SilentKnight SK-Zone User Manual

ISOLATED QUADRANT
INSTALLATION AND MAINTENANCE INSTRUCTIONS
SK-Zone Interface Module
SPECIFICATIONS
Normal Operating Voltage: 15 to 32 VDC Maximum Current Draw: 5.1 mA (LED on) Average Operating Current: 270µA (LED flashing) EOL Resistance: 3.9K Ohms Maximum IDC Wiring Resistance: 25 Ohms External Supply Voltage (between Terminals T10 and T11) DC Voltage: Regulated 24 VDC Ripple Voltage: 0.1 Volts RMS maximum Current: 90mA per module Temperature Range: 32˚F to 120˚F (0˚C to 49˚C) Humidity: 10% to 93% Non-condensing Dimensions: 41/2˝ H × 4˝ W × 11/4˝ D (Mounts to a 4˝ square by 21/8˝ deep box.) Accessories: SMB500 Electrical Box
BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to the control panel installation manual for detailed system information. If the modules will be installed in an existing operational system, inform the opera­tor and local authority that the system will be temporarily out of service. Dis­connect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The SK-Zone Interface Module is intended for use in intelligent, two-wire systems, where the individual address of each module is selected using the built-in rotary switches. This module allows intelligent panels to interface and monitor two-wire conventional smoke detectors. It transmits the status (nor­mal, open, or alarm) of one full zone of conventional detectors back to the control panel. All two-wire detectors being monitored must be UL compatible with this module.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible Silent Knight system control panel only (list available from Silent Knight).
FIGURE 1. CONTROLS AND INDICATORS:
MOUNTING
The SK-Zone mounts directly to 4-inch square electrical boxes (see Figure 2). The box must have a minimum depth of 21/8 inches. Surface mounted electri­cal boxes (SMB500) are available from Silent Knight
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and regulations. This module is intended for power-limited wiring only.
1. Install module wiring in accordance with the job drawings and appropri­ate wiring diagrams.
2. Set the address on the module per job drawings.
3. Secure module to electrical box (supplied by installer), as shown in Figure 2.
FIGURE 2. MODULE MOUNTING:
I56-3440-001
12 Clintonville Road, Northford, CT 06472
203.484.7161; Fax: 203.484.7118 www.silentknight.com
C1059-00
COMPATIBLE TWO-WIRE SYSTEM SENSOR SMOKE DETECTORS FOR USE WITH SK-ZONE INTERFACE MODULE WITH ZONE IDENTIFIER A:
C1066-00
Detector Compatibility Detector Base Base Max Model ID Type Model Identifier Detectors
1451 A Ionization B401/B A 20 2451 A Photoelectric B401/B A 20 2451TH A Photoelectric with Thermal B401/B A 20 1400 A Ionization N/A 20 2400 A Photoelectric N/A 20 2400TH A Photoelectric with Thermal N/A 20 1100 A Ionization N/A 20 1151 A Ionization B110LP/B401 A 20 2100 A Photoelectric N/A 20 2100T A Photoelectric with Thermal N/A 20 2151 A Photoelectric B110LP/B401 A 20
*Used in combination with MTL isolator model MTL3043.
SK-460-012 1 I56-3440-001
FIGURE 3. INTERFACE TWO-WIRE CONVENTIONAL DETECTORS, NFPA STYLE B:
(+)
(–)
(+)
(–)
(+)
(–)
+
LISTED BATTERY-BACKUP SWITCHED
REGUALTED DC POWER SUPPLY
POWER TO THE INTERFACE MODULE MUST BE EXTERNALLY SWITCED TO RESET THE DETECTORS. A RELAY CONTROL MODULE CAN BE USED TO SWITCH POWER FROM A STANDARD POWER SUPPLY (SEE FIGURE 5).
OPTIONAL BRANCH CIRCUIT
TO NEXT INTERFACE
MODULE. MODULE
SUPERVISES SUPPLY
VOLTAGE AND
DETECTOR LOOP.
(+)
(–)
TERMINAL WIRING MUST
BE POWER LIMITED.
TO NEXT
DEVICE
INTERFACE
MODULE
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
CONNECT MODULES TO
LISTED COMPATIBLE
CONTROL PANELS ONLY.
FROM
PA NEL OR
PREVIOUS
DEVICE
3.9K EOL
RESISTOR
(INCLUDED)
A2143-10
DO NOT LOOP WIRE UNDER TERMINALS. BREAK ALL WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS. DETECTORS MUST BE UL LISTED COMPATIBLE WITH MODULE. INSTALL DETECTORS PER MANUFACTURER’S INSTALLATION INSTRUCTIONS
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
+
DO NOT MIX FIRE ALARM INITIATING, SUPERVISORY, OR SECURITY DEVICES ON THE SAME MODULE.
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
LISTED
BATTERY-BACKUP
SWITCHED REGUALTED
DC POWER SUPPLY
POWER TO THE INTERFACE MODULE MUST BE EXTERNALLY SWITCED TO RESET THE DETECTORS. A RELAY CONTROL MODULE CAN BE USED TO SWITCH POWER FROM A STANDARD POWER SUPPLY (SEE FIGURE 5).
OPTIONAL BRANCH CIRCUIT TO NEXT INTERFACE MODULE. MODULE SUPERVISES SUPPLY
VOLTAGE AND
DETECTOR LOOP.
TERMINAL WIRING MUST
BE POWER LIMITED.
3.9K EOL RESISTOR
REQUIRED AT TERMINALS
8 & 9 (INCLUDED) A2143-10
DO NOT LOOP WIRE UNDER TERMINALS. BREAK ALL WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS. DETECTORS MUST BE UL LISTED COMPATIBLE WITH MODULE. INSTALL DETECTORS PER MANUFACTURER’S INSTALLATION INSTRUCTIONS
INTERFACE
MODULE
TO NEXT
DEVICE
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PA IR
IS RECOMMENDED
CONNECT MODULES TO
LISTED COMPATIBLE
CONTROL PANELS ONLY.
FROM
PANEL OR
PREVIOUS
DEVICE
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
+
+
DO NOT MIX FIRE ALARM INITIATING, SUPERVISORY, OR SECURITY DEVICES ON THE SAME MODULE.
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
CONNECT MODULES TO LISTED COMPATIBLE
CONTROL PANELS ONLY.
FROM
PANEL OR
PREVIOUS
DEVICE
RELAY CONTROL
MODULE
TO NEXT
DEVICE
POWER LIMITED DC POWER SUPPLY, LISTED FOR FIRE PROTECTION WITH BATTERY BACKUP
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
FIGURE 4. INTERFACE TWO-WIRE CONVENTIONAL DETECTORS, NFPA STYLE D:
C1061-00
FIGURE 5. RELAY CONTROL MODULE USED TO DISCONNECT A POWER SUPPLY:
SK-460-012 2 I56-3440-001 ©2009 Honeywell International Inc.
C1062-00
C0945-00