INSTALLATION AND MAINTENANCE INSTRUCTIONS
SK-Monitor-2 Dual Monitor Module
SPECIFICATIONS
Normal Operating Voltage: 15 to 32 VDC
Maximum Current Draw: 6.4 mA (LED on)
Average Operating Current: 750µA (LED flashing)
Max. SLC wiring Resistance: 40 ohms
EOL Resistance: 47K Ohms
Max. IDC wiring resistance: 1,500 Ohms
Maximum IDC Voltage: 11.7 Volts
Maximum IDC Current: 240µA
Temperature Range: 32˚F to 120˚F (0˚C to 49˚C)
Humidity: 10% to 93% Non-condensing
Dimensions: 41/2˝ H x 4˝ W x 11/4˝ D (Mounts to a 4˝ square by 21/8˝ deep box.)
Accessories: SMB500 Electrical Box
BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
modules will be installed in an existing operational system, inform the operator and local authority that the system will be temporarily out of service. Disconnect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The Dual Monitor Module is intended for use in intelligent, two wire systems.
It provides two independent 2-wire initiating device circuits (IDC), at two separate, consecutive addresses. It is capable of monitoring normally open contact fire alarm and supervisory devices, or either normally open or normally
closed security devices. The module has a single panel controlled red LED.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
Silent Knight system control panel (list available from Silent Knight).
FIGURE 1. CONTROLS AND INDICATORS:
MOUNTING
Mounts directly to 4-inch square electrical boxes (see Figure 2). The box
must have a minimum depth of 21/8 inches. Surface mounted electrical boxes
(SMB500) are available from Silent Knight.
FIGURE 2A. MODULE MOUNTING:
I56-3435-002
12 Clintonville Road, Northford, CT 06472
203.484.7161; Fax: 203.484.7118
www.silentknight.com
C1075-00
C1067-00
SK-460-011 1 I56-3435-002
WIRING
H
L
TWO INITIATING DEVICE CIRCUITS (L&H), EACH
POWER LIMITED TO 240 mA @ 11 VDC MAX.
UL LISTED CONTACT CLOSURE DEVICES MAY
BE USED. DO NOT MIX FIRE ALARM INITIATING,
SUPERVISORY, OR SECURITY DEVICES ON THE
SAME INITIATING DEVICE CIRCUIT.
INSTALL CONTACT CLOSURE DEVICES PER
MANUFACTURER’S INSTALLATION INSTRUCTIONS.
47k EOL
RESISTOR
ELR-47k
47k EOL
RESISTOR
ELR-47k
TO NEXT
DEVICE
(+)
(−)
(+)
(−)
(+)
(−)
FROM PANEL OR
PREVIOUS DEVICE
CONNECT MODULES TO LISTED
COMPATIBLE CONTROL PANELS ONLY
MONITOR L (TERMINALS 6 & 7) RESPONDS AT ADDRESS
SET ON CODE SWITCHES. MONITOR H (TERMINALS 8 &
9) RESPONDS AT NEXT HIGHER ADDRESS.
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX. SHIELDED-TWISTED
PAIR IS RECOMMENDED
MONITOR
MODULE
ALL WIRING SHOWN IS
SUPERVISED AND POWER LIMITED
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations. This module is intended for power limited wiring only.
1. Install module wiring in accordance with the job drawings and appropriate wiring diagrams.
2. Set the address on the module per job drawings.
NOTE: Monitor module L (using terminals 6 and 7) responds at the ad-
dress set on the code switches. Monitor module H (using terminals 8 and
9) will automatically respond at the next higher address. For example, if
the code switches are set to 76, module L will respond at address 76 and
module H will respond at address 77. Use caution to avoid duplicate addressing of modules on the system.
3. Secure module to electrical box (supplied by installer), as shown in
Figure 2.
FIGURE 3. TYPICAL 2-WIRE INITIATING CIRCUIT CONFIGURATION, NFPA STYLE B:
SK-460-011 2 I56-3435-002
©2009 Honeywell International Inc.
C1074-00