To properly use the product, read this manual thoroughly and retain
for easy reference, inspection, and maintenance. Ensure the end user
receives this manual.
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or
by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of Yaskawa.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because Yaskawa is
constantly striving to improve its high-quality products, the information contained in this manual is subject to change without
notice. Every precaution has been taken in the preparation of this manual. Yaskawa assumes no responsibility for errors or
omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
Yaskawa manufactures products used as components in a wide variety of industrial systems and equipment. The selection and
application of Yaskawa products remain the responsibility of the equipment manufacturer or end user. Yaskawa accepts no
responsibility for the way its products are incorporated into the final system design. Under no circumstances should any
Yaskawa product be incorporated into any product or design as the exclusive or sole safety control. Without exception, all
controls should be designed to detect faults dynamically and fail safely under all circumstances. All systems or equipment
designed to incorporate a product manufactured by Yaskawa must be supplied to the end user with appropriate warnings and
instructions as to the safe use and operation of that part. Any warnings provided by Yaskawa must be promptly provided to
the end user. Yaskawa offers an express warranty only as to the quality of its products in conforming to standards and
specifications published in the Yaskawa manual. NO OTHER WARRANTY, EXPRESS OR IMPLIED, IS OFFERED.
Yaskawa assumes no liability for any personal injury, property damage, losses, or claims arising from misapplication of its
products.
u
Applicable Documentation
The following manuals are available for the Z1000 Bypass:
Yaskawa AC Drive Z1000 Bypass Technical Manual for HVAC Fan and Pump (SIEPYAIZ1B01)
Read this manual first. This manual is packaged together with the product and contains basic information required to install
and wire the bypass. It also gives detailed information on fault diagnostics, parameter settings, and BACnet specifications.
The purpose of this manual is to prepare the Z1000 Bypass for a trial run with an application and for basic operation. This
manual is also available for download on the Yaskawa documentation website, www.yaskawa.com.
Z1000-Series AC Drive User Manual (TOEPC71061645)
This manual contains basic information required to install and wire the drive. It also gives detailed information on fault
diagnostics, parameter settings, and BACnet specifications. The purpose of this manual is to prepare the drive for a trial
run with an application and for basic operation. This manual is available for download on the Yaskawa documentation
website, www.yaskawa.com.
Z1000-Series AC Drive Programming Manual (SIEPC71061645)
This manual provides detailed information on parameter settings, drive functions, maintenance, and MEMOBUS/Modbus
specifications. Use this manual to expand drive functionality. This manual is available for download on the Yaskawa
documentation website, www.yaskawa.com.
Software Applicability
n
The Metasys N2 communication protocol is applicable in Z1000 drive software version VSE910000.
u
Terms
Note: Indicates supplemental information that is not related to safety messages.
Drive: Yaskawa Z1000-Series Drive
Bypass: Yaskawa Z1000 Bypass
u
Registered Trademarks
Metasys® N2 is a trademark of Johnson Controls, Inc.
All other trademarks are the property of their respective owners.
u
Supplemental Safety Information
Read and understand this manual before installing, operating, or servicing this option. The option must be installed according
to this manual and local codes.
The following conventions are used to indicate safety messages in this manual. Failure to heed these messages could result in
serious or possibly even fatal injury or damage to the products or to related equipment and systems.
WARNING
Read and understand this manual before installing, operating or servicing this drive. The drive must be installed according
to this manual and local codes.
The following conventions are used to indicate safety messages in this manual. Failure to heed these messages could result
in serious or fatal injury or damage to the products or to related equipment and systems.
DANGER
Indicates a hazardous situation, which, if not avoided, will result in death or serious injury.
WARNING
Indicates a hazardous situation, which, if not avoided, could result in death or serious injury.
WARNING! may also be indicated by a bold key word embedded in the text followed by an italicized safety message.
CAUTION
Indicates a hazardous situation, which, if not avoided, could result in minor or moderate injury.
CAUTION! may also be indicated by a bold key word embedded in the text followed by an italicized safety message.
