SILENT KNIGHT INTELLIKNIGHT 5820XL, INTELLIKNIGHT 5820XL-EVS Installation And Operation Instruction Manual

INTELLIKNIGHT
5820XL
5820XL-EVS
Addressable Fire System
Emergency Voice System
Installation and Operations Manual
Document LS10061-001SK-E 10/30/2014 Rev:
P/N LS10061-001SK-E:E ECN: 14-0724
E
Installation Procedure
Installation Precautions - Adherence to the following will aid in problem-free installation with long-term reliability: WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources
of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserti ng card s, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood. CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system operation, this product must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Re-acceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified. This system meets NFPA requirements for operation within the range of 0°C-49°C (32°F-120°F) or humidity within the range of 10%-93% at 30°C (86°F) non­condensing. However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27º C/60-80º F . Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage. Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered. Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits. Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, or printed circuit board location. Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal. fire alarm control panels contain static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. Th ese instructions must be followed to avoid damage to the control panel and associated equipment. Fire Alarm Control Panel (FACP) operation and reliability depend upon proper installation.
While installing a fire alarm system may make lower insurance rates possible, it is not a substitute for fire insurance! An automatic fire alarm system - typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control with remote notification capability - can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire. Any fire alarm system may fail for a variety of reasons: Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second floor detector, for example, may not sense a first floor or basement fire. Furthermore, all types of smoke detectors, including ionization and photoelectric types, have sensing li mitations. No type of smoke detector can sense every kind of fire caused by carelessness and safety hazards like smoking in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children playing with matches, or arson.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire. Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time. Rate-of-Rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment listed for service with your control panel. Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. The most common cause of fire alarm malfunctions, however, is inadequate maintenance. All devices and system wiring should be tested and maintained by professional fire alarm installers following written procedures supplied with each device. System inspection and testing should be scheduled monthly or as required by national and/or local fire codes. Adequate written records of all inspections should be kept.
Contents
Section 1
Introduction ..................................................................................................................................................1
1.1 Overview of Basic System ...........................................................................................................1
1.1.1 Addressable Fire Alarm Control/Communicator Hardware Features ...................................1
1.1.2 5820XL-EVS Emergency Voice Hardware Features ............................................................1
1.1.3 Software Features ................................................................................................................2
1.2 About this Manual ........................................................................................................................2
1.2.1 Terms Used in this Manual ...................................................................................................2
1.3 Compatible Products .................................................... ... ... ....................................... ... ... ............3
1.4 How to Contact Silent Knight .......................................................................................................4
Section 2
Agency Listings, Approvals, and Requirements .......................................1
2.1 Federal Communications Commission (FCC) .............................................................................1
2.2 Underwriters Laboratories (UL) ...................................................................................................2
2.2.1 Requirements for All Installations .........................................................................................2
2.2.2 Requirements for Central Station Fire Alarm Systems ................ ......................................... 2
2.2.3 Requirements for Local Protected Fire Alarm Systems ......... .......................... .....................3
2.2.4 Requirements for Remote Station Protected Fire Alarm Systems .......................................3
Section 3
Before You Begin Installation ..............................................................................................1
3.1 What’s in the Box? ......................................................................................................................1
3.2 Environmental Specifications ................... .... .......................................... .....................................1
3.3 Electrical Specifications ................... ... .........................................................................................2
3.4 Wiring Specifications ...................................................................................................................3
3.5 Board Assembly Diagram ...................... ... .... ...............................................................................5
3.6 Calculating Current Draw and Standby Battery ...........................................................................6
3.6.1 Current Draw Worksheet Requirements .......................... ......................... .......................... ..6
3.6.2 Current Draw Worksheet for SK SLC Devices ...... ... ... .... ... ... ... ... .... ... ... ... ............................6
3.6.3 Current Draw Worksheet for SD SLC Devices ...................................................................10
3.6.4 Maximum Battery Standby Load ........................................................................................12
3.7 Installation Tasks Overview .......................................................................................................12
Section 4
Control Panel Installation ..........................................................................................................1
4.1 Mounting the Control Panel Cabinet ...........................................................................................1
4.1.1 Preventing Water Damage ...................................................................................................1
4.1.2 Removing the 5820XL / 5820XL-EVS Assembly from the Housing .....................................1
4.2 AC Connection ................... ... ... .... ... ... ... ... .... ...................................... .... ... ... ... .... ... .....................1
1
Model 5820XL/ 5820XL-EVS Installation Manual
4.3 Battery Connection ......................................................................................................................2
4.3.1 RBB Accessory Cabinet ........... ....................................... ... ... ... ... .... ... ..................................3
4.3.1.1 Installing the RBB Accessory Cabinet and Batteries ..................................................3
4.4 SBUS Wiring ......................................................... .... ... ... ....................................... ... ..................4
4.4.1 Calculating Wiring Distance for SBUS Modules ................................................................... 5
4.4.2 Wiring Configurations ...........................................................................................................7
4.5 5860 Remote Annunciator Installation ........................................................................................8
4.5.1 Mounting the 5860 ................................................................................................................9
4.5.1.1 Flush Mounting ..........................................................................................................10
4.5.1.2 Surface Mounting ......................................................................................................12
4.5.2 Model 5860 Connection to the Panel ................................................. ... ... .... ... ... ... ... .... ......12
4.6 5815XL Installation ....................................................................................................................12
4.6.1 5815XL Connection to the Panel ........................................................................................13
4.7 5824 Serial/Parallel Interface Module Installation .....................................................................14
4.7.1 Selecting 5824 Options ......................................................................................................15
4.8 5880 LED I/O Module ................................................................................................................16
4.8.1 5880 Board Layout ................... ... ... ....................................... ... ... .... ... ... ... ..........................16
4.8.2 5880 Connection to Panel ..................................................................................................16
4.8.3 LED Wiring .........................................................................................................................18
4.8.4 Dry Contact Wiring .............................................................................................................18
4.9 5865-3 / 5865-4 LED Annunciator Installation ........................ ................ ................ ................ ...20
4.9.1 5865 Connection to Panel ..................................................................................................20
4.9.2 5865 Mounting ................... .... ...................................... .... ... ... .............................................21
4.10 Configuring Modules .................................................................................................................22
4.10.1 Assigning SBUS Module IDs ............................................................................................22
4.11 Telephone Connection ..............................................................................................................23
4.12 Flexputs
I/O Circuits ...............................................................................................................23
4.12.1 Conventional Notification Appliance .................................................................................23
4.12.1.1 Class B Notification Wiring .......................................................................................24
4.12.1.2 Class A Notification Wiring .......................................................................................24
4.12.2 Conventional Input Switch Circuits ...................................................................................25
4.12.2.1 Class B Inputs ..........................................................................................................26
4.12.2.2 Class A Inputs ..........................................................................................................26
4.12.3 Installing 2-Wire Smoke Detectors ................................................................................... 27
4.12.3.1 Installing 2-Wire Class B Smoke Detectors .............................................................27
4.12.3.2 Installing 2-Wire Class A Smoke Detectors .............................................................28
4.12.4 Installing 4-Wire Smoke Detectors ................................................................................... 28
4.12.4.1 Installing 4-Wire Class B Smoke Detectors .............................................................28
4.12.4.2 Installing 4-Wire Class A Smoke Detectors .............................................................29
4.12.5 Auxiliary Power Installation .............. .......................... ....................... ...................... ..........30
4.12.5.1 Door Holder Power ...................................................................................................30
4.12.5.2 Constant Power ........................................................................................................30
4.12.5.3 Resettable Power ........................ ...................................... .......................................30
4.12.5.4 Sounder Sync Power ...............................................................................................31
4.13 On-Board Relays (Conventional) ..............................................................................................31
4.13.1 Trouble Relay .................. .... ...................................... .... ... ... ... ... .... ...................................31
4.13.2 Programmable Relays ......................................................................................................31
4.14 Remote Station Applications .....................................................................................................31
4.14.1 Keltron Model 3158 Installation ........................................................................................31
4.14.2 City Box Connection Using the 5220 Module ...................................................................32
4.14.3 NFPA 72 Polarity Reversal ...............................................................................................33
4.14.3.1 Using the 5220 Module ............................................................................................33
4.14.3.2 Using the 7644* Module ...........................................................................................34
4.14.4 Using the SD500-ARM Addressable Relay Module .........................................................35
2
4.14.5 Using a MR-201/T Control Relay From Air Products ........................ .......................... ......35
4.14.6 Transmitter Activated by Dry Contacts ...................................... .... ... ... ... .... ... ... ... ... ..........37
Section 5
SK SLC Device Installation .....................................................................................................1
5.1 List of SK SLC Devices ...............................................................................................................1
5.2 List of SD SLC Devices ...............................................................................................................2
5.3 Maximum Number of Devices .....................................................................................................2
5.4 Wiring Requirements for SLC Devices ........................................................................................3
5.4.1 Wiring 5815XL in Style 4 (Class B) Configuration ................................................................ 3
5.4.2 Wiring 5815XL in Style 6 & 7 (Class A) Configuration ........................................... ...............5
5.5 Wiring SK SLC Detectors ............................................................................................................5
5.6 Addressing SK SLC Devices .......................................................................................................6
5.7 Wiring SD SLC Detectors ............................................................................................................7
5.8 Addressing SD Devices ...............................................................................................................7
5.8.1 SD505-APS, SD505-AHS, and SD505-AIS ..........................................................................7
5.8.2 SLC Devices with DIP Switches ...........................................................................................9
Section 6
Programming Overview ...............................................................................................................1
6.1 Security and Data Protection .................... ................. ................ ................ ................ ..................1
6.2 JumpStart Autoprogramming ......................................................................................................1
6.2.1 Input Points ............... ...................................... .... ... ....................................... ... ... ..................2
6.2.2 Output Points ........................................................................................................................2
6.2.3 Running JumpStart AutoProgramming .................................................................................2
6.3 Mapping Overview .......................................................................................................................4
6.3.1 Input Point Mapping .................. ... ... ... .... ... ... ....................................... ... ... .... ... ... ... ... ............5
6.3.2 Output Circuit Mapping .........................................................................................................6
6.3.3 Zone Event Mapping ............................................................................................................7
6.3.4 Mapping LED Points .............................................................................................................9
6.4 Programming Using the 5660 Silent Knight Software Suite ......................................... ... .... ... ... ..9
6.5 Programming Using an Annunciator .........................................................................................10
6.5.1 Entering / Exiting the Program Menu ..................................................................................10
6.5.1.1 Moving through the Menus ........................................................................................11
6.5.1.2 Selecting Options and Entering Data ........................................................................11
6.5.1.3 Editing Keys ..............................................................................................................12
6.6 Programming Menu Quick Reference ....................................................................................... 13
Section 7
Programming .............................................................................................................................................1
7.1 UL 864 / UL 2572 Programming Requirements ..................... ... ... ... ... .... .....................................1
7.2 Modules ................................. ............................................. .........................................................1
7.2.1 Edit Modules .........................................................................................................................2
7.2.1.1 Naming Modules .........................................................................................................2
7.2.1.2 Editing Module Features .............................................................................................2
7.2.2 Adding a Module ................ .... ...................................... .... ... ... ...............................................2
7.2.3 Deleting a Module .................................................................................................................3
3
Model 5820XL/ 5820XL-EVS Installation Manual
7.2.4 View Module List ..................................................................................................................3
7.3 Zone ............................................................................................................................................3
7.3.1 Edit Zone ..............................................................................................................................3
7.3.1.1 Edit Zone Name ..........................................................................................................4
7.3.1.2 Edit Zone Properties ...................................................................................................4
7.3.1.3 Zone Outputs ..............................................................................................................5
7.3.1.4 Cadence Patterns .......................................................................................................7
7.3.1.5 Zone Accessory Options .............................................................................................8
7.3.2 Add Zone .................................................................................. ... .........................................9
7.3.3 Delete Zone ........................................... ... ....................................... ... ..................................9
7.3.4 View Zone Points ..................................................................................................................9
7.4 Group ........................................................................................................................................10
7.4.1 Edit Group ..........................................................................................................................10
7.4.1.1 Edit Group Name ......................................................................................................10
7.4.1.2 Edit Group Properties ................................................................................................11
7.4.2 Add Group ................... ....................................... ... ... ... ....................................... ... .............12
7.4.3 Delete Group ............... ... ... ....................................... ... .... ... ................................................12
7.4.4 View Group Points ..............................................................................................................13
7.4.5 Edit Output Group Templates .............................................................................................13
7.5 Point ..........................................................................................................................................14
7.5.1 Point Programming For 5815XL Module ............................................................................14
7.5.2 Point Programming For Internal or External Power Module ......................... ... ... ... ... .... ... ...18
7.5.3 Point Programming For 5880, 5865, EVS-50W, EVS-100W,
EVS-125W and EVS-CE4 Modules ....................................................................................20
7.5.4 Point Programming For EVS-VCM and EVS-RVM Modules ..............................................20
7.5.5 Assigning a Name to Points ...............................................................................................21
7.6 System Options ............................................... ... ... .... ... ... ....................................... ... ... .............22
7.6.1 Reporting Account ..............................................................................................................22
7.6.1.1 Edit Accounts ............................................................................................................22
7.6.1.2 Auto Test Time ..........................................................................................................24
7.6.2 Phone Lines ........................................................................................................................24
7.6.2.1 Dialing Prefix .............................................................................................................25
7.6.2.2 Number of Answer Rings ................... ... .... ... ... ... .... ...................................... ... .... ... ...25
7.6.2.3 Dial Option (TouchTone or Pulse) .............................................................................26
7.6.2.4 Rotary Format ...........................................................................................................26
7.6.2.5 Line Monitor ..............................................................................................................26
7.6.2.6 Answering Machine Bypass ......................................................................................26
7.6.3 System Event Outputs ................. ... ... .... ... ... ....................................... ... ... .... ... ... ... .............26
7.6.3.1 Trouble Events ..........................................................................................................27
7.6.3.2 System Alarm Cadence ............................................... ... ... .... ... ... ... ..........................27
7.6.4 Time Options ......................................................................................................................28
7.6.4.1 Water Flow Delay ......................................................................................................28
7.6.4.2 Alarm Verification Time .............................................................................................28
7.6.4.3 Low AC Report Delay ................... ... ... ... .... ... ... ... .... ...................................... ... .... ... ...29
7.6.4.4 Clock Display Format (AM/PM or Military) ................................................................29
7.6.4.5 Change AC Line Frequency ......................... ................................................ ............. 29
7.6.5 Miscellaneous Options ............................................. ... .... ...................................... ... .... ......29
7.6.5.1 Synchronize Strobes Active During Silence ..............................................................29
7.6.5.2 Auto Display Oldest Event ........................................................................................30
7.6.5.3 Report by Zone or by Point .......................................................................................30
7.6.5.4 Plex Door Option .......................................................................................................30
7.6.5.5 Single Key Acknowledge ..........................................................................................30
7.6.6 Daylight Savings .................................................................................................................30
7.6.6.1 Automatic Daylight Savings Adjustment ............................................. ... ... ... ... .... ... ...30
4
7.6.6.2 Daylight Saving Time Start and End .........................................................................30
7.6.7 Edit Banner .........................................................................................................................31
7.6.8 SLC Family .........................................................................................................................32
7.7 JumpStart Autoprogramming ....................................................................................................32
7.8 Computer Account .....................................................................................................................33
7.9 Access Codes ...........................................................................................................................34
7.9.1 Profile Edit Menu ................................................................................................................35
7.9.1.1 Edit Name .................................................................................................................35
7.9.1.2 Edit Access Code ......................................................................................................35
7.9.1.3 Panel Functions ........................................................................................................35
7.10 Voice Options . .... ...................................... .... ... ... ....................................... ... ... .... ......................35
7.10.1 EVS-VCM Maintenance ....................................................................................................35
7.10.1.1 PC Connection .........................................................................................................36
7.10.1.2 Local Recording .......................................................................................................36
7.10.2 Edit Voice Commands ......................................................................................................36
7.10.3 EVS System Options ........................................................................................................36
7.10.3.1 Enable EVS System .................................................................................................36
7.10.3.2 Edit Command Priority ............................................................................................. 37
7.10.3.3 Edit Command Mapping ...........................................................................................37
7.10.3.4 Edit Timers ...............................................................................................................38
7.10.3.5 Edit Event Names ....................................................................................................38
Section 8
System Operation ................................................................................................................................1
8.1 User and Installer Default Codes ................................................................................................1
8.2 Annunciator Description ..............................................................................................................1
8.2.1 LCD Display ..........................................................................................................................1
8.2.2 Banner ............................................... .... ...................................... .... ... ... ...............................1
8.3 Key Operation .............................................................................................................................2
8.4 Menu System .................................................. ... ....................................... ... ... ............................2
8.4.1 Main Menu Overview ............................................................................................................3
8.4.2 Using the Menus ...................................................................................................................3
8.5 Basic Operation ...........................................................................................................................3
8.5.1 Setting Time and Date ..........................................................................................................3
8.5.2 Disable / Enable a Point .......................................................................................................3
8.5.2.1 Disable / Enable NACs by Template ...........................................................................4
8.5.3 Disable / Enable NACs by Group .........................................................................................4
8.5.3.1 Disable / Enable Zone Points ......................................................................................4
8.5.4 View Event History ...............................................................................................................4
8.5.5 To clear the event history ............ ....................................... ... ... ... .... ... ... ...............................4
8.5.6 Conduct a Fire Drill ................... ... ... ....................................... ... ... .... .....................................4
8.5.7 Conduct an Indicator Test ....................................................................................................4
8.5.8 Conduct a Walk Test ......... .... ... ... ... ... .... ...................................... .... ... ... ...............................5
8.5.9 Conduct a Dialer Test .................. ... ... ....................................... ... .... ... ..................................5
8.5.10 Silence alarms or troubles ..................................................................................................5
8.5.11 Reset alarms ......................................................................................................................6
8.5.12 Check Detector Sensitivity Through Point Status ...............................................................6
8.5.13 View Status of a Point ........................................................................................................7
8.5.14 View Alarms, Supervisories or Troubles .............................................................................7
8.5.15 View System Information ....................................................................................................7
8.5.16 Reset Items ........................................................................................................................7
5
Model 5820XL/ 5820XL-EVS Installation Manual
8.5.16.1 Reset Dialer ...............................................................................................................7
8.5.16.2 Reset DSP USB .........................................................................................................7
8.5.17 Communicating with a Remote Computer ..........................................................................8
8.5.18 Working with a Printer ........................................................................................................9
8.6 Operation Mode Behavior ............................................................ ... ... .......................................10
8.7 Releasing Operations ............................ ... .... ...................................... .... ... ... ... .... ... ...................15
8.7.1 Single Interlock Zone Releasing .........................................................................................16
8.7.2 Double Interlock Zone Releasing ................................ .... ... ... ... ... .... ... ................................17
8.8 Smoke Alarm Verification ................................................ ... .... ... ... ... ... .... ... ... ... ..........................18
Section 9
Emergency Voice System Operation .........................................................................1
9.1 Overview .....................................................................................................................................1
9.2 LOC Functionality ......................... ... ... ... ... .... ...................................... .... ... ... ... .... ... .....................1
9.2.1 Keys and LEDs ............... ... .... ... ... ... ... .... ...................................... .... .....................................1
9.2.1.1 EVS Control Key .........................................................................................................1
9.2.1.2 EVS Control LED ........................................................................................................2
9.2.1.3 ALL CALL Key .............................................................................................................2
9.2.1.4 NON-ACTIVE CALL Key .............................................................................................2
9.2.1.5 EVS Message Keys ....................................................................................................2
9.2.1.6 EVS Message LEDs ....................................................................................................2
9.2.1.7 Select Keys .................................................................................................................2
9.2.1.8 Select Key LEDs .........................................................................................................2
9.2.2 Gaining EVS Control ............................................................................................................3
9.2.2.1 LOC Priority .................................................................................................................3
9.2.2.2 LOC Lockout ...............................................................................................................3
9.2.2.3 User Profile Access Control ........................................................................................4
9.2.3 Manual EVS ..........................................................................................................................4
9.2.3.1 Switching between Microphone Mode and Message Mode ........................................4
9.2.3.2 Activating/Deactivating Output Groups Dynamically .............................. ..................... 4
9.2.4 Microphone Mode .................................................................................................................4
9.2.5 Message Mode .....................................................................................................................5
9.2.6 Custom EVS Event ...............................................................................................................5
9.2.7 Passing EVS Control ............................................................................................................5
9.2.8 Exit EVS Control Menu .........................................................................................................5
9.2.9 Relinquish EVS Control ........................................................................................................5
9.2.10 EVS Reset .............................................................................................................
