SilentKnight SK-Relaymon-2 User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
I56-3735-000
SK-RELAYMON-2 Multiple Module with
12 Clintonville Road, Northford, CT 06472
203.484.7161; Fax: 203.484.7118
Two Relay Outputs and Two Monitor Inputs
SPECIFICATIONS
Normal Operating Voltage: 15 to 32 VDC Maximum Current Draw: 24 mA (4 LEDs on) Average Operating Current: 1.3 mA, 1 communication every 5 seconds Temperature Range: 32˚F to 120˚F (0˚C to 49˚C) Humidity: 10% to 93% Non-condensing Addressing: Module base address=Relay Output #1, Module base address +1=Monitor Input #1, Module base address +2=Relay Output #2, Module base address +3=Monitor Input #2 Dimensions: 4.675˝ H x 4.275˝ W x 1.4˝ D (Mounts to a 4˝ square by 21/8˝ deep box.) Accessories: SMB500 Electrical Box; EA-CB Barrier Relay Contact Rating: 3A at 30 VDC EOL Resistance: 47K Ohms (monitor iputs only) Maximum IDC wiring resistance: 1500 Ohms Maximum IDC Voltage: 10.2 Volts Maximum IDC Current: 450µA
RELAY CONTACT RATINGS:
CURRENT RATING MAXIMUM VOLTAGE LOAD DESCRIPTION APPLICATION
2 A 25 VAC PF = 0.35 Non-coded
3 A 30 VDC Resistive Non-coded
2 A 30 VDC Resistive Coded
0.46 A 30 VDC (L/R = 20ms) Non-coded
0.7 A 70.7 VAC PF = 0.35 Non-coded
0.9 A 125 VDC Resistive Non-coded
0.5 A 125 VAC PF = 0.75 Non-coded
0.3 A 125 VAC PF = 0.35 Non-coded
www.silentknight.com
BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to the control panel installation manual for detailed system information. If the modules will be installed in an existing operational system, inform the opera­tor and local authority that the system will be temporarily out of service. Dis­connect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The SK-RELAYMON-2 multi output-input module is intended for use in in­telligent, two-wire systems, where the individual address of each module is selected using the built-in rotary decade switches. It is capable of replacing two individual relay control modules and two Class B monitor modules. Each relay output is intended for Form C switching applications which do not re­quire wiring supervision for the load circuit. Each monitor input is intended to interface between a fire alarm control panel and one or more devices. Each relay output has its own green LED. Each monitored input has its own bi­color LED, which can be controlled by the control panel.
The module address is selected by means of rotary decade address switches (See Figure 1). These can be accessed from the front of the module. A screw­driver should be used to rotate the wheels to select the desired addresses. Each module can use up to four (4) addresses. The base address selected via the rotary address switches will be assigned to relay output #1 from 00 to 156. The module will automatically assign the next three addresses as appropriate to monitored input #1, relay output #2, and monitored input #2.
SK-460-019 1 I56-3735-000
If relay output #2 or monitored input #2 are not used, please switch the cor­responding DIP switch to the ‘OFF’ position with the screwdriver (See Figure 1A). These two addresses will then be free to be used for other devices on the loop. NOTE: If relay output #2 is disabled and monitored input #2 is enabled, the address for monitored input #2 will be module base address +3. Module base address +2 (reserved for relay output #2) will then be open for other devices.
COMPATIBILITY REQUIREMENTS
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and regulations.
1. Install module wiring in accordance with the job drawings and appropri­ate wiring diagrams.
2. Set the address on the module per job drawings.
3. Secure module to electrical box (supplied by installer), as shown in Figure 2.
WARNING
(-)
FIGURE 1. CONTROLS AND INDICATORS:
MOUNTING
The module mounts directly to 4-inch square electrical boxes (see Figure 2). The box must have a minimum depth of 21/8 inches. Surface mounted electri­cal boxes (SMB500) are available from System Sensor. The module can also mount to the DNR(W) duct housing.
FIGURE 2. MODULE MOUNTING:
C0917-05
FIGURE 1A. DISABLING OUTPUT #2 AND INPUT #2
C01080-01
FIGURE 3. TYPICAL 2-WIRE INITIATING CIRCUIT CONFIGURATION, NFPA STYLE B:
ANY NUMBER OF UL LISTED CONTACT
CLOSURE DEVICES MAY BE USED. THE
RELAY IS PROGRAMMABLE, E.G. IT WILL
OPERATE FOR ANY SIGNAL FOR WHICH THE
SYSTEM IS PROGRAMMED. DO NOT MIX FIRE
ALARM INITIATING, SUPERVISORY, OR
SECURITY DEVICES ON THE SAME MODULE.
INITIATING DEVICE CIRCUIT (IDC) - NFPA STYLE B
POWER LIMITED: 450µA MAX. @ 10.2 VDC MAX
INSTALL CONTACT CLOSURE DEVICES PER
MANUFACTURER’S INSTALLATION INSTRUCTIONS.
IDC TERMINALS ARE SUPERVISED AND POWER LIMITED
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
TO NEXT
DEVICE
(+)
(+)
ISOLATED
QUADRANT
C1081-00
(-)
FROM PANEL OR
(+)
PREVIOUS DEVICE
CONNECT MODULES TO LISTED COMPAT-
IBLE CONTROL PANELS ONLY
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
(-)
47K EOL
RESISTOR
ELR-47K
IF ANY WIRING TO TERMINALS 7 -12 IS NONPOWER LIMITED, THE EA-CB BARRIER IS REQUIRED. THE EA-CB INCLUDES A NONPOWER LIMITED LABEL, WHICH MUST BE PLACED OVER THE POWER LIMITED TERMINAL INFORMATION ON THE NAMEPLATE LABEL.
TWISTED PAIR
IS RECOMMENDED
47K EOL
RESISTOR
ELR-47K
C1051-07
All relay switch contacts are shipped in the standby (open) state, but may have transferred to the activated (closed) state during shipping. To ensure that the switch contacts are in their correct state, modules must be made to communicate with the panel before connecting circuits controlled by the module.
SK-460-019 2 I56-3735-000 ©2011 Honeywell International, Inc.
Loading...