NOTICE
Indicates a property damage message.
NOTICE: may also be indicated by a bold key word embedded in the text followed by an italicized safety message.
General Safety
n
General Precautions
• The diagrams in this manual may be indicated without covers or safety shields to show details. Replace the covers or shields before
operating the drive and run the drive according to the instructions described in this manual.
• Any illustrations, photographs, or examples used in this manual are provided as examples only and may not apply to all products to
which this manual is applicable.
• The products and specifications described in this manual or the content and presentation of the manual may be changed without notice
to improve the product and/or the manual.
• When ordering a new copy of the manual due to damage or loss, contact your Yaskawa representative or the nearest Yaskawa sales
office and provide the manual number shown on the front cover.
• If nameplate becomes worn or damaged, order a replacement from your Yaskawa representative or the nearest Yaskawa sales office.
DANGER
Heed the safety messages in this manual.
Failure to comply will result in death or serious injury.
The operating company is responsible for any injuries or equipment damage resulting from failure to heed the warnings in
this manual.
Electrical Shock Hazard
Do not connect or disconnect wiring while the power is on.
Failure to comply will result in death or serious injury.
Failure to comply will result in death or serious injury. Before servicing, disconnect all power to the equipment. The internal
capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC
bus voltage is below 50 Vdc. To prevent electric shock, wait for at least the time specified on the warning label once all
indicators are OFF, and then measure the DC bus voltage level to confirm it has reached a safe level.
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Do not perform a withstand voltage test on any part of the drive.
Failure to comply could result in damage to the sensitive devices within the drive.
Do not operate damaged equipment.
Failure to comply could result in further damage to the equipment.
Do not connect or operate any equipment with visible damage or missing parts.
Do not expose the drive to halogen group disinfectants.
Failure to comply may cause damage to the electrical components in the drive.
Do not pack the drive in wooden materials that have been fumigated or sterilized.
Do not sterilize the entire package after the product is packed.
The bypasses can be monitored and controlled by a controller on a Metasys N2 network (N2) using RS-485 technology. The
bypass act as slaves on the N2 network.
Up to 255 bypasses can communicate on a single N2 network. If more bypasses or N2 devices are required, another N2 network
is required.
The N2 node address is configurable by a parameter in the bypass. This defines the physical address of the bypass on the N2
network.
Once the addressing is set, a controller can initiate communication to the bypass. The bypass will perform the specified function
and then send a response back to the controller.
Figure 1 Connecting Multiple Bypasses to a Metasys N2 Network
N2 specifications appear in the following table:
ItemSpecifications
InterfaceRS-485
Communication Speed: 9600 bps
Communication Parameters
ProtocolMetasys N2
Max Number of Drives255 per N2 Network Segment
Data Length: 8-bit (fixed)
Parity: None
Stop Bit: 1-bit (fixed)
This section explains how to connect the drive to an N2 network and the network termination required for a connection.
u
Network Cable Connection
Follow the instructions below to connect the bypass to a N2 network.
With the power shut off, connect the communications cable to the bypass controller and the master. Use terminal TB3
1.
for N2.
Figure 2 Serial Communications Cable Connection Terminal (TB3)
Note:Separate the communications cables from the main circuit cables and other wiring and power cables. Use shielded cables for
2.
3.
4.
5.
6.
7.
the communications cables, and properly shielded clamps to prevent problems caused by electrical interference.
Check or set the termination resistor selection at all slaves. Refer to the description in the Network Termination
section for details on the termination resistor.
Switch the power on.
Set the parameters needed for serial communications (Z3-01 through Z3-11) using the digital operator.
Shut the power off and wait until the display on the digital operator goes out completely.
Turn the power back on.
The bypass is now ready to begin communicating with the master.
Figure 3 explains the wiring diagrams for multiple connections using N2 communication.
