SILENT KNIGHT INTELLIKNIGHT 5700 Installation And Operation Manual

Page 1
INTELLIKNIGHT
MODEL 5700
Addressable Fire Control Panel
Installation and Operations Manual
Document 151295 08/27/09 Rev:
P/N 151295: K ECN 09-570
Page 2
Page 3
Installation Procedure
Installation Precautions - Adherence to the following will aid in problem-free installation with long-term reliability: WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood. CAUTION - System Re-acceptance T est after Software Changes: To ensure proper system operation, this product must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Re-acceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified. This system meets NFP A requirements for operation wi thin the range of 0°C-49°C (32°F-120°F) or humidity within the range of 10%-93% at 30°C (86°F) noncondensing. However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27º C/60-80º F. V erify that wir e sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage. Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered. Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits. Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, or printed circuit board location. Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal. Silent Knight fire alarm control panels contain static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation.
While installing a fire alarm system may make lower insurance rates possible, it is not a
151295
Page 4
substitute for fire insurance! An automatic fire alarm system - typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control with remote notification capability - can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire. Any fire alarm system may fail for a variety of reasons: Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second floor detector, for example, may not sense a first floor or basement fire. Furthermore, all types of smoke detectors, including ionization and photoelectric types, have sensing limitations. No type of smoke detector can sense every kind of fire caused by carelessness and safety hazards like smoking in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children playing with matches, or arson.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire. Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time. Rate-of-Rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment listed for service with your control panel. Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. The most common cause of fire alarm malfunctions, however, is inadequate maintenance. All devices and system wiring should be tested and maintained by professional fire alarm installers following written procedures supplied with each device. System inspection and testing should be scheduled monthly or as required by National and/or local fire codes. Adequate written records of all inspections should be kept.
Page 5
Contents
Section 1
Introduction ..............................................................................................................................................1-1
1.1 Overview of Basic System ....................................................................................................................... 1-1
1.1.1 Hardware Features ............................ ................................................................................................ 1-1
1.1.2 Software Features ............................................................................................................................. 1-2
1.2 About this Manual .................................................................................................................................... 1-2
1.2.1 Terms Used in this Manual ............................................................................................................... 1-2
1.3 Compatible Products ................................................................................................................................ 1-3
1.4 How to Contact Silent Knight .................................................................................................................. 1-5
Section 2
Agency Listings, Approvals, and Requirements ...................................2-1
2.1 Federal Communications Commission (FCC) ......................................................................................... 2-1
2.2 Underwriters Laboratories (UL) ..............................................................................................................2-3
2.2.1 Requirements for All Installations .................................................................................................... 2-3
2.2.2 Requirements for Central Station Fire Alarm Systems .................................................................... 2-4
2.2.3 Requirements for Local Protected Fire Alarm Systems ...................................................................2-4
2.2.4 Requirements for Remote Station Protected Fire Alarm Systems - Digital Alarm Communicator
Transmitter (DACT) ......................................................................................................................... 2-4
Section 3
Before You Begin Installing ...............................................................................................3-1
3.1 What’s in the Box? ................................................................................................................................... 3-1
3.2 Environmental Specifications .................................................................................................................. 3-1
3.3 Electrical Specifications ........................................................................................................................... 3-2
3.4 Wiring Specifications ........................................................ ....................................................................... 3-3
3.5 Board Assembly Diagram ........................................................................................................................ 3-4
3.6 Calculating Current Draw and Standby Battery ......................................................................................3-5
3.6.1 Worksheet Requirements .................................................................................................................. 3-5
3.6.1.1 Current Draw Worksheet for SK SLC Devices ................................................. .................... 3-6
3.6.1.2 Current Draw Worksheet for Hochiki SLC Devices ............................................................. 3-9
3.6.1.3 Maximum Battery Standby Load ......................................................................................... 3-11
151295 i
Page 6
Model 5700 Installation and Operation Manual
Section 4
Control Panel Installation ......................................................................................................4-1
4.1 Mounting the Control Panel Cabinet .......................................................................................................4-1
4.1.1 Preventing Water Damage ................................................................................................................4-1
4.1.2 Removing the 5700 Assembly from the Housing .............................................................................4-1
4.1.3 Dead Front Installation and removal ................................................................................................ 4-1
4.1.3.1 Installing the Dead Front ........................................................................................................ 4-2
4.1.3.2 Dead Front Removal ..............................................................................................................4-2
4.2 AC Connection ......................................................................................................................................... 4-3
4.3 Battery Connection .................................................................................................................................. 4-4
4.3.1 RBB Accessory Cabinet ...................................................................................................................4-5
4.3.1.1 Installing the RBB Accessory Cabinet and Batteries .............................................................4-5
4.4 SBUS Wiring ........................................................................................................................................... 4-7
4.4.1 Calculating Wiring distance for SBUS modules ..............................................................................4-7
4.4.2 Wiring Configurations ............................ ........................................................................................ 4-10
4.4.2.1 How to Power SBUS Devices From Auxiliary Power Supply ............................................4-10
4.5 Remote Annunciator 5860 Installation ..................................................................................................4-11
4.5.1 Mounting the 5860 .......................................................................................................................... 4-12
4.5.1.1 Flush Mounting .................................................................................................................... 4-13
4.5.1.2 Surface Mounting .................................................................................................................4-15
4.5.2 Model 5860 Connection to the Panel ..............................................................................................4-16
4.6 5824 Serial/Parallel Printer Interface Module Installation ....................................................................4-16
4.6.1 Selecting 5824 Options ...................................................................................................................4-18
4.7 5880 LED Driver Module ...................................................................................................................... 4-19
4.7.1 5880 Board Layout ......................................................................................................................... 4-19
4.7.2 FACP Connection ........................................................................................................................... 4-20
4.7.3 LED Wiring ....................................................... ............................................................................. 4-21
4.7.4 Dry Contact Wiring ........................................................................................................................4-22
4.8 5865-3 / 5865-4 LED Annunciator Installation ..................................................................................... 4-23
4.8.1 FACP Connection ........................................................................................................................... 4-23
4.8.2 5865 Mounting ................................................................................................................................ 4-24
4.9 Configuring Modules ............................................................................................................................. 4-25
4.9.1 Assigning Module IDs .................................................................................................................... 4-25
4.10 Telephone Connection ........................................................................................................................... 4-26
4.11 5211 Ground Start Relay ........................................................................................................................ 4-26
4.12 Notification Appliance/Auxiliary Power Circuits .................................................................................. 4-27
4.12.1 Conventional Notification Appliance ............................................................................................. 4-27
4.12.1.1 Class B Notification Wiring .................................................................................................4-27
4.12.1.2 Class A Notification Wiring ................................................................................................ 4-28
4.12.2 Auxiliary Power Installation ...........................................................................................................4-29
4.12.2.1 Door Holder Power ..............................................................................................................4-29
4.12.2.2 Constant Power .................................................................................................................... 4-30
4.12.2.3 Resettable Power .......................... ........................................................................................ 4-30
4.13 On-Board Relays (Conventional) ........................................................................................................... 4-30
4.13.1 Common Trouble Relay ..................................................................................................................4-30
4.13.2 Programmable Relays ..................................................................................................................... 4-30
4.14 Remote Station Applications .................................................................................................................4-31
4.14.1 Keltron Model 3158 Installation ..................................................................................................... 4-31
4.14.2 City Box Connection Using the 5220 Module ................................................................................4-32
4.14.3 NFPA 72 Polarity Reversal .............................................................................................................4-33
4.14.3.1 Using the 5220 Module ........................................................................................................4-33
4.14.3.2 Using the 7644 Module ........................................................................................................4-35
4.14.4 Using the SD500-ARM Addressable Relay Module ...................................................................... 4-36
4.14.5 Using a MR-201/T Control Relay From Air Products ................................................................... 4-37
ii 151295
Page 7
Contents
4.14.6 Transmitter Activated by Dry Contacts .......................................................................................... 4-38
Section 5
SK and Hochiki SLC Device Installation ...........................................................5-1
5.1 List of SK SLC Devices ...........................................................................................................................5-1
5.2 List of Hochiki SLC Devices ................................................................................................................... 5-2
5.3 Maximum Number of Devices ................................................................................................................. 5-3
5.4 Wiring Requirements for SLC Devices ..................................... .............................................................. 5-3
5.4.1 Wiring SLC in Style 4 (Class B) Configuration ........................................................... .................... 5-3
5.4.2 Wiring SLC Devices in Style 6 & 7 (Class A)
Configuration ....................................................................................................................................5-6
5.5 Wiring SK SLC Detectors ........................................................................................................................ 5-7
5.6 Addressing SK SLC Devices ...................................................................................................................5-8
5.7 Wiring Hochiki Detectors ............................................................................................... ......................... 5-9
5.8 Addressing Hochiki Devices ............................................................ ......................................................5-10
5.8.1 SD505-APS, SD505-AHS, & SD505-AIS ..................................................................................... 5-10
5.8.2 Hochiki SLC Devices with Dip Switches .......................................................................................5-12
Section 6
Programming Overview ...........................................................................................................6-1
6.1 JumpStart Autoprogramming ................................................................................................................... 6-1
6.1.1 Input Points ....................................................................................................................................... 6-2
6.1.2 Output Points ..................................................... ............................................................................... 6-2
6.1.3 Running JumpStart ........................................................................................................................... 6-2
6.2 Mapping Overview .................................................................................................................................. 6-4
6.2.1 Input Point Mapping .........................................................................................................................6-5
6.2.2 Output Circuit Mapping ............................................................................................. ....................... 6-6
6.2.3 Zone Event Mapping ........................................................................................................................ 6-7
6.2.4 Mapping LED Points ........................................................................................................................ 6-9
6.3 Programming Using the 5660 Silent Knight Software Suite ................................................................. 6-10
6.4 Programming Using an Annunciator ....................................................... ... ...........................................6-10
6.4.1 Entering / Exiting the Program Menu ................................. ............................................................ 6-11
6.4.2 Moving through the Menus ............................................................................................................. 6-11
6.4.3 Selecting Options and Entering Data ..............................................................................................6-12
6.4.4 Editing Keys ................................................................................................................................... 6-12
6.5 Programming Menu Quick Reference ...................................................................................................6-13
Section 7
Programming ......................................................................................................................................... 7-1
7.1 UL 864 Programming Requirements .......................................................................................................7-1
7.2 SLC Family ..............................................................................................................................................7-2
7.3 Modules ....................................................................................................................................................7-2
7.3.1 Edit Modules .....................................................................................................................................7-2
7.3.1.1 Naming Modules .............................................................. ......................................................7-3
7.3.1.2 Module, Wiring Class ............................................................................................................ 7-3
7.3.2 Adding a Module ............................................ .................................................................................. 7-3
7.3.3 Deleting a Module .................................... ........................................................................................ 7-4
151295 iii
Page 8
Model 5700 Installation and Operation Manual
7.4 Zone .........................................................................................................................................................7-5
7.4.1 Edit Zone ........................................... .............................................................. .................................. 7-5
7.4.1.1 Edit Zone Name .................................................................................................... ................. 7-5
7.4.1.2 Edit Zone Properties ...............................................................................................................7-6
7.4.1.3 Zone Outputs ..........................................................................................................................7-8