9.2.11 Access Control ...................................................................................................................6
9.3 EVS Super User ..........................................................................................................................6
9.4 EVS Point Functionality ...............................................................................................................6
9.4.1 EVS Point Activations ...........................................................................................................6
9.4.2 EVS-VCM Points ..................................................................................................................7
9.5 EVS 5880 ....................................................................................................................................7
9.5.1 EVS (1-8) 5880 Module ........................................................................................................7
9.5.2 Enable 5880 EVS .................................................................................................................7
9.6 EVS LOC Programming ..............................................................................................................7
9.6.1 Adding an LOC ............................................... .... ... ... ... .... ... ...................................... ............7
9.6.2 Editing an LOC .....................................................................................................................8
9.6.2.1 LOC Priority .................................................................................................................8
9.6.2.2 LOC Association .........................................................................................................8
9.7 Amplifier Programming ................................................................................................................9
.............6
6
9.7.1 Adding an Amplifier ..............................................................................................................9
9.7.2 Editing an Amplifier ...............................................................................................................9
9.8 Event Priority .............................................................................................................................10
9.8.1 System Control ............................................ ... ....................................... ... .... ... ...................10
9.8.2 System Override ............. ... ....................................... ... .... ... ...................................... ..........10
9.8.3 EVS Event Priority ..............................................................................................................10
9.8.4 View Active Alarms, Troubles and Supervisory Signals .....................................................11
9.9 Using the Microphone ...............................................................................................................11
9.9.1 Microphone Functionality ....................................................................................................11
9.9.2 Custom EVS Event .............................................................................................................11
9.9.3 Fire Page ............................................................................................................................12
9.9.4 Emergency Page ................................................ ... ... ... .... ... ... .............................................12
9.9.5 Paging ............................................ ... .... ... ... ... .... ...................................... .... ......................12
9.10 Recording Custom Messages ...................................................................................................13
9.10.1 Recording Messages 1-15 Using Aux Audio Input ...........................................................14
9.10.2 Recording Messages 1-15 Using the Microphone ............................................................16
9.10.3 Erasing User Message ................. ... .... ... ... ....................................... ... ... .... ... ... ... ... .... ......17
9.10.4 Using EVS Message Manager Software ..........................................................................18
9.11 EVS Priority ...............................................................................................................................19
9.11.1 Priority Rules ....................................................................................................................19
9.12 Defining Output Group Type .....................................................................................................20
9.13 Voice Command Mapping .........................................................................................................21
9.13.1 Voice System Mapping .....................................................................................................21
9.13.2 EVS Voice Aux Inputs (Dynamic with VCM/RVM in the system) .....................................21
9.13.3 Edit Command Mapping ...................................................................................................23
9.13.3.1 Mapping for Voice Commands .............................. ............................................. ...... 23
9.14 EVS Timer Options ....................................................................................................................24
9.14.0.2 Timers include ..........................................................................................................24
9.14.0.3 EVS Timer Menu ......................................................................................................24
Section 10
Reporting .........................................................................................................................................................1
10.1 Receivers Compatible with the Control Panel .............................................................................1
10.2 Reporting Formats Table .............................................................................................................1
Section 11
Testing and Troubleshooting ...............................................................................................1
11.1 Troubleshooting ........................................ ................. ................... ................ ...............................1
11.2 Common Problems .......................... ... ... ... .... ... ....................................... ... ... ... .... ... ... ... ... ............1
11.3 Periodic Testing and Maintenance ..............................................................................................3
11.4 Event History ...............................................................................................................................3
11.5 Built-in Troubleshooting and Testing Tools .................................................................................3
11.5.1 SLC Device Locator ............................................................................................................3
11.5.2 SLC Multiple Locator ..........................................................................................................5
11.5.3 I/O Point Control .................................................................................................................6
11.5.4 Earth Fault Resistance .......................................................................................................7
7
Model 5820XL/ 5820XL-EVS Installation Manual
Section 12
Installation Records .......................................................................................................................... 1
12.1 Detector and Module Point Record .............................................................................................1
12.2 Conventional Output Point Record ............................... ............................................. ..................5
Appendix A
Compatible Device ..............................................................................................................................1
Appendix B
Special Characters Lists .............................................................................................................1
Silent Knight Fire Product Warranty and Return Policy Manufacturer Warranties and Limitation of Liability IntelliKnight 5820XL Basic Operating Instructions 5820XL-EVS Basic Operating Instructions
8
LS10061-001SK-E
Section 1 Introduction
The IntelliKnight 5820XL Fire Alarm Control/Communicator is an addressable fire control system that meets the requirements of UL 864.
The 5820XL/EVS integrates an Emergency Voice System that meets the requirements of UL 864 and UL 2572.
1.1 Overview of Basic System
The IntelliKnight 5820XL and 5820XL-EVS base system is packaged as an assembled stack of 3 circuit boards mounted to an aluminum housing.
1.1.1 Addressable Fire Alarm Control/Communicator Hardware Features
The IntelliKnight 5820XL and 5820XL-EVS panel has one signaling line circui t (SLC). Up to three
additional SLC loops can be added using the 5815XL SLC expander. The SLC(s) supports SK addressable detectors and modules or SD protocol detectors and modules.
Each SLC supports 99 SK detectors and 99 SK modules for a total of 396 SK detectors and 396 SK modules
per 5820XL/EVS or 127 SD devices for a total of 508 SD devices per 5820XL/EVS.
6.0A of output power is available through 6 sets of terminals for notification and auxiliary applications.
Each circuit is power limited per UL 864 and can source up to 3.0A (total output power must not exceed
6.0A).
Built-in dual phone line, digital alarm communicator/transmitter (D ACT).
Reports events to central station by point or by zone.
UL Listed for pre-action and deluge releasing systems.
Dedicated Form C trouble relay and two general purpose Form C programmable relays.
Basic system operation can be performed using a key or a user code.
Can be used with up to twelve Model 5860s Remote Annunciators (sold separately).
Supports the 5865-3, 5865-4, and 5880 in any combination for a total of eight devices on one control panel.
Printing of detector status, event history, and real time event log available through the Model 5824 Serial/
Parallel Printer Interface Module (sold separately).
Supports conventional 2-wire & 4-wire detectors using the 6 Flexput™ circuits.
Add six Flexput™ circuits with each 5895XL Intelligent Power Module (up to eight 5895XLs per system).
See note below.
Add four notification/auxiliary power circuits with each 5496 Intelligent Power Module. See note below.
Note: The system can support a maximum of eight Intelligent Power modules, either the 5895XL or 5496, in any
combination.
1.1.2 5820XL-EVS Emergency Voice Hardware Features
The EVS-VCM has a built-in Digital Message Repeater.
15 EVS messages.
Single enclosure for system control components.
SBUS addressable amplifier. The system can support a combination of up to four EVS-50W, EVS-125W or
EVS-100W amplifiers for a maximum of 500 watts per system.
On-board supervised microphone.
5820XL/EVS can support up to four EVS-RCU's (Remote Command Units).
1-1
Model 5820XL/ 5820XL-EVS Installation Manual LS10061-001SK-E
Up to 32 mappable speaker circuits using a combination of EVS-50W, EVS-100W, EVS-125W and
EVS-CE4's.
Supports 25 Vrms or 70.7 Vrms speaker circuits using EVS-50W or EVS-100W.
Supports 25 Vrms speaker circuits using EVS-125W.
1.1.3 Software Features
Advanced smoke detector features:
Automatic drift compensation Maintenance alert region Point status meets calibrated smoke test requirements for NFPA 72
“JumpStart” feature for easy programming.
125 software zones, 250 output groups.
Non-volatile event history stores 1000 events.
A choice of output patterns available for notification outputs, including ANSI 3.41 temporal signal.
Built-in synchronization appliance support for AMSECO, Faraday, Gentex
Wheelock.
®
®
, System Sensor®, and
1.2 About this Manual
This manual is intended to be a complete reference for all installation and operation tasks for the 5820XL* and 5820XL/EVS**. Please let us know if the manual does not meet your needs in any way. We value your feedback!
* All references to 5820XL within this manual are applicable to the 5820XL-EVS. ** Further installation instructions for the 5820XL-EVS and accessories can be found in the EVS Series
installation manual P/N LS10062-001-SK-E.
1.2.1 Terms Used in this Manual
The following terminology is used with the above mentioned control panels:
Term Description
SLC Signaling line circuit Module The term module is used for all hardware devices except for SLC
addressable devices and notification appliances. This includes the 5820XL/ EVS panel itself and the built-in 5897 power supply. It also refers to any (optional) 5815XL SLC expansion modules.
Input Point An addressable sensing device, such as a smoke or heat detector or a
contact monitor device. Input Zone A protected area made up of input points. Output Point
(or “Output Circuit”) Output Group (OPG) A group of output points. Operating characteristics are common to all output
Output (or “Cadence”) Pattern The pattern that the output will use, for example, Constant, March Code,
Mapping Mapping is the process of specifying which outputs are activated when
EVS Emergency Voice System.
A notification point or circuit for notification appliances. Relay circuits and
auxiliary power circuits are also considered output points.
points in the group.
ANSI 3.41. Applies to zones and special system events. See Section 7.6.3.2
for additional information.
certain events occur in the system. Section 6.3 explains mapping in detail.
1-2
LS10061-001SK-E Introduction
1.3 Compatible Products
Table 1-1 lists the products available from Silent Knight for use with the 5820XL and 5820XL-EVS.
Table 1-1: 5820XL/EVS Compatible Products
Type of Device Model Description
SK Addressable
SLC Devices
SD Addressable
SLC Devices
Other Modules
Misc.
See Section 5.1 for a list of compatible devices.
See Section 5.2 for a list of compatible devices.
5815XL SLC Expander Allows an additional 127 SD devices or 99 SK detectors and 99 SK modules to
5824 Serial/Parallel Printer Interface Module
5895XL Intelligent Power Module
5496 Intelligent Power Module Provides 4 additional Notification Appliance Circuits/
5860 and 5860R Remote Fire Alarm Annunciator
5860TG and 5860TR Trim Ring Kit
5865-3 and 5865-4 LED Annunciator
5880 LED I/O Module Driver for up to 40 LEDs. Interfaces with customized
5883 General Purpose Relay Module
EVS-VCM Voice Control Module used with the 5820XL-EVS. EVS-SW24 24 switch expander used with the 5820XL-EVS. EVS-50W 50 watt audio amplifier. EVS-125W 125 watt audio amplifier. EVS-100W 50/100 watt Intelligent amplifier EVS-50WBU External backup amplifier EVS-CE4 Provides 4 additional audio circuits for the EVS-50W or
EVS-RVM Remote Voice Microphone used with the
7860 Telephone Cord RJ31X cord for connecting phone line to the 5820XL/EVS. 5660 Silent Knight Software
Suite (SKSS)
5670 Silent Knight Software Suite (SKSS)
RBB Remote Battery Box for mounting backup batteries that are too large to fit into
be added to the system. Up to three 5815XLs per system. Allows a printer to be attached for the system for on-site event logging, detector
status and event history reports. Two maximum per system. Provides additional power, six Flexput™ circuits, and
two Form C relays. Max. 8 per system see Model 5895XL Installation Instructions P/N 151142.
Auxiliary power. (Up to 8 per system). Same operation, similar appearance as on-board
annunciator. Up to 12 5860s per system. 5860 is gray; 5860R is red.
Trim ring kits for surface mounting the 5860 annunciator. 5860TG is gray; 5860TR is red.
LED annunciator can display up to 30 LEDs (15 red and 15 yellow). 5865-4 has key switches for silence and reset, and a system trouble LED.
annunciator boards. In addition, the 5880 has eight generic switch input points.
Provides 10 Form C relays. Designed to be driven by the 5880. Up to four, 5883s can be used with each 5880 module.
EVS-125W.
5820XL-EVS.
“For communication and panel programming with a Windows-based computer. Remote access requires a modem.” (not sold by Silent Knight, see Table 1-2 for compatible modems). Enables remote viewing of detector status and event history.
Facility management software. For remote viewing of detector status and event history. Remote access requires a modem (not sold by Silent Knight).
the main FACP cabinet. Dim.: 16" W x 10" H x 6" D (40.64 cm W x 25.4 cm H x
15.24 cm D)
5895XLs and 5496s can be used in any combination, up to a total of twelve devices on one system.
up to a total of 12 5860s on one system.
5865-3, 5865-4, and 5880 can be used in any combination, up to a total of eight devices on one panel.
For use with 5820XL­EVS only. Refer to the
EVS-Series Installation Manual P/
N LS10062-001SK-E for more information on these accessories.
1-3
Model 5820XL/ 5820XL-EVS Installation Manual LS10061-001SK-E
The following modems have been tested by Silent Knight for compatibility with the IntelliKni ght 5820XL and 5820XL-EVS and the Silent Knight Software Suite software packages:
Table 1-2: Compatible Modems
Manufacturer Model
US Robotics 28.8
LifeStyle
Motorola
MultiTech MT19321ZDX
28.8, 3400 series Premier 33.6
1.4 How to Contact Silent Knight
If you have a question or encounter a problem not covered in this manual, contact Silent Knight Technical Support at 800-446-6444.
To order parts, contact Silent Knigh t Sal e s at 800-328-0103. IntelliKnight
Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72 manufacturer’s recommendations, state and local codes, and the recommendations contained in Guide for the Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off or give early warning in as many as 35% of all fires. While fire alarm systems are designed to provide warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons. For example:
®
is a registered trademark of Silent Knight; Flexput™ is a trademark of Silent Knight
Limitations of Fire Alarm Systems
),
Particles of combustion or smoke from a developing fire may not reach the sensing chambers of smoke detectors because: Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow. Smoke particles may become cold, stratify, and not reach the ceiling or upper walls where detectors are located. Smoke particles may be blown away from detectors by air outlets Smoke particles may be drawn into air returns before reaching the detector.
In general, smoke detectors on one level of a structure cannot be expected to sense fires developing on another level.
The amount of smoke present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors are subject to false alarms and nuisance alarms and may have been disconnected by users. For example, a smoke detector located in or near a kitchen may go into nuisance alarm during normal operation of kitchen appliances. In addition, dusty or steamy environments may cause a smoke detector to falsely alarm. If the location of a smoke detector causes an abundance of false alarms or nuisance alarms, do
1-4
LS10061-001SK-E Introduction
not disconnect the smoke detector; call a professional to analyze the situation and recommend a solution.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially within bedrooms), smoking in bed, violent explosions (caused by escap ing gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and are designed to alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Heat detectors are designed to protect property, not life.
Warning devices (including horns, sirens, and bells) may not alert people or wake up sleepers who are located on the other side of closed or partially open doors. A warning device that activates on a different floor or level of a dwelling or structure is less likely to awaken or alert people. Even persons who are awake may not notice the warning if the alarm is muffled by noise from a stereo, radio, air conditioner or other appliance, or by passing traffic. Audible warning devices may not alert the hearing-impaired (strobes or other devices should be provided to warn these people). Any warning device may fail to alert people with a disability , deep sleepers, people who have recently used alcohol or drugs, or people on medication or sleeping pills.
Please note that: i) Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy. ii) Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or com-
prehend the meaning of the signal. It is the property owner’s responsibility to conduct fire drills and other training exercises to make people aware of fire alarm signals and instruct on the proper reaction to alarm signals.
iii) In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
Telephone lines needed to transmit alarm signals from a premises to a central station may be out of service or temporarily out of service. For added protection against telephone line failure, backup radio transmission systems are recommended.
System components, though designed to last many years, can fail at any time. As a precautionary measure, it is recommended that smoke detectors be checked, maintained, and replaced per manufacturer’s recommendations.
System components will not work without electrical power. If system batteries are not serviced or replaced regularly, they may not provide battery backup when AC power fails.
Environments with high air velocity or that are dusty or dirty require more frequent maintenance.
In general, fire alarm systems and devices will not work without power and will not function properly unless they are maintained and tested regularly.
While installing a fire alarm system may make the owner eligible for a lower insurance rate, an alarm system is not a substitute for insurance. Property owners should continu e to act prud ently in protecting the premises and the people in their premises and should properly insure life and property and buy sufficient amounts of liability insurance to meet their needs.