RS-485 Interface
n
3 Connecting to a Network
Figure 3 RS-485 Interface
Note:Turn on DIP switch S1 on the bypass that is located at the end of the network. If S1 is missing, then an external 120 ohm resistor must be
placed across terminals TXRX+ and TXRX-. All other slave devices must have this DIP switch set to the OFF position (or if S1 is missing,
no external resistor must be used).
u
Network Termination
The two ends of the network line must be terminated with a 120 ohm resistor between the TXRX+ and TXRX- signals. The
Z1000 Bypass has a built in termination resistor that can be enabled or disabled using DIP switch S1. If a bypass is located at
the end of a network line, enable the termination resistor by setting DIP switch S1 to the ON position. Disable the termination
resistor on all slaves that are not located at the network line end.
Note:Some bypass controllers do not have DIP switch S1. in such cases an external 120 ohm resistor must be placed across the
TXRX+ and TXRX- signals if the bypass controller is at the end of a network line.
Sets the drive slave address used for communications.
Note:Cycle the power after changing this parameter to enable the new setting.
No.NameSetting RangeDefault
Z3-02Serial Communications Node Address Select0 to FFH1FH
Each slave drive must be assigned a unique slave address for serial communications to work. Slave addresses do not need to
be assigned in sequential order, but no two drives may share the same address.
Z3-03: Serial Communications Baud Rate Select
n
Sets the communication speed.
Note:1. Cycle the power after changing this parameter to enable the new setting.
No.NameSetting RangeDefault
Z3-03Serial Communications Baud Rate Select0 to 83
Note:Cycle the power after changing this parameter to enable the new setting.
No.NameSetting RangeDefault
Z3-04Serial Communications Parity Select0 to 20
Setting 0: No parity
Setting 1: Even parity
Setting 2: Odd parity
Z3-05: Serial Communications Fault Select
n
Selects the action to take when a serial communications fault is selected. If communications is lost for more than the time
programmed in Z3-06, then a communication fault is detected.
Note:Cycle the power after changing this parameter to enable the new setting.
Fault FB14 will display in the operator and an EF0 fault will be sent to the drive.
Setting 3: Fault with EF0 and Open Bypass Contactor K3.
Fault FB14 will display in the operator, an EF0 fault will be sent to the drive, and bypass contactor K3 will be opened.
Setting 4: Alarm and run at preset speed set in Z3-10.
Alarm AL14 will display in the operator.
Z3-06: Serial Communications Fault Time Select
n
Sets the time allowed to elapse since receiving serial communications before triggering a communications fault. A value of
0.0 means to never time out.
No.NameSetting RangeDefault
Z3-06Serial Communications Fault Detection Time0.0 to 99.9 s2.0 s
Z3-07: Serial Communications Receive to Transmit Wait Time
n
Sets the time to delay a serial communications response to a serial communications command.
No.NameSetting RangeDefault
Z3-07Serial Communications Receive to Transmit Wait Time0 to 99 ms5 ms
Figure 4 Serial Communications Receive to Transmit Wait Time Setting
Z3-10: Cable Loss Pre-set Speed
n
When a serial communicaions fault is detected and Z3-05=4, the value here will become the frequency reference.
No.NameSetting RangeDefault
Z3-10Cable Loss Pre-set Speed0.0 to 60.0 Hz0.0 Hz
Z3-11: Serial Communication Fault Detection Selection
n
Enables or disables the serial communications fault detection.
No.NameSetting RangeDefault
Z3-11Serial Communication Fault Detection Selection0 or 11
Setting 0: Disabled
No communication error detection. Ignore setting in Z3-05.
Setting 1: Enabled
If the bypass does not receive data from the master for longer than the time set to Z3-06, then a FB14 Serial Communicaions
fault will be triggered and the bypass will operate as determined by parameter Z3-05.
The drive operations that can be performed by N2 communication depend on drive parameter settings. This section explains
the functions that can be used and related parameter settings.
u
Observing the Bypass Operation
A controller can perform the following actions with N2 communications at any time regardless of parameter settings (except
for Z3-oo parameters):
• Observe drive status and drive control terminal status from a controller
• Read and write parameters
• Set and reset faults
• Set multi-function inputs.