7.4.1.4 Cadence Patterns .................................................................................................................. 7-11
7.4.2 Add Zone ..................................................... ................................................................................... 7-12
7.4.3 Delete Zone ......................... ... .............................................................. ...........................................7-12
7.4.4 View Zone Points ....................................................................................................... ..................... 7-13
7.5 Group ..................................................................................................................................................... 7-14
7.5.1 Edit Group ............................................ .............................................................. ............................. 7-14
7.5.1.1 Edit Group Name ................................................................................................................. 7-14
7.5.1.2 Edit Group Properties ......................................... .................................................................. 7-15
7.5.2 Add Group ...................................................... ................................................................................ 7-17
7.5.3 Delete Group ...................................................................................................................................7-18
7.5.4 View Group Points .......................................................................................................................... 7-18
7.5.5 Edit Output Group Templates .........................................................................................................7-19
7.6 Point ....................................................................................................................................................... 7-20
7.6.1 Point Programming For SLC ..................................................................................... ..................... 7-20
7.6.2 Point Programming For Internal
or External Power Module (5496) ..................................................................................................7-23
7.6.3 Point Programming For 5880 and 5865 Modules ........................................................................... 7-24
7.6.3.1 Assigning a Name to a Points .......................................... ....................................................7-25
7.7 System Options ......................................................................................................................................7-26
7.7.1 Reporting Account .......................................................................................................................... 7-26
7.7.1.1 Edit Accounts ....................................................................................................................... 7-27
7.7.1.2 Auto Test Time .................................................................................................................... 7-29
7.7.2 Phone Lines .....................................................................................................................................7-29
7.7.2.1 Dialing Prefix ....................................................................................................................... 7-30
7.7.2.2 Number of Answer Rings ....................................................................................................7-30
7.7.2.3 Dial Option (TouchTone or Pulse) .......................................................................................7-31
7.7.2.4 Rotary Format ...................................................................................................................... 7-31
7.7.2.5 Line Monitor ........................................................................................................................ 7-31
7.7.2.6 Ground Start Relay ...............................................................................................................7-31
7.7.2.7 Answering Machine Bypass ........................................... ......................................................7-32
7.7.3 Sys. Event Outputs .......................................................................................................................... 7-32
7.7.3.1 Trouble Events .....................................................................................................................7-33
7.7.3.2 System Alarm Cadence ........................................................................................................ 7-34
7.7.4 Miscellaneous Options 1 ................................................................................................................. 7-35
7.7.4.1 Water Flow Delay ................................................................................................................ 7-35
7.7.4.2 Low AC Report Delay ......................................................................................................... 7-36
7.7.4.3 Automatic Daylight Savings Adjustment ............................................................................ 7-36
7.7.4.4 Clock Display Format (AM/PM or Military) .......................................................................7-36
7.7.4.5 Change AC Line Frequency ................................................... ..............................................7-36
7.7.5 Miscellaneous Options 2 ................................................................................................................. 7-37
7.7.5.1 Synchronize Strobes Active During Silence ........................................................................ 7-37
7.7.5.2 Auto Display Oldest Event .................................................................................................. 7-37
7.7.5.3 Report by Zone or by Point ..................................................................................................7-37
7.7.6 Miscellaneous Options 3 ................................................................................................................. 7-38
7.7.6.1 Alarm Verification Time ......................................................................................................7-38
7.7.6.2 Daylight Saving Time Start and End ................................................................................... 7-38
7.7.7 Edit Banner Message ...................................................................................................................... 7-39
7.8 JumpStart Autoprogramming ................................................................................................................. 7-40
7.9 Computer Account ................................................................................................................................. 7-41
iv 151295
Page 9
Contents
7.10 Access Codes ......................................................................................................................................... 7-42
7.10.1 Profile Edit Menu ............................................................................................................................ 7-43
7.10.1.1 Edit Name ............................................................................................ ................................ 7-43
7.10.1.2 Edit Access Code ................................................................................................................. 7-43
7.10.1.3 Panel Functions .................................................................................................................... 7-43
Section 8
System Operation ............................................................................................................................8-1
8.1 Annunciator Description .......................................................................................................................... 8-1
8.1.1 LCD Displays ...................................................................................................................................8-1
8.1.2 Banner ...............................................................................................................................................8-2
8.2 Menu System ............................................................................................................................................8-2
8.2.1 Main Menu Overview ....................................................................................................................... 8-3
8.2.2 Using the Menus ............................... ................................................................................................ 8-3
8.3 Basic Operation ........................................................................................................................................8-4
8.3.1 Setting Time and Date ...................................................................................................................... 8-4
8.3.2 Disable / Enable NACs by Group .....................................................................................................8-4
8.3.3 Disable / Enable a Template ................................. ............................................................................ 8-4
8.3.4 Disable / Enable a Zone .................................................................................................................... 8-4
8.3.5 Disable / Enable a Point .................................................................................................................... 8-4
8.3.6 View Event History ..................................... ..................................................................................... 8-5
8.3.6.1 To clear the event history ....................................................................................................... 8-5
8.3.7 Conduct a Fire Drill .......................................................................................................................... 8-5
8.3.8 Conduct an Indicator Test .................................................................................................................8-6
8.3.9 Conduct a Walk Test ......................................................................................................................... 8-6
8.3.10 Conduct a Dialer Test .......................................................................................................................8-7
8.3.11 Silence alarms or troubles ................................................................................................................. 8-7
8.3.12 Reset alarms ...................................................................................................................................... 8-7
8.3.13 Check Detector Through Point Status ..............................................................................................8-7
8.3.14 View Status of a Point ..................................................... ................................................................. 8-8
8.3.15 View Alarms or Troubles ................................................................................................................. 8-8
8.3.16 View System Information .................................................................................................................8-8
8.3.17 Reset dialer ....................................................................................................................................... 8-8
8.3.18 Communicating with a Remote Computer ....................................................................................... 8-9
8.3.19 Working with a Printer ................................................................................................................... 8-10
8.4 Operation Mode Behavior ...................................................................................................................... 8-11
8.5 Releasing Operations ............................................................................................................................. 8-14
8.5.1 Single Interlock Zone Releasing ........................ ............................................................................. 8-15
8.5.2 Double Interlock Zone Releasing ................................................................................................... 8-16
8.6 Smoke Alarm Verification ..................................................................................................................... 8-18
Section 9
Reporting ..................................................................................................................................................... 9-1
9.1 Receivers Compatible with the Control Panel .........................................................................................9-1
9.2 Reporting Formats Dialer Outputs ......................................................................................................... 9-1
151295 v
Page 10
Model 5700 Installation and Operation Manual
Section 10
Testing and Troubleshooting ......................................................................................... 10-1
10.1 Troubleshooting ..................................................................................................................................... 10-1
10.2 Common Problems ................................................................................................................................. 10-1
10.2.1 Periodic Testing And Maintenance .................................................................................................10-2
10.2.2 Event History .................................................................................................................................. 10-3
10.3 Built-in Troubleshooting and Testing Tools ..........................................................................................10-3
10.3.1 SLC Device Locator .......................................................................................................................10-3
10.3.2 SLC Multi Locator .......................................................................................................................... 10-4
10.3.3 I/O Point Control ............................................................................................................................ 10-5
10.4 Earth Ground Fault Resistance ..............................................................................................................10-5
Section 11
Installation Records ....................................................................................................................11-1
11.1 Detector and Module Point Record ........................................................................................................11-1
Appendix A
Compatible Devices .....................................................................................................................A-1
Appendix B
Special Characters Lists .........................................................................................................B-1
Silent Knight Fire Product Warranty and Return Policy Model 5700 Basic Operating Instructions
vi 151295
Page 11
Section 1 Introduction
The 5700 Fire Alarm Control / Communicator is an addressable fire control system that meets the requirements of UL 864.
1.1 Overview of Basic System
1.1.1 Hardware Features
The 5700 has one signaling line circuit (SLC) that supports 50 SK detectors and 50 SK modules or 50 Hochiki protocol devices.
2.5A of output power is available through 2 sets of terminals for notification appliance circuits or auxiliary applications. Each circuit is power limited per UL 864 and can source up to 2.5A (total output power for both circuits must not exceed 2.5A).
Built-in dual phone line, digital alarm communicator/transmitter (DACT).
Reports events to central station by point or by zone.
UL Listed for pre-action and deluge releasing systems.
Two general purpose Form C programmable relays.
One Form C Trouble Relay.
Basic system operation can be performed from the on-board, or any remote annunciator.
Up to 20 user profiles can be programmed, each having custom access code, and main menu items.
Can be used with up to 8 Model 5860 Remote Annunciators (sold separately).
Can be used with Model 5865-3, 5865-4, and 5880 in any combination for a total of eight devices on one control panel. See Sections 4.7 and 4.8 for additional information on these models.
Printing of detector status, event history, and real time event log available through the Model 5824 Serial / Parallel Interface (sold separately).
125 software zones, 125 output groups.
Add 6 Flexput™ circuits with each 5895XL Intelligent Power Module (up to eight 5895XLs per system). See note below.
Add 4 Notification/Auxiliary power circuits with each 5496 Intelligent Power Module (up to eight 5496s per system). See note below.
Note: The system can support a maximum of eight intelligent power modules, either the 5895XL or 5496, in any
combination.
151295 1-1
Page 12
Model 5700 Installation and Operation Manual
1.1.2 Software Features
Advanced smoke detector features: –Automatic drift compensation –Maintenance alert region –Point status eliminates calibrated smoke test requirements for NFPA 72
“JumpStart” feature for easy programming
Non-volatile event history stores 1000 events
A choice of output patterns available for notification outputs, including ANSI 3.41 temporal signal
Built-in synchronization appliance support for Faraday, Gentex®, Wheelock®, or System Sensor ®.
1.2 About this Manual
This manual is intended to be a complete reference for all installation and operation tasks for the 5700. Please let us know if the manual does not meet your needs in any way. We value your feedback!
1.2.1 Terms Used in this Manual
The following terminology is used with the 5700 system:
Term Description
SLC Signaling Line Circuit Module The term module is used for all hardware devices except for
SLC addressable devices and notification appliances. This includes the 5700 panel itself.
Input Point An addressable sensing device, such as a smoke or heat detector
or a contact monitor device. Input Zone A protected area made up of input points. Output Point
(or Output Circuit)
Group (or “Output Group”) A group of output points. Operating characteristics are common
Output (or “Cadence”) Pattern The pattern that the output will use, for example, Constant,
Mapping Mapping is the process of specifying which outputs are
A notification point or circuit for notification appliances. Relay
circuits and auxiliary power circuits are also considered output
points.
to all output points in the group.
March Code, ANSI 3.41. Applies to zones and special system
events. See Section 7.7.3.2 for additional information.
activated when certain events occur in the system. Section 6. 2
explains mapping in detail.
1-2 151295
Page 13
Introduction
1.3 Compatible Products
The chart below lists the products available from Silent Knight for use with the 5700.
Type of
Device
SK Addressable SLC Devices
Hochiki Addressable SLC Devices
Other Modules
Software
Misc.
Model Description
See Section 5.1 for a list of compatible devices.
See Section 5.2 for a list of compatible devices.
5824 Serial/Parallel Printer Interface Module
5895XL Provides additional power, six Flexput circuits, and two Form C relays. Max 8 per
5496 Intelligent Power Module
5860 and 5860R Remote Fire Alarm Annunciator
5860TG and 5860TR Trim Ring Kit
5865-3 and 5865-4 LED Annunciator
5880 LED Driver Module Driver for up to 40 LEDs. Interfaces with customized annunciator boards. In addition
5883 General Purpose Relay Module
7860 Telephone Cord RJ31X cord for connecting phone line to the 5700. 5660
Silent Knight Software Suite (SKSS)
5670 SKSS Facility Management Software
7628 UL Listed End-of-line resistor DF-50 Dead Front insert
Allows a printer to be attached for the system for on-site event logging, detector status and event history reports. Two maximum per system.
system. See 5895XL Installation Manual (PN 151142) for more information. Provides 4 additional Notification Appliance Circuits/Auxiliary power. (Up to 8 per
5700 system.) Same operation, similar appearance as the on-board annunciator. Up to 8 5860s per
system. 5860 is gray; 5860R is red. Trim ring kits for surface mounting the 5860/5860R annunciator.
5860TG is gray; 5860TR is red. LED annunciator can display up to 30 LEDs (15 red and 15 yellow). 5865-4 has key
switches for silence and reset, and a system trouble LED.
the 5880 has eight generic switch input points. Provides 10 Form C relays. Designed to be driven by the 5880. Up to four, 5883s can
be used with each 5880 module.
For communication and panel programming with a W i ndows-based computer and modem (not sold by Silent Knight, see Table 1-1 for compatible modems). Enables remote viewing of detector status and event history.
For remote viewing of detector status and event history. Requires a modem (not sold by Silent Knight).
