INSTALLATION AND MAINTENANCE INSTRUCTIONS
WARNING
I56-3439-000
SK-Relay-6 Six Relay Control Module
Normal Operating Voltage: 15-32 VDC Stand-By Current:1.45 mA Alarm Current: 32 mA (assumes all six relays have been switched once and all six LEDs solid on) Temperature Range: 32°F to 120°F (0°C to 49°C) Humidity: 10 to 85% Non-condensing Dimensions: 6.8˝ H × 5.8˝ W × 1.0˝ D Accessories: IDP-ACB cabinet and chassis Wire Gauge: 12-18 AWG Relay Current: 30 mA/Relay Pulse (15.6 mS pulse duration) pulse under panel control
BEFORE INSTALLING
If the modules will be installed in an existing operational system, inform the operator and local authority that the system will be temporarily out of service. Disconnect the power to the control panel before installing the modules. This system contains static sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are re­moved from the body. The housing cabinet should be metallic and suitably grounded.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The SK-Relay-6 Six Relay Control Module is intended for use in an intelligent alarm system. Each module is intended for Form-C switching applications, which do not require wiring supervision for the load circuit. A single isolated set of dry relay contacts is provided for each module, which is capable of being wired for either normally open or normally closed for each operation. Each module has its own address. A pair of rotary code switches is used to set the address of the first module from 01 to 94(or 01 to 154 for panels that sup­port 159 addresses). The remaining modules are automatically assigned to the next five higher addresses. Provisions are included for disabling a maximum of three unused modules to release the addresses to be used elsewhere. Each SK-Relay-6 module also has panel controlled green LED indicators. The panel can cause the LEDs to blink, latch on, or latch off.
CURRENT RATING MAXIMUM VOLTAGE LOAD DESCRIPTION APPLICATION
3 A 30 VDC Resistive Non-coded
2 A 30 VDC Resistive Coded .9 A 110 VDC Resistive Non-coded .9 A 125 VDC Resistive Non-coded .5 A 30 VDC Inductive (L/R=5ms) Coded
1 A 30 VDC Inductive (L/R=2ms) Coded .3 A 125 VAC Inductive (PF=.35) Non-coded
1.5 A 25 VAC Inductive (PF = .35) Non-coded .7 A 70.7 VAC Inductive (PF=.35) Non-coded
2 A 25 VAC Inductive (PF=.35) Non-coded
Contents include:.
(6) 1 × 3 Terminal Blocks (1) 1 × 4 Terminal Blocks (2) 11/4˝ (32mm) Stand offs (4) Machine Screws (2) Nuts (1) Shunt (NOTE: For the disable position, not more than one shunt shall be
installed at the same time)
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible Silent Knight system control panel.
7550 Meridian Circle, Maple Grove, MN 55369-4927
763.493.6455, 800.328.0103; Fax: 763.493.6475 http://www.silentknight.com
All relay switch contacts are shipped in the standby state (open) state, but may have transferred to the activated (closed) state during shipping. To ensure that the switch contacts are in their correct state, modules must be made to communicate with the panel before connecting circuits controlled by the module.
SK-460-007 1 I56-3439-000
COMPONENTS
0
1
2
3
4
5
6 7 8
9
0
7 8
6
5
4
3
2
1
9
10
11
12
13
14
15
BASE ADDRESS
ADDRESS
DISABLE
0
1
2
3
4
5
6 7 8
9
0
7 8
6
5
4
3
2
1
9
BASE ADDRESS
ADDRESS
DISABLE
NONE
ONE
TWO
THREE
10
11
12
13
14
15
BACKBOX MOUNTING HOLES
2
1
3
1
2
1
3
The following is a description of the SK-Relay-6 mounting framework:
One or two SK-Relay-6 modules can be installed in a IDP-ACB cabinet•
The IDP-ACB cabinet has a built-in chassis that will accommodate one or two SK-Relay-6 modules.
FIGURE 1: IDP-ACB CABINET
C0234-05
The front SK-Relay-6 module positions of each chassis are offset below the rear SK-Relay-6 module positions so that all of the status indicators are visible. For cabinet dimensions refer to IDP-ACB instruction manual.
INSTALLATION STEPS
1. Cabinet Mounting
In a clean, dry area, mount the backbox using the four holes provided in
the back surface of the cabinet.
FIGURE 2: TYPICAL MOUNTING hOLE LOCATIONS
Step 1: Insert the bottom of the SK-Relay-6 module down into a rear slot on
the chassis.
Step 2: Carefully swing the upper edge of the board back towards the back of
the chassis until it touches the two standoffs.
Step 3: Align two 4-40 screws with the two standoffs and tighten. Step 4: Address and wire the modules according to the instructions in this
manual.