Note:
u
Controlling the Bypass
Select an external reference and adjust the parameters in Table 1 accordingly to start and stop the drive or set the frequency
reference using N2 communications.
Input settings from the input terminals So and from N2 communications are both linked by a logical OR operation.
Table 1 Setting Parameters for Bypass Control from N2
Reference SourceParameterNameRequired Setting
External Reference 1
Z1-07Frequency Reference Select2
Z1-08Run Command Select2
Refer to the Z1000 Bypass Technical Manual for details on external reference parameter selections.
Z1000 Bypass Functions
n
Each of the following functions must be enabled during start-up:
Start and Stop the Bypass
Set the Run Forward Command (BO 1) to run the in the forward direction. Set the Run Reverse Command (BO 2) to run the
in the reverse direction. Run/Stop Monitor (BI 1) shows the current run status. Forward/Reverse Monitor (BI 2) shows the
current direction.
NOTICE: Damage to Equipment. Improper motor direction may damage HVAC equipment if parameter b1-04, Reverse Enable, is set to 0
(Enable).
Lock the Z1000 Bypass Panel
This function is not supported in the Z1000 Bypass.
Digital Inputs
Multi-Function Input S3 (BO 5) through Multi-Function Input S7 (BO 9) are physical digital inputs on the bypass. They can
be set either by external devices, such as limit or pressure switches, or by the network. Their function depends on how the
bypass has been programmed. Refer to the Z1000 Bypass Technical Manual section on Multi-Function Inputs (Z2-03 through
Z2-07) for detailed information on the use and programming of the multi-function inputs. The multi-function input status can
be monitored through Multi-Function Input 3 Monitor (BI 15) through Multi-Function Input 7 Monitor (BI 19). The MultiFunction Input # Monitor state is the logical OR of the serial command value (BO 5 through BO 9) and the state of the external
connection.
Note:The multi-function inputs can be set by both external devices or over the network. Use caution when connecting the multi-function inputs
Digital Outputs
to external devices to ensure correct system operation.
Multi-Function Output 7 (BI 10) through Multi-Function Output 9 (BI 12) are physical digital outputs on the bypass. Their
function depends on how the bypass is programmed. Refer to the Z1000 Bypass Technical Manual section on Multi-Function
Outputs (Z2-23 through Z2-25) for detailed information on the use and programming of the multi-function outputs.
Loop Gain
PI Proportional Gain (AO 4) and PI Integral Time (AO 5) are the gain and integral time parameters used by the Z1000. The
Z1000 PI loop is structured differently than the Metasys loop. Refer to the Z1000 Bypass Technical Manual section on PI for
information on Z1000 PI loop functions.
The Fault Monitor (BI 4) and Drive Ready Monitor (BI 3) show the current status of the bypass. The Fault Code (AI 10)
contains the code for the most current fault. The LST Fault Code (AI 19) contains the code for the previous drive fault. Refer
to Fault Trace / History Register Contents on page 14 for descriptions of the fault codes. The drive faults can be reset
through the Fault Reset Command (BO 4). The Fault Reset Command is only available when the Run Forward Command and
the Run Reverse Command are both OFF.
Cable Loss Configuration and Behavior
n
This section describes the configurable cable loss feature of the drive. This feature offers a user maximum flexibility in
determining drive response to a loss of communication.
Drive Behavior at Loss of Communication
The drive can be configured to respond to an interval without receipt of a message in one of the following methods:
• Continue at last speed
• Continue at last speed with alarm
• Continue at preset speed
• Ramp to Stop with FB14 fault
• Coast to Stop with FB14 fault
• Emergency Stop with FB14 fault
Metasys N2 I/O
Three Metasys N2 outputs are used to select the desired behavior:
• AO 21 – Cable Loss Timeout
• AO 22 – Cable Loss Speed
• BO 11 – Communication Fault Enable
Table 2 Cable Loss Behavior Summary
BehaviorF6-03 Z3-05
Decelerate to stop (stop time in C1-02) FB14
Fault.