Note: 5865-3, 5865-4, and 5880 can be used in any combination, up to a total of eight devices on one panel.
151295 1-3
Page 14
Model 5700 Installation and Operation Manual
The following modems have been tested by Silent Knight for compatibility with the 5700 and the Silent Knight Software Suite software packages:
Table 1-1: Compatible Modems
Manufacturer Model
US Robotics 28.8 Motorola LifeStyle
28.8, 3400 series Premier 33.6
Multi-Tech MT19321ZDX
1-4 151295
Page 15
Introduction
1.4 How to Contact Silent Knight
If you have a question or encounter a problem not covered in this manual, contact Silent Knight Technical Support at 800-446-6444.
To order parts, contact Silent Knight Sales at 800-328-0103 or 203-484-7161 in Connecticut.
151295 1-5
Page 16
Model 5700 Installation and Operation Manual
Limitations of Fire Alarm Systems
Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer’s recommendations, State and local codes, and the recommendations contained in Guide for the Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off or give early warning in as many as 35% of all fires. While fire alarm systems are designed to provide warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons. For example:
Particles of combustion or smoke from a developing fire may not reach the sensing chambers of smoke detectors because:
Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
Smoke particles may become cold, stratify, and not reach the ceiling or upper walls where detectors are located.
Smoke particles may be blown away from detectors by air outlets Smoke particles may be drawn into air returns before reaching the detector.
In general, smoke detectors on one level of a structure cannot be expected to sense fires developing on another level.
The amount of smoke present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photo electronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors are subject to false alarms and nuisance alarms and may have been disconnected by users. For example, a smoke detector located in or near a kitchen may go into nuisance alarm during normal operation of kitchen appliances. In addition, dusty or steamy environments may cause a smoke detector to falsely alarm. If the location of a smoke detector causes an abundance of false alarms or nuisance alarms, do not disconnect the smoke detector; call a professional to analyze the situation and recommend a solution.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially within bedrooms), smoking in bed, violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and are designed to alarm only when
1-6 151295
Page 17
Introduction
heat on their sensors increases at a predetermined rate or reaches a predetermined level. Heat detectors are designed to protect property, not life.
Warning devices (including horns, sirens, and bells) may not alert people or wake up sleepers who are located on the other side of closed or partially open doors. A warning device that activates on a different floor or level of a dwelling or structure is less likely to awaken or alert people. Even persons who are awake may not notice the warning if the alarm is muffled by noise from a stereo, radio, air conditioner or other appliance, or by passing traffic. Audible warning devices may not alert the hearing-impaired (strobes or other devices should be provided to warn these people). Any warning device may fail to alert people with a disability, deep sleepers, people who have recently used alcohol or drugs, or people on medication or sleeping pills.
Please note that: i) Strobes can, under certain circumstances, cause seizures in people with conditions
such as epilepsy.
ii) Studies have shown that certain people, even when they hear a fire alarm signal, do not
respond or comprehend the meaning of the signal. It is the property owner’s responsi­bility to conduct fire drills and other training exercises to make people aware of fire alarm signals and instruct on the proper reaction to alarm signals.
iii) In rare instances, the sounding of a warning device can cause temporary or permanent
hearing loss.
Telephone lines needed to transmit alarm signals from a premises to a central station may be out of service or temporarily out of service. For added protection against telephone line failure, backup radio transmission systems are recommended.
System components, though designed to last many years, can fail at any time. As a precautionary measure, it is recommended that smoke detectors be checked, maintained, and replaced per manufacturer’s recommendations.
System components will not work without electrical power. If system batteries are not serviced or replaced regularly , they may not provide battery backup when AC power fails.
Environments with high air velocity or that are dusty or dirty require more frequent maintenance.
In general, fire alarm systems and devices will not work without power and will not function properly unless they are maintained and tested regularly.
While installing a fire alarm system may make the owner eligible for a lower insurance rate, an alarm system is not a substitute for insurance.
Property owners should continue to act prudently in protecting the premises and the people in their premises and should properly insure life and property and buy sufficient amounts of liability insurance to meet their needs.
151295 1-7
Page 18
Model 5700 Installation and Operation Manual
Requirements and recommendations for proper use of fire alarm systems in­cluding smoke detectors and other fire alarm devices:
Early fire detection is best achieved by the installation and maintenance of fire detection equipment in all rooms and areas of the house or building in accordance with the requirements and recommendations of the current edition of the National Fire Protection Association Standard 72, National Fire Alarm Code (NFPA 72), the manufacturer’s recommendations, State and local codes and the recommendations contained in Guide for the Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. For specific requirements, check with the local Authority Having Jurisdiction (ex. Fire Chief) for fire protection systems.
Requirements and Recommendations include:
Smoke Detectors shall be installed in sleeping rooms in new construction and it is
recommended that they shall also be installed in sleeping rooms in existing construction.
It is recommended that more than one smoke detector shall be installed in a hallway if it is
more than 30 feet long.
It is recommended that there shall never be less then two smoke detectors per apartment or
residence.
It is recommended that smoke detectors be located in any room where an alarm control is
located, or in any room where alarm control connections to an AC source or phone lines are made. If detectors are not so located, a fire within the room could prevent the control from reporting a fire.
All fire alarm systems require notification devices, including sirens, bells, horns, and/or
strobes. In residential applications, each automatic alarm initiating device when activated shall cause the operation of an alarm notification device that shall be clearly audible in all bedrooms over ambient or background noise levels (at least 15dB above noise) with all intervening doors closed.
It is recommended that a smoke detector with an integral sounder (smoke alarm) be
located in every bedroom and an additional notification device be located on each level of a residence.
To keep your fire alarm system in excellent working order, ongoing maintenance is
required per the manufacturer’s recommendations and UL and NFPA standards. At a minimum the requirements of Chapter 10 of NFPA 72 shall be followed. A maintenance agreement should be arranged through the local manufacturer’s representative. Maintenance should be performed annually by authorized personnel only.
The most common cause of an alarm system not functioning when a fire occurs is
inadequate maintenance. As such, the alarm system should be tested weekly to make sure all sensors and transmitters are working properly.
1-8 151295
Page 19
Section 2 Agency Listings, Approvals, and Requirements
Install and maintain in accordance with NFPA 72. Detector spacing shall be in accordance to NFPA 72. End-of -line relays and resistors shall be placed within the electrical box located and the end of the initiating circuit. Testing and maintenance should be performed according to NFPA 72.
2.1 Federal Communications Commission (FCC)
The following information must be provided to the telephone company before the 5700 can be connected to the phone lines:
A Manufacturer: Silent Knight B Model Number: 5700 C FCC registration number: US: AC6AL05B205700
Ringer equivalence: 0.5B D Type of jack: RJ31X E Facility Interface Codes: Loop Start: 02LS2
Ground Start: 02GS2
F Service Order Code: 9.0F
4. This device may not be directly connected to coin telephone or party line services.
5. This device cannot be adjusted or repaired in the field. In case of trouble with the device, notify the installing company or return to:
Silent Knight 12 Clintonville Road Northford, CT 06472-1610 (203) 484-7161
6. If the 5700 causes harm to the telephone network, the telephone company will notify the user in advance that temporary discontinuance of service may be required. If advance notice is not practical, the telephone company will notify the user as soon as possible. Users have the right to file complaints, if necessary, with the Federal Communications Commission.
151295 2-1
Page 20
Model 5700 Installation and Operation Manual
7. The telephone company may make changes in its facilities, equipment, operations, or pro­cedures that could affect the operation of the equipment. If this happens, the telephone company will provide advance notice to allow you to make the necessary modifications to maintain uninterrupted service.
Warning
This device has been verified to comply with FCC Rules Part 15. Operation is subject to the following conditions: (1) This device may not cause radio interference, and (2) This device must accept any interference received, including interference that may cause undesired operation.
a) This equipment complies with Part 68 of the FCC rules and the requirements adopted by
the ACTA. On the wiring diagram of this equipment is a label that contains, among other information, a product identifier in the format US: AC6AL05B-205700. If requested, this number must be provided to the telephone company.
b) See Section 4.10 for phone jack information. c) A plug and jack used to connect this equipment to the premises wiring and telephone
network must comply with the applicable FCC Part 68 rules and requirements adopted by the ACTA. A compliant telephone cord and modular plug is provided with this product. It is designed to be connected to a compatible modular jack that is also compliant. See installation instructions for details.
d) The REN is used to determine the number of devices that may be connected to a telephone
line. Excessive RENs on a telephone line may result in the devices not ringing in response to an incoming call. In most but not all areas, the sum of RENs should not exceed five (5.0). To be certain of the number of devices that may be connected to a line, as determined by the total RENs, contact the local telephone company. For products approved after July 23, 2002, the REN for this product is part of the product identifier that has the format US: AC6AL05B-205700. The digits represented by ## are the REN without a decimal point (e.g., 03 is a REN of 0.3). For earlier products, the REN is separately shown on the label.
e) If this equipment 5700 causes harm to the telephone network, the telephone company will
notify you in advance that temporary discontinuance of service may be required. But if advance notice isn't practical, the telephone company will notify the customer as soon as possible. Also, you will be advised of your right to file a complaint with the FCC if you believe it is necessary.
f) The telephone company may make changes in its facilities, equipment, operations or
procedures that could affect the operation of the equipment. If this happens the telephone company will provide advance notice in order for you to make necessary modifications to maintain uninterrupted service.
g) If trouble is experienced with this equipment 5700, for repair or warranty information,
please contact Silent Knight (see Section 1.4). If the equipment is causing harm to the telephone network, the telephone company may request that you disconnect the equipment until the problem is resolved.
h) See warranty in back of this manual for repair and replacement information. i) Connection to party line service is subject to state tariffs. Contact the state public utility
commission, public service commission or corporation commission for information.
2-2 151295
Page 21
Agency Listings, Approvals, and Requirements
j) If your home has specially wired alarm equipment connected to the telephone line, ensure
the installation of this 5700 does not disable your alarm equipment. If you have questions about what will disable alarm equipment, consult your telephone company or qualified installer.
Electrical Safety Advisory:
Parties responsible for equipment requiring AC power should consider including an advisory notice in their customer information suggesting the customer use a surge arrestor. Telephone companies report that electrical surges, typically lightning transients, are very destructive to customer terminal equipment connected to AC power sources. This has been identified as a major nationwide problem.
2.2 Underwriters Laboratories (UL)
2.2.1 Requirements for All Installations
General requirements are described in this section. When installing an individual device, refer to the specific section of the manual for additional requirements. The following subsections list specific requirements for each type of installation (for example, Central Station Fire Alarm systems, Local Protected Fire Alarm systems, and so on). See Section 8.5 for information on releasing operation.
1. All field wiring must be installed in accordance with NFPA 70 National Electric Code.
2. Use the addressable smoke detectors specified in Section 5.2 of this manual.
3. Use UL listed notification appliances compatible with the 5700 from those specified in the Appendix at the back of this manual.
4. A full system checkout must be performed any time the panel is programmed.
Restricted Options:
The loss of AC signal is defaulted to 3 hours however the system allows settings from 0 ­30 hours. For UL certified installations this number must be set from 1 to 3 hours.
The system allows the use of non-latching spot type smoke detectors. This feature may not be used in commercial applications whereby a general alarm is sounded. It is intended for elevator recall, door holding applications, and hotel/motel room applications.
The system allows the Alarm Verification time to be set from 1 to 255 seconds. For UL certified installations the setting must be a maximum of 60 seconds.
Call forwarding shall not be used.
When two count is used detector spacing shall be cut in half, you shall not use the alarm verification feature, and no delay shall be used.
P.A.S feature shall be used only with automatic detectors.
151295 2-3
Page 22
Model 5700 Installation and Operation Manual
2.2.2 Requirements for Central Station Fire Alarm
Systems
1. Use both phone lines. Enable phone line monitors for both lines.
2. You must program a phone number and a test time so that the 5700 sends an automatic daily test to the central station.
3. Do not use the ground start option.
4. The AC Loss Hours option must be set from 6-12 hours.
5. The Attempts to Report option must be set for 5.
2.2.3 Requirements for Local Protected Fire Alarm
Systems
At least one UL listed supervised notification appliance must be used.
