SilentKnight SK-Heat User Manual

3
2
1
3
2
1
3
2
1
(–)
(+)
+-
UL LISTED COMPATIBLE
CONTROL PANEL
CAUTION: DO NOT LOOP WIRE UNDER TERMINAL 1 OR 2. BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
CLASS A OPTIONAL WIRING
REMOTE
ANNUNCIATOR
(–)
(+)
TENS ONES
9
10
11 12
13
14
15
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
INSTALLATION AND MAINTENANCE INSTRUCTIONS
I56-3429-001R
SK-Heat, SK-Heat-ROR, and SK-Heat-HT Intelligent Plug-In Temperature Sensors
SPECIFICATIONS
Diameter: 6.1˝ (155mm) installed in B210LP; 4.1˝ (104mm) installed in B501 Height: 2.0˝ (51mm) Weight: 4.8 ounces (137 gm) Installation Temperature: –4°F to 100°F (–20°C to 38°C), SK-Heat and SK-Heat-ROR; –4°F to 150°F (–20°C to 66°C), SK-Heat-HT Operating Humidity Range: 10% to 93% Relative Humidity, Non-condensing Mounting: B210LP flanged base; B501 flange less base Voltage Range: 15 to 32 Volts DC Peak Standby Current: 300 µA @ 24 VDC LED Current: 6.5 mA @ 24 VDC Fixed Temperature Rating: 135°F (57°C) SK-Heat and SK-Heat-ROR; 190°F (88°C) SK-Heat-HT Rate-of-Rise Detection: Responds to greater than 15°F/minute; SK-Heat-ROR
This sensor must be installed in compliance with the control panel system installation manual. The installation must meet the requirements of the Au­thority Having Jurisdiction (AHJ). Sensors offer maximum performance when installed in compliance with the National Fire Protection Association (NFPA); see NFPA 72.
Before installing sensors, please read the system wiring and installation man­ual thoroughly. This manual provides detailed information on sensor spac­ing, placement, zoning, and special applications. Copies of these manuals are available from Silent Knight.
Models SK-Heat, SK-Heat-ROR and SK-Heat-HT are intelligent sensors that utilize a state-of-the-art thermistor sensing circuit for fast response. These sensors are designed to provide open area protection with 50 foot spacing capability as approved by UL 521. Model SK-Heat is a fixed temperature sensor with 135° F fixed temperature alarm. SK-Heat-ROR is a rate-of-rise tempera­ture sensor with 135° F fixed temperature alarm. Model SK-Heat-HT is a high temperature sensor with 190° F fixed temperature alarm.
Two LEDs on each sensor light to provide a local, visible sensor indication. Remote LED annunciator capability is available as an optional accessory (Part No. RA400Z/RA100Z).
Models SK-Heat, SK-Heat-ROR, and SK-Heat-HT require compatible ad­dressable communications to function properly. Connect these sensors to listed-compatible control panels only.
WIRING GUIDE
All wiring must be installed in compliance with the National Electrical Code, applicable local codes and the Authority Having Jurisdiction. Proper wire gauges should be used. The installation wires should be color coded to limit wiring mistakes and ease system troubleshooting. Improper connections will prevent a system from responding properly in the event of a fire.
Remove power from the communication line before installing sensors.
1. Wire the sensor base (supplied separately) per the wiring diagram, see Figure 1.
2. Set the desired address on the sensor address switches, see Figure 2.
3. Install the sensor into the sensor base. Push the sensor into the base while turning it clockwise to secure it in place.
4. After all sensors have been installed, apply power to the control unit and activate the communication line.
5. Test the sensor(s) as described in the TESTING section of this manual.
SK-400-006 1 I56-3429-001R
12 Clintonville Road, Northford, CT 06472
203.484.7161; Fax: 203.484.7118 www.silentknight.com
FIGURE 1. WIRING DIAGRAM:
C0129-00
FIGURE 2:
C0162-00
TAMPER RESISTANCE
The sensor base includes a tamper proof feature which when activated pre­vents removal of the sensor without the use of a tool. See the installation instruction manual for the sensor base for details in using this feature.
TESTING
Before testing, notify the proper authorities that the system is undergoing maintenance, and will temporarily be out of service. Disable the system to prevent unwanted alarms.
All sensors must be tested after installation and periodically thereafter. Test­ing methods must satisfy the Authority Having Jurisdiction (AHJ). Sensors offer maximum performance when tested and maintained in compliance with NFPA 72.
A. Test Magnet (Model No. M02-04 - optional)
LED
TEST MAGNET MARKER
LED
TEST MAGNET MARKER
1. Place the optional test magnet against the cover in the magnet test area, as shown in Figure 3, to activate the test feature (part number K200-07-00).
2. The LEDs should latch on within 10 seconds, indicating alarm and annunciating the panel.
3. Reset the detector at the system control panel.
B. Direct Heat Method (Hair dryer of 1000–1500 watts)
1. From the side of the detector, direct the heat toward the sensor. Hold the heat source about 6 inches (15 cm) away to prevent damage to the cover during testing.
2. The LEDs on the detector should light when the temperature at the detector reaches the alarm setpoint. If the LEDs fail to light, check the power to the detector and the wiring in the detector base.
3. Reset the detector at the system control panel.
Detectors that fail these tests should be cleaned as described under MAIN­TENANCE and retested. If the detectors still fail these tests, they should be returned for repair.
FIGURE 3. VIEWS SHOWING POSITION OF TEST MAGNET:
MAINTENANCE
NOTE: Before cleaning notify the proper authorities that the system is un­dergoing maintenance, and therefore the system will temporarily be out of service. Disable the loop or system undergoing maintenance to prevent un­wanted alarms.
It is recommended that the sensor be removed from its mounting base for easier cleaning and that sensors be cleaned at least once a year. Use a vacuum cleaner to remove dust from the sensing chamber.
FIGURE 4:
C0151-00
FM CLASSIFICATION
RTI ratings are for installations which must comply with FM 3210.
SK-Heat RTI: FAST
SK-Heat-ROR RTI: V2-FAST
SK-Heat-HT RTI: QUICK
C0152-00
Please refer to insert for the Limitations of Fire Alarm Systems
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installa­tion. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: – Reorient or relocate the receiving antenna. – Increase the separation between the equipment and receiver. – Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. – Consult the dealer or an experienced radio/TV technician for help.
SK-400-006 2 I56-3429-001R ©2009 Honeywell International Inc.
FCC STATEMENT
Loading...