SilentKnight SKE-SRM User Manual

SKE-SRM Remote Microphone Module Installation Instructions
The SKE-SRM is a supervised remote microphone assembly that can be added to the SKE-Series voice evacuation system.
Compatibility
The SKE-SRM is compatible with the SKE­Series voice evacuation system.
Mounting
It is important to protect the SKE-SRM control panel from water. To prevent water damage, the following conditions should be avoided when installing the units:
Do not mount directly on exterior walls, especially masonry walls (condensation)
Do not mount directly on exterior walls below grade (condensation)
Protect from plumbing leaks
Protect from splash caused by sprinkler inspection ports
Do not mount in areas with humidity-gener­ating equipment (such as dryers, production machinery)
When selecting a location to mount the SKE­SRM cabinet, the unit should be mounted where it will NOT be exposed to temperatures outside the range of 0°C-49°C (32°F-120°F) or humidity outside the range of 10%-85% at 30°C (86°F) noncondensing.
To mount the remote microphone cabinet:
1. Remove the SKE-SRM from it’s packing container.
2. Unlock the cabinet and remove the cabinet door.
3. Unplug microphone from microphone connector. Place microphone in a safe location while completing cabinet installation.
4. Remove the cover plate by un-screwing the four cover plate screws. Set the screws aside for later use.
5. Remove the remote microphone chassis assembly by un-screwing the two chassis assembly screws. See Figure 1.
Chassis Mounting Screw
Figure 1: Remote Microphone Chassis Assembly
P/N 151396
SKE-SRM Remote Microphone Module Installation Instructions
6. Mount the cabinet using the appropriate screws and anchors, through the cabinet mounting holes. See Figure 2.
Cabinet Mounting Holes
Figure 2: Cabinet Mounting Hole Locations
Wiring
Use shielded 4 conductor 22 AWG (up to 5000 feet) wiring for the remote microphone. The wiring is supervised by the main panel if switch 4 on SW2 is set to ON.
Figure 3 illustrates how to wire the SKE-SRM to the main control panel.
Microphone
Gain
Supervised Power Limited
Figure 3: The SKE-SRM Wiring Connections to the
SKE-450
Electical Specifications
Ground Fault Impedance To Any Terminal: 0 Ω
Standby Input Power: 27.4 VDC @ 30 mA
Alarm Input Power: 27.4 VDC @ 30 mA
Maple Grove, MN 55369-4927
763-493-6455 or 800-328-0103
© 2005 Silent Knight PN 151396 Rev B
2
7550 Meridian Circle
Fax: 763-493-6475
www.silentknight.com