2.2.4 Requirements for Remote Station Protected Fire
Alarm Systems - Digital Alarm Communicator Transmitter (DACT)
1. Do not exceed the current load restrictions shown in Section 3.6.
2. The AC Loss Hours option must be set from 1-3 hours.
2-4 151295
Page 23
Section 3 Before You Begin Installing
This section of the manual is intended to help you plan your tasks to facilitate a smooth installation. Please read this section thoroughly, especially if you are installing a 5700 panel for the first time.
3.1 What’s in the Box?
The 5700 ships with the following hardware:
A cabinet with all hardware assembled
Two keys for the front door
Installation and Operation manual P/N 151295.
Ten 4.7K ohm end-of-line resistors
A battery cable for batteries wired in series
3.2 Environmental Specifications
It is important to protect the 5700 control panel from water. To prevent water damage, the following conditions should be AVOIDED when installing the units:
Intended for indoor use in dry locations only
Do not mount directly on exterior walls, especially masonry walls (condensation)
Do not mount directly on exterior walls below grade (condensation)
Protect from plumbing leaks
Protect from splash caused by sprinkler system inspection ports
Do not mount in areas with humidity-generating equipment (such as dryers, production machinery)
When selecting a location to mount the 5700 control panel, the unit should be mounted where it will NOT be exposed to temperatures outside the range of 0°C-49°C (32°F-120°F) or humidity outside the range of 10%-93% at 30°C (86°F) noncondensing.
151295 3-1
Page 24
Model 5700 Installation and Operation Manual
3.3 Electrical Specifications
Table 3-1 list the terminal block on the 5700 as well as a description of the each individual terminal and their respective electrical rating. For location of the terminals refer to Figure 3-2. See also Section 4 for installation.
Table 3-1: Terminal Descriptions
Terminal No.
Terminal Block 1
Terminal Block 2
Label
Group Individual Voltage Current
NO Normally open relay contact
RELAY 1
NC Normally closed relay contact NO Normally open relay contact
RELAY 2
NC Normally closed relay contact
TELCO 1
PHONE 1
TELCO 2
PHONE 2
TROUBLE
SLC IN
SLC OUT
SLC PROG
SBUS
NAC1*
NAC2*
RING Phone Line 1 Telco Ring
TIP Phone Line 1 Telco Tip
RING Phone Line 1 Phone Ring
TIP Phone Line 1 Phone Tip
RING Phone Line 2 Telco Ring
TIP Phone Line 2 Telco Tip
RING Phone Line 2 Phone Ring
TIP Phone Line 2 Phone Tip NO Normally open relay contact
NC Normally closed relay contact
– + – + – + –
+ A B
+
+
Description
27.4 VDC 2.5 A, resistiveCOM Common terminal
27.4 VDC 2.5 A, resistiveCOM Common terminal
27.4 VDC 2.5 A, resistiveCOM Common terminal
Used for Class A installations 32 VDC 100 mA
SLC terminals 32 VDC 100 mA
Used for programming SLC Detectors
SBUS Power 27.4 VDC 0.5 A
SBUS Communication 5 VDC 100 mA
Notification Appliance Circuit/Auxiliary power
Notification Appliance Circuit/Auxiliary power
32 VDC 100 mA
27.4 VDC
27.4 VDC
Rating
2.5 Amp NAC or Aux power
2.5 Amp NAC or Aux power
* Regulated NAC application. When programmed for releasing, NAC are Special Application.
3-2 151295
Page 25
Before You Begin Installing
Relay
NAC/Aux Power Outputs
SBUS
Phone
SLC IN/OUT
AC Power Input
Devices
Lines
Outputs
1/4” spacing must be maintained between each of these circuit types; as well as between power limited and non-power limited circuits.
Battery
3.4 Wiring Specifications
Induced noise (transfer of electrical energy from one wire to another) can interfere with telephone communication or cause false alarms. To avoid induced noise, follow these guidelines:
Isolate input wiring from high current output and power wiring. Do not pull one multi­conductor cable for the entire panel. Instead, separate the wiring as follows:
High voltage AC power Terminals SLC loops Audio input/output Phone line circuits Notification circuits NAC1 through NAC2 SBUS Relay circuits
Do not pull wires from different groups through the same conduit. If you must run them together, do so for as short a distance as possible or use shielded cable. Connect the shield to earth ground at the panel. You must route high and low voltages separately.
Route the wiring around the inside perimeter of the cabinet. It should not cross the circuit board where it could induce noise into the sensitive microelectronics or pick up unwanted RF noise from the high speed circuits. See Figure 3-1 for an example.
High frequency noise, such as that produced by the inductive reactance of a speaker or bell, can also be reduced by running the wire through ferrite shield beads or by wrapping it around a ferrite toroid.
151295 3-3
Figure 3-1 Wire Routing Example
Page 26
Model 5700 Installation and Operation Manual
On-board Annunciator
NAC/Aux
Power Circuits
Form C Relays
Phone Lines
SLC In/Out,
SLC Programming
AC Power Input
SBUS
Connections
Battery Connector
Programming Port
Form C
Trouble Relay
Terminal Block 1
Terminal Block 2
120 VAC,
60 Hz, 1.5A
24 VDC
3.5 Board Assembly Diagram
Figure 3-2 Model 5700 Assembly
Figure 3-2 shows the circuit boards, and annunciator. If you should need to remove the control board for repair, remove the three mounting screws which hold the control board in the cabinet. Then lift the control board out of the cabinet.
3-4 151295
Page 27
Before You Begin Installing
3.6 Calculating Current Draw and Standby Battery
This section is for helping you determine the current draw and standby battery needs if you are using SK addressable devices (Table 3-2) or Hochiki addressable devices (Table 3-3).
3.6.1 Worksheet Requirements
The following steps must be taken when determining 5700 current draw and standby battery requirements.
1. For the 5700, the worst case current draw is listed for the panel, addressable devices, and all SBUS expanders. Fill in the number of addressable devices that will be used in the sys­tem and compute the current draw requirements for alarm and standby. Record this infor­mation in the Current Calculation Worksheet at Line A.
2. Add up the current draw for all auxiliary devices and record in the table at Line B.
3. Add up all notification appliance loads and record in the table at Line C.
4. For notification appliance circuits and auxiliary devices not mentioned in the manual, refer to the device manual for the current ratings.
5. Make sure that the total alarm current you calculated, including current for the panel itself, does not exceed 2.5 A. This is the maximum alarm current for the 5700 control panel.
If the current is above 2.5 A you will need to use a notification power expander(s) such as the Silent Knight 5496 intelligent power module, to distribute the power loads so that the 5700 or the power expanders do not exceed their power rating. Refer to the current draw worksheets provided with the 5496 manual so you do not exceed their power require­ments.
6. Complete the remaining instructions in the Current Calculation Worksheet for determining battery size requirements.
151295 3-5
Page 28
Model 5700 Installation and Operation Manual
3.6.1.1 Current Draw Worksheet for SK SLC Devices
Use T able 3-2 to determine current requirements during alarm/battery standby operation when SK SLC devices are installed. (Copy the page if additional space is required.) You can install up to 50 SK detectors and 50 SK modules.
Table 3-2: Current Calculation Worksheet for SK Devices
Device # of Devices Current per Device
For each device use this formula: This column X This column = Current per number of devices. Fire Panel (Current draw from battery) 1 Addressable SLC Detectors
SK-Photo SK-Photo-T mA mA SK-Ion mA mA SK-Heat mA mA SK-Heat-HT mA mA
SK-Beam (without integral test)
(50 max.)
SK-Beam-T
SK-DUCT SK-Acclimate
SK-Heat-ROR mA mA
5
(with integral test)
6
Standby: 200 mA 200 mA Alarm: 325 mA 325 mA
Standby/Alarm: 0.27 mA
SLC
Aux. Pwr
1
SLC
Aux. Pwr
SLC
Standby/Alarm: 0.3 mA
Standby/ Alarm: 2 mA
Standby: 2 mA mA Alarm: 8.5 mA mA Standby/
Alarm: 2 mA Standby: 2 mA mA Alarm: 8.5 mA mA Standby/
Alarm: 0.27 mA
Standby
Current
mA mA
mA mA mA mA
Alarm
Current
3-6 151295
Page 29
Before You Begin Installing
Table 3-2: Current Calculation Worksheet for SK Devices
Device # of Devices Current per Device
Addressable SLC Modules
SLC
SK-Control
Aux Pwr
SK-Monitor SK-Minimon mA mA SK-Pull-SA/SK-Pull-DA SK-Monitor-2 Standby/Alarm: 0.75 mA mA mA SK-Mon-10 Standby/Alarm: 3.5 mA mA mA SK-Relay-6 Standby/Alarm: 1.45 mA mA mA
(50 max.)
SK-Control-6
SK-Relay Standby/Alarm: 0.255 mA mA mA
SK-Zone
SK-Zone-6
SLC Accessories
B501BHT-2 Sounder Base
B224RB Relay Base Standby/Alarm: 0.5 mA mA mA RTS151/151 KEY Alarm: 7.5 mA RA100Z Alarm: 10 mA SLC Isolator Devices SK-Iso (Isolator Module) (100 max.) Standby/Alarm: 0.45 mA mA mA B224BI Isolator Base (50 max.) Standby/Alarm: 0.5 mA Accessories Modules
5860 Remote Fire Alarm Annunciator (8 max) 5824 Serial / Parallel Module (2 max.) Standby/Alarm: 45 mA mA mA
5496 Notification Power Expander 5895XL Standby/Alarm: 10 mA mA mA
(50 max.)
(8 max.)
Standby/Alarm 0.375 mA
1
SLC
Aux Pwr
Aux Pwr
SLC
Aux Pwr SLC Standby/Alarm 2mA mA mA
Aux Pwr SLC Alarm: 0.7 mA
Standby 20mA mA Alarm 25mA mA
Standby/Alarm: 10 mA mA mA
Standby/ 0.375 mA Alarm: 0.375 mA
Standby/ 1.7 mA mA Alarm: 7 mA mA
Standby/ 2.25 mA Alarm: 2.25 mA Standby/ 8 mA mA
Alarm: 20 mA mA
Standby 12 mA mA mA Alarm 90 mA mA mA Standby/
Alarm 0.27 mA Standby 50 mA mA mA Alarm 270 mA mA mA
Standby: 1 mA mA Alarm: 15 mA mA
Standby
Current
mA
mA mA
mA
mA mA
Alarm
Current
mA
mA
mA
mA mA
151295 3-7
Page 30
Model 5700 Installation and Operation Manual
Table 3-2: Current Calculation Worksheet for SK Devices
Device # of Devices Current per Device
5865-4 LED Annunciator (with reset and silence switches)
5865-3 LED Annunciator
5880 Generic LED Driver Module
(8 max.)
Standby
Current
Standby: 35 mA mA Alarm: 145 mA mA
Standby: 35 mA mA Alarm: 145 mA mA Standby: 35 mA mA Alarm: 200 mA mA
Alarm
Current
Standby: 0 mA mA
5883 Relay Interface (32 max.)
Alarm: 220 mA
mA
(22 mA per relay)
A Total System Current
Auxiliary Devices
3
Refer to devices manual for current rating.
Alarm/Standby: mA mA mA Alarm/Standby: mA mA mA Alarm/Standby: mA mA mA Alarm/Standby: mA mA mA
B Auxiliary Devices Current
Notification Appliance Circuits Refer to device manual for current rating.
Alarm: mA mA Alarm: mA Alarm: mA
mA mA
Alarm: mA mA
C Notification Appliances Current
mA D Total current ratings of all devices in system (line A + line B + C) mA mA E Total current ratings converted to amperes (line D x .001): A A F Number of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5): H G Multiply lines E and F. Total standby AH AH H Alarm sounding period in hours. (For example, 5 minutes = .0833 hours) H I Multiply lines E and H. Total alarm AH J
Add lines G and I.
4
Total ampere hours
required
AH
AH
1. Total does not include isolator devices or accessory bases.
3. If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is removed during that time. However, during normal operation, door holders draw current and must be included in the
2.5A total current that can be drawn from the panel.
