
1.6 Prepare cable entries via the 20mm knockouts provided
in the top and rear of back box using appropriate glanding system.
1.7 Remove any debris from the back box.
2 CONNECTING THE MAINS & BATTERY
2.1 Connect mains wiring to terminal block in the back box as marked. Note: AN EARTH CONNECTION MUST BE MADE TO THE TERMINAL BLOCK AS MARKED.
2.2 With the mains supply isolated, replace the lower plastic cover assembly containing the PCB. Ensure the battery wires are routed to the top left-hand side of the back box and the transformer secondary wires are routed towards the right hand side. The PCB locating holes should engage on the metal mounting tabs shown in figure 2.
2.3 Reconnect the transformer secondary wires to the PCB terminals marked ‘AC’. Note: Polarisation of this connection is unimportant
2.4 Fit and tighten the two securing screws that hold the PCB moulding in place. Ensure that the moulding has properly engaged at the bottom of the metal back box. Do not over tighten two retaining screws.
2.5 Fit battery into left-hand side of the back box and connect battery using leads supplied. Ensure correct polarity is always observed.
The panel is now active and will indicate a ‘POWER FAULT’ and “GENERAL FAULT” until the mains supply is re-instated, and the panel ‘RESET’.
2.6 Instate the mains supply, enter access code then press the ‘RESET’ button.
2.7 Check panel is operating normally. The panel should only show the green “POWER ON” indicator.
2.8 You have now proved that the panel is free of faults.
3 EXTERNAL WIRING
-
DETECTOR ZONE CONNECTION
This fire alarm control panel is supplied with End Of Line Resistor/s for the zone circuit/s. This is for use with just manual call points (Break Glass) units, however if removable smoke/heat detectors are used the End Of Line Resistor/s must be replaced with Active End Of Line Device/s (ZF19). Please note these units are polarised.
3.1 DISCONNECT MAINS SUPPLY & BATTERY.
3.2 Connect the zone wiring, one zone at a time, transferring
either the End Of Line Resistor or Active End Of Line Device (ZF19), if removable smoke/heat detectors are being employed. The ZF19 devices are polarised and should be connected with Red/Orange wire to the +ve and Black to the –ve. See Figure 3 & 6 for typical application.
3.3 Repeat the above procedure until all the required circuits are connected.
3.4 Connect the sounder wiring one circuit at a time, transferring the end of line resistor to the last sounder on that circuit.
3.5 Repeat the above procedure until all the required sounder circuits are connected.
3.6 ReInstate the mains supply, enter access code then press the ‘RESET’ button.
3.7 Refit plastic fascia. Do not over tighten two retaining
screws.
BATTERY
CABLE ENTRY POINTS TOP & BOTTOM
PCB TERMINAL BLOCKS
TOP
COVER
FIXING
POINTS
METALWORK HOUSING
SECONDARY TRANSFORMER WIRES
BOTTOM
COVER
FIXING
POINTS
FIGURE 2a
- TERMINAL ARRANGEMENT
FIGURE 2b
- FAULT / FIRE AUXILIARY RELAY
GENERAL DESCRIPTION
Options included that are covered by EN54
Test Condition (10.0) Fire Alarm Devices (7.8)
Ancillary functions provided but not required by EN54
Class change Repeater
Accessories:
The panel is designed for use with CHLORIDE BARDIC ZF range of fire accessories.
TECHNICAL SPECIFICATIONS
Power Supply requirements
230Vac +10 - 15% 50Hz Maximum Power consumption 50VA Fuse rating - T125mA
The mains supply should be carefully wired using flat twin and earth of not less than 1mm
2
between the mains connector block and an externally mounted secure switched fused spur outlet with contact separation of at least 3mm. The switched spur unit should be fused with a 2A fuse.
Battery
24 Hour standby 1 x 12 V 2.6 Ah (minimum) Fuse rating - F1.6A
Weight
4.2 Kg (including 2.6 Ah battery & carton) approx.
Detection Circuits
No more than 30 devices of any type per zone. 20 smoke or heat detectors maximum per zone. 30 Call Points maximum per zone.
Alarm Sounder Circuits
300mA total through 2 circuits. Nominal Voltage 25.3V (+2.7V / -1V) Fuse rating - F315mA
Auxiliary 24V Supply
This is specifically not for fire protection devices. 50mA maximum. Nominal Voltage 25.3V (+2.7V / -1V) Fuse rating - F125mA
Auxiliary Relay
Volt free change over contacts rated at 1A 30VDC Fuse Rating 1A Note, the Auxiliary relay is configured as a fault relay, as standard (EN54 requirement), however the relay can be configured as an auxiliary fire relay, by moving a jumper link from the fault position to the fire position on the back of the PCB.
AUXILIARY REL AY
123
FAULT NC C NO
FIRE NO C NC
The N/C and N/O contacts change position, when the jumper is moved to the fire position.
Class Change
Activated by using volt free N/O contacts between the -ve of AUX 24V output and the CLASS CHANGE output. See Figure 5 for typical application.
Cabling
Unless otherwise recommended, and taking into account voltage drop, not less than 1mm
2
is recommended. Sounder circuits should use cable that is fire proof. All cabling should be earthed to the metal back box via the cable gland. Conductors carrying fire alarm power signals should be separated from conductors used for carrying other systems.
OPERATING INSTRUCTIONS
Access to “SUPERVISOR MODE” for panel operation:-
To operate this fire alarm control panel, it is necessary to gain access to the “Supervisor Mode”, to do this enter the four digit security password code, on the yellow push buttons. This security code should have been given to the responsible person on system hand over. After entering the correct code the “Supervisor Mode” LED will illuminate.
The panel will time out of “Supervisor Mode” if the ‘RESET’ button is pressed or 20 seconds have elapsed since the last button was pressed.
The following functions can all be employed in the “Supervisor Mode”.
‘SOUNDERS ON/OFF’
If the sounders are silent, because either the panel is in alarm and the sounders have been “Silenced”, or if there is no alarm, the sounders will be activated by pressing this button. If the sounders are on, and they are to be switched off, then press the ‘SOUNDERS ON/OFF’ push button to silence the alarm.
‘RESET’
This will cause all faults and fires conditions to be cancelled, if a fault still exists then it will re-appear within 10 seconds of this reset.
‘MUTE PANEL’
To silence the panel’s internal buzzer press ‘MUTE PANEL’ push button. The panel will continue to beep at a reduced rate until the condition causing the buzzer to sound is rectified or reset.
‘LAMP TEST’
Hold down ‘SELECT / LAMP TEST’ push button for a minimum of two seconds. Release once the test is complete.
Loading...
+ 5 hidden pages