Ventilation Planning Guide

For THERMADOR PROFESSIONAL Ranges,

Rangetops, and Hoods

Guide de Planification de Ventilation

Pour les cuisinières, surface de cuisson, et hottes

PROFESSIONAL de THERMADOR

Guía de Planificación de Ventilación

Para las estufas, placas de cocción, y campanas PROFESSIONAL de THERMADOR

Models | Modèles |

Modelos:

PRO GRAND DUAL

FUEL RANGES

PRO GRAND GAS

RANGES

PRO HARMONY DUAL FUEL RANGES

PRO HARMONY GAS RANGES

PRO RANGETOPS

PRO WALL HOODS

PRO CHIMNEY

HOODS

PRO CUSTOM

INSERT HOODS

Ventilation Planning Guide

It is recommended that a THERMADOR PROFESSIONAL hood is used with a THERMADOR PROFESSIONAL range or rangetop. The following range and rangetop ventilation combinations are approved installations.

All blower models referenced may not be compatible with all hoods referenced. Refer to www.thermador.com for a complete selection of ventilation options, blowers, and accessories.

IMPORTANT NOTES:

See related Thermador Manuals for additional information.

Thermador recommends not exceeding 50 ft. (15.24 m) equivalent length of duct.

Keep duct runs as short and straight as possible. Elbows and transitions fittings reduce air flow efficiency. Back to back elbows and “S” turns give very poor delivery and are not recommended. A short straight length of duct at the inlet of a remote blower gives the best delivery.

For Thermador Pro Ranges applications with a non-approved Thermador hood. The hood and/or blower must be rated for 1 CFM for every 100 BTU on the Range/Rangetop.

If the range has a 12'' Griddle, add an additional 200 CFM to the estimated blower capacity.

If the range has a 24'' Griddle, add an additional 400 CFM to the estimated blower capacity.

If the range has a Grill, add an additional 400 CFM to the estimated blower capacity.

If the range has a Grill and a Griddle, add an additional 600 CFM to the estimated blower capacity.

For island applications, it is recommended to use a hood width that exceeds the width of the range by 6'' (152 mm), overlapping the range or rangetop by a minimum of 3'' (76 mm) on each end.

A 25 foot extension cable (EXTNCB25) is available for purchase to connect the hood to in-line or remote blowers, if required.

English | 1 |

Range hoods with selectable blowers:

Range or Rangetop

Recommended

Min. Integral

Min. In-Line or

Other Available

Model

Hood Models

Blower

Remote Blower

Blowers

 

 

 

 

 

NOTE – All Range/Hood/Blower combinations below must use minimum 6" diameter duct.

 

 

 

 

 

 

30''

PH30HS

VTN630*

VTI610*

N/A

 

 

 

VTR630*

 

 

 

 

 

 

NOTE – All Range/Hood/Blower combinations below must use minimum 8" diameter duct.

 

 

 

 

 

 

30''

PH30HS, HPCN36NS, PH36GS,

VTN1030*

VTI1010*

VTR1330*

 

PH36HS, VCIN36JP

VTN1090*

VTR1030*

VTN1080*

 

 

 

 

 

36'' without Grill or Griddle

HPCN36NS, PH36GS, PH36HS,

 

 

 

36'' with Griddle

VCIN36JP, PH42GS, HPCN48NS,

 

 

 

 

PH48GS, PH48HS, VCIN48JP

 

 

 

 

 

 

 

 

48'' with Griddle only

HPCN48NS, PH48GS, PH48HS,

 

 

 

 

VCIN48JP, PH54GS, VCIN54JP

 

 

 

 

 

 

 

 

NOTE – All Range/Hood/Blower Combinations below must use minimum 10" diameter duct.

 

 

 

 

 

 

36'' with Grill

HPCN36NS, PH36GS, PH36HS,

VTN1030*

VTI1010*

VTR1330*

 

VCIN36JP, PH42GS, HPCN48NS,

VTN1090*

VTR1030*

VTN1080*

 

PH48GS, PH48HS, VCIN48JP

 

 

 

48'' with Grill

HPCN48NS, PH48GS, PH48HS,

 

 

 

48" with Grill and Griddle

VCIN48JP, PH54GS, VCIN54JP

 

 

 

 

VCIN60RP, PH60GS

VTN1090*

 

 

60" with Grill and Griddle

VCIN60RP, PH60GS

VTN1090*

 

 

60" with Double Griddle

 

 

 

 

* Indicates a letter designating the release year.

Range hoods with blower included:

Range or Rangetop Model

Recommended Hood Models

 

 

NOTE – All Range/Hood/Blower combinations below must use minimum 6" diameter duct.

 

 

30''

HPWB30FS

 

 

NOTE – All Range/Hood/Blower combinations below must use minimum 8" diameter duct.

 

 

30''

HPCB36NS, HPWB36FS, VCIB36JP

36'' without Grill or Griddle

HPCB36NS, HPWB36FS, VCIB36JP, HPCB48NS, HPWB48FS, VCIB48JP

36'' with Griddle

 

48'' with Griddle only

HPCB48NS, HPWB48FS, VCIB48JP, VCIB54JP

NOTE – All Range/Hood/Blower Combinations below must use minimum 10" diameter duct.

 

 

36'' with Grill

HPCB36NS, HPWB36FS, VCIB36JP, HPWB48FS, VCIB48JP

 

 

48'' with Grill

HPCB48NS, HPWB48FS, VCIB48JP, VCIB54JP

48" with Grill and Griddle

 

 

 

English | 2 |