4. Use next size battery with capacity greater than required.
5. SK-Beam-T draws a maximum of 500mA from auxiliary power only when the test feature is used. This should be considered when determining auxiliary power capacity but not calculated into current requirements for day to day operation.
6. The SK-Duct housing contains a vacant mount for a SK-Relay (sold separately). Current draw for the SK-Relay is calculated by increasing the SK-Relay row of the calculation sheet by one for each SK-Relay used with a SK-Duct.
3-8 151295
Page 31
Before You Begin Installing
3.6.1.2 Current Draw Worksheet for Hochiki SLC Devices
Use T able 3-3 to determine current requirements during alarm/battery standby operation when Hochiki SLC devices are installed. (Copy the page if additional space is required).
Table 3-3: Current Calculation Worksheet for Hochiki Devices
2 2
Standby
Current
mA mA
mA mA
mA mA
mA mA
mA mA mA
mA mA
Device # of Devices Current per Device
For each device use this formula: This column X This column = Current per number of devices. Fire Panel (Current draw from
battery) Addressable SLC Devices SD500-AIM
SD500-MIM mA mA SD500-ARM mA mA SD500-PS/SD500-PSDA mA mA SD505-AIS SD505-AHS mA mA SD505-APS mA mA
SD500-ANM
SD500-LED
SD500-SDM
SLC Accessory Bases SD505-6RB (50 max.) Standby/Alarm: .082 mA mA mA
SD505-6SB (50 max.)
SD505-ADHR SD505-DUCTR
SD505-DTS SD505-DTS-K SD505-ADH SD505-DUCT
SLC Isolator Devices SD500-LIM (100 max.)
SD505-6IB
1
(50 max.)
(50 max.)
(50 max.)
(50 max.)
(50 max.)
(50 max.)
(50 max.)
(50 max.)
Standby: 200 mA 200 mA Alarm: 325 mA 325 mA
1
Standby/Alarm: 0.55 mA
Aux. Pwr
1
SLC
Aux. Pwr
1
SLC
Aux. Pwr
1
SLC
Aux. Pwr
SLC
Aux. Pwr
SLC
Standby/Alarm 0.092 mA mA mA
Standby: 8 mA mA Alarm: 60 mA mA Standby/
Alarm: .55 mA Standby: 10 mA mA Alarm: 220 mA mA LED: 10 mA mA mA Standby/
Alarm: 0.55 mA Standby: 20 mA mA Alarm: 106 mA mA Standby/
Alarm: .55 mA
Standby: 1 mA mA Alarm: 32 mA mA Standby/
Alarm: .082 mA Standby: 20 mA Alarm: 62 mA
Standby/ Alarm: .5 mA
None, included with SD505-ADHR worst case.
None, included with detector current.
Alarm
Current
mA
151295 3-9
Page 32
Model 5700 Installation and Operation Manual
Table 3-3: Current Calculation Worksheet for Hochiki Devices
Device # of Devices Current per Device
Standby
Current
Alarm
Current
Accessories Modules 5860 Remote Fire Alarm
Annunciator
(8 max.)
Standby: 20 mA mA
Alarm: 25 mA mA 5824 Serial / Parallel Module (2 max.) Standby/Alarm: 45 mA mA mA 5496 Notification Power Expander 5895XL Intelligent Power Expander Standby/Alarm 10 mA mA mA
(8 max.)
5865-4 LED Annunciator (with reset and silence switches)
5865-3 LED Annunciator
(8 max.)
5880 Generic LED Driver Module
Standby/Alarm: 10 mA mA mA
Standby: 35 mA mA
Alarm: 145 mA mA
Standby: 35 mA mA
Alarm: 145 mA mA
Standby: 35 mA mA
Alarm: 200 mA mA
Standby: 0 mA mA 5883 Relay Interface (32 max.)
Alarm: 220 mA
mA
(22 mA per relay)
A Total System Current
Auxiliary Devices
3
Refer to devices manual for current rating.
Alarm/Standby: mA mA mA
Alarm/Standby: mA mA mA
Alarm/Standby: mA mA mA
Alarm/Standby: mA mA mA
B Auxiliary Devices Curren t
Notification Appliance Circuits Refer to device manual for current rating.
Alarm: mA mA
Alarm: mA
Alarm: mA
mA mA
Alarm: mA mA
C Notification Appliances Current
mA D Total current ratings of all devices in system (line A + line B + C) mA mA E Total current ratings con verted to amperes (line D x .001): A A F Number of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5): H G Multiply lines E and F. Total standby AH AH H Alarm sounding period in hours. (For example, 5 minutes = .0833 hours) H I Multiply lines E and H. Total alarm AH J
Add lines G and I.
4
Total ampere hours
required
AH
AH
1. Total does not include isolator devices or accessory bases.
2. If using 24 VDC aux power only. No standby or alarm current for battery calculation if using 24 VAC, 120 VAC or 240 VAC.
3. If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is removed during that time. However, during normal operation, door holders draw current and must be included in the
6.0A total current that can be drawn from the panel.
4. Use next size battery with capacity greater than required.
3-10 151295
Page 33
Before You Begin Installing
3.6.1.3 Maximum Battery Standby Load
The table below shows the maximum battery standby load for the 5700 based on 24 and 60 hours of standby. The standby load calculations of line D in the Current Draw Calculation Worksheet (Table 3-3) must be less than the number shown in the table below for the battery size used and standby hours required.
Rechargeable Battery Size
7 AH 221 mA 85 mA 18 AH 675 mA 250 mA 35 AH 1.1 A 450 mA
Max. Load for 24 hrs.
Standby, 5 mins. Alarm
*Max. Load for 60 hrs.
Standby, 5 mins. Alarm
* Required for NFPA 72 Auxiliary Protected Fire Alarm systems for Fire Alarm Service (City Box) and Remote
Station Protected Fire Alarm systems (Polarity Reversal) and Digital Alarm Communicator/Transmitter (DACT).
Warning!
Silent Knight does not support the use of batteries smaller than those listed in table above. If you use a battery too small for the installation, the system could overload the battery resulting in the installation having less than the required 24 hours standby power. Use the Current Calculation Worksheet to calculate the correct battery amperes/hour rating needed for your installation.
151295 3-11
Page 34
Model 5700 Installation and Operation Manual
3-12 151295
Page 35
Section 4 Control Panel Installation
Caution!
To avoid the risk of electrical shock and damage to the unit, power should be OFF at the control panel while installing or servicing.
4.1 Mounting the Control Panel Cabinet
Read the environmental specifications in Section 3.2 before mounting the 5700 panel. The 5700 cabinet dimensions are:
12-3/4” W x 15-1/8” H x 3-3/8” D (32.39 cm W x 38.42 cm H x 8.57 cm D).
The 5700 panel should be located within a secured area, where it is accessible to main drop wiring runs and where it can be easily tested and serviced. End-users responsible for maintaining the panel should be able to hear alarms and troubles. When selecting a location, keep in mind that the panel itself is the main source of alarm and trouble annunciation.
When mounting on interior walls, use appropriate screw anchors in plaster. When mounting on concrete, especially when moisture is expected, attach a piece of 3/4 inch plywood to the concrete surface and then attach the 5700 to the plywood. Also mount any other desired components to the plywood.
DO NOT flush-mount the 5700 cabinet in a wall designated as a fire break.
4.1.1 Preventing Water Damage
Water damage to the fire system can be caused by moisture entering the cabinet through the conduits. Conduits that are installed to enter the top of the cabinet are most likely to cause water problems. Installers should take reasonable precautions to prevent water from entering the cabinet. Water damage is not covered under warranty.
4.1.2 Removing the 5700 Assembly from the Housing
If it should ever be necessary to remove the control panel assembly from the cabinet for repair, do so by removing the screws that hold the control panel in to the cabinet. Do not attempt to disassemble the circuit boards.
4.1.3 Dead Front Installation and removal
This section provides instructions to install and or remove the optional dead front (DF-50) for the control panel cabinet.
151295 4-1
Page 36
Model 5700 Installation and Operation Manual
Dead Front Panel
4.1.3.1 Installing the Dead Front
Follow these steps to properly install the dead front panel into the control panel cabinet.
1. Remove the top two annunciator screws, do not discard them they will be reused. See Figure 4-1 for annunciator screw location.
2. Set the dead front into the cabinet as shown in Figure 4-1.
3. Reinsert the two annunciator screws as shown in Figure 4-1.
Figure 4-1 Dead Front Installation and Removal
4. Insert the two screws with the star washers into the bottom of the cabinet to secure the dead front into place. See Figure 4-1.
4.1.3.2 Dead Front Removal
Follow these steps to properly remove the dead front panel from the control panel cabinet.
1. Remove the two annunciator screws, do not discard them. See Figure 4-1.
2. Remove the two screws and star washers from the bottom of the cabinet. See Figure 4-1.
3. Remove the dead front panel from the control panel cabinet.
4. Reinsert the two annunciator screws. See Figure 4-1.
4-2 151295
Page 37
Control Panel Installation
To AC
Ground
Supervised
4.2 AC Connection
At installation, connect the AC terminals to the power source as shown in Figure 4-2. It may be necessary for a professional electrician to make this connection.
The AC terminals are rated at 120 VAC, 60 Hz, 1.5A.
151295 4-3
Figure 4-2 120VAC Power Connection
Page 38
Model 5700 Installation and Operation Manual
Red
Black
Battery Jumper
(P/N 140694)
Shipped With Panel
UL Listed 12V Battery
UL Listed 12V Battery
Battery 2
Battery 1
Supervised
4.3 Battery Connection
The control panel battery charge capacity is 7.0 to 35 AH. The main control cabinet can house batteries up to 7 AH, larger capacity batteries can be housed in a Remote Battery Box (P/N RBB). See Section 4.3.1 for deteails.Use 12V batteries of the same AH rating. Determine the correct AH rating as per your current load calculation (see Section 3.6).
Maximum battery charging current 3.1 Amps. Wire batteries in series to produce a 24-volt equivalent. Do not parallel batteries to increase
the AH rating. The following steps and diagram explain how to connect the batteries.
1. Connect the black wire from the control panel negative (–) battery terminal to the negative (–) side of Battery #2.
2. Connect the jumper wire provided (P/N 140694) from the positive (+) side of Battery #2 to the (–) negative side of Battery #1.
3. Connect the red wire from the control panel positive (+) terminal to the positive (+) side of Battery #1.
4-4 151295
Figure 4-3 Battery Connection
Page 39
Control Panel Installation
Cabinet
Mounting Holes
4.3.1 RBB Accessory Cabinet
The Model RBB Accessory cabinet can be used when your backup batteries requirements use backup batteries that are too large to fit into the main control panel cabinet. The RBB cabinet holds batteries up to the 35 AH size. The RBB dimensions are 16" W x 10" H x 6" D (40.64 cm W x 25.4 cm H x 15.24 cm D).
4.3.1.1 Installing the RBB Accessory Cabinet and Batteries
To properly install the accessory cabinet and backup batteries, follow these steps:
1. Mount the accessory cabinet. See figure Figure 4-4 for the four cabinet mounting holes.
If mounting onto drywall the accessory cabinet must be mounted onto 3/4-inch ply-
wood. This is necessary because the weight of the batteries inside the accessory cabi­net could cause the cabinet to pull away from the drywall.
When mounting on concrete, especially when moisture is expected, attach a piece of
3/4-inch plywood to the concrete surface and then attach the RBB cabinet to the ply­wood.
If using the battery cable extenders provided (P/N 140643), mount the RBB cabinet no
more than 18" away from the main control panel cabinet. This will ensure that the bat­tery cables reach the battery terminals.