1-5
Model 5820XL/ 5820XL-EVS Installation Manual LS10061-001SK-E
Requirements and recommendations for proper use of fire alarm systems including smoke de­tectors and other fire alarm devices:
Early fire detection is best achieved by the installation and maintenance of fire detection equipment in all rooms and areas of the house or building in accordance with the requirements and recommendations of the current edition of the National Fire Protection Association Standard 72, National Fire Alarm Code (NFPA 72), the manufacturer’s recommendations, State and local codes and the recommendations contained in Guide for the Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. For specific requirements, check with the local Authority Having Jurisdiction (ex. Fire Chief) for fire protection systems.
Requirements and recommendations include:
Smoke detectors shall be installed in sleeping rooms in new construction and it is recommended that they shall also be installed in sleeping rooms in existing construction.
It is recommended that more than one smoke detector shall be installed in a hallway if it is more than 30 feet long.
It is recommended that there shall never be less then two smoke detectors per apartment or residence.
It is recommended that smoke detectors be located in any room where an alarm control is located, or in any room where alarm control connections to an AC source or phone lines are made. If detectors are not so located, a fire within the room could prevent the control from reporting a fire.
All fire alarm systems require notification devices, including sirens, bells, horns, and/or strobes. In residential applications, each automatic alarm initiating device when activated shall cause the operation of an alarm notification device that shall be clearly audible in all bedrooms over ambient or background noise levels (at least 15dB above noise) with all intervening doors closed.
It is recommended that a smoke detector with an integral sounder (smoke alarm) be located in every bedroom and an additional notification device be located on each level of a residence.
T o keep your fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer’s recommendations and UL and NFPA standards. At a minimum the requirements of Chapter 7 of NFPA 72 shall be followed. A maintenance agreement should be arranged through the local manufacturer’s representative. Maintenance should be performed annually by authorized personnel only.
The most common cause of an alarm system not functioning when a fire occurs is inadequate maintenance. As such, the alarm system should be tested weekly to make sure all sensors and transmitters are working properly.
1-6
LS10061-001SK-E
Section 2 Agency Listings, Approvals, and Requirements
2.1 Federal Communications Commission (FCC)
1. The following information must be provided to the telephone company before the 5820XL or 5820XL-EVS can be connected to the phone lines:
A Manufacturer: Silent Knight by Honeywell B Model Number: IntelliKnight 5820XL and
5820XL-EVS
C FCC registration number: AC6USA-23901-AL-E
Ringer equivalence: 0.8B D Type of jack: RJ31X E Facility Interface Codes: Loop Start: 02LS2 F Service Order Code: 9.0F
This equipment complies with Part 68 of the FCC rules and the requirements adopted by ACTA. On the inside cover of this equipment is a label that contains, among other information, a product identifier. If requested, this information must be provided to the telephone company.
A plug and jack used to connect this equipment to the premises wiring and telephone network must comply with the applicable FCC Part 68 rules and requirements adopted by the ACTA. A compliant telephone cord (not provided) and modular jack must be utilized with this product. It is designed to be used with a modular jack that is also compliant.
The REN (ringer equivalence number) provided on this installation sheet is used to determine the number of devices that may be connected to the public switched telephone network. This number must not exceed 5.0. Since this product has an REN of .8, the number of devices is limited. The REN number is embedded in the FCC registration number as 10B.
If the 5820XL or 5820XL-EVS causes harm to the telephone network, the telephone company will notify you in advance that the temporarily discontinuance of service may be required. But if advance notice is not practical, the telephone company will notify the customer as soon as possible. Also, you will be advised of your right to file a complaint with the FCC if you believe it is necessary.
The telephone company may make changes in its facilities, equipment, operations or procedures that could affect the operation of the equipment. If this happens the telephone company will provide advance notice in order for you to make necessary modifications to maintain uninterrupted service.
If trouble is experienced with the 5820XL or 5820XL-EVS, for repair or warranty information, please contact Silent Knight at 1-800-328-0103 or www.silentknight.com. If the equipment is causing harm to the telephone network, the telephone company may request that you disconnect the 5820XL or 5820XL-EVS until the problem has been resolved.
This product cannot be adjusted or repaired in the field. It must be returned to the factory for service. This equipment is not designed for use with party line service. Connection to party line service is subject to state
tariffs. You may contact the state public utility com mission, public service commission or corporation commission for information.
Since the 5820XL/5820XL-EVS is a commercial fire alarm panel, it must be connected upstream of all other equipment utilizing the phone lines. If you have questions about the installation, contact your telephone company
2-1
LS10061-001SK-E Agency Listings, Approvals, and Requirements
or a qualified installer.
Warning
This device has been verified to comply with FCC Rules Part 15. Operation is subject to the following conditions: (1) This device may not cause radio interference, and (2) This device must accept any interference received, including interference that may cause undesired operation.
2.2 Underwriters Laboratories (UL)
2.2.1 Requirements for All Installations
General requirements are described in this section. When installing an individual device, refer to the specific section of the manual for additional requirements. The following subsections list specific requirements for each type of installation (for example, Central Station Fire Alarm systems, Local Protected Fire Alarm systems, and so on). See Section 8.7 for information on releasing operation.
1. All field wiring must be installed in accordance with NFPA 70 National Electric Code.
2. Use the addressable smoke detectors specified in Section 5.2 (SD devices) or Section 5.1 (SK devices) of this manual and/or conventional detectors listed in the compatibility chart. (See Appendix A).
3. Use UL listed notification appliances compatible with the 5820XL/EVS from those specified in Appendix A of this manual.
4. A full system checkout must be performed any time the panel is programmed.
Restricted Options:
The loss of AC signal is defaulted to 3 hours, however the system allows settings from 0 - 30 hours. For UL certified installations this number must be set from 1 to 3 hours.
The system allows the use of non-latching spot type smoke detectors. This feature may not be used in commercial applications whereby a general alarm is sounded. It is intended for elevator recall, door holding applications, and hotel/motel room applications.
The system allows the Alarm V erification time to be set from 1 to 255 seconds. For UL certified installations the setting must be a minimum of 60 seconds.
Call forwarding shall not be used.
When two count is used: detector spacing shall be cut in half, you shall not use the alarm verification feature, and no delay shall be used.
P.A.S. (positive alarm sequence) feature shall be used only with automatic detectors.
2.2.2 Requirements for Central Station Fire Alarm Systems
1. Use both phone lines. Enable phone line monitors for both lines.
2. You must program a phone number and a test time so that the 5820XL/5820XL-EVS sends an automa ti c daily test to the central station.
3. The AC Loss Hours option must be set from 1-3 hours.
4. The Attempts to Report option must be set for 5.
2-2
Model 5820XL/ 5820XL-EVS Installation Manual LS10061-001SK-E
2.2.3 Requirements for Local Protected Fire Alarm Systems
At least one UL listed supervised notification appliance must be used.
2.2.4 Requirements for Remote Station Protected Fire Alarm
Systems
1. Do not exceed the current draw load restrictions shown in Section 3.6.
2. The AC Loss Hours option must be set from 15-30 hours.
2-3
LS10061-001SK-E
Section 3 Before You Begin Installation
This section of the manual is intended to help you plan your tasks to facilitate a smooth installation. Please read this section thoroughly, especially if you are installing a 5820XL/EVS panel for the first time.
3.1 What’s in the Box?
The IntelliKnight 5820XL ships with the following hardware:
A cabinet with all hardware assembled
Two keys for the front door
Two keys for user operation of the on-board annunciator (i nstaller operations require the Installer’s Code)
Ten 4.7K ohm end-of-line resistors
A battery cable for batteries wired in series
The IntelliKnight 5820XL-EVS ships with the following hardware:
A cabinet with all hardware assembled
Two keys for the front door
Two keys for user operation of the on-board annunciator (i nstaller operations require the Installer’s Code)
Ten 4.7K ohm end-of-line resistors
A battery cable for batteries wired in series
T en 15K ohm end-of-line resistors
EVS-VCM Voice Control Module
Supervised microphone
3.2 Environmental Specifications
It is important to protect the IntelliKnight 5820XL/5820XL-EVS control panel from water. To prevent water damage, the following precautions should be FOLLOWED when installing the units:
Intended for indoor use in dry locations only
Do not mount directly on exterior walls, especially masonry walls (condensation)
Do not mount directly on exterior walls below grade (condensation)
Protect from plumbing leaks
Protect from splash caused by sprinkler system inspection ports
Do not mount in areas with humidity-generating equipment (such as dryers, productio n machi nery)
When selecting a location to mount the IntelliKnight 5820XL/ 5820XL-EVS control panel, the unit should be mounted where it will NOT be exposed to: temperatures outside the range of 0°C-49°C (32°F-120°F) or humidity exceeding 93% noncondensing.
3-1
LS10061-001SK-E Before You Begin Installation
3.3 Electrical Specifications
Table 3-1: Terminal Descriptions and Electrical Specification
Terminal # and Label Description
Rating
Voltage Current
1 L AC input (hot) 120 VAC, 60 Hz 2.7 A N/A 2 Earth ground N/A N/A N/A 3 N AC input (neutral) 120 VAC, 60 Hz 2.7 A N/A 4 X *I/O 6 Flexput™ Circuits 24 VDC 3.0A notification and auxiliary
power circuits 5O 100 mA for initiation circuits 6 X *I/O 5 Flexput™ Circuits 24 VDC 3.0A notification and auxiliary
power circuits 7 O 100 mA for initiation circuits 8 X *I/O 4 Flexput™ Circuits 24 VDC 3.0A notification and auxiliary
power circuits 9O 100 mA for initiation circuits 10 X *I/O 3 Flexput™ Circuits 24 VDC 3.0A notification and auxiliary
power circuits 11 O 100 mA for initiation circuits 12 X *I/O 2 Flexput™ Circuits 24 VDC 3.0A notification and auxiliary
13 O 100 mA for initiation circuits 14 X *I/O 1 Flexput™ Circuits 24 VDC 3.0A notification and auxiliary
15 O 100 mA for initiation circuits 16 B SBUS OUT SBUS communication 5 VDC 100 mA 0 17 A 18 + SBUS power 24 VDC 1.0 A 19 ­20 B SBUS IN Used for Class A installations 0 21 A 22 + 23 ­24 N.C. RELAY 1 General Purpose Relay 1 24 VDC 2.5 A, resistive N/A 25 C 26 N.O. 27 N.C. RELAY 2 General Purpose Relay 2 24 VDC 2.5 A, resistive N/A 28 C 29 N.O. 30 N.C. TROUBLE Trouble Relay 24 VDC 2.5 A, resistive N/A 31 C 32 N.O. 33 SC- L1 34 SC+ * Regulated for NAC circuits, special applications when used for releasing or auxiliary power circuits
SLC OUT
SLC terminals 32 VDC 150 mA 0
power circuits
power circuits
Earth Ground
Faults
0
0
0
0
0
0
3-2
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
Table 3-1: Terminal Descriptions and Electrical Specification
Terminal # and Label Description
Rating
Voltage Current
35 SC- L2 36 SC+ 37 Ring Phone Line 1 Telco Ring N/A 0 38 Tip Phone Line 1 Telco Tip 39 Ring Phone Line 1 Premises Ring 40 Tip Phone Line 1 Premises Tip 41 Ring Phone Line 2 Telco Ring N/A 0 42 Tip Phone Line 2 Telco Tip 43 Ring Phone Line 2 Premises Ring 44 Tip Phone Line 2 Premises Tip 45 SC- SLC Programming Terminal
46 SC+ SLC Programming Terminal
SLC IN
Used for Class A installations 0
32 VDC 150 mA 0
(-)
32 VDC 150 mA
(+)
Earth Ground
Faults
3.4 Wiring Specifications
Induced noise (transfer of electrical energy from one wire to another) can interfere with telephone communication or cause false alarms. To avoid induced noise, follow these guidelines:
Isolate input wiring from high current output and power wiring. Do not pull one multi-conductor cable for the entire panel. Instead, separate the wiring as follows:
High voltage AC power, Terminals 1-3 SLC loops Terminals 33-36 Audio input/output Phone line circuits, Terminals
37-44 Notification circuits Terminals 4-15 SBUS Terminals 16-23 Relay circuits Terminals 24-32
Do not pull wires from different groups through the same conduit. If you must run them together, do so for as short a distance as possible or use shielded cable. Connect the shield to earth ground at the panel. You must route high and low voltages separately.
Route the wiring around the inside perimeter of the cabinet. It should not cross the circuit board where it could induce noise into the sensitive microelectronics or pick up unwanted RF noise from the high speed circuits. See Figure 3-1 for an example.
High frequency noise, such as that produced by the inductive reactance of a speaker or bell, can also be reduced by running the wire through ferrite shield beads or by wrapping it around a ferrite toroid.
3-3
LS10061-001SK-E Before You Begin Installation
Figure 3-1 Wire Routing Example
3-4
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
Chassis Mounting Nuts
Chassis Mounting Nuts
To ACOn-board Annunciator
Key Switch Input
Programming Ports
3.5 Board Assembly Diagram
Figure 3-2 Model 5820XL / 5820XL-EVS Assembly
Figure 3-2 shows the circuit boards, metal housing and annunciator that attach the 5820XL / 5820XL-EVS assembly to the cabinet. If you should need to remove the board assembly for repair, remove the four mounting nuts which hold the assembly in the cabinet. Then lift the entire assembly out of the cabinet. Do not attempt to remove the circuit boards from the metal bracket.
3-5
LS10061-001SK-E Before You Begin Installation
3.6 Calculating Current Draw and Standby Battery
This section is for helping you determine the current draw and standby battery needs if you are using SK addressable devices (Table 3-2) or SD addressable devices (Table 3-3).
3.6.1 Current Draw Worksheet Requirements
The following steps must be taken when determining 5820XL/5820XL-EVS current draw and standby battery requirements.
1. You will use the Current Draw Worksheet to determine current draw and standby battery requirements. Use Table 3-2 if installing SK SLC Devices and Table 3-3 if installing SD SLC Devices. For the 5820XL / 5820XL-EVS, the worst case current draw is listed for the panel, addressable devices, and all SBUS expand­ers. Fill in the number of addressable devices and expanders that will be used in the system and compute the current draw requirements for alarm and standby. Record this information in the Current Draw Worksheet on Line A.
2. Add up the current draw for all auxiliary devices and record in the table on Line B.
3. Add up the current draw for all notification appliances and record in the table on Line C.
4. For notification appliances and auxiliary devices not mentioned in the manual, refer to the device manual for the current ratings.
5. Make sure that the total alarm current you calculated, including current for the panel itself, does not exceed
6.0 A. This is the maximum alarm current for the 5820XL / 5820XL-EVS control panel. If the current is above 6.0 A you will need to use a notification power expander(s) such as the Silent Knight
5495 or the 5895XL intelligent power expander, to distribute the power loads so that the 5820XL / 5820XL­EVS or the power expanders do not exceed their power ratings. Refer to the current draw worksheets pro­vided with the 5495 or the 5895XL manuals so you do not exceed their power ratings.
6. Complete the remaining instructions in the appropriate Current Draw Works heet for determining battery size requirements.
3.6.2 Current Draw Worksheet for SK SLC Devices
Use to determine current requirements during alarm/battery standby operation SK SLC devices are installed. when SD SLC devices are installed. You can install up 99 SK detectors SD per loop (396 points max per panel) and 99 SK modules per loop (396 points max per panel). Copy this section if additional space is required.
Table 3-2 Current Draw Worksheet for SK SLC Devices
Device # of Devices Current per Device
For each device use this formula: This column X This column = Current per number of devices. Fire Panel (battery current draw) 1 Standby: 275 mA 275 mA
Alarm: 440 mA 440 mA
Standby
Current
Alarm
Current
3-6
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
Table 3-2 Current Draw Worksheet for SK SLC Devices
Device # of Devices Current per Device
Addressable SLC Detectors SK-PHOTO SK-PHOTO-T mA mA SK-ION mA mA SK-HEAT mA mA SK-HEAT-HT mA mA SK-ACCLIMATE mA mA SK-HEAT-ROR mA mA
5
SK-DUCT
SK-BEAM (without integral test)
SK-BEAM-T
SK-FIRE-CO Addressable SLC Module
SK-MONITOR SK-MINIMON mA mA SK-PULL-SA mA mA SK-PULL-DA mA mA SK-MONITOR-2 Standby/Alarm: .75 mA mA mA SK-MON-10 Standby/Alarm: 3.5 mA mA mA
SK-CONTROL
SK-CONTROL-6
SK-RELAY Standby/Alarm: .255 mA mA mA SK-RELAY-6 Standby/Alarm: 1.45 mA mA mA
SK-RELAYMON-2
SK-ZONE
SK-ZONE-6
(includes PhotoR)
4
(with integral test)
(99 max/loop
& 396 max/
panel)
(99 max/loop
& 396 max/
panel)
(99 max/loop
& 396 max/
panel)
Standby/Alarm: .30 mA
1
1
1
SLC Standby/Alarm: 2 mA
Aux. Pwr Standby: 2 mA mA
Alarm: 8.5 mA mA
SLC Standby/Alarm: 2 mA
Aux. Pwr Standby: 2 mA mA
Alarm: 8.5 mA mA
SLC S t andby: .30mA mA
Alarm: 7.2mA mA
Standby/Alarm: .375 mA
SLC Standby: 2.25 mA mA
Alarm: 2.25 mA mA
Aux Pwr Standby: 1.7 mA mA
Alarm: 7 mA mA
SLC Standby: 2.25 mA mA
Alarm: 2.25 mA
Aux Pwr Standby: 8 mA mA
Alarm: 20 mA mA
Standby: 1.3 mA mA Alarm: 24 mA mA Aux Pwr Standby 12 mA mA
Alarm 90 mA mA
SLC Standby/
Alarm .27 mA
Aux Pwr Standby 50 mA mA
Alarm 270 mA mA
SLC Standby/Alarm 2 mA mA mA
Standby
Current
mA mA
6
mA mA
mA mA
mA mA
Alarm
Current
3-7
LS10061-001SK-E Before You Begin Installation
Table 3-2 Current Draw Worksheet for SK SLC Devices
Device # of Devices Current per Device
SLC Modules
Aux Pwr Standby: .50 mA mA
B200SR Sounder Base
SLC Standby .30 mA mA Aux Standby .50 mA mA
B200S Sounder Base
(99 max/loop
B200SR-LF Low Frequency Sounder Base
B200S-LF Low Frequency Sounder Base
B224RB Relay Base Standby/Alarm: 0.5 mA mA mA RTS151/151 KEY Alarm: 7.5 mA RA100Z Alarm: 10 mA SLC Isolator Devices SK-ISO (Isolator Module) B224BI Isolator Base Standby/Alarm: .5 mA mA mA Accessories Modules 5815XL SLC Expander (3 max.) Standby/Alarm: 55 mA mA mA 5860 Remote Fire Alarm
Annunciator * EVS-RCU contains one 5860 and
must be added to the calculation here.