The steps in Figures 4a and 4b describe and illustrate module installation when the rear chassis position and the position in front of it will be filled. Front position installation is possible only if the rear position is filled with a module.
FIGURE 4A: INSTALLATION OF SK-RELAY-6 MODULE IN A REAR ChASSIS POSITION, METhOD TwO
C0244-00
C0235-00
2. Module Installation
There are two methods for installing a module in the rear position of a
chassis. Method one is for installation of a rear module only, when no module will be installed in front of it. Refer to Figure 3 for instructions. Method two is for installation of a rear module when another module will be installed in the chassis position in front of it. Refer to Figures 4a and 4b for method two. All necessary screws and standoffs are supplied with the modules.
FIGURE 3: INSTALLATION OF REAR MODULE ONLY, METhOD ONE
Step 1: Insert the bottom edge of the SK-Relay-6 module down into a rear slot
of the chassis.
Step 2: Carefully swing the bottom edge of the board towards the back of the
board until it touches the short standoff attached to the chassis.
Step 3: Align the long standoff with the short standoff and tighten.
FIGURE 4B: INSTALLATION OF SK-RELAY-6 MODULE IN FRONT ChAS­SIS POSITION
C0245-00
Step 1: Insert the bottom edge of the SK-Relay-6 module down into a front
slot of the chassis.
Step 2: Carefully swing the upper edge of the board towards the back of the
chassis until it touchesthe 11/4˝ (31.75mm) standoffs installed on the rear module.
Step 3: Align two 4-40 screws with the two standoffs and tighten. Step 4: Address and wire the modules according to the instructions in this
manual.
C0249-00
SK-460-007 2 I56-3439-000
wIRING
0
1
2
3
4
5
6
7
8
9
0
7
8
6
5 4 3
2
1
9
10
11
12
13
14
15
N.C.
N.O.
COMMON
ADDRESS 5
N.C.
N.O.
COMMON
ADDRESS 4
N.C.
N.O.
COMMON
ADDRESS 3
N.C.
N.O.
COMMON
ADDRESS 2
N.C.
N.O.
COMMON
ADDRESS 1
N.C.
N.O.
COMMON
ADDRESS 0
SLC
BASE ADDRESS
ADDRESS
DISABLE
NONE
ONE TWO
THREE
6.8"
5.8"
FROM PANEL
OR PREVIOUS DEVICE
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
SEE PANEL INSTRUCTION
MANUAL FOR
WIRE REQUIREMENTS
TO NEXT
DEVICE
+
+
+
NC
NO
COMMON
RELAY CONNECTIONS
STA TUS
INDICATORS
NOTE: All wiring must conform to applicable local codes, ordinances, and regulations.
1. Install module wiring in accordance with the job drawings and appropri­ate wiring diagrams.
2. Make electrical connections by stripping approximately 1/4˝ (6.35mm) of insulation from the end of the wire sliding the bare end of the wire under the clamping plate, and tightening the clamping plate screw.
3. Set the address on the modules per the job drawing. Use the rotary code switches to set the address of the first module between 01 and 94 (or 01 and 154 for panels that support 159 addresses). The remaining modules are automatically assigned to the next five higher addresses. For exam­ple, if the base address switch is set to 28, the next five modules will be addressed to 29, 30, 31, 32, and 33. DO NOT set the lowest address above 94(or 154 for panels that support 159 addresses), as the other modules will be assigned to nonexistent addresses.
4. A shunt is provided to disable a maximum of three unused modules. Modules are disabled from the highest address and work downward. If two modules are disabled, the lowest four addresses will be functional, while the highest two will be disabled. For example, if the shunt for Ad­dress Disable is placed on “two” and the base address switch is set to 28, the modules will be assigned to 28, 29, 30 and 31.
NOTE: The SK-Relay-6 must have power cycled for shunt changes to take effect.
NOTES:
The relay contacts on the SK-Relay-6 may be connected to either a • power-limited or non power-limited source, this wiring must remain separated by at least 1/4˝ (6.35 mm) from all power-limited wiring.
Power-limited circuits must employ type FPL, FPLR, or FPLP cable as • required by Article 760 of the NEC.
For easier wiring, assign all power-limited wiring to one side rather than • alternating with non power-limited.
PROGRAMMING
The modules are programmed as modules in each system according to the programming instructions in the appropriate FACP manual.
FIGURE 5: wIRING AND PROGRAMMING ThE SK-RELAY-6 MODULE
C0250-04
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular instal­lation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: – Reorient or relocate the receiving antenna. – Increase the separation between the equipment and receiver. – Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. – Consult the dealer or an experienced radio/TV technician for help.
SK-460-007 3 I56-3439-000