Figure 4-4 RBB Cabinet Mounting Holes
2. Connect the main control panel battery cables to the battery cable extenders as shown in Figure 4-5.
Figure 4-5 Splicing Control panel Battery Cable to RBB Battery Cable Extenders
151295 4-5
Page 40
Model 5700 Installation and Operation Manual
Conduit
Conduit Coupler
++
--
RBB Cabinet Cover Screws
RBB Cabinet Cover Screws
Cover Plate
Mounting Keyholes
3. Run extended battery cable from control panel cabinet through conduit to RBB cabinet. See Figure 4-6.
Figure 4-6 Battery Connections in the RBB Cabinet
Note: Figure 4-6 is an example of how the wire connections can be routed. However, any other cabinet knock-
outs (on either the main control panel or the RBB cabinet), that are not previously being used may be uti­lized to connect conduit between the two cabinets.
4. Connect battery leads to the backup battery terminals. See Figure 4-6. Observe the proper polarity to prevent damage to the batteries or the control panel.
5. Insert the RBB cover screws into the cover mounting holes (see Figure 4-6). Screw the cover screw 3/4 of the way into the cover mounting hole.
6. Align the cover plate mounting keyhole over the cover mounting screws. See Figure 4-7.
Figure 4-7 Cover Plate Mounting Keyholes and Cover Mounting Screws Alignment
7. Slide the cover into place and tighten the cover mounting screws. See Figure 4-7.
4-6 151295
Page 41
Control Panel Installation
4.4 SBUS Wiring
This section contains information on calculating SBUS wire distances and the types of wiring configurations (Class B).
4.4.1 Calculating Wiring distance for SBUS modules
The following instructions will guide you in determining the type of wire and the maximum wiring distance that can be used with control panel SBUS accessory modules.
To calculate the wire gauge that must be used to connect SBUS modules to the control panel, it is necessary to calculate the total worst case current draw for all modules on a single 4­conductor bus. The total worst case current draw is calculated by adding the individual worst case currents for each module. The individual worst case values are shown in the table below .
Note: Total worst case current draw on a single SBUS cannot exceed 1 amp.
Model Number Worst Case Current Draw
5860 Fire Annunciator .100 amps 5824 Parallel/Serial Interface .040 amps 5880 LED Driver Module .200 amps 5865 LED Fire Annunciator .145 amps 5496 Notification Power Supply .010 amps
After calculating the total worst case current draw, Table 4-1 specifies the maximum distance the modules can be located from the panel on a single wire run. The table insures 6.0 volts of line drop maximum. In general, the wire length is limited by resistance, but for heavier wire gauges, capacitance is the limiting factor.
151295 4-7
Page 42
Model 5700 Installation and Operation Manual
These cases are marked in the chart with an asterisk (*). Maximum length can never be more than 6,000 feet, regardless of gauge used. (The formula used to generate this chart is shown in the note below).
Table 4-1: Wire Distances Per Wire Gauge Using Copper Wire
Wiring Distance: SBUS Modules to Panel
Total Worst Case
Current Draw (amps)
0.100 1852 ft. 4688 ft. * 6000 ft. * 6000 ft.
0.200 926 ft. 2344 ft. 3731 ft. 5906 ft.
0.300 617 ft. 1563 ft. 2488 ft. 3937 ft.
0.400 463 ft. 1172 ft. 1866 ft. 2953 ft.
0.500 370 ft. 938 ft. 1493 ft. 2362 ft.
0.600 309 ft. 781 ft. 1244 ft. 1969 ft.
0.700 265 ft. 670 ft. 1066 ft. 1687 ft.
0.800 231 ft. 586 ft. 933 ft. 1476 ft.
0.900 206 ft. 521 ft. 829 ft. 1312 ft.
1.000 (Max) 185 ft. 469 ft. 746 ft. 1181 ft.
22 Gauge 18 Gauge 16 Gauge 14 Gauge
Note: The following formulas were used to generate the wire distance chart:
Maximum Resistance (Ohms) =
Maximum Wire Length (Feet) =
(6000 feet maximum)
where: Rpu = Ohms per 1000 feet for various wire gauges (see table below)
Total Worst Case Current Draw (amps)
Maximum Resistance (Ohms)
6.0 Volts
Rpu
* 500
Table 4-2: Typical Wire Resistance Per 1000 ft. Using Copper Wire
Wire Gauge Ohms per 1000 feet (Rpu)
22 16.2 18 6.4 16 4.02 14 2.54
4-8 151295
Page 43
Wiring Distance calculation example:
Suppose a system is configured with the following SBUS modules: 2 - Module 5860 Fire Annunciator 1 - 5496 Notification Power Expander 1 - 5865 LED Fire Annunciator 1 - 5824 Parallel/Serial Interface
The total worst case current is calculated as follows:
5860 Current Draw = 2 x .100 amps = .200 amps 5496 Current Draw = 1 x .010 amps = .010 amps 5865 Current Draw = 1 x .200 amps = .145 amps 5824 Current Draw = 1 x .040 amps = .040 amps Total Worst Case Current Draw = .395 amps
Control Panel Installation
Using this value, and referring to the Wiring Distance table, it can be found that the available options are:
370 feet maximum using 22 Gauge wire 938 feet maximum using 18 Gauge wire 1493 feet maximum using 16 Gauge wire 2362 feet maximum using 14 Gauge wire
151295 4-9
Page 44
Model 5700 Installation and Operation Manual
Supervised Power Limited
5495 or 5499
SBUS Device
Control Panel
Supervised Power Limited
4.4.2 Wiring Configurations
Figure 4-8 illustrates Class B configuration.
Figure 4-8 SBUS Class B Wiring
4.4.2.1 How to Power SBUS Devices From Auxiliary Power Supply
Figure 4-9 illustrates how to power SBUS devices from an Auxiliary Power Supply such as the 5495 or 5499, when the maximum number of SBUS devices exceeds the SBUS power requirments.
Figure 4-9 Powering SBUS Devices From 5495 or 5499
Note: The earth ground jumper on the 5495/5499 must be removed in this configuration.
4-10 151295
Page 45
Control Panel Installation
4.5 Remote Annunciator 5860 Installation
The optional Model 5860 Remote Annunciator, shown in Figure 4-10, performs the same functions as the on-board annunciator. Operation is identical. Up to 8 annunciators can be added to the 5700 system.
Figure 4-10 Model 5860 Remote Annunciator, Front View
5860 installation involves the following steps:
1. Make sure power is off at the panel.
2. Mount the 5860 in the desired location (see Section 4.5.1).
3. Connect the 5860 to the panel (see Section 4.5.2).
4. Use the dipswitches on the back of the 5860 to assign an ID# to the 5860 (see Section
4.9.1).
5. The new 5860 module must be added to the system through programming. JumpStart will add the module automatically (see Section 6.1). You can also add it manually (see Section
7.3.2). Select a name, if desired (see Section 7.3.1.1).
151295 4-11
Page 46
Model 5700 Installation and Operation Manual
4.5.1 Mounting the 5860
This section of the manual describes mounting the remote annunciator. The annunciator can be flush- or surface-mounted.
Figure 4-11 shows the parts of the annunciator. Instructions for disassembling and mounting appear on the following pages.
4-12 151295
Figure 4-11 Annunciator Parts
Page 47
Control Panel Installation
The 5860 comes from the factory fully assembled. You must disassemble it for mounting. To disassemble the annunciator, use a 5/64 hex wrench to remove the set screws, located on the bottom of the annunciator bezel. (See Figure 4-12 for location of the set screws.)
Figure 4-12 Annunciator Back Box and Bezel Details
4.5.1.1 Flush Mounting
This section of the manual describes flush mounting. You can flush-mount with or without an electrical box.
151295 4-13
Page 48
Model 5700 Installation and Operation Manual
Flush Mounting with an Electrical Box
The 5860 annunciator can be used with the following types of electrical boxes: 4S, single­gang, and double-gang.
If an electrical box is used, the box must be 1-3/8” back from the face of the wall to accommodate the annunciator. Studs used with an electrical box must be two by fours (or larger).
Figure 4-13 Placement of Electrical Box for Flush Mounting
Flush Mounting Steps
1. Cut a hole in the sheet rock to the following dimensions: 8-1/4” w x 6-5/8” h. If an electri­cal box is used, the box must be 1-3/8” back from face of wall to accommodate the annun­ciator (see Figure 4-13).
2. Remove knockout holes as needed for wires.
3. Fit the annunciator back box into the hole and stabilize with mounting wires. Angle the mounting wires into the first hole past the sheet rock. Secure the wires behind the screws as shown in Figure 4-14. When all four wires are in place, the back box should fit snugly into the hole in the sheet rock.
4-14 151295
Page 49
Control Panel Installation
4. After the annunciator wiring to the panel has been completed (described in Section 4.5.2), replace the electronic assembly in the back box. Place the bezel over the back box and tighten the set screws on the bezel.
Figure 4-14 Flush Mounting the Back Box
4.5.1.2 Surface Mounting
The 5860 can be mounted directly to a surface or can be attached to a single, double, or four­square electrical box. The Model 5860TG/TR trim ring kit is available for use when surface mounting.
1. Drill holes in the surface to match the screw holes on the back box.
2. Fit the trim ring over the back box.
3. Attach the back box to the surface using screws provided.
4. After the annunciator wiring to the panel has been completed (described in Section 4.5.2), replace the electronic assembly in the back box. Place the bezel over the back box and tighten the set screws on the bezel.
151295 4-15
Page 50
Model 5700 Installation and Operation Manual
Supervised Power Limited
4.5.2 Model 5860 Connection to the Panel
Connect the 5860 to the panel as shown in Figure 4-15.
Figure 4-15 Model 5860 Connection to the Panel
4.6 5824 Serial/Parallel Printer Interface Module
Installation
The 5824 serial/parallel printer interface module allows you to connect a printer to the panel, so you can print a real-time log of system events, a report of detector status, and event history . Instructions for installing the 5824 appear below.
5824 installation involves the following steps:
1. Make sure power is off at the panel.
2. Connect the 5824 to the panel as shown in Figure 4-16.
Note: Two 5824s per panel maximum.
3. Use the dipswitches on the back of the 5824 board to assign an ID# to the 5824 (see Sec­tion 4.9.1).
4. Configure the 5824 device through programming. See Section 4.6.1.
4-16 151295
Page 51
5. Connect a printer to the 5824 as shown in Figure 4-17.
Supervised Power Limited
To Serial Printer
To Parallel Printer
Control Panel Installation
Figure 4-16 5824 Connection to the Panel
Figure 4-17 Printer Connection
151295 4-17
Page 52
Model 5700 Installation and Operation Manual
711
ENTER
ENTER
4.6.1 Selecting 5824 Options
Configuring the 5824 includes the following steps:
Add the module to the system. JumpStart will add the module automatically (see Section
6.1). You can also add it manually (see Section 7.3.2).
Select a name, if desired (see Section 7.3.1.1).
Select options for the printer and the output port. See below.
Printer and Output Port Options
1. From the Main Menu, select for Program Menu.
2. Select for Module.
3. Select for Edit Module.
4. From the list that displays, select the 5824 module you want to configure.
5. Press to bypass the next two screens. A screen similar to the one shown in Figure 4-18 will display.
Figure 4-18 Selecting Printer and Output Port Options
6. Select options for the printer as needed for your installation. Most printers are parallel.
7. If you are using a serial printer, use the next screen to select serial port options as required for your printer. Refer to your printer manual if you need more information.
Option Choices
Baud Rate: 75 - 19200 Data Bits: 5 - 8 Stop Bits: .5, 1, 2 Parity: None, Even, Odd
4-18 151295
Page 53
Control Panel Installation
SBUS Connection
SBUS Address DIPs
Dry Contact Inputs - Supervised/Power Limited
4.7 5880 LED Driver Module
The 5880 is an LED driver board that can be used in a wide variety of applications, including as an interface with most customized floor plan annunciator boards. The 5880 can drive up to 40 LEDs and has one PZT controller. The 5880 also has eight inputs for dry contact monitoring. The following sub-sections describe hardware installation. Refer to Section 6 for programming information.
4.7.1 5880 Board Layout
Figure 4-19 is a picture of the 5880 board showing locations of screw terminals for connection to the panel and contact monitor wiring; pin connectors for connecting LEDs; and the dipswitch for selecting an SBUS ID number.