5824 Serial/Parallel Printer Interface Module
5496 Intelligent Power Module 5895XL IntelliKnight Power Module Standby/Alarm: 10 mA mA mA
5865-4 LED Annunciator (with reset and silence switches)
5865-3 LED Annunciator
5880 I/O Module
5883 Relay Interface (32 max.)
EVS-VCM Voice Control Module (1 max.)
EVS-SW24 Switch Expander (5 max.)
EVS-50W or EVS-125W Audio Amplifier with/without EVS-CE4
EVS-RVM Remote Voice Module * The EVS-RCU contains one EVS-
RVM and must be added to the calculation here
EVS-100W 100W amplifier (4 max.) Standby/Alarm: 10 mA mA mA
& 396 max/
panel)
(100 max/loop
& max/panel)
(12 max.)
(2 max.)
(8 max.)
(8 max.)
(4 max.)
(4 max.)
SLC Standby .30 mA mA Aux Pwr Standby: 1 mA mA
Aux Standby .55 mA mA
SLC Standby .30 mA mA
Standby/Alarm: .45 mA mA mA
Standby: 20 mA mA Alarm: 25 mA mA
Standby/Alarm: 45 mA mA mA
Standby/Alarm: 10 mA mA mA
Standby: 35 mA mA Alarm: 145 mA mA Standby: 35 mA mA Alarm: 145 mA mA Standby: 35 mA mA Alarm: 200 mA mA Standby: 0 mA mA Alarm: 220 mA
(22 mA per relay) Standby: 70 mA mA Alarm: 100 mA mA Standby: 10 mA mA Alarm: 25 mA mA Standby: 10 mA mA Alarm: 10 mA mA Standby: 70 mA mA Alarm: 100 mA mA
Alarm: 35 mA mA
Alarm (high vol) 35 mA mA
Alarm: 125 mA mA
Alarm (high vol) 140 mA mA
Standby
Current
Alarm
Current
mA mA
mA
3-8
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
Table 3-2 Current Draw Worksheet for SK SLC Devices
Device # of Devices Current per Device
EVS-100WBU backup daughter card
Auxiliary Devices
Notification Appliance Circuits Refer to device manual for current rating.
Total current ratings of all devices in system (line A + line B + C) mA mA Total current ratings converted to amperes (line D x .001): A A Number of standby hours: H Multiply lines E and F. Total standby AH AH Alarm sounding period in hours. (For example, 5 minutes = .0833 hours) H Multiply lines E and H. Total alarm AH
Add lines G and I.
2
3
(4 max.)
Standby/Alarm: 10 mA mA mA
Total System Current
Refer to devices manual for current rating.
Alarm/Standby: mA mA mA Alarm/Standby: mA mA mA Alarm/Standby: mA mA mA Alarm/Standby: mA mA mA
Auxiliary Devices Current
Alarm: mA Alarm: mA Alarm: mA Alarm: mA
Notification Appliances Current
Total ampere hours
required
Standby
Current
AH
Alarm
Current
mA mA mA mA mA
AH
1. Total does not include isolator devices or accessory bases.
2. If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is removed during that time. However, during normal operation, door holders draw current and must be included in the
6.0A total current that can be drawn from the panel.
3. Use next size battery with capacity greater than required.
4. SK-BEAM-T draws a maximum of 500mA from Auxiliary power only when the test feature is used. this should be considered when determining auxiliary power capacity but not calculated into current requirements for day to day operation.
5. The SK-DUCT housing contains a vacant mount for a SK-RELAY (sold separately). Current draw for the SK-RELAY is calculated by increasing the SK-RELAY row of the calculation sheet by one for each SK-RELAY used with a SK­DUCT.
6. The F ACP can only support 5 devices w/LED’s on. This current draw has been added to the panels alarm current.
3-9
LS10061-001SK-E Before You Begin Installation
3.6.3 Current Draw Worksheet for SD SLC Devices
Use to determine current requirements during alarm/battery standby operation when SD SLC devices are installed. You can install up SD devices per loop (Max per panel). Copy this section if additional space is required.
Table 3-3: Current Draw Worksheet for SD SLC Devices
5
2 2
Standby
Current
mA mA
mA
mA mA
Device # of Devices Current per Device
For each device use this formula: This column X This column = Current per number of devices. IntelliKnight 5820XL Fire Panel (Current
draw from battery) Addressable SLC Devices
SD500-AIM SD500-MIM mA mA SD500-PS mA mA SD500-ARM mA mA SD505-AHS mA mA SD505-AIS mA mA SD505-APS mA mA SD500-ANM
SD500-SDM
SD500-LED
SLC Accessory Bases SD505-6RB (508 max.) Standby/Alram: .082 mA mA mA SD505-6SB
SD505-DUCTR
SD505-DTS-K (508 max.) None, included with SD505-DUCTR worst case. SD505-DUCT (508 max.) None, included with detector current. SLC Isolator Devices SD500-LIM (1024 max.) SD505-6IB (508 max.) Accessories Modules 5815XL SLC Expander (3 max.) Standby/Alarm: 55 mA mA mA 5860 Remote Fire Alarm Annunciator. *EVS-RCU contains one 5860 and must be added to the calculation here.”. 5824 Serial/Parallel Printer Interface (2 max.) Standby/Alarm: 45 mA mA mA 5895XL IntelliKnight Power Expander 5496 Intelligent Power Module Standby/Alarm: 10 mA mA mA 5865-4 LED Annunciator (with reset and silence switches)
5865-3 LED Annunciator Standby: 35 mA mA
5880 LED I/O Module Standby: 35 mA mA
1
(508 max.)
(508 max.)
(508 max.)
(100 max.)
(508 max.)
(508 max.)
(12 max.)
(8 max.)
(8 max.)
Standby: 275 mA 275 mA Alarm: 440 mA 440 mA
1
Standby/Alarm: .55 mA
Aux. Pwr
1
SLC S t andby/Alarm: .55 mA mA mA SLC S t andby/Alarm: .55 mA mA
1
Aux. Pwr
Aux. Pwr
1
SLC S tandby/Alarm: .55 mA mA mA
Aux. Pwr
SLC S tandby/Alarm .082 mA mA mA
Aux. Pwr
SLC S t andby/Alarm: .5 mA mA mA
Standby/Alarm .092 mA
Standby: 20 mA mA Alarm: 25 mA
Standby/Alarm: 10 mA mA mA
Standby: 35 mA mA Alarm: 145 mA mA
Alarm: 145 mA mA
Alarm: 200 mA mA
Standby: 8 mA mA Alarm: 60 mA mA
Standby: 20 mA mA Alarm: 106 mA mA Standby: 10 mA mA Alarm: 220 mA mA LED: 10 mA mA mA
Standby: 1 mA mA Alarm: 32 mA mA
Standby: 20 mA Alarm: 62 mA
Alarm
Current
mA
mA
3-10
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
Table 3-3: Current Draw Worksheet for SD SLC Devices
Device # of Devices Current per Device
5883 Relay Interface
EVS-VCM Voice Control Module
EVS-SW24 Switch Expander
EVS-50W or EVS-125W Audio Amplifier with/without EVS-CE4
EVS-RVM Remote Voice Module * The EVS-RCU contains one EVS-RVM
and must be added to the calculation here
EVS-100W 100W Amplifier (4 max.) Standby/Alarm: 10 mA mA mA EVS-100WBU backup daughter card (4 max.) Standby/Alarm: 10 mA mA mA
A Total System Current
Auxiliary Devices
B Auxiliary Devices Current
C Notification Appliances Current D Total current ratings of all devices in system (line A + line B + C) mA mA E Total current ratings converted to amperes (line D x .001): A A F Number of standby hours: H G Multiply lines E and F. Total standby AH AH H Alarm sounding period in hours. (For example, 5 minutes = .0833 hours) H I Multiply lines E and H. Total alarm AH J
Add lines G and I.
3
4
(32 max.)
(1 max.)
(5 max.)
(4 max.)
(4 max.)
Standby: 0 mA mA
Alarm: 220 mA
Standby: 70 mA mA Alarm: 100 mA mA Standby: 10 mA mA Alarm: 25 mA mA Standby: 10 mA mA Alarm: 10 mA mA Standby: 70 mA mA
Alarm: 100 mA
Refer to devices manual for current rating.
Alarm/Standby: mA mA mA Alarm/Standby: mA mA mA Alarm/Standby: mA mA mA Alarm/Standby: mA mA mA
Alarm: mA Alarm: mA Alarm: mA Alarm: mA
(22 mA per relay)
Total ampere hours
required
Standby
Current
AH
Alarm
Current
mA
mA
mA mA mA mA mA
AH
1. Total does not include isolator devices or accessory bases.
2. If using 24 VDC aux power only. No standby or alarm current for battery calculation if using 24 VAC, 120 VAC or 240 VAC.
3. If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is removed during that time. However, during normal operation, door holders draw current and must be included in the 6.0A total current that can be drawn from the panel.
4. Use next size battery with capacity greater than required.
5. The FACP can only support 2 devices w/LED’s on. This current draw has been added to the panels alarm current.
3-11
LS10061-001SK-E Before You Begin Installation
3.6.4 Maximum Battery Standby Load
Table 3-4 shows the maxim um battery standby load for the 5820XL/5820XL-EVS based on 24 and 60 hours of standby. The standby load calculations of line D in the Current Draw Calculation Worksheet (Table 3-2 for SK devices and Table 3-3 SD devices) must be less than the number shown in Table 3-4 for the battery size used and standby hours required.
Table 3-4: Maximum Battery Standby Load
Rechargeable Battery Size
7 AH 270 mA 105 mA 12 AH 475 mA 190 mA 18 AH 685 mA 270 mA 35 AH 1.3 A 540 mA
Max. Load for 24 hrs.
Standby, 5 mins. Alarm
*Max. Load for 60 hrs.
Standby, 5 mins. Alarm
* Required for NFPA 72 Auxiliary Protected Fire Alarm systems for Fire Alarm Service (City Box) and Remote
Station Protected Fire Alarm systems (Polarity Reversal) and Digital Alarm Communicator/Transmitter (DACT)
* 33AH max battery size for FM (factory mutual) installations.
Warning!
Silent Knight does not support the use of batteries smaller than those listed in Table 3-4. If you use a battery too small for the installation, the system could overload the battery resulting in the installation having less than the required 24 hours standby power. Use Table 3-4 to calculate the correct battery amperes/hour rating needed for your installation.
3.7 Installation Tasks Overview
This section provides a chart listing tasks that need to be performed when installing the 5820XL/5820XL-EVS system. The chart is intended to be a handy way for you to make sure you have completed all necessary tasks. Unless noted, these tasks do not have to be performed in the order they are listed here.
Important: Connect and address SLC devices before running JumpStart AutoProgramming.
Main Panel Hardware Installation
Mount the control panel cabinet. Connect AC. Install 5815XL SLC expander modules. Required if more than 127 SLC devices are used. Install 5860 Remote Fire Alarm Annunciator modules. Install 5865 or LED Annunciator modules. Install 5880 LED I/O modules. Install notification appliances. Install auxiliary power devices. Install the 5824 Serial/Parallel Printer Interface modules. Connect batteries (typically last step).
Task
See Sec.
(for more info.)
4.1
4.2
4.6
4.5
4.9
4.8
4.12
4.12.5
4.7
4.3
3-12
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
Task
See Sec.
(for more info.)
SLC Device Hardware Installation
Perform these steps before running JumpStart.
Connect device bases to the loop.
Set device addresses.
Physically connect detectors to their bases. Connect relay and contact monitor modules.
SK 5.5 SD 5.7
SK 5.6 SD 5.8
5.4 & see device
install instructions
JumpStart AutoProgramming
JumpStart is for initial system programming. JumpStart automatically selects some options for SLC devices. See “Input Point (SLC Device) Configuration” section of this chart for other options.
JumpStart makes selections for the following options. You can customize options, if necessary. Device type (detector or switch) configured by JumpStart. To change, see 7.7 Program type of detector (heat, photoelectric, or ionization) selected by JumpStart. To change, see 7.7
6.2 & 7.7
System Software Configuration
Select low AC hours report time (3 hours by default). Select Auto Test Time (2:00 AM by default). Enable/disable automatic DST adjustment feature (enabled by default). Change clock display format (12-hour with AM/PM by default). Set up reporting accounts. Select options for phone lines. Select system-wide response to trouble conditions, if desired. Select system-wide cadence patterns for special conditions (fire drill, Aux1 and Aux2
7.6.4.2
7.6.2
7.6.6.1
7.6.4.4
7.6.1
7.6.2
7.6.3
7.6.3.2
alarms) if desired. Customize banner message (message that displays on LCD in normal mode) if desired.
7.6.7
Input Point (SLC Device) Configuration
JumpStart automatically selects some options for SLC devices (see “JumpStart” section of this chart). You can change options selected by JumpStart, if necessary and further customize input point options.
Select device family (SK or SD). Only one device family can be used per control panel. Program type of switch (manual pull, fire drill, and so on), if necessary. (JumpStart assigns
7.6.8
7.5
all switches as Manual Pull type.) If the installation incl u de s duct detectors, program detector type. (JumpStart does not
7.5
distinguish duct detectors from ordinary smoke detectors.) Assign a name (or description) to the point. Assign input points to zones, if necessary. (JumpStart assigns all input points to Zone 1.)
7.5.5
7.5
Zone Configuration
Add the zone to the system if it does not already exist. (Zone 1 created by JumpStart.) Program a name (or description) for the zone. Select alarm delay options (detection characteristics) for zone. Select heat detector trip temperature and/or smoke sensitivity level for photoelectric smoke
7.3.2
7.3.1.1
7.3.1.2
7.3.1.2
detectors. (JumpStart selects 150°F for heat detectors and Low sensitivity for smoke detectors.)
3-13
LS10061-001SK-E Before You Begin Installation
Task
Output Point Configuration
Conventional notification circuits (circuits 1-6):
Enable circuits used for notification appliances through programming (if necessary). (JumpStart enables circuits 1-6 as Notification.)
Conventional relay circuits (circuits 7-8):
Select options for relay circuits, if desired. Note: Relay circuits will always output continuously (constant pattern), even if assigned to an Output Group that uses a different output pattern.
Auxiliary power circuits (circuits 1-6):
Enable any circuit used for auxiliary power devices through programming. Select type of power (door holder, constant, or resettable)
Addressable relay modules
Assign addressable relay modules to output groups through programming. (JumpStart assigns all relay modules to Group 1.)
LED output points (from the 5880 LED I/O module or 5865/66 LED Annunciator)
Assign LED modules to output groups through programming.
All output circuits (1-8):
Disable (set to UNUSED) any unused circuits. If you do not disable unused output circuits, they will cause a trouble condition (unless an EOL resistor is used).
Select a name for the point.
See Sec.
(for more info.)
7.5
7.5
7.5
7.5
7.5
7.5.3
7.5
7.5.5
Output Group Configuration
Add a group to the system if it does not already exist. Assign output points to a group. Assign a name (or description) for the group.
Select “group properties” (see below).
Latching / non-latching Silencing option Select options for activation with system switches. Map zones to output groups that will activate when zone goes into alarm. Select a cadence pattern for outputs in the zone.
Emergency Voice System
EVS Super User EVS Priority Table & Rules EVS Device Priority Voice Command Mapping EVS System Options EVS-VCM Maintenance
7.4.2
7.5
7.4.1.1
7.4.1
7.4.1
7.4.1
7.3.1.3
7.3.1.3
9.3
9.8
9.6
9.13
7.10.3
7.10.1
3-14
LS10061-001SK-E
Section 4 Control Panel Installation
Caution!
To avoid the risk of electrical shock and damage to the unit, power should be OFF at the control panel while installing or servicing.
4.1 Mounting the Control Panel Cabinet
Read the environmental specifications in Section 3.2 before mounting the control panel cabinet. This will ensure that you select a suitable location.
The panel should be accessible to main drop wiring runs. It should be mounted as close to the center of the building as possible and located within a secured area, but should be accessible for testing and service.
Mount the control panel cabinet so it is firmly secured to the wall surface. When mounting on concrete, especially when moisture is expected, attach a piece of 3/4-inch plywood to the concrete surface and then attach the cabinet to the plywood. Also mount any other modules to the plywood.
The 5820XL cabinet can be surface- or flush-mounted. Cabinet dimensions are
16.2" W x 26.4" H x 4.2" D. There should be 1.5" to 1.75" of cabinet extruding from the wall, this should be measured from either the top edge or bottom edge to the exterior side of the sheet rock. Do NOT flush mount in a wall designated as a fire break.
The 5820XL-EVS cabinet can be surface or flush mounted. Cabinet dimensions are 20" W x 26.5" H x 4.6" D. There should be 1.5" to 1.75" of cabinet extruding from the wall, this should be measured from either the top edge or bottom edge to the exterior side of the sheet rock. Do NOT flush mount in a wall designated as a fire break.
4.1.1 Preventing Water Damage
Water damage to the fire system can be caused by moisture entering the cabinet through the conduits. Conduits that are installed to enter the top of the cabinet are most likely to cause water problems. Installers should take reasonable precautions to prevent water from entering the cabinet. Water damage is not covered under warranty.
4.1.2 Removing the 5820XL / 5820XL-EVS Assembly from the Housing
If it should ever be necessary to remove the control panel assembly from the cabinet for repair, do so by unscrewing the nuts that connect the control panel assembly to the cabinet. Do not attempt to disassemble the circuit boards. See Section 3.5 for location of the nuts.
4.2 AC Connection
At installation, connect the AC terminals to the power source as shown in Figure 4-1. It may be necessary for a professional electrician to make this connection.
Warning
To reduce the risk of electric shock, this product is provided with a grounding type power supply cord. Connect product to a grounded receptacle.
4-1
Control Panel Installation LS10061- 001SK-E
To Control Panel
Red
Black
Battery Jumper
(P/N 140694)
Shipped With Panel
12V Gel Cell Battery
12V Gel Cell Battery
The AC terminals are rated at 120 VAC, 60 Hz, 2.7A.
Figure 4-1 120 VAC Power Connection for the 5820XL/EVS
4.3 Battery Connection
The control panel battery charge capacity is 7.0 to 35 AH. Use 12V batteries of the same AH rating. Determine the correct AH rating as per your current load calculation (see Section 3.6).
