INSTALLATION AND MAINTENANCE INSTRUCTIONS
0
7
8
6
5
4
3
2
1
9
10
11
12
13
14
15
(+)
(–)
TO
NEXT
DEVICE
BLACK
RED
(+)
(–)
(+)
(–)
VIOLET
YELLOW
0
1
2
3
4
5
6
7
8
9
SIGNAL LINE CIRCUIT (SLC)
47k EOL
INCLUDED
(ELR-47k)
UL LISTED
COMPATIBLE
CONTROL
PANEL
ALL WIRING
SHOWN IS
SUPERVISED AND
POWER LIMITED
TENS
ONES
12 Clintonville Road, Northford, CT 06472
SK-Minimon Monitor Module
SpECIfICATIONS
Nominal Operating Voltage: 15-32 VDC
Average Operating Current: 375µA Maximum (group poll); 350µA (direct poll); 600µA Maximum Communicating, IDC Shorted)
EOL Resistance: 47K Ohms
Maximum SLC Wiring Resistance: 40 Ohms
Max. IDC Wiring Resistance: 1,500 Ohms
Maximum IDC Voltage: 11 Volts
Maximum IDC Current: 450µA
Temperature Range: 32˚F to 120˚F (0˚C to 49˚C)
Humidity: 10% to 93% Non-condensing
Dimensions: 1.3˝ H x 2.75˝ W x 0.5˝ D
Wire length: 6˝ minimum
BEfORE INSTALLINg
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
modules will be installed in an existing operational system, inform the operator and local authority that the system will be temporarily out of service. Disconnect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
gENERAL DESCRIpTION
The SK-Minimon monitor module can be installed in a single gang junction
box directly behind the monitored unit. Its small size and light weight allow it
to be installed without rigid mounting (see Figure 1). The SK-Minimon is intended for use in intelligent, two-wire systems where the individual address of
each module is selected using rotary switches. It provides a Class B initiating
device circuit for normally open contact fire alarm and security devices.
COMpATIBILITy REqUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
Silent Knight system control panel (list available from Silent Knight).
fIgURE 1:
MOUNTINg AND WIRINg
NOTE: This module is intended to be wired and mounted without rigid connections inside a standard electrical box. All wiring must conform to applicable local codes, ordinances and regulations.
1. Connect the red (+) and black (–) wires to the positive and negative
loop power leads of the signaling line circuit (SLC).
2. Connect the violet (+) and yellow (–) wires to a two-wire, normally
open initiating loop.
3. Install the specified EOL resistor value to terminate the initiating loop.
4. Set the address on the module per job drawings.
5. Install the module in the desired mounting location.
fIgURE 2. TypICAL CLASS B STyLE B INITIATINg DEvICE
CIRCUIT CONfIgURATION:
203.484.7161; Fax: 203.484.7118
www.silentknight.com
I56-3444-001
SK-460-014 1 I56-3444-001
©2009 Honeywell International Inc.
C0614-02