Note:In Bypass mode, bypass
contactor will open and motor
will coast to stop.
Coast to stop FB14 fault.
Note:In Bypass mode, bypass
contactor will open and motor
will coast to stop.
Fast stop (stop time in C1-09) FB14 fault.
Note:In Bypass mode, bypass
contactor will open and motor
will coast to stop.
Continue at last speed300XX
Continue at last speed with alarm31Timeout IntervalXOn
Continue at preset speed with alarm34Timeout IntervalPreset speedOn
Note:1. Communication must first be established and then lost for these features to function as described. If a bypass is powered-up without a
cable connected or with the master controller offline, a communications timeout does not occur.
2. For modes that describe the bypass running after a communications timeout, a run command must have been issued (BO 1 = ‘On’ or
BO 2 = ‘On’) prior to loss of communications. For safety purposes, the drive will not automatically restart from a stopped condition. If
a user requires the drive to restart automatically, additional external wiring is required to accomplish this (consult factory).
3. Upon expiration of the communications timeout interval, the FAULT LED lights and remains lit until communication is restored.
03Timeout IntervalXOn
13Timeout IntervalXOn
23Timeout IntervalXOn
Cable Loss Timeout
(AO 21)
Cable Loss Speed
(AO 22)
Communication Fault
Enable
(BO 11)
Continue at Last Speed
In this mode, Cable Loss Timeout (AO 21) is set to 0, disabling the cable loss feature. The other two settings Cable Loss Speed
(AO 22) and Communication Fault Enable (BO 11) are ignored. If communication is lost, the drive simply maintains its last
commanded state. The drive will not display an alarm or fault to indicate it has lost communication. This behavior can also
be achieved by setting parameter Z3–05 to “0”.
For this condition, Communication Fault Enable (BO 11) must be enabled and Cable Loss Speed (AO 22) should be set to a
value other than 0. An AL14 Serial Communications Alarm is shown.
Continue at Preset Speed with Alarm
In this mode, Cable Loss Timeout (AO 21) is set to the desired interval, Cable Loss Speed (AO 22) is set to the desired preset
speed and Z3–05 is set to “4”. If the time between messages exceeds the timeout interval, the drive speed command (AO 1)
is set to the Cable Loss Speed (AO 22) and the drive continues running at this new speed. Communication Fault Enable (BO
11) must be set to ‘On’.
Stop with Fault (FB14)
Communication Fault Enable (BO 11) must be set to ‘On’. In this mode, Cable Loss Timeout (AO 21) is set to the desired
interval and parameter F6-03 is set to a value of 0,1 or 2. If the time between messages exceeds the timeout interval, the drive
will declare an EF0 fault and the drive speed command (AO 1) will be set to 0. The stopping method is determined by the
setting of F6-03.
• F6–03 = 0 selects Ramp to Stop. The deceleration time or the slope of the ramp is determined by the setting of drive parameter
C1-02
• F6–03 = 1 selects Coast to Stop. The drive does not attempt to control the rate of deceleration.
• F6–03 = 2 selects Emergency or Fast Stop. The deceleration time is determined by the setting of drive parameter C1-09.