Wire batteries in series to produce a 24-volt equivalent. Do not parallel batteries to increase the AH rating.
* It is recommended that you replace batteries every five years.
Figure 4-2 Battery Connection
4-2
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
Cabinet
Mounting Holes
4.3.1 RBB Accessory Cabinet
The Model RBB Accessory cabinet can be used when your backup batteries requirements use backup batteries that are too large to fit into the main control panel cabinet. The RBB cabinet holds batteries up to the 35 AH size. The RBB dimensions are 16" W x 10" H x 6" D (40.64 cm W x 25.4 cm H x 15.24 cm D).
4.3.1.1 Installing the RBB Accessory Cabinet and Batteries
To properly install the accessory cabinet and backup batteries, follow these steps:
1. Mount the accessory cabinet. See Figure 4-3 for the four cabinet mounting holes.
If mounting onto drywall the accessory cabinet must be mounted onto 3/4-inch plywood. This is neces­sary because the weight of the batteries inside the accessory cabinet could cause the cabinet to pull away from the drywall.
When mounting on concrete , especially when mo isture is expected, attach a piece of ¾” plywood to the concrete surface and then attach the RBB cabinet to the plywood.
If using the battery cable extenders provided (P/N 140643), mount the RBB cabinet no more than 18" away from the main control panel cabinet. This will ensure that the battery cables reach the battery ter­minals.
Figure 4-3 RBB Cabinet Mounting Holes
2. Connect the main control panel battery cables to the battery cable extenders as shown in Figure 4-4.
Figure 4-4 Splicing Control panel Battery Cable to RBB Battery Cable Extenders
4-3
Control Panel Installation LS10061- 001SK-E
Conduit
Conduit Coupler
+
+
-
-
RBB Cabinet Cover Screws
RBB Cabinet Cover Screws
Cover Plate
Mounting Keyholes
3. Run extended battery cable from control panel cabinet through conduit to RBB cabinet. See Figure 4-5.
Figure 4-5 Battery Connections in the RBB Cabinet
Note: Figure 4-5 is an example of how the wire connections can be routed. However, any other cabinet knock-
outs (on either the main control panel or the RBB cabinet), that are not previously being used may be uti­lized to connect conduit between the two cabinets.
4. Connect battery leads to the backup battery terminals. See Figure 4-5. Observe the proper polarity to prevent damage to the batteries or the control panel.
5. Insert the RBB cover screws into the cover mounting holes. See Figure 4-5. Screw the cover screw ¾ of the way into the cover mounting hole.
6. Align the cover plate mounting keyhole over the cover mounting screws. See Figure 4-6.
Figure 4-6 Cover Plate Mounting Keyholes and Cover Mounting Screws Alignment
7. Slide the cover into place and tighten the cover mounting screws. See Figure 4-6.
4.4 SBUS Wiring
This section contains information on calculating SBUS wire distances and the types of wiring configurations (Class A and B).
4-4
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
4.4.1 Calculating Wiring Distance for SBUS Modules
The following instructions will guide you in determining the type of wire and the maximum wiring distance that can be used with control panel SBUS accessory modules.
To calculate the wire gauge that must be used to connect SBUS modules to the control panel, it is necessary to calculate the total worst case current draw for all modules on a single 4-conductor bus. The total worst case current draw is calculated by adding the individual worst case currents for each module. The individual worst case values are shown in the table below.
Note: Total worst case current draw on a single SBUS cannot exceed 1 amp. If a large number of accessory mod-
ules are required, and the worst case current draw will exceed the 1 amp limit, then the current draw must be distributed using 5895XL Power Expanders. Each 5895XL Power Expander provides an additional SBUS, with an additional 1 amp of SBUS current. Wiring distance calculations are done separately for each 5895XL, and separately for the control panel itself.
Model Number Worst Case Current Draw
5860 Fire Annunciator .100 amps 5824 Serial/Parallel Printer Interface Module .040 amps 5880 LED I/O Module .250 amps 5865 LED Annunciator .200 amps 5895XL Intelligent Power Supply .010 amps 5496 Intelligent Power Supply .010 amps EVS-50W .010 amps EVS-125W .010 amps EVS-100W .010 amps EVS-100W with EVS-100WBU .010 amps EVS-VCM / EVS-VCM with EVS-SW24* ** .080 amps / .105 amps EVS-RCU / EVS-RCU with EVS-SW24* ** .080 amps / .105 amps
Note: Refer to if using SD SLC devices and Table 3-2 if using SK SLC devices for maximum number of each type
of device that can be used per system
* All devices must use the same SBUS and VBUS. ** When doing wire calculations, use .080 amps per device with .105 amps for the last device. After calculating the total worst case current draw, Table 4-1 specifies the maximum distance the modules can be
located from the panel on a single wire run. The table ensures 6.0 volts of line drop maximum. In general, the wire length is limited by resistance, but for heavier wire gauges, capacitance is the limiting factor.
4-5
Control Panel Installation LS10061- 001SK-E
These cases are marked in the chart with an asterisk (*). Maximum length can never be more than 6,000 feet, regardless of gauge used. The formula used to generate this chart is shown in the note below.
Table 4-1: Wire Distances Per Wire Gauge Using Copper Wire
Wiring Distance: SBUS Modules to Panel
Total Worst Case
Current Draw (amps)
0.100 1852 ft. 4688 ft. * 6000 ft. * 6000 ft.
0.200 926 ft. 2344 ft. 3731 ft. 5906 ft.
0.300 617 ft. 1563 ft. 2488 ft. 3937 ft.
0.400 463 ft. 1172 ft. 1866 ft. 2953 ft.
0.500 370 ft. 938 ft. 1493 ft. 2362 ft.
0.600 309 ft. 781 ft. 1244 ft. 1969 ft.
0.700 265 ft. 670 ft. 1066 ft. 1687 ft.
0.800 231 ft. 586 ft. 933 ft. 1476 ft.
0.900 206 ft. 521 ft. 829 ft. 1312 ft.
1.000 (Max) 185 ft. 469 ft. 746 ft. 1181 ft.
22 Gauge 18 Gauge 16 Gauge 14 Gauge
Note: The following formulas were used to generate the wire distance chart:
Maximum Resistance (Ohms) =
Maximum Wire Length (Feet) =
(6000 feet maximum)
where: Rpu = Ohms per 1000 feet for various wire gauges (see table below)
Total Worst Case Current Draw (amps)
Maximum Resistance (Ohms)
6.0 Volts
Rpu
* 500
Table 4-2: Typical Wire Resistance Per 1000 ft. Using Copper Wire
Wire Gauge Ohms per 1000 feet (Rpu)
22 16.2 18 6.4 16 4.02 14 2.54
Wiring Distance calculation example:
Suppose a system is configured with the following SBUS modules: 2 - Module 5860 Fire Annunciator 1 - 5895XL Intelligent Power Expander 1 - 5865 LED Annunciator 1 - 5824 Serial/Parallel Interface Module
4-6
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
Supervised Power Limited
Caution
For proper system supervision do not use looped wire under terminals marked A, B, +, and - of the SBUS device connectors. Break wire runs to provide supervision of connections.
The total worst case current is calculated as follows:
5860 Current Draw = 2 x .100 amps = .200 amps 5895XL Current Draw = 1 x .010 amps = .010 amps 5865 Current Draw = 1 x .200 amps = .200 amps 5824 Current Draw = 1 x .040 amps = .040 amps Total Worst Case Current Draw = .450 amps
Using this value, and referring to the Wiring Distance table, it can be found that the available options are: 370 feet maximum using 22 Gauge wire 938 feet maximum using 18 Gauge wire 1493 feet maximum using 16 Gauge wire 2362 feet maximum using 14 Gauge wire
4.4.2 Wiring Configurations
Figure 4-7 illustrates Class A wiring configuration and Figure 4-8 illustrates Class B configuration.
Figure 4-7 SBUS Class A Wiring
4-7
Control Panel Installation LS10061- 001SK-E
Supervised Power Limited
Figure 4-8 SBUS Class B Wiring
4.5 5860 Remote Annunciator Installation
The optional Model 5860 Remote Annunciator, shown in Figure 4-9, performs the same functions as the on­board annunciator. It can initiate and end fire drills with a single key press and view event history by alarms, supervisories, or troubles. Up to 12 annunciators can be added to the IntelliKnight 5820XL / 5820XL-EVS system.
Note: The EVS-RCU contains a 5860 and counts toward one of the eight annunciators.
Figure 4-9 Model 5860 Remote Annunciator, Front View
4-8
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
5860 installation involves the following steps:
1. Make sure power is off at the panel.
2. Mount the 5860 in the desired location (see Section 4.5.1).
3. Connect the 5860 to the panel (see Section 4.5.2).
4. Use the DIP switches on the back of the 5860 to assign an ID# to the 5860 (see Section 4.10.1).
5. The new 5860 module must be added to the system through programming. JumpStart will add the module automatically (see Section 6.2). You can also add it manually (see Section 7.2.2). Select a name, if desired (see Section 7.2.1.1).
4.5.1 Mounting the 5860
This section of the manual describes mounting the remote annunciator. The annunciator can be flush- or surface­mounted. Figure 4-10 shows the parts of the annunciator. Instructions for disassembling and mounting appear on the following pages.
Figure 4-10 Annunciator Parts
4-9
Control Panel Installation LS10061- 001SK-E
Set screw location.
Loosen set screws to remove bezel
when disassembling annunciator.
Knockout holes
Holes for surface mounting.
Holes for inserting wires for flush mounting (located in all corners).
Stand-off
(throughout)
Screw for placement
of mounting wires
(top and bottom).
The 5860 comes from the factory fully assembled. You must disassemble it for mounting. To disassemble the annunciator, use a 5/64 hex wrench to remove the set screws, located on the bottom of the annunciator bezel. (See Figure 4-11 for location of the set screws).
Figure 4-11 Annunciator Back Box and Bezel Details
4.5.1.1 Flush Mounting
This section of the manual describes flush mounting. You can flush-mount with or without an electrical box.
Flush Mounting with an Electrical Box
The 5860 annunciator can be used with the following types of electrical boxes: 4S, single-gang, and double­gang.
If an electrical box is used, the box must be 1-3/8” back from the face of the wall to accommodate the
4-10
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
Sheet rock
Sheet rock
Electrical Box
Annunciator
back box
1-3/8"
When flush-mounting using an
electrical box, the box must be
1-3/8" from face of wall.
Electrical box applications require
2 by 4 construction minimum.
studs
electrical
box
annunciator
back box
(outline)
wall
Examples of Electrical Box Use
Electrical Box Placement
Insert wires at an angle into the first holes past the sheet rock.
Secure the wires behind this screw.
Attach second set of wires to top of back box.
annunciator. Studs used with an electrical box must be two by fours (or larger).
Flush Mounting Steps
1. Cut a hole in the sheet rock to the following dimensions: 8-¼” W x 6-5/8” H. If an electrical box is used, the box must be 1-3/8” back from face of wall to accommodate the annunciator (see Figure 4-12).
2. Remove knockout holes as needed for wires.
3. Fit the annunciator back box into the hole and stabilize with mounting wires. Angle the mounting wires into the first hole past the sheet rock. Secure the wires behind the screws as shown in Figure 4-13. When all four wires are in place, the back box should fit snugly into the hole in the sheet rock.
4. After the annunciator wiring to the panel has been completed (described in Section 4.5.2), replace the elec­tronic assembly in the back box. Place the bezel over the back box and tighten the set screws on the bezel.
Figure 4-12 Placement of Electrical Box for Flush Mounting
Figure 4-13 Flush Mounting the Back Box
4-11
Control Panel Installation LS10061- 001SK-E
Supervised Power Limited
4.5.1.2 Surface Mounting
The 5860 can be mounted directly to a surface or can be attached to a single, double, or four-square electrical box. The Model 5860TG/TR trim ring kit is available for use when surface mounting.
1. Drill holes in the surface to match the screw holes on the back box.
2. Fit the trim ring over the back box.
3. Attach the back box to the surface using screws provided.
4. After the annunciator wiring to the panel has been completed (described in Section 4.5.2), replace the elec­tronic assembly in the back box. Place the bezel over the back box and tighten the set screws on the bezel.
4.5.2 Model 5860 Connection to the Panel
Connect the 5860 to the panel as shown in Figure 4-14.
Figure 4-14 Model 5860 Connection to the Panel
4.6 5815XL Installation
The 5815XL SLC expander lets you add 127 SD addressable devices or 99 SK detectors and 99 SK modules. Add up to three 5815XLs to a system to achieve the maximum number of devices on the system.
To install the 5815XL:
1. Make sure power is off at the panel.
2. Mount the 5815XL in the 5820XL cabinet, the 5895XL cabinet, or the 5815RMK remote mounting kit. Use the standoffs located under the control panel board assembly and secure with screws provided with the 5815XL. For additional information, also see Model 589 5XL Installation Instructions (P/N 151142) or 5815RMK Remote Mounting Kit Installation Instructions (P/N 151391).
3. Connect the 5815XL to the control panel. (See Section 4.6.1.)
4. Use on-board DIP switches to select an SBUS ID#. (See Section 4.10.1).
5. The new 5815XL module must be added to the system through programming. JumpStart will add the mod­ule automatically (see Section 6.2). You can also add it manually (see Section 7.2.2). Select a name, if desired (see Section 7.3.1.1).
6. You are now ready to connect SLC devices to the 5815XL (see Section 5.4.2).
4-12
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
Supervised Power Limited
Figure 4-15 is a drawing of the 5815XL board, showing the location of terminals and DIP switches.
Figure 4-15 5820XL Board
4.6.1 5815XL Connection to the Panel
Connect the 5815XL to the control panel as shown in Figure 4-16. After the 5815XL is connected to the panel, it must be added to the system. This programming step is described in Section 4.10.
Figure 4-16 5815XL Connection to Main Panel Assembly
4-13
Control Panel Installation LS10061- 001SK-E
Supervised Power Limited
4.7 5824 Serial/Parallel Interface Module Installation
The 5824 serial/parallel interface module allows you to connect a printer to the panel, so you can print a real-time log of system events, a report of detector status, and event history. Instructions for installing the 5824 appear below.
The 5824 and the printer connected to the 5824 Parallel port is ancillary, the serial port can be used for primary fire signaling. The printer must be a UL 864 listed printer.
5824 installation involves the following steps:
1. Make sure power is off at the panel.
2. Connect the 5824 to the panel as shown in Figure 4-17.
Note: Two 5824s per panel maximum.
3. Use the DIP switches on the back of the 5824 board to assign an ID# to the 5824 (see Section 4.10.1).
4. Configure the 5824 device through programming. See Section 4.7.1.
5. Connect a printer to the 5824 as shown in Figure 4-18.
Figure 4-17 5824 Connection to the Panel
4-14
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
Model 5824 (with housing)
T o Parallel Printer
To Se rial Printer
Figure 4-18 Printer Connection
4.7.1 Selecting 5824 Options
Configuring the 5824 includes the following steps:
Add the module to the system. JumpStart will add the module automatically (see Section 6.2). You can also add it manually (see Section 7.2.2).
Select a name, if desired (see Section 7.2.1.1).
Select options for the printer and the output port. See below.
Printer and Output Port Options
1. From the Installer Main Menu, select 7 for Program Menu.
2. Select 1 for Module.
3. Select 1 for Edit Module.
4. From the list that displays, select the 5824 module you want to configure.
5. The right arrow must be pressed twice to skip over the Enter Module ID and Enter Module name options. A screen similar to the one shown in Figure 4-19 will display.
Figure 4-19 Selecting Printer and Output Port Options
6. Select options for the printer as needed for your installation. Most printers are parallel.
4-15
Control Panel Installation LS10061- 001SK-E
SBUS Connection
SBUS Address DIPs
Dry Contact Inputs
7. If you are using a serial printer, use the next screen to select serial port options as required for your printer. Refer to your printer manual if you need more information.
Option Choices
Baud Rate: 75 - 19200 Data Bits : 5 - 8 Stop Bits: .5, 1, 2 Parity: None, Even, Odd
4.8 5880 LED I/O Module
The 5880 is an LED driver board that can be used in a wide variety of applications, including as an interface with most customized floor plan annunciator boards. The 5880 can drive up to 40 LEDs and has one PZT controller. The 5880 also has eight inputs for monitoring dry contacts. When used with the 5820X L-EVS the 5880 inputs can be programmed to replicate the eight EVS buttons located on the front of the voice control module. (See section 9.5 for programming options). The following sub-sections describe hardware installation. Refer to Section 7 for programming information.
4.8.1 5880 Board Layout
Figure 4-20 shows the locations of screw terminals for connection to the panel and contact monitor wiring; pin connectors for connecting LEDs; and the DIP switch for selecting an SBUS ID number for the 5880.
4.8.2 5880 Connection to Panel
The 5880 connects to the panel via the SBUS. Make connections as shown in Figure 4-21. After the 5880 is
Figure 4-20 5880 Board Layout
4-16
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
Supervised Power Limited
connected to the panel, it must be added to the system. This programming step is described in Section 4.10.
Figure 4-21 5880 Connection to Main Control Panel Assembly
4-17
Control Panel Installation LS10061- 001SK-E
11
20
12 13 14
15 16 17 18 19
LED Power
no connection
Anode
Cathode
LEDs
P2
5880 LED Outputs
1
10
2 3 4
5 6 7 8 9
LED Power
Programmable Open Collector Output
Not mappable.
Matches PZT pattern
on on-board
annunciator
Anode
Cathode
LEDs
P1
Connectors P3 and P4 wired same as P2.
4.8.3 LED Wiring
There are four 12-pin connectors on the 5880 board for connecting LEDs. Each LED gets its power from Pin 11. Internal resistors are sized so that there is approximately 10 mA of current for each LED, no series resistors are required. LED outputs can be mapped to output circuits. See Section 6 for programming details.
Wire the LEDs as shown in Figure 4-22. On connector P1, Pin 12 is an open collector output for controlling a PZT. If used, the 5880 PZT will match the
PZT pattern of the on-board (or 5860) annunciator.
Note: The circuit connected to “Open Collector Output” (last pin on P1) must be current limited so that no more
than 100 mA of current is allowed to flow into the open collector transistor.
4.8.4 Dry Contact Wiring
The 8 input circuits on the 5880 board are for monitoring switch inputs-any type of switch supported by the control panel can be used with the 5880. For example, you can use a 5880 to monitor pull stations, water flo w, tamper, reset, or silence switches.
Wire dry contacts as shown in Figure 4-23. Notice grouping of terminals; power terminals are shared by two
Figure 4-22 5880 Board Layout
4-18
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
Supervised
4.7k EOL model 7628
inputs.