Figure 4-19 5880 Board Layout
151295 4-19
Page 54
Model 5700 Installation and Operation Manual
Supervised Power Limited
4.7.2 FACP Connection
The 5880 connects to the panel via the SBUS. Make connections as shown in Figure 4-20. After the 5880 is connected to the panel, it must be added to the system. This programming step is described in Section 4.9.
Figure 4-20 5880 Connection to Main Control Panel Assembly
4-20 151295
Page 55
Control Panel Installation
4.7.3 LED Wiring
There are four 12-pin connectors on the 5880 board for connecting LEDs. Each LED gets its power from Pin 11. Internal resistors are sized so that there is approximately 10 mA of current for each LED, no series resistors are required. LED outputs can be mapped to output circuits. See Section 6 for programming details.
Wire the LEDs as shown in Figure 4-21. On connector P1, Pin 12 is a programmable open collector output for controlling a PZT. If
used, the 5880 PZT will match the PZT pattern of the on-board (or 5860) annunciator.
Note: The circuit connected to “Open Collector Output” (last pin on P1) must be current limited so that no more
than 100 mA of current is allowed to flow into the open collector transistor.
151295 4-21
Figure 4-21 5880 Board Layout
Page 56
Model 5700 Installation and Operation Manual
Model 7628
Supervised
4.7kΩ EOL
4.7.4 Dry Contact Wiring
The 8 input circuits on the 5880 board are for monitoring switch inputs-any type of switch supported by the control panel can be used with the 5880. For example, you can use a 5880 to monitor pull stations, water flow, tamper, reset, or silence switches.
Wire dry contacts as shown in Figure 4-22. Notice grouping of terminals; power terminals are shared by two inputs.
Figure 4-22 Dry Contact Wiring
4-22 151295
Page 57
Control Panel Installation
Supervised Power Limited
4.8 5865-3 / 5865-4 LED Annunciator Installation
The 5865-3 and 5865-4 are LED annunciators. The 5865-4 has 30 mappable LEDs, remote silence and reset key switches, and a general system trouble LED. The 5865-3 has 30 mappable LEDs only. These are arranged as 15 pairs of red (typically used for alarm) and yellow (typically used for trouble) LEDs.
Installation of the 5865-3 and 5865-4 is identical. The key switches and the trouble LED follow the behavior of other system annunciators and do not require any installation steps. The following sub-sections describe how to install the 5865-3 and 5865-4 hardware. Refer to Section 6 for programming information.
Note: This manual uses “5865” when referring to aspects of the 5865-3 and 5865-4 that are common to both
models.
Figure 4-23 5865-3 and 5865-4 Assembly (front view)
4.8.1 FACP Connection
The 5865 connects to the panel via the SBUS. Make connections as shown in Figure 4-24. After the 5865 is connected to the panel, it must be added to the system. This programming step is described in Section 4.9.
151295 4-23
Figure 4-24 5865 Connection to the FACP
Page 58
Model 5700 Installation and Operation Manual
4.8.2 5865 Mounting
Mount the 5865-4 to a standard 4-gang electrical box. Mount the 5865-3 to a standard 3-gang electrical box. In Figure 4-25, the 5865-4 attached to a 4-gang box is used as an example.
Figure 4-25 5865 Mounting Example
The 5865 ships with a set of zone description labels that can be inserted into the 5865 board assembly. These labels can be used in a typewriter or can be written on by hand.
Slide the labels under the plexiglass as shown in Figure 4-26. The LEDs will show through the label when illuminated.
Figure 4-26 Inserting Zone Description Labels
4-24 151295
Page 59
Control Panel Installation
4.9 Configuring Modules
This section describes how to configure any system hardware modules that have been added to the system.
4.9.1 Assigning Module IDs
When installing a hardware module (such as, 5824, 5860, 5496, 5865-3 or 5865-4), you must use the dipswitches on the module to assign an ID# to the module.
Figure 4-27 shows all possible dipswitch positions and their correlation to a numerical ID. For example, to select ID 2, place dipswitch 2 in the up position.
Refer to Section 7.3 to edit, add, delete, and view module list.
151295 4-25
Figure 4-27 Possible module addresses
Page 60
Model 5700 Installation and Operation Manual
Supervised
5211 Ground
Start Relay Socket
4.10 Telephone Connection
Connect the telephone lines as shown in Figure 4-28. The Model 7860 phone cord is available from Silent Knight for this purpose.
A number of programmable options are available for customizing telephone lines. These options are described in Section 7.7.
Figure 4-28 Connection of Telephone Lines
4.11 5211 Ground Start Relay
Note: Do not use ground start in UL installations.
If connecting the control panel to a ground start telephone network, you must use the 5211 ground start relay (order separately).
To install the 5211:
1. Install the 5211 on the ground relay socket as shown in Figure 4-28.
2. Enable ground start through the ground start programming option as described in Section
7.7.2.6.
4-26 151295
Page 61
Control Panel Installation
Supervised Power Limited
Notification Wiring
4.12 Notification Appliance/Auxiliary Power Circuits
Two outputs are built-in to the 5700 FACP which can be programmed to be used as NACs (Class A or Class B) or as Aux power.
This section of the manual explains how to install conventional notification appliances and how these terminals can be used for auxiliary power.
4.12.1 Conventional Notification Appliance
This sub-section of the manual explains how to install conventional notification appliances for Class A (Style Z) and Class B (Style Y) configurations.
4.12.1.1 Class B Notification Wiring
You must use an appliance from the list of compatible appliances in the Appendix A at the back of this manual.
To install a Class B notification appliance circuit:
1. Wire Class B Notification appliances as shown in Figure 4-29.
2. Configure the circuit through programming (see Section 7.6).
Figure 4-29 Class B Notification Appliance Circuit Wiring
151295 4-27
Page 62
Model 5700 Installation and Operation Manual
Supervised Power Limited
4.12.1.2 Class A Notification Wiring
You must use an appliance from the list of compatible appliances in the Appendix at the back of this manual.
To install a Class A notification appliance circuit:
1. Wire the Class A notification appliances as shown in Figure 4-30.
Caution
For proper system supervision do not use looped wire under terminals marked – and + of the Flexput connectors. Break wire runs to provide supervision of connections.
2. Configure the circuit for Class A in programming (see Section 7.6).
Figure 4-30 Class A Notification Appliance Circuit Configuration
4-28 151295
Page 63
Control Panel Installation
Non-Supervised Power Limited
4.12.2 Auxiliary Power Installation
NAC Circuits 1and 2 on the control panel can be used as auxiliary power circuits. The three types of auxiliary power available are:
Door Holder (see section 4.12.2.1)
Constant (see section 4.12.2.2)
Resettable Power (see section 4.12.2.3)
Auxiliary power circuits are power limited. Each circuit can source up to 2.5A (total current for system must not exceed 2.5A).
To install an auxiliary power circuit:
1. Wire the NAC circuit(s) that will be used for auxiliary power. See Figure 3-2 for location of NAC circuits.
2. Configure the auxiliary power output through programming (see section 7.6).
4.12.2.1 Door Holder Power
Door holder power is intended for fire door applications. When there are no alarms in the system and the panel has AC power, door holder circuits have 27.4 volt power present at their terminals. Any alarm will cause power to disconnect. Power will be re-applied when the system is reset. If AC power is off for more than 15 seconds, the auxiliary door holder power will be disconnected to conserve the battery backup. When AC power is restored, power is immediately restored to the door holder circuits.
Figure 4-31 Example of an Auxiliary Power For Door Holder
Note: Figure 4-31 uses UL listed door holder Model 1400 from Door Control International as an example.
151295 4-29
Page 64
Model 5700 Installation and Operation Manual
Connect to Power Limited Sources only
4.12.2.2 Constant Power
Use constant power for applications that require a constant auxiliary power source. Power is always present at Constant circuits.
4.12.2.3 Resettable Power
Resettable power is typically used to power beam detectors, flame detectors and conventional 4-wire smoke detectors. For circuits selected as Resettable, 27.4 volt power is always present at the terminals unless a system reset occurs. If a system reset occurs, power is disconnected from the terminals for 30 seconds, then re-applied.
4.13 On-Board Relays (Conventional)
The control panel has two built-in programmable relays and a built-in trouble relay. All relays are Form C rated at 2.5 A @ 27.4 VDC Resistive.
Figure 4-32 Location of Conventional Relay Circuits
Note: The N.C. contact is the relay contact that is closed when the panel has power and there are no alarm or
trouble conditions.
4.13.1 Common Trouble Relay
The control panel has a dedicated Form C trouble relay built into terminals labeled TROUBLE. The relay provides a normally open and a normally closed contact. The trouble relay will deactivate under any trouble condition. Form C rated at 2.5 A @ 27.4 VDC Resistive.
4.13.2 Programmable Relays
The control panel has two Form C programmable relays built into terminals labeled RELAY 1 or RELAY 2. Each relay provides a normally open and a normally closed contact.
To install one or two programmable relays, follow these steps.
1. Wire Relay 1 and/or Relay 2 as needed for your application. See Figure 4-32 for the loca­tion of the relay terminals.
2. Configure the relay through programming (see section 7.6).
4-30 151295
Page 65
Control Panel Installation
A 5496 Must Be Used for NAC Circuits
Example
Intended for connection to a polarity reversal circuit of a remote station receiving unit having compatible ratings.
4.14 Remote Station Applications
4.14.1 Keltron Model 3158 Installation
The control panel is compatible with Keltron Model 3158, used for direct connection to a Keltron receiver. The 3158 reports alarms, supervisories, and troubles. The 3158 is intended for connection to a polarity reversal circuit of a remote station receiving unit having compatible ratings.
The steps for connecting the 3158 to the control panel. Refer to the 3158 installation instructions for complete information.
1. Wire the 3158 to the control panel as shown in the connection list and Figure 4-33.
2. Wire the 3158 within 20 feet of the control panel. Wiring must be enclosed in conduit.
3. Program control panel Relay 2 for alarm.
4. Program NAC circuit 2 for alarm.
5. Program NAC circuit 1 for supervisory non latching.
Note: NACs must be programmed for continuous and non-silencing.
Figure 4-33 Keltron 3158 Connection to Control Panel
151295 4-31
Page 66
Model 5700 Installation and Operation Manual
Non-Supervised Non-Power Limited
Note: NAC Circuit 2 Used as an Example. Either NAC Circuit Can Be Used.
4.14.2 City Box Connection Using the 5220 Module
This section describes how to connect the control panel to a municipal fire alarm box or “city box” as required by NFPA 72 Auxiliary Protected Fire Alarm systems for fire alarm service. The city (master) box is an enclosure that contains a manually operated transmitter used to send an alarm to the municipal communication center which houses the central operating part of the fire alarm system.
City Box Standby Current: 0 (Notification supervision current
accounted for in control panel draw.) Alarm Current: 1 Amp for 1 second Max Voltage: 27.4 VDC The maximum coil and wire resistance (combined) must not exceed 30 ohms. To install the 5220 for city box connection:
1. Use one of the knockouts on the right side of the control panel to connect the 5220 using a
short piece of conduit (must not exceed 20 feet in length).
2. Wire the 5220 to the control panel as shown in Figure 4-34. This drawing also shows how
to connect the city box coil to terminals 3 and 4 on the 5220. Do not install an EOL resis­tor in the terminals of the NAC circuit used for this application.
3. Connect earth ground wire to the 5220 chassis with mounting screw.
4. Program the NAC circuit used as a continuous and non-silencing. Refer to Section 7.6.1
for zone grouping and mapping.
It is not possible to reset the remote indication until you clear the condition and reset the control panel.
4-32 151295
Figure 4-34 City Box Connection
Page 67
Control Panel Installation
4.14.3 NFPA 72 Polarity Reversal
4.14.3.1 Using the 5220 Module
When the 5220 is wired and programmed for polarity reversal, it reports alarm and trouble events to a remote site. Alarms will override trouble conditions and it will not be possible to reset the remote indicator until the condition is cleared and the control panel is reset.