Z1000 Bypass Fault Numbers
n
Table 3 Fault Trace / History Register Contents
Fault CodeFault Name
0002HUndervoltage (Uv1)
0003HControl Power Supply Undervoltage (Uv2)
0004HSoft Charge Circuit Fault (Uv3)
0006HGround Fault (GF)
0007HOvercurrent (oC)
0008HOvervoltage (ov)
0009HHeatsink Overheat (oH)
000AHHeatsink Overheat (oH1)
000BHMotor Overload (oL1)
000CHDrive Overload (oL2)
000DHOvertorque Detection 1 (oL3)
0010HBraking Resistor Overheat (rH)
0011HExternal Fault at Input Terminal S3 (EF3)
0012HExternal Fault at Input Terminal S4 (EF4)
0013HExternal Fault at Input Terminal S5 (EF5)
0014HExternal Fault at Input Terminal S6 (EF6)
0015HExternal Fault at Input Terminal S7 (EF7)
001BHInput Phase Loss (PF)
001CHOutput Phase Loss (LF)
001DHMotor Overheat (PTC input) (oH3)
001EHDigital Operator Connection (oPr)
001FHEEPROM Write Error (Err)
0020HMotor Overheat (PTC input) (oH4)
0021HMEMOBUS/Modbus Communication Error (CE)
0022HOption Communication Error (bUS)
0027HOption External Fault (EF0)
0028HPI Feedback Loss (FbL)
0029HUndertorque Detection 1 (UL3)
002BHHigh Slip Braking Overload (oL7)
0030HHardware Fault (including oFx)
0036HOutput Current Imbalance (LF2)
0037HPullout Detection (Sto)
Fault CodeFault Name
003BHToo Many Speed Search Restarts (SEr)
0041HPI Feedback Loss (FbH)
0042HExternal Fault 1, Input Terminal S1 (EF1)
0043HExternal Fault 2, Input Terminal S2 (EF2)
0046HCurrent Offset Fault (CoF)
0047HPLC Detection Error 1 (PE1)
0048HPLC Detection Error 2 (PE2)
004DHOutput Voltage Detection Fault (voF)
0052HNode Setup Fault (nSE)
005AHMotor Underload Protection (UL6)
0083HA/D Conversion Error (CPF02)
0084HPWM Data Fault (CPF03)
0087HEEPROM Memory Data Error (CPF06)
0088HTerminal Board Connection Error (CPF07)
0089HEEPROM Serial Communication Fault (CPF08)
008CHRAM Fault (CPF11)
008DHFlash Memory Circuit Exception (CPF12)
008EHWatchdog Circuit Exception (CPF13)
008FHControl Circuit Fault (CPF14)
0091HClock Fault (CPF16)
0092HTiming Fault (CPF17)
0093HControl Circuit Fault (CPF18)
0094HControl Circuit Fault (CPF19)
0095HHardware Fault at Power Up (CPF20)
0096HHardware Fault at Communication Start Up (CPF21)
0097HA/D Conversion Fault (CPF22)
0098HPWM Feedback Fault (CPF23)
0099HDrive Unit Signal Fault (CPF24)
009AHTerminal Board is Not Properly Connected. (CPF25)
To prevent a communications overrun in the slave drive, the master should wait a certain time between sending messages to
the same drive. In the same way, the slave drive must wait before sending response messages to prevent an overrun in the
master. This section explains the message timing.
u
Command Messages from Master to Bypass
The master must wait for a specified time between receiving a response and resending the same type of command to the same
slave bypass to prevent overrun and data loss. The minimum wait time depends on the command as shown in Table 4.
Table 4 Minimum Wait Time for Sending Messages
Command TypeExampleMinimum Wait Time
• Control command (Run, Stop)
1
• Set inputs/outputs
• Read monitors and parameter values
2Write parameters
3Save changes using an Enter command
H5-11 = 0: 50 ms
H5-11 = 1: 200 ms
200 ms to 2 s, depending on the number
of parameters that were changed
4Enter with storage to drive EEPROM after initialization5 s
<1> If the bypass receives command type 1 data during the minimum wait time, it will perform the command and then respond. However, if it receives
a command type 2 or 3 during that time, either a communication error will result or the command will be ignored.
5 ms
<1>
<1>
<1>
Figure 5 Minimum Wait Time for Sending Messages
Set a timer in the master to check how long it takes for the slave bypass units to respond to the master. If no response is received
within a certain amount of time, the master should try resending the message.
u
Response Messages from Bypass to Master
If the bypass receives a command from the master, it will process the data received and wait for the time set in Z3-07 until it
responds. Increase Z3-07 if the drive response causes overrun in the master.