Figure 4-23 Dry Contact Wiring
4-19
Control Panel Installation LS10061- 001SK-E
Supervised Power Limited
4.9 5865-3 / 5865-4 LED Annunciator Installation
The 5865-3 and 5865-4 are LED annunciators. The 5865-4 has 30 mappable LEDs, remote silence and reset key switches, and a general system trouble LED. The 5865-3 has 30 mappable LEDs only. These are arranged as 15 pairs of red (typically used for alarm) and yellow (typically used for trouble) LEDs.
Installation of the 5865-5 and 5865-4 is identical. The key switches and the trouble LED follow the behavior of other system annunciators and do not require any installation steps. The following sub-sections describe how to install the 5865-3 and 5865-4 hardware. Refer to Section 6 for programming information.
Note: This manual uses “5865” when referring to aspects of the 5865-3 and 5865-4 that are common to both
models.
Figure 4-24 5865-3 and 5865-4 Assembly (front view)
4.9.1 5865 Connection to Panel
The 5865 connects to the panel via the SBUS. Make connections as shown in Figure 4-25. After the 5865 is connected to the panel, it must be added to the system. This programming step is described in Section 4.10.
Figure 4-25 5865 Connection to the FACP
4-20
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
4.9.2 5865 Mounting
Mount the 5865-4 to a standard 4-gang electrical box. Mount the 5865-3 to a standard 3-gang electrical box. In Figure 4-26, the 5865-4 attached to a 4-gang box is used as an example.
Figure 4-26 5865 Mounting Example
The 5865 ships with a set of zone description labels that can be inserted into the 5865 board assembly. These labels can be used in a typewriter or can be written on by hand. Slide the labels under the plexiglass as shown in Figure 4-27. The LEDs will show through the label when illuminated.
Figure 4-27 Inserting Zone Description Labels
4-21
Control Panel Installation LS10061- 001SK-E
4.10 Configuring Modules
This section describes how to configure any system hardware modules that have been added to the system.
4.10.1 Assigning SBUS Module IDs
When installing a hardware module (such as, 5815XL, 5824, 5860, 5496, 5895XL, 5865-3, 5865-4, EVS-50W, EVS-125W, EVS-100W, EVS-RVM, or EVS-VCM), you must use the DIP switches on the module to assign an ID# to the module.
Figure 4-28 shows all possible DIP switch positions and their correlation to a numerical ID. For example, to select ID 2, place DIP switch 2 in the up position.
Refer to Section 7.2 to edit, add, delete, and view module list.
Figure 4-28 Possible module addresses
4-22
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
4.11 Telephone Connection
Connect the telephone lines as shown in Figure 4-29. The Model 7860 phone cord is available from Silent Knight for this purpose.
A number of programmable options are available for customizing telephone lines. These options are described in Section 7.6.
Figure 4-29 Connection of Telephone Lines
4.12 Flexputs
The six Flexput™ circuits are an innovative and versatile feature of the control panel. They can be used as: Class A or B notification circuits, Class A or B initiation circuits (either 2 or 4 wire detectors), or as auxiliary power (resettable, continuous, door holder, or sounder sync).
The polarity of the Flexput terminals differs depending on whether the circuit is programmed as an input or an output circuit. If the circuit is programmed as an input circuit (for a detector or normally open contact) the X terminal is negative and O terminal is positive. If the circuit is programmed as an output circuit (Aux pow er or NAC) then the X terminal is positive and the O terminal is negative.
This section of the manual explains how to install conventional notification appliances and initiatin g devices to be used with the system.
I/O Circuits
4.12.1 Conventional Notification Appliance
This sub-section of the manual explains how to install conventional notification appliances for Class A (Style Z) and Class B (Style Y) configurations.
4-23
Control Panel Installation LS10061- 001SK-E
Alarm Polarity Shown.
4.7 kEOL Supervised
Power Limited
Notification Wiring
Max. Impedance: 1.5
Regulated 24 VDC Full Wave Rectified
27.4 VDC, 3A per Circuit, 6A max Combined
4.12.1.1 Class B Notification Wiring
You must use an appliance from the list of compatible appliances in the Appendix A at the back of this manual. To install a circuit:
1. Wire Class B Notification appliances as shown in Figure 4-30.
2. Configure the circuit through programming (see Section 7.5).
Figure 4-30 Class B Notification Appliance Circuit Wiring
4.12.1.2 Class A Notification Wiring
You must use an appliance from the list of compatible appliances in the Appendix at the back of this manual. To install a Class A notification appl iance circuit:
1. Wire the Class A notification appliances as shown in Figure 4-31.
Caution
For proper system supervision do not use looped wire under terminals marked O and X of the Flexput connectors. Break wire runs to provide supervision of connections.
4-24
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
Supervised Power Limited
Regulated 24 VDC Full Wave Rectified
27.4 VDC, 3A per Circuit, 6A max Combined
2. Configure the circuit for Class A in programming (see Section 7.5).
Figure 4-31 Class A Notification Appliance Circuit Configuration
Note: In programming an y point that us es multip le Flexp ut circuits, the lowest Flexput circuit number is used to
refer to the circuit pair. For example, Figure 4-31 uses both Flexput circuit 5 and 6, so in programming it would be referred to as point 5.
4.12.2 Conventional Input Switch Circuits
This section of the manual explains how to install conventional initiating devices for Class A (Style D) or Class B (Style B) configurations.
4-25
Control Panel Installation LS10061- 001SK-E
Supervised Power Limited
4.7 kEOL
4.12.2.1 Class B Inputs
You can connect conventional Class B switches, such as waterflow switches and pull stations, directly to the Flexput circuits of the control panel.
To install a Class B switch:
1. Wire the Class B switch as shown in Figure 4-32.
2. Configure the circuit through programming (see Section 7.5).
Figure 4-32 Class B Input Switches
4.12.2.2 Class A Inputs
You can connect conventional Class A switches, such as waterflow switches and pull stations, directly to the Flexput circuits of the control panel.
To install a Class A switch:
1. Wire the Class A switch as shown in Figure 4-33.
Caution
For proper system supervision do not use looped wire under terminals marked + and – of the Flexput connectors. Break wire runs to provide supervision of connections.
4-26
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
Note: Flexput circuit 5 and 6
used as an example. Any Flexput point pairing could be used.
Supervised
Power Limited Note: Flexput circuit 5
used as an example. Any Flexput circuit could be used.
4.7 kEOL
Supervised Power Limited
2. Configure the circuit through programming (see Section 7.5).
Figure 4-33 Class A initiating Switches
Note: In programming an y point that us es multip le Flexp ut circuits, the lowest Flexput circuit number is used to
refer to the circuit pair. For example, Figure 4-33 uses both Flexput circuit 5 and 6, so in programming it would be referred to as point 5.
4.12.3 Installing 2-Wire Smoke Detectors
Any compatible UL listed two-wire smoke detector can be used with the control panel (see Appendix A for list of compatible smoke detectors). Figure 4-34 and Figure 4-35 illustrate how to connect a UL listed 2-wire detector to the control panel.
4.12.3.1 Installing 2-Wire Class B Smoke Detectors
To install a Class B two-wire smoke detector, wire as shown in Figure 4-34.
Figure 4-34 Two-Wire Class B Smoke Detector
4-27
Control Panel Installation LS10061- 001SK-E
Note: Flexput circuit 5 and 6
used as an example. Any Flexput point pairing could be used.
Supervised Power Limited
4.12.3.2 Installing 2-Wire Class A Smoke Detectors
To install a Class A two-wire smoke detector, wire as shown in Figure 4-35.
Figure 4-35 Two-Wire Class A Smoke Detector Connections
Note: In programming an y point that us es multip le Flexp ut circuits, the lowest Flexput circuit number is used to
refer to the circuit pair. For example, Figure 4-35 uses both Flexput circuit 5 and 6, so in programming it would be referred to as point 5.
4.12.4 Installing 4-Wire Smoke Detectors
Any compatible UL listed four-wire smoke detector can be used with the control panel (see Appendix A for list of compatible smoke detectors). Figure 4-34 and Figure 4-35 illustrate how to connect a UL listed four-wire detector to the control panel.
4.12.4.1 Installing 4-Wire Class B Smoke Detectors
Figure 4-36 illustrates how to install a 4-wire Class B smoke detector. Conventions used for wiring 4-wire Class B loops:
1. Up to three Class B 4-wire smoke detector loops can be connected to the control panel at once.
2. Each Class B loop input is paired with a unique power source as shown in Figure 4-36.
4-28
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
Air Products
PAM-2
Model 160150
Supervision
Module
ESL 449CT
Note: Flexput circuit 5 and 6
used as an example. Any Flexput point pairing could be used.
Supervised Power Limited
4.7 kEOL
Air Products
PAM-2
Model 160150
Supervision
Module
Air Products
PAM-2
Model 160150
Supervision
Module
Supervised Power Limited
3. Each loop gets smoke power from the even numbered Flexput circuit and the contact input is connected to the odd numbered Flexput circuit.
Figure 4-36 Class B 4-Wire Smoke Detector Connections
Note: In programming an y point that us es multip le Flexp ut circuits, the lowest Flexput circuit number is used to
refer to the circuit pair. For example, Figure 4-36 uses both Flexput circuit 5 and 6, so in programming it would be referred to as point 5.
4.12.4.2 Installing 4-Wire Class A Smoke Detectors
Figure 4-37 illustrates how to install a 4-wire Class A detectors. Conventions used for wiring 4-wire Class A loops:
1. Up to two Class A 4-wire loops can be connected to the control panel at once.
2. Smoke power is supplied to each Class A loop as shown in Figure 4-37.
Figure 4-37 Class A 4-Wire Smoke Detector Connections
4-29
Control Panel Installation LS10061- 001SK-E
Note: In programming any point that uses multiple Flexput circuits are always referred to as the lowest Flexput
circuit number used. For example, Figure 4-37 uses Flexput circuits 1, 2, 3 together and 4, 5, 6 together. In programming (1, 2, 3) would be referred to as point 1, and (4, 5, 6) would be referred to as point 4.
4.12.5 Auxiliary Power Installation
Flexput Circuits 1-6 on the control panel can be used as auxiliary power circuits. The four types of auxiliary power available are:
Door Holder Power (see Section 4.12.5.1)
Constant Power (see Section 4.12.5.2)
Resettable Power (see Section 4.12.5.3)
Sounder Sync Power (see Section 4.12.5.4)
Auxiliary power circuits are power limited. Each circuit can source up to 3A (total current for all Flexput circuits must not exceed 6.0 A).
To install an auxiliary power circuit:
1. Wire the Flexput circuit(s) that will be used for auxiliary power. See Figure 4-38 for location of Flexput cir­cuits.
2. Configure the auxiliary power output through programming (see Secti on 7.5).
Figure 4-38 Flexput Circuit Location
4.12.5.1 Door Holder Power
Door holder power is intended for fire door applications. When there are no alarms in the system and the panel has AC power, do or hold er circ uits have 24-volt power present at their terminals. Any alarm will caus e power to disconnect. Power will be re-applied when the system is reset. If AC power is off for more than 15 seconds, the auxiliary door holder power will be disconnected to conserve the battery backup. When AC power is restored, power is immediately restored to the door holder circuits.
Use a UL listed door holder ESL DHX-1224, for this application.
4.12.5.2 Constant Power
Use constant power for applications that require a constant auxiliary power source. Power is always present at Constant circuits.
4.12.5.3 Resettable Power
Resettable power is typically used to power beam detectors, flame detectors and conventional 4-wire smoke detectors. For circuits selected as Resettable, 24-volt power is always present at the terminals unless a system reset occurs. If a system reset occurs, power is disconnected from the terminals for 30 seconds, then re-applied.
4-30
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
4.12.5.4 Sounder Sync Power
Sounder Sync Power continuously outputs the System Sensor synchronization pattern and is int e nded for use with B200S sounder bases.
4.13 On-Board Relays (Conventional)
The control panel has two built-in programmable relays and a built-in trouble relay. All relays are Form C rated at 2.5 A @ 24 VDC.
Figure 4-39 Location of Conventional Relay Circuits
4.13.1 Trouble Relay
The control panel has a dedicated Form C trouble relay built into terminals 30-32. The relay provides a normally open and a normally closed contact. The trouble relay will deactivate under any trouble condition.
Note: The N.C. contact is the relay contact that is closed when the panel has power and there are no trouble con-
ditions.
4.13.2 Programmable Relays
The control panel has two Form C programmable relays built into terminals 24-29. Each relay provides a normally open and a normally closed contact.
To install one or two programmable relays, follow these steps.
1. Wire Relay 1 and/or Relay 2 as needed for your application. See Figure 4-39 for the location of the relay ter­minals.
2. Configure the relay through programming (see Section 7.5).
4.14 Remote Station Applications
4.14.1 Keltron Model 3158 Installation
The control panel is compatible with Keltron Model 3158, used for direct connection to a Keltron receiver. The 3158 reports alarms, supervisories, and troubles.
The steps for connecting the 3158 to the control panel. Refer to the 3158 installation instructions for complete information.
1. Wire the 3158 to the control panel as shown in the connection list and Figure 4-40.
2. Wire the 3158 within 20 feet of the control panel. Wiring must be enclosed in conduit.
3. Program control panel Relay 1 for alarm.
4. Program Flexput circuit 5 for alarm.
4-31
Control Panel Installation LS10061- 001SK-E
Not suitable for remote station where separate transmission supervisory (if applicable), an d
protected premise service circuits are required for fire trouble signals. Intended for connection to a
polarity reversal circuit of a remote station receiving unit having compatible ratings.
Example
5. Program Flexput circuit 6 for supervisory non latching.
Table 4-3: Keltron 3158 to Control Panel Connections
Terminal # Connects To Terminal # Connects To
3158 Term. 1 To Keltron receiving equipment 3158 Term. 8 Control panel Term. 28 3158 Term. 2 To Keltron receiving equipment 3158 Term. 9 Control panel Term. 5 3158 Term. 3 Earth ground 3158 Term. 10 Control panel Term. 4 3158 Term. 4 Not used; no connection. Control panel Term. 6 Control panel Term. 29 3158 Term. 5 Control panel Term. 18 Control panel Term. 28 Control panel Term. 31 3158 Term. 6 Control panel Term. 19 Control panel Term. 29 Control panel Term. 30 3158 Term. 7 Control panel Term. 7
Figure 4-40 Keltron 3158 Connection to Control Panel
4.14.2 City Box Connection Using the 5220 Module
This section describes how to connect the control panel to a local energy municipal fire alarm box or “city box” as required by NFPA 72 Auxiliary Protected Fire Alarm systems for fire alarm service. The city (master) box is an enclosure that contains a manually operated transmitter used to send an alarm to the municipal communication center which houses the central operating part of the fire alarm system.
City Box Standby Current: 0 (Notification supervision current accounted for in control panel draw). Alarm Current: 1 Amp for 1 second 27.2 VDC max The maximum coil and wire resistance (combined) must not exceed 30 ohms. To install the 5220 for city box connection:
1. Use one of the knockouts on the right side of the control panel to connect the 5220 using a short piece of conduit (must not exceed 20 feet in length).
2. Wire the 5220 to the control panel as shown in Figure 4-41. This drawing also shows how to connect the city
box coil to terminals 3 and 4 on the 5220. Do not install an EOL resistor in the terminals of the Flexput cir­cuit used for this application.
3. Connect earth ground wire to the 5220 chassis with mounting screw.
4-32
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
Note: Flexput Circuit 1 Used as an example. Any Flexput circuit could be used.
All circuits non-power-limited
All wiring non-supervised
4. Program the Flexput circuit used as a notification circuit, continuous and non-silencing. Refer to Section 7.5 for point programming, Section 7.5 for group settings, and Section 7.3 for zone settings and mapping.
It is not possible to reset the remote indication until you clear the condition and reset the control panel.
Figure 4-41 City Box Connection
4.14.3 NFPA 72 Polarity Reversal
Note: Intended for connection to a polarity reversal circuit of a control unit at the protected premises having
compatible rating.
4.14.3.1 Using the 5220 Module
When the 5220 is wired and programmed for polarity reversal, it reports alarm and trouble events to a remote site. Alarms will override trouble conditions and it will not be possible to reset the remote indicator until the condition is cleared and the control panel is reset.
If an alarm condition occurs, the alarm relay will close, overriding the trouble condition. Standby Current: 100 mA, 24 VDC
Alarm: 100 mA, 24 VDC To install the 5220 for polarity reversal, follow the steps below:
1. Locate the knockout on the right side of the control panel cabinet to connect the 5220 using a short piece of conduit (must not exceed 20 feet in length).
2. Wire the 5220 to the control panel using the four-wire pigtail provided as shown in Figure 4-42. This dia­gram also shows how to connect the 5220 to the remote indicator. Do not install an EOL resistor in the ter­minals of the Flexput circuit used for this application.
3. Connect earth ground wire to the 5220 chassis with mounting screw.
4. Program the Flexput circuit used as a notification circuit, continuous and non-silencing. Refer to Section 7.5 for point programming, Section 7.4 for group settings, and Section 7.3 for zone settings and mapping.
4-33
Control Panel Installation LS10061- 001SK-E
All circuits power-limited.
All wiring supervised.
Note: Flexput circuit 1 and Relay 1 used as examples. Any Flexput circuit and either relay 1 or relay 2 could be used.
Jumper these terminals when City Box is not used.
Intended for connection to a Polarity Reversal circuit of a Remote Station receiving unit having compatible ratings.
5. If necessary, adjust loop current using the potentiometer (R10) on the 5220 board. Normal loop current is 2­to-8 mA with a 1k ohm remote station receiving unit. Maximum loop resistance is 3k ohm.
Figure 4-42 Polarity Reversal Connection Using the 5220 Module
4.14.3.2 Using the 7644* Module
When the 7644 is used for polarity reversal, it allows alarm and trouble events to be reported to a remote site. Alarms will override trouble conditions and it will not be possible to reset the remote indicator until the condition is cleared and the control panel is reset.
To install the 7644 for polarity reversal:
1. Wire the 7644 to the control panel as shown in Figure 4-43. Do not install an EOL resistor on the terminals of the Flexput circuit used.
Note: Use only Flexput circuits on the control panel for reverse polarity.
2. Program the Flexput circuit as a notification circuit. See Section 7.5.2.
3. Map the group to activate constant on from the zone event. See Section 7.3.1.3.
4. Program the output group characteristics as non-silenceable and reverse polarity. See Section 7.4.1.2.
Figure 4-43 Polarity Reversal Connection Using the 7644
Note: *When ordering, request as P/N 7644-L8
4-34
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
UL Listed EOL
1 k
To City Box
Intended for Connection to a Polarity Reversal Circuit of A Remote Station Receiving Unit Having Compatible Rating.
Must be installed in City Box enclosure
4.14.4 Using the SD500-ARM Ad dressable Relay Module
When the SD500-ARM is wired for polarity reversal, it reports alarm and trouble events to a remote site. Alarms will override trouble conditions and it will not be possible to reset the remote indicator until the condition is cleared and the control panel is reset.
Wire the SD500-ARM as shown in Figure 4-44.
Figure 4-44 Polarity Reversal Connection Using the SD500-ARM Module
4.14.5 Using a MR-201/T Control Relay From Air Products
When the MR-201/T control relay is wired for polarity reversal, it reports alarm and trouble events to a remote site. Alarms will override trouble conditions and it will not be possible to reset the remote indicator until the condition is cleared and the control panel is reset.
If an alarm condition occurs, the alarm relay will close, overriding the trouble condition. Current: 15 mA max. Operating Voltage: 24 VDC nominal Resistance: 4 K To install the MR-201/T for polarity reversal, follow the steps below:
4-35
Control Panel Installation LS10061- 001SK-E
Intended for Connection to a Polarity Reversal Circuit of A Remote Station Receiving Unit Having Compatible
Rating.
1. Wire the MR-201/T as shown in Figure 4-45.
Figure 4-45 Wiring the MR-201/T
2. Program the Flexput circuit for non silence NAC circuit (see Section 7.5).
4-36
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
4.14.6 Transmitter Activated by Dry Contacts
This section describes the connection of a UL 864 listed remote station transmitter to the 5820XL/5820XL-EVS FACP dry contacts. The FACP contacts must be supervised by the remote station transmitter module using end­of-line resistors (ELRs) with a value determined by the transmitter manufacturer. Power is also provided by the remote station transmitter manufacturer. Refer to the remote station transmitter manufacturer’s manual for details.
4-37
LS10061-001SK-E
Section 5 SK SLC Device Installation
Caution!
To avoid the risk of electrical shock and damage to the unit, power should be OFF at the control panel while installing or servicing.
5.1 List of SK SLC Devices
The following SK SLC devices can be used with the control panel. SK detectors include a 6" base. See the appropriate section number in this manual or the device installation instructions (packaged with the device) for more information.
Note: The control panel supports the use of either SK SLC devices or SD SLC devices. You cannot
install both SLC device types on the control panel.
SK
Part Number
SK-Photo Photoelectric smoke detector SK-Photo-T Photoelectric smoke detector with thermal (135°F) SK-PhotoR Photoelectric detector with remote test capability SK-Acclimate Multicriteria photoelectric smoke detector with thermal (135°F) SK-Beam Reflected beam smoke detector without test feature SK-Beam-T Reflected beam smoke detector with test feature SK-Ion Ionization smoke detector I56-3428-001 SK-Duct Photoelectric duct smoke detector with extended air speed range I56-3432-000 SK-Heat Fixed temperature thermal detector (135°F)
SK-Heat-HT Fixed high temperature thermal detector (190°F) SK-Pull-SA Addressable single action pull station I56-3446-000 SK-Pull-DA Addressable dual action pull station I56-3447-000 SK-Iso Fault isolator module I56-3445-000 SK-Monitor Monitor module I56-3442-000 SK-Minimon Mini monitor module I56-3444-000 SK-Monitor-2 Dual input monitor module I56-3435-000 SK-Mon-10 10 input monitor module I56-3443-000 SK-Relay Addressable relay module I56-3438-000 SK-Relay-6 Six relay control module I56-3439-000 SK-Relaymon-2 Dual relay/monitor module I56-3735-000 SK-Zone Addressable zone interface module I56-3440-000 SK-Zone-6 Six zone interface module I56-3441-000 SK-Control Supervised control module I56-3436-000 SK-Control-6 Six circuit supervised control module I56-3437-000 SK-Fire-CO CO Smoke Detector I56-3945-000 B200S Sounder Base I56-3387-00 B201LP 6" mounting base I56-0595-00 B224BI 6" isolator base I56-0725-00 B224RB 6" relay base I56-3737-00 B200SR Sounder base I56-3392-00 B501 4" mounting base I56-0357-00
Model Name/Description
Installation
Instruction PN
I56-3426-001
I56-3433-001
I56-3429-000SK-Heat-ROR Rate-of-rise thermal detector with 135° fixed temperature
5-1
SK SLC Device Installation LS10061-001SK-E
Part Number
B200SR-LF B200S-LF
SK
Model Name/Description
Low Frequency Sounder Base Low Frequency Sounder Base
Installation
Instruction PN
I56-4152-00 I56-4151-00
5.2 List of SD SLC Devices
The following SD SLC devices can be used with the control panel. SD detector bases are sold separately. See the appropriate section number in this manual or the device installation instructions (packaged with the device) for more information.
Note: The control panel supports the use of either SD SLC devices or SK SLC devices. You cannot install both
SLC device types on this control panel.
SD
Model Number
SD505-APS Photoelectric smoke detector
SD505-AHS Absolute temperature heat detector. Trip point range from 135°F–150°F (0°C–37°C) SD505-6AB 6" base for use with the SD505-AHS, SD505-AIS, and SD505-APS 150955 SD505-6IB 6" short circuit isolator base for use with the SD505-AHS, SD505-AIS, and SD505-APS 151175 SD505-6RB 6" relay base for use with the SD505-AHS, SD505-AIS, and SD505-APS 151192 SD505-6SB 6" sounder base for use with the SD505-AHS, SD505-AIS, and
SD505-APS SLC devices
SD505-DUCT Duct Housing including the SD505-APS Analog Photoelectric Smoke Sensor. Intake
tubing for duct available in three lengths: SD505-T2 (2.5 foot); SD505-T5 (5 foot);
SD505-T10 (10 foot) SD505-DUCTR Duct Housing with relay including the SD505-APS Analog Photoelectric Smoke Sensor. SD500-PS/-PSDA Single or dual action addressable pull station 151177 SD500-AIM Addressable input module (switch input), standard size, DIP switch configurable 151071 SD500-MIM Mini input monitor module (switch input), small size, DIP switch configurable. Fits in
single-gang box with manual pull station switch SD500-ANM Addressable notification module 151109 SD500ARM Addressable relay module DIP switch configurable 151091 SD500-SDM Addressable smoke detector module. Use to assign an address to a loop of
conventional devices SD500-LIM Line isolator module. Fits in a double gang box 151125 SD500-LED Addressable LED driver module. Capable of driving up to 80 LEDs. Up to 40 SD500-
LED Driver Modules can be used per SLC loop SD505-DTS-K Remote test switch & LED indicator for the SD505-DUCTR 1700-09882
Model Name/Description
Installation
Instruction PN
150955SD505-AIS Ionization smoke detector
151191
1700-09882
151071
151193
151232
5.3 Maximum Number of Devices
The 5820XL/5820XL-EVS supports SK or SD devices on one system. The maximum number of devices per system varies depending on device protocol and the number of 5815XL signaling circuit loop (SLC) expan ders added to the system. Device support is as follows:
SK Devices–A system can support a total of 396 SK detectors and 396 SK modules. 99 devices can be added to 5820XL/5820XL-EVS control panel. Each optional 5815XL adds another 99 detectors and 99 modules. Add up to three 5815XLs to 5820XL/5820XL-EVS system to achieve the maximum number of devices on the system.
OR
5-2
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
SD Devices–5820XL/5820XL-EVS system can support a total of 508 SD SLC detectors and modules, in any combination. 127 devices can be attached to 5820XL/5820XL-EVS control panel. Each optional 5815XL adds another 127 devices. Add up to three 5815XLs to 5820XL/5820XL-EVS system to achieve the 508 point capacity.
5.4 Wiring Requirements for SLC Devices
The following information applies to all SLC devices. Refer to the section that describes the type of device you are installing for details.
5.4.1 Wiring 5815XL in Style 4 (Class B) Configuration
No special wire is required for addressable loops. The wire can be untwisted, unshielded, solid or stranded as long as it meets the National Electric Code 760-51 requirements for power limited fire protective signaling cables. Wire distances are computed using copper wire.
Maximum wiring resistance is 40 ohms for SK device and 50 ohms for SD devices. Maximum loop length depends on the wire gauge. See Table Table 5-1 and Table 5-2.
Table 5-1 Maximum Distance for SK Devices
Wire Gauge Max. Distance for SK Modules
22 AWG 1200 feet 18 AWG 3100 feet 16 AWG 4900 feet 14 AWG 7900 feet 12 AWG 10,000 feet
Table 5-2 Maximum wiring distance for SD Devices
Wire Gauge Max. Distance for SD Modules
22 AWG 1500 feet 18 AWG 3900 feet 16 AWG 6200 feet 14 AWG 10,000 feet
5-3
SK SLC Device Installation LS10061-001SK-E
Figure 5-1 and Figure 5-2 show how wire length is determined for out & back tap and T-Tap style wiring.
Figure 5-1 Calculating wire run length for a simple out and back
When using T-taps, the total length of all taps and the main bus must not exceed 40,000 feet. This requirement must be met in addition to the maximum distance requirements for the various wire gauges.
Figure 5-2 Calculating Wire Run Length for a T-tap
5-4
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
5.4.2 Wiring 5815XL in Style 6 & 7 (Class A) Configuration
The following figure illustrates how to wire the SLC loop for Style 6 or Style 7 Class A installations.
Note: Style 6 does not use short circuit isolator devices. Note: Style 7 wiring requires an isolator module as the first device on the in and the out loops. Note: No t-taps allowed on class A SLC loops.
Figure 5-3 Class A SLC Configuration
Caution
For proper system supervision do not use looped wire under terminals marked SLC + and – of the SLC device connectors. Break wire runs to provide supervision of connections.
5.5 Wiring SK SLC Detectors
This section describes how to install SK heat and smoke detectors. All detectors ship with installation instructions. Refer to the detectors’ installation instructions for more detailed information.
This information applies to the following SK models:
SK-Photo Photoelectric Smoke Detector
SK-Photo-T Photoelectric Smoke Detector with Thermal
SK-Acclimate Photoelectric Smoke Detector with Thermal
SK-Heat Fixed T emperature Detector
SK-Heat-T High Temperature Thermal Detector
SK-Heat-ROR Rate-of-Rise Thermal Detector
SK-Ion Ionization Smoke Detector
SK-Fire-CO CO Detector
To wire SK detectors:
5-5
SK SLC Device Installation LS10061-001SK-E
Caution: Do not loop wire under Terminal 1 or 2.
Break wire run to provide supervision of connections.
Example 1: Device Set to 01.
Example 2: Device Set to 42.
All dials labeled for
ONES or TENS position.
1. Wire device bases as shown in Figure 5-4.
2. Set the address for each device as described in Section 5.6.
Figure 5-4 Heat and Smoke Detector Connection to the Panel.
5.6 Addressing SK SLC Devices
All SK devices are addressed using the two rotary dials that appear on the device board. Use the ONES rotary dial to set the ones place in a one or two digit number, and use the TENS rotary dial to set the tens place in a two digit number.
SK device addresses are handled differently than SD device addresses. The control panel recognizes when an SK detector or SK module is installed. For this reason, SK detectors can be assigned any unique address from 1 to 99, and SK modules can be assigned any unique address from 1 to 99. Unlike SD detectors and modules which share addresses 1 through 99, there can be an SK detector using address 1 and an SK module using address 1. 0 is an invalid address.
Example 1: To select device address 1, turn the ONES rotary dial to 1 and the TENS rotary dial to 0 as shown in Figure 5-5.
Example 2: To select device address 42, turn the ONES rotary dial to 2 and the TENS rotary dial to 4 as show in Figure 5-5.
Figure 5-5 SK SLC Device Addressing Using Rotary Dials
5-6
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
5.7 Wiring SD SLC Detectors
This section describes how to install SD heat and smoke detectors. All detectors ship with installation instructions. Refer to each detectors' installation instructions for more detailed information.
This information applies to the following SD models:
• SD505-AHS Heat Detector
• SD505-AIS Ionization Smoke Detector
• SD505-APS Photoelectric Smoke Detector
To wire SD505-APS, SD505-AHS, or SD505-AIS detectors:
1. Wire device bases as shown in Figure 5-6.
2. Set the address for each device as described in Section 5.8.
Figure 5-6 Heat or Smoke Detector Connection to the FACP
5.8 Addressing SD Devices
This section explains how to address SD detectors and modules.
5.8.1 SD505-APS, SD505-AHS, and SD505-AIS
The SD505-APS photoelectric smoke detector, SD505-AHS heat detector, and SD505-AIS ionization smoke detector are easily addressed at the FACP . An access code with the option to Set SLC Device Address enabled is required to perform this task.
To address a SD505-APS, SD505-AHS, and SD505-AIS:
5-7
SK SLC Device Installation LS10061-001SK-E
1. Connect a detector base temporarily to the programming terminals as shown in Figure 5-7. (You can use the same base for each detector.)
Figure 5-7: Temporary Connection of Detector Base to Panel for Addressing
2. Enter the Installer code. The panel will automatically go to the main menu.
3. Select 2 for Point Functions.
4. Select 3 for Set SLC Device Address.
5. Select “Yes” by pressing the up arrow, then press ENTER. (The panel will go into trouble at this point. You can use the SILENCE key to stop the PZT. The trouble will clear automatically when the panel re-boots when you finish programming.)
6. When the wait message clears, the following options display: 1- for Read Address. Use to read (or check) a single detector’s address.
2- for Write Address. Use to program a single detector’s address. 3- for Seq. Programming. Use to program more than one detector in sequential order.
7. If you are changing addresses, write the programmed address on the back of the device.
8. T o exit press left arrow until fully exited.
5-8
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
5.8.2 SLC Devices with DIP Switches
Input and relay module addresses are set using the DIP switches on the module board. The chart below shows the available addresses. For example, to select address 3, place DIP switches 1 and 2 in the up position. The range of valid addresses is 1-127.
0 is an invalid address.
Figure 5-8 SD SLC Device Addressing Using DIP Switches
5-9
LS10061-001SK-E
Section 6 Programming Overview
This section of the manual is intended to give you an overview of the programming process. Please read this section of the manual carefully, especially if you are programming the control panel for the first time.
The JumpStart AutoProgrammin g feature auto mates many pro gramming task s and selects defau lt options f or the system. You should run JumpStart at least once when you are installing the system. See Section 6.2 for details. After you run JumpStart, you may need to do some additional programming depending on your installation. Section 7 of this manual covers manual programmable options in detail.
Programming the panel can be thought of as a three part process. You must program:
System options. These are options that affect general operation of the panel (see Section 7.6 for details).
Options for input points and zones. These are primarily options that control the detection behavior of devices (see Section 7.5 for details).
Options for output points and groups. This includes selecting characteristics for output groups and mapping output circuits to output groups (see Section 7.4 for details).
6.1 Security and Data Protection
Communication Security - Level 1 Stored Data Security - Level 0
Physical Security - Level 1 Access Control Security - Level 1
6.2 JumpStart Autoprogramming
The JumpStart AutoProgramming feature allows for faster system setup. When you run JumpStart (immediately after addressing SLC devices), the system scans devices on all SLC loops and determines device type (for example, ionization smoke detector or heat sensor) and selects some system options based on the device type. JumpStart AutoProgramming saves the installer from having to program options for each device. Depending on the application, the installer may need to make some changes after JumpStart AutoProgramming completes.
See Section 6.2.3 for complete details about running JumpStart AutoProgramming.
IMPORTANT
JumpStart is intended to be run one time only, immediately after SLC devices have been addressed and connected. JumpStart will reset all manually programmed options to default settings. Do not run JumpStart after you have configured the system.
6-1
Programming Overview LS10061-001SK-E
6.2.1 Input Points
JumpStart will determine the number and type of input points (detectors or contact monitor modules) on each SLC loop. JumpStart assigns the correct detector type (heat, ionization or photoelectric), so the installer does not need to edit the device type for detectors. Any contact monitor modules on the system will be assigned ty pe “Manual Pull.” The installer will need to manually change the switch type if manual pull is not correct.
JumpStart creates one zone (Zone 1) and assigns all input points to Zone 1. Zone 1 is mapped to Output Group 1. If the system has an EVS-50W, EVS-100W or EVS-125W Amplifier, then Output Group 2 will also be created and all input points will be mapped to both Group 1 and Group 2. After JumpStart completes, you can re-map to configure a multiple zone/output group system (see Section 7.3.1.3). For a general explanation of mapping see Section 6.3.
6.2.2 Output Points
The 5820XL JumpStart creates three output groups. The 5820XL-EVS with amplifiers will create four output groups. The output circuits are assigned as follows:
Circuits 1-6: Configured as Notification and assigned to Group 1. JumpStart automatically programs Zone 1 to activate Group 1 using constant on output when an alarm condition occurs.
Circuit 7 (Relay 1): Assigned to Group 249. JumpStart automatically programs Zone 1 to activate Group 249 using constant on output when a supervisory condition occurs.
Circuit 8 (Relay 2): Assigned to Group 250. JumpStart automatically programs Zone 1 to activate Group 250 using constant on output when an alarm occurs.
Amplifier Circuits: Assigned to Group 2. JumpStart automatically programs Zone 1 to activate Group 2.
Addressable output points (Relay modules, NAC Modules, Sounder Bases, Relay Bases): All addressable relay devices will be configured as “Output Pt” (general purpose output point) and assigned to Group 1.
Note: Relay output is constant even if the zone activating the relay is programmed with an output pattern.
6.2.3 Running JumpStart AutoProgramming
Run JumpStart immediately after you have addressed and connected all input devices (detectors, pull stations, and etc.) and output devices (notification appliances, relays, etc.).
Note: If you need to install a few devices after you have run JumpStart, you can install them manually. Follow
instructions in Section 7 for configuration.
To run JumpStart, follow these steps:
1. Select 7 for Program Menu. Enter the Access Code
2. Select 6 for JumpStart AutoProgramming.
3. The message “WARNING WILL DELETE all system options” displays on the LCD. Select Yes to continue. A series of messages displays for the next several seconds. JumpStart scans the SLC loops for devices. This can take several minutes, depending on the number of devices attached.
4. When the message, “SLC FAMILY” message appears, select SK or SD; depending on the type of SLC devices the panel is using, and press ENTER to accept.