This section describes the Metasys N2 point database. This database features 100 logical points: 38 Analog Inputs (AI), 32
Analog Outputs (AO), 19 Binary Inputs (BI) and 11 Binary Outputs (BO). These points configure, control, and monitor the
operation of the drive.
u
Metasys N2 Analog Input (AI) Summary
Table 5 Metasys N2 Analog Input Summary (Bypass to Metasys N2)
Object IDObject NameUnitsBypass Parameter
AI 1Speed Reference0.01 HzU1-01
AI 2Output Speed0.01 HzU1-02
AI 3Output Current0.1 AU1-03/UB-01 in Drive/Bypass Mode
AI 4kWatt Hour MeterkWhU4-10
AI 5Output Power0.1 kWhU1-08
AI 6Drive Temperature
AI 7PI Feedback0.01%U5-01
AI 8AC Output Voltage0.1 VacU1-06
AI 9DC Bus Voltage1 VdcU1-07
AI 10Fault Code–U2-01/UB-09. Reads UB-09 first and if 0 returns U2-01
AI 11Elapsed Time - Hours1 hourU4-01
AI 12Elapsed Time - 10K Hours10K hoursU4-01
AI 13MWatt Hour meterMWhU4-11
AI 14Drive Rated CurrentAn9-01
AI 15Communication Error Code–Not supported. Always returns 0
Two points are defined for reading drive parameters:
• AO 30 – Specifies the parameter to be read from the bypass.
• AI 38 – Reports the value of the parameter specified in AO 30.
When this point is read, it retrieves data from the parameter and sends it to the controller
Example: Writing a value of 387 (183 hex) to AO 30 specifies drive parameter b1-04. Reading AI 38 returns the current setting
of parameter b1-04 to the controller.
u
Writing Drive Parameters
Two points are defined for writing to drive parameters:
• AO 31 – Specifies the parameter to be written to
• AO 32 – Entry location of the value to be written to the parameter specified in AO 31. When this point is written to, it will
write the value to the drive. An ENTER or ACCEPT command does not need to be sent for the data to be taken by the drive.
The behavior of the write is the same as with the digital operator. If the drive is running, there are a limited number of drive
parameters that can be written to.
Example: Writing a value of 387 (183 hex) to AO 31 specifies drive parameter b1-04. Writing a value of 1 to AO 32 sets b1-04
to 1 and disables the drive for reverse run.
151 Lorong Chuan, #04-01, New Tech Park, 556741, Singapore
Phone: 65-6282-3003
http://www.yaskawa.com.sg
YASKAWA ELECTRIC (SHANGHAI) CO., LTD.
No. 18 Xizang Zhong Road, 17F, Harbour Ring Plaza, Shanghai, 200001, China
Phone: 86-21-5385-2200
http://www.yaskawa.com.cn
YASKAWA ELECTRIC (SHANGHAI) CO., LTD. BEIJING OFFICE
Room 1011, Tower W3 Oriental Plaza, No. 1 East Chang An Ave.,
Dong Cheng District, Beijing, 100738, China
Phone: 86-10-8518-4086
YASKAWA ELECTRIC TAIWAN CORPORATION
9F, 16, Nanking E. Rd., Sec. 3, Taipei, 104, Taiwan
Phone: 886-2-2502-5003
Fax: 55-11-5581-8795
Fax: 44-1236-458182
Fax: 82-2-784-8495
Fax: 65-6289-3003
Fax: 86-21-5385-3299
Fax: 86-10-8518-4082
Fax: 886-2-2505-1280
YASKAWA AMERICA, INC.
In the event that the end user of this product is to be the military and said product is to be employed in any weapons systems or the manufacture
thereof, the export will fall under the relevant regulations as stipulated in the Foreign Exchange and Foreign Trade Regulation s. Therefore, be sure
to follow all procedures and submit all relevant documentation according to any and all rules, regulations and laws that may apply.
Specifications are subject to change without notice for ongoing product modifications and improvements.