5. When the message “Configuring System Done” displays, press any key to continue.
6-2
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
6. Select one of the following options from the menu that displays.
1 - Review System Press 1 if you need to review the JumpStart configuration. 2 - Repeat JumpStart Press 2 if you need to rerun JumpStart for any reason.
1. If you are ready to make the JumpStart configuration permanent, select 3.
2. The system will ask you if the installation contains duct detectors. If there are none, select 2 for No and skip to Step 8. If the system contains duct detectors, select 1 for Yes and continue with Step 3.
3. From the list that displays, select the SLC that contains the duct detectors.
4. The first photoelectric or ionization detector on the system will display. Select 1 for DUCT and 2 for NonDUCT.
5. Press to select the next detector. Select 1 for DUCT and 2 for NonDUCT. Continue
3 - Accept Configuration
4 - Enter Programming
until all duct detectors have been selected. (Note: You can move backwards through the list with ).
6. When you reach the last detector on this device, press .
7. The system will ask you if there are more duct detectors in the system. If there are, select 1 for Yes and repeat from Step 3. If there are no more duct detectors, select 2 for No and continue with Step 8.
8. The system will restart in 10 seconds. You can press 1 to restart immediately.
9. After the system resets, it will use the new JumpStart configuration.
If you want to go directly to Program Mode to configure any devices, press 4. The Programming Menu appears and you can begin programming.
6-3
Programming Overview LS10061-001SK-E
6.3 Mapping Overview
This section of the manual is an overview of mapping. Details about how to select mapping options appear in the appropriate subsections in Section 7.
Mapping is an important concept with the control panel. In general terms, mapping is assigning or linking events to outputs that should activate when events occur. You do this by assigning input points to input zones, output points to output groups and then linking or mapping zones and output gro ups.
Figure 6-1 is a brief overview of the concept of mapping. The next several pages of the manual show these subjects in detail.
Figure 6-1 Mapping Overview
6-4
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
6.3.1 Input Point Mapping
Input points are assigned to input zones, as the example in Figure 6-2 shows. Any input point can be assigned to any input zone. (Input points can be assigned to one zone only. An input point can be designated as “Unused,” which means it has not been assigned to a zone).
Figure 6-2 Input Point Assignment Example
6-5
Programming Overview LS10061-001SK-E
6.3.2 Output Circuit Mapping
Figure 6-3 is a simple example showing how to assign notification and relay output circuits to groups. For an example of a simple floor above/floor below application, see Figure 6-5.
Figure 6-3 Example of Assigning Output Circuits to Groups
6-6
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
6.3.3 Zone Event Mapping
There are 11 types of events that can occur in zones (see below). For each event type, you can activate up to 8 output groups and patterns. If it is necessary to map to more than 8 output groups, an output group template may be used (see Section 7.4.5 for information on output group templates). Event types are:
Manual Pull Alarm
Water Flow Alarm
Detector Alarm (heat or smoke detectors)
Aux 1 and Aux 2 Alarm (user-specified alarm types)
Pre-alarm
Supervisory
Status Points
Trouble
CO Alarm
CO Supervisory
Figure 6-4 Example of Zone Events Mapped to Output Groups and Patterns
6-7
Programming Overview LS10061-001SK-E
Figure 6-5 Example of Zone Events Mapped to Output Groups and Patterns
6-8
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
6.3.4 Mapping LED Points
Figure 6-6 is a simple example showing how LED points are mapped to zones and output groups. Typically you would create two output groups for each zone, one for alarms and one for troubles. (LED points are available when Models 5865-3/4 and/or 5880 are used with the system.)
Figure 6-6 Example of LED Points Mapped to Output Groups
6.4 Programming Using the 5660 Silent Knight Software Suite
You can use the 5660 Silent Knight Software Suite (SKSS) to program the control panel onsite or remotely. SKSS is an optional software package that lets you easily program the control panel using a Windows-based computer and a modem*. When using SKSS, you can set up the programming options for the panel, save the options in a file, then download the file to the panel. You connect to the control panel directly using the control
(Applies to Models 5865-3/4 and 5880)
6-9
Programming Overview LS10061-001SK-E
panel’s onboard USB or serial port or remotely using a modem. If you need to connect to an older control panel that does not have a USB port, and your laptop does not have a serial port, use a USB to serial converter. SKSS is available for download online. See the SKSS manual (PN 151240) for more information.
*Modems not sold by Silent Knight. See Table 1-2 for a list of modems that have been tested for compatibility with the control panel and SKSS.
6.5 Programming Using an Annunciator
You can program the control panel from a system annunciator, using either the control panel’s on-board annunciator or a Remote Annunciator.
The following subsections describe programming basics, including a description of editing keys available for programming and how to move through programming menus. Section 7 contains specific information about individual programming options.
6.5.1 Entering / Exiting the Program Menu
To enter Program Mode:
1. Enter the Installer Code (factory programmed default code is 5820).
2. The display prompts you to press the
7).
Figure 6-7 Keypad Enabled Screen
3. Then press 7. The menu option displays. See Section 7 for detailed menu information and Section 6.6 for a quick reference listing all programmable options and JumpStart defaults.
or ENTER key to bring up the Installer Main Menu. (See Figure 6-
To exit Program Mode:
When you have completed working with the menus, press left arrow several times until you are exited from programming mode. Two prompts will display. The first prompt is to make sure you intended to leave the Program Menu (select Yes or No as appropriate). The second prompt is for accepting all changes. If you select No, any changes you have made since you entered the Program Menu will have no effect.
6-10
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
6.5.1.1 Moving through the Menus
Figure 6-8 shows how to move through Program Menu screens, using the System Options screen as an example.
Figure 6-8 Moving through Program Menu
6.5.1.2 Selecting Options and Entering Data
There are several ways to make programming selections using the control panel depending on which screen you are currently viewing. The chart below is a generic explanation.
To Press
Enter the number The corresponding number on the annunciator. Enter numeric data The appropriate number on the annunciator.
Enter text (alphanumeric data)
Select from a scrolling list
Enter each character individually by using the or arrow keys until the one you wish to select displays. Then press to select the character.
The or arrow keys to move through the list of available options. When the option you want to select is displayed, press ENTER.
6-11
Programming Overview LS10061-001SK-E
6.5.1.3 Editing Keys
The keys shown in Figure 6-9 are available for use when you are in the program menu.
Figure 6-9 Editing Keys available from Program Menu
6-12
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
6.6 Programming Menu Quick Reference
This section of the manual lists all Program Menu options in the order they appear on the sub-me nus. Default settings are indicated in text or marked with an asterisk (*). The comments column provide quick information and a reference to a section (if applicable) which has more detailed information.
Table 6-1: Programming Quick Reference Table
Menu Options/Defaults(*) Comments
Edit Module Settings (if applicable)
*1 Count 2 Count Alarm Ver. PAS SNGL ILOCK DBL ILOCK
135° to *150°F 135° to 190°F,
*150°F
250, (and 02 if voice); Pattern 00
*No GroupAux 2 (A2)
*Group 249, Pattern 00
*No Groups
Section 7.2.1
Section 7.2.2
Section 7.3.1.2
SD devices Section
7.3.1.2 SK devices Section
7.3.1.2
Section 7.3.1.3 Section 7.3.1.4
Edit Module Select Module
5815XL-SLC 5860 Keystat. 5824-Ser/Par/IO 5895XL Pwr Sup 5496 NAC Expand 5880-LED/IO Dev
Module
Zone Edit Zone Select Zone to Edit
Add Module
Delete Module
View Module List
5865-LED Annun. EVS-50W EVS-125W EVS-100W EVS-VCM EVS-RVM
List of Module Section 7.2.3
List of Module Section 7.2.4
Enter Module ID
Edit Zone Name Section 7.3.1.1
Zone Properties
Zone Outputs
Enter Module Name
Verification Type
Heat Temp Set
Manual Pull (MP) *Groups 01 & Water Flow (WF)
Detector Alarm (DE) Aux 1 (A1)
Pre-alarm (PR) Fire Supervisory (SU) Trouble (TR)
Status Point (SP)
6-13
Programming Overview LS10061-001SK-E
Table 6-1: Programming Quick Reference Table
Menu Options/Defaults(*) Comments
*Groups 01, 250; Pattern 00
*Group 249; Pattern 00
SD Devices. Section
7.3.1.4, Section 7.3.1.5 SK Devices. Section
7.3.1.4, Section 7.3.1.5
Section 7.3.3
Section 7.3.4
*Non-Latching (NL)
Section 7.4.1.2
Latching (LA) *Silenceable Non-
Silenceable (NON-SIL)
Auto Unsilence (AUT UNSIL)
Silence After Inhibit Delay (SIL-INHIB)
Auto Shutdown (SHUT­DOWN)
Silenceable Section
7.4.1.2 Non-Silenceable Section
7.4.1.2 Auto Un-silenced
Section 7.4.1.2 Silence after inhib delay.
Section 7.4.1.2
Automatic Shutdown Section 7.4.1.2
*NO RP
Section 7.4.1.2RP-TRB
RP-NTR Y or *N Section 7.4.1.2
*Y or N Section 7.4.1.2 Y or *N
Y or *N
Section 7.4.1.2
Section 7.4.1.2
Zone
Group
CO Alarm (CO)
Zone Outputs
CO Supervisory (Sco)
Edit Zone Select Zone to Edit
Zone Accessory Opt
Cadence 00-16, 23; *02 Fire Cadence 00, 01, *02, 23
CO Cadence 0 0, 01, 02, *23 Local Zone Y or *N Section 7.3.1.5
Add Zone Section 7.3.2 Delete Zone View Zone
Points
Select Zone to be Deleted
Select Zone to View
Group Name Section 7.4.1.1
Latching Options
Silencing Options
1
Edit Group Select Group
Group Properties
Polarity
Group Activates for all Man. Pull
Group Activates for Fire Drill
Group Activates for Aux 1
Group Activates for Aux 2
Ignore Global Cadence Y or *N Section 7.4.1.2
6-14
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
Table 6-1: Programming Quick Reference Table
Menu Options/Defaults(*) Comments
Y or *N
Group
Point
Voice EVAC Only
Allow Override
Edit Group Select Group
1
Add Group Section 7.4.2 Delete
Group View Group
Points
Edit OPG Template
Internal and External 5815XL, SK Devices
Select Group to Delete
Select Group Section 7.4.4
Select Template Number
Sensor Point #
Group Properties
Select Group Section 7.4.5 Include in
template Select Pattern 0-21, 23 Section 7.3.1.4, Section 7.4.5 UNUSED
DETECTOR
ECS Only Voice Switch # Override Cadence
Pattern Delay
Y or *N Section 7.4.5
PHOTO, ION, HEAT, ACCLIMATE, HEAT HT , PHOT-HEAT, BEAM
(Default Voice Group 2: *Y)
*Y or N *00 - 40 (Voice
Group: *01) *00-21, 23 05-60 minutes
(*15)
*Latching (LA) or Non­Latching (NL)
*Silenceable (SI) or Non­Silenceable (NS)
Zone # (*001) *NO
ACCESSORY SDR BAS, RL Y BAS
Single/Multi Station: *NST, SST, MST
Station Silenceable: *SIL, NSL
Accessory Group # (*001)
Point Name
Section 7.4.1.2
Section 7.4.3
Section 7.5.1
6-15
Programming Overview LS10061-001SK-E
Table 6-1: Programming Quick Reference Table
Menu Options/Defaults(*) Comments
*Latching (LA) or Non­Latching (NL)
*Silenceable (SI) or Non­Silenceable (NS)
Zone # (*001) *NO
ACCESSORY, DCT RLY
Single/Multi Station: *NST, SST, MST
Station Silenceable: *SIL, NSL
Accessory Group # (*001)
Point Name *Latching (LA)
or Non­Latching (NL)
*Silenceable (SI) or Non­Silenceable (NS)
Zone # (*001) *NO
ACCESSORY, SDR BAS, RL Y BAS, I-SdrBa,
Single/Multi Station: *NST, SST, MST
Station Silenceable: *SIL, NSL
Accessory Group # (*001)
Point Name *Latching (LA)
or Non­Latching (NL)
*Silenceable (SI) or Non­Silenceable (NS)
Zone # (*001) *NO
ACCESSORY, DCT RLY
Section 7.5.1
Point (cont.)
Internal and External 5815XL, SK Devices
DETECTOR PHOT DUCT
Sensor Point #
PHOTO, ION, HEAT, ACCLIMATE, HEAT HT , PHOT-HEAT, BEAM
SUP DET
PHOT DUCT
6-16
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
Table 6-1: Programming Quick Reference Table
Menu Options/Defaults(*) Comments
Single/Multi Station: *NST, SST, MST
Station Silenceable: *SIL, NSL
Accessory Group # (*001)
Point Name *Latching (LA)
or Non­Latching (NL)
*Silenceable (SI) or Non­Silenceable (NS)
Zone # (*001) *NO
ACCESSORY, SDR BAS, RL Y BAS, I-SdrBa
Single/Multi Station: *NST, SST, MST
Station Silenceable: *SIL, NSL
Accessory Group # (*001)
Point Name
*Silenceable (SI) or Non­Silenceable (NS)
Zone # (*001) Point Name *Latching (LA)
or Non­Latching (NL)
*Silenceable (SI) or Non­Silenceable (NS)
Zone # (*001) Point Name *Silenceable
(SI) or Non­Silenceable (NS)
Point Name
Section 7.5.1
Point (cont.)
Internal and External 5815XL, SK Devices
Sensor Point #
Module Point #
SUP DET PHOT DUCT
ALRM Fire/ALRM CO,
CO FIRE
UNUSED
SWITCH
ALRM Fire/SUPR CO, SUPR Fire/ALRM CO, SUPR Fire/SUPR CO
MAN_PULL, PAS_ACK, DET SW, MAN REL, ILOCK, CO DET SW
WATERFLOW, SUPERVSY, ZN_AUX1, ZN_AUX2, TAMPER
FIREDRILL, SILENCE, RESET
6-17
Programming Overview LS10061-001SK-E
Table 6-1: Programming Quick Reference Table
Menu Options/Defaults(*) Comments
*Latching (LA) or Non­Latching (NL)
Point (cont.)
Internal and External 5815XL, SK Device
Internal and External 5815XL, SK Devices
Module Point #
Module Point #
SYS_AUX1, SYS_AUX2
SWITCH
STATUS PT
OUTPUT PT
NOTIF
RELAY
DETECTOR 2WIRE SMK
AUX CONST, AUX RESET, AUX DOOR
OUTPUT PT AUX RESET, AUX
DOOR
*Silenceable (SI) or Non­Silenceable (NS)
Point Name Zone # (*001) Used to activate an
Point Name
Group # (*001) Point Name
Point Name
Group # (*001) Point Name
Point Name *Silenceable
(SI) or Non­Silenceable (NS)
Zone # (*001) Point Name
Section 7.5.1
ancillary output group that does not activate alarm, sound PZT, display status, or report events. Reset has no effect on this point. Section 7.5.1
Section 7.5.1
6-18
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
Table 6-1: Programming Quick Reference Table
Menu Options/Defaults(*) Comments
UNUSED
*Latching (LA) or Non­Latching (NL)
*Silenceable (SI) or Non­Silenceable (NS)
Zone # (*001) *NO
ACCESSORY, SDR BAS, RL Y BAS
Single/Multi Station: *NST, SST, MST
Station Silenceable: *SIL, NSL
Accessory Group # (*001)
Point Name *Latching (LA)
or Non­Latching (NL)
*Silenceable (SI) or Non­Silenceable (NS)
Zone # (*001) *NO
ACCESSORY, DCT RLY
Single/Multi Station: *NST, SST, MST
Station Silenceable: *SIL, NSL
Accessory Group # (*001)
Point Name *Silenceable
(SI) or Non­Silenceable (NS)
Zone # (*001) Point Name
Section 7.5.1
Point (cont.)
Internal and External 5815XL, SD Devices
Point #
PHOTO, ION, HEAT
DETECTOR
PHOT DUCT, ION DUCT
2 WIRE SMK
6-19
Programming Overview LS10061-001SK-E
Table 6-1: Programming Quick Reference Table
Menu Options/Defaults(*) Comments
*Latching (LA) or Non­Latching (NL)
*Silenceable (SI) or Non­Silenceable (NS)
Zone # (*001) *NO
ACCESSORY, SDR BAS, RL Y BAS
Single/Multi Station: *NST, SST, MST
Station Silenceable: *SIL, NSL
Accessory Group # (*001)
Point Name *Latching (LA)
or Non­Latching (NL)
*Silenceable (SI) or Non­Silenceable (NS)
Zone # (*001) *NO
ACCESSORY, DCT RLY
Single/Multi Station: *NST, SST, MST
Station Silenceable: *SIL, NSL
Accessory Group # (*001)
Point Name
Section 7.5.1
Point (cont.)
Internal and External 5815XL, SD Devices
PHOTO, ION, HEAT
Point # SUP DET
PHOT DUCT, ION DUCT
6-20
Model 5820XL / 5820XL-EVS Installation Manual LS10061-001SK-E
Table 6-1: Programming Quick Reference Table
Menu Options/Defaults(*) Comments
*Silenceable (SI) or Non­Silenceable (NS)
Zone # (*001) Point Name *Latching (LA)
or Non­Latching (NL)
*Silenceable (SI) or Non­Silenceable (NS)
Zone # (*001) Point Name *Silenceable
(SI) or Non­Silenceable (NS)
Point Name *Latching (LA)
or Non­Latching (NL)
*Silenceable (SI) or Non­Silenceable (NS)
Point Name Zone # (*001) Used to activate an
Point Name
Group # (*001) Point Name
Point Name
Group # (*001) Point Name
Point Name UNUSED,
NOTIF Group # (*001) Point Name
Section 7.5.1
ancillary output group that does not activate alarm, sound PZT, display status, or report events. Reset has no effect on this point.
Section 7.5.1
Section 7.5.1
Point (cont.)
Internal and External 5815XL, SD Devices
Point #
MAN_PULL, PAS_ACK, DET SW, MAN REL, ILOCK, CO DET SW
WATERFLOW, SUPERVSY, ZN_AUX1, ZN_AUX2, TAMPER
SWITCH
NOTIF
RELAY
SLC LED LED # (01-80)
FIREDRILL, SILENCE, RESET
SYS_AUX1, SYS_AUX2
STATUS PT
OUTPUT PT AUX CONST,
AUX RESET, AUX DOOR
OUTPUT PT AUX RESET, AUX
DOOR
6-21
Loading...