If an alarm condition occurs, the alarm relay will close, overriding the trouble condition. Standby Current: 100 mA Alarm: 100 mA Max. Voltage: 27.4 VDC To install the 5220 for polarity reversal, follow the steps below:
1. Locate the knockout on the right side of the control panel cabinet to connect the 5220
using a short piece of conduit (must not exceed 20 feet in length).
2. Wire the 5220 to the control panel using the four-wire pigtail provided as shown in Figure
4-35. This diagram also shows how to connect the 5220 to the remote indicator. Do not install an EOL resistor in the terminals of the NAC circuit used for this application.
3. Connect earth ground wire to the 5220 chassis with mounting screw.
4. Program the NAC circuit used as continuous and non-silencing. Refer to Section 7.6.1 for
zone grouping and mapping.
151295 4-33
Page 68
Model 5700 Installation and Operation Manual
Note: NAC circuit 1 and Relay 2 used as examples. Either NAC circuit and Relay
Not suitable for remote station protected premises service where separate transmission circuits are required for fire supervisory (if applicable), and trou bl e signals.
circuit can be used.
Program Relay for Alarm.
Max Voltage: 27.4 VDC Max Current: 1 Amp
5. If necessary, adjust loop current using the potentiometer (R10) on the 5220 board. Normal
loop current is 2-to-8 mA with a 1k ohm remote station receiving unit. Maximum loop resistance is 3k ohm.
Figure 4-35 Polarity Reversal Connection Using the 5220 Module
4-34 151295
Page 69
Control Panel Installation
4.14.3.2 Using the 7644 Module
When the 7644 is used for polarity reversal, it allows alarm and trouble events to be reported to a remote site. Alarms will override trouble conditions and it will not be possible to reset the remote indicator until the condition is cleared and the control panel is reset.
To install the 7644 for polarity reversal:
1. Wire the 7644 to the control panel as shown in Figure 4-36. Do not install an EOL resistor
on the terminals of the NAC circuit used.
Note: Use only NAC circuits on the control panel for reverse polarity.
2. Program the NAC circuit as a notification circuit. See Section 7.5.1.
3. Map the group to activate constant on from the zone event. See Section 7.5.1.2.
4. Program the output group characteristics as non-silenceable and reverse polarity. See Sec-
tion 7.5.1.2.
Figure 4-36 Polarity Reversal Connection Using the 7644
151295 4-35
Page 70
Model 5700 Installation and Operation Manual
UL Listed Model 7642
Intended for Connection to a Polarity Reversal Circuit of A Remote Station Receiving Unit Having Compatible Rating.
Supervised Power Limited
To Remote Receiving Station
UL Listed Model 7642
Note: UL Listed Model 7642 must be permanently mounted
4.14.4 Using the SD500-ARM Addressable Relay Module
When the SD500-ARM is wired for polarity reversal, it reports alarm and trouble events to a remote site. Alarms will override trouble conditions and it will not be possible to reset the remote indicator until the condition is cleared and the control panel is reset.
Relay 2 must be programmed for Alarm (default). Max Current: 1A Max. Voltage: 27.4 VDC
Note: If you need to transmit supervisories or trouble conditions, additional SD500-ARM modules must be added.
Use relay 1 to transmit supervisory conditions. Use the trouble relay to transmit trouble conditions.
Wire the SD500-ARM as shown in Figure 4-37.
Figure 4-37 Polarity Reversal Connection Using the SD500-ARM Module
4-36 151295
Page 71
Control Panel Installation
Supervised Power Limited
Intended for Connection to a Polarity Reversal Circuit of A Remote Station Receiving Unit Having Compatible Rating.
Note: UL Listed Model 7642 must be permanently mounted
4.14.5 Using a MR-201/T Control Relay From Air Products
When the MR-201/T control relay is wired for polarity reversal, it reports alarm and trouble events to a remote site. Alarms will override trouble conditions and it will not be possible to reset the remote indicator until the condition is cleared and the control panel is reset.
If an alarm condition occurs, the alarm relay will close, overriding the trouble condition. Current: 15 mA max.
Operating Voltage: 24 VDC nominal; 27.4 VDC max. Resistance: 4 KΩ
To install the MR-201/T for polarity reversal, follow the steps below:
1. Wire the MR-201/T as shown in Figure 4-38.
2. Program the NAC circuit for non silence NAC circuit (see Section 7.6).
Note: If you need to transmit supervisories or trouble conditions, additional relay modules must be added. Use
151295 4-37
relay 1 to transmit supervisory conditions. Use the trouble relay to transmit trouble conditions.
Figure 4-38 Polarity Reversal Connection Using the MR-201/T Relay
Page 72
Model 5700 Installation and Operation Manual
4.14.6 Transmitter Activated by Dry Contacts
This section describes the connection of a UL 864 listed remote station transmitter to the 5700 FACP dry contacts. The FACP contacts must be supervised by the remote station transmitter module using end-of-line resistors (ELRs) with a value determined by the transmitter manufacturer . Power is also provided by the remote station transmitter manufa cturer. Refer to the remote station transmitter manufacturer’s manual for details.
4-38 151295
Page 73
Section 5 SK and Hochiki SLC Device Installation
Caution!
To avoid the risk of electrical shock and damage to the unit, power should be OFF at the
control panel while installing or servicing.
5.1 List of SK SLC Devices
The following SK SLC devices can be used with the control panel. See the device installation instructions for more information (packaged with the device).
Note: The control panel supports the use of either SK SLC devices or Hochiki SLC devices. You cannot install
both SLC device types on the control panel.
SK
Part Number
SK-Photo Photoelectric smoke detector
SK-Acclimate Multi criteria photoelectric smoke detector with thermal (135°F) SK-Beam Reflected beam smoke detector without test feature SK-Beam-T Reflected beam smoke detector with test feature SK-Ion Ionization smoke detector I56-3428-000R SK-Duct Photoelectric duct smoke detector with extended air speed range I56-3432-000R SK-Heat Fixed temperature thermal detector (135°F)
SK-Heat-HT Fixed high temperature thermal detector (190°F) SK-Pull-SA Addressable single action pull station I56-3446-001 SK-Pull-DA Addressable dual action pull station I56-3447-001 SK-Iso Fault isolator module I56-3445-000 SK-Monitor Monitor module I56-3442-000 SK-Minimon Mini monitor module I56-3444-000 SK-Monitor-2 Dual input monitor module I56-3435-000 SK-Mon-10 10 input monitor module I56-3443-000 SK-Relay Addressable relay module I56-3438-000 SK-Relay-6 Six relay control module I56-3439-000 SK-Zone Addressable zone interface module I56-3440-000 SK-Zone-6 Six zone interface module I56-3441-000 SK-Control Supervised control module I56-3436-000 SK-Control-6 Six circuit supervised control module I56-3437-000 SK-6AB 6" mounting base K200-07-00 B224BI 6" isolator base D450-15-00 B224RB 6" relay base D450-16-01 B501BHT-2 6" temporal sounder base D550-06-00 B501 4" mounting base D550-02-00
Model Name/Description
Section/ Install
Sheet PN
I56-3426-000RSK-Photo-T Photoelectric smoke detector with thermal (135°F)
I56-3433-000R
I56-3429-000RSK-Heat-ROR Rate-of-rise thermal detector with 135° fixed temperature
151295 5-1
Page 74
Model 5700 Installation and Operation Manual
5.2 List of Hochiki SLC Devices
The following Hochiki SLC devices can be used with the control panel. See the appropriate section number in this manual or the device installation instructions (packaged with the device) for more information.
Note: The control panel supports the use of either Hochiki SLC devices or SK SLC devices. You cannot install
both SLC device types on this control panel.
Section No./
Model Number Model Name/Description
SD505-APS Photoelectric smoke detector.
SD505-AHS Absolute temperature heat detector. Trip point range from 135°F–150°F (0°C–37°C). SD505-6AB 6" base for use with the SD505-AHS, SD505-AIS, and SD505-APS. 150955 SD505-6IB 6" short circuit isolator base for use with the SD505-AHS, SD505-AIS, and SD505-APS 151175 SD505-6RB 6" relay base for use with the SD505-AHS, SD505-AIS, and SD505-APS 151192 SD505-6SB 6" sounder base for use with the SD505-AHS, SD505-AIS, and
SD505-APS SLC devices
SD505-DUCT Duct Smoke Detector. Duct Housing including the SD505-APS Analog Photoelectric Smoke
Sensor. Intake tubing fo r duct available in three lengths: SD505-T2 (2.5 foot); SD505-T5 (5 foot); SD505-T10 (10 foot)
SD505-DUCTR Duct Detector housing with relay base. Duct housing with relay base including SD505-APS
Analog Photoelectric Smoke detector pre-installed
SD505-ADH Duct Detector Housing for use with the SD505-AIS or SD505-APS smoke detectors. Intake
tubing for duct available in three lengths: STS-2.5: Duct widths 1.0’ to 2.5’; STS-5.0: Duct widths 2.5’ to 5.0’; STS-10.0: Duct widths
5.0’ to 10.0’ When ordering SD505-ADH, specify intake tub ing size and o rder the ap propriate
smoke detector (if needed). SD505-ADHR Duct detector housing with relay (for use with SD505-AIS or SD505-APS smoke detectors) 151126 SD500-PS/-PSDA Single or dual action addressable pull station 151177 SD500-AIM Addressable input module (switch input), standard size, dipswitch configurable 151071 SD500-MIM Mini input monitor module (switch input), small size, dipswitch configurable. Fits in single-
gang box with manual pull station switch. SD500-ANM Addressable notification module 151109 SD500ARM Addressable relay module dipswitch configurable. 151091 SD500-SDM Addressable smoke detector module. Use to assign an address to a loop of conventional
devices. SD500-LIM Line isolator module. Fits in a double gang box. 151125 SD500-LED Addressable LED driver module. Capable of driving up to 80 LEDs. Up to 40 SD500-LED
Driver Modules can be used per SLC loop. SD505-DTS,SD505-DTS-K Remote test switch & LED indicator for the SD505-ADHR 151126
Installation
Instructions PN
Section 5SD505-AIS Ionization smoke detector
151191
1700-09882
1700-09882
151040
151071
151193
151232
5-2 151295
Page 75
SK and Hochiki SLC Device Installation
5.3 Maximum Number of Devices
The 5700 supports SK or Hochiki devices on one 5700 system. The maximum number of devices per system varies depending on device protocol. Device support is as follows:
SK Devices–A 5700 system can support a total of 50 SK detectors and 50 SK modules.
OR
Hochiki Devices–A 5700 system can support a total of 50 Hochiki SLC detectors and modules, in any combination.
5.4 Wiring Requirements for SLC Devices
The following information applies to all SLC devices. Refer to the section that describes the type of device you are installing for details.
5.4.1 Wiring SLC in Style 4 (Class B) Configuration
No special wire is required for addressable loops. The wire can be untwisted, unshielded, solid or stranded as long as it meets the National Electric Code 760-51 requirements for power limited fire protective signaling cables. Wire distances are computed using copper wire.
Maximum wiring resistance is 40 ohms for SK device and 50 ohms for Hochiki devices. Maximum loop length depends on the wire gauge.
Table 5-1 Maximum wiring distance for SK Modules
Wire Gauge Max. Distance for SK
22 AWG 1200 feet 18 AWG 3100 feet 16 AWG 4900 feet 14 AWG 7900 feet 12 AWG 10,000 feet
Table 5-2 Maximum wiring distance for Hochiki Devices
Wire Gauge Max. Distance for Hochiki
22 AWG 1500 feet 18 AWG 3900 feet 16 AWG 6200 feet 14 AWG 10,000 feet
151295 5-3
Page 76
Model 5700 Installation and Operation Manual
The following figures show how length is determined for out and back tap and T-Tap style wiring.
Figure 5-1 Calculating wire run length for a simple out and back
5-4 151295
Page 77
SK and Hochiki SLC Device Installation
When using T-taps, the total length of all taps and the main bus must not exceed 40,000 feet. This requirement must be met in addition to the maximum distance requirements for the various wire gauges.
Figure 5-2 Calculating Wire Run Length for a T-tap
151295 5-5
Page 78
Model 5700 Installation and Operation Manual
5.4.2 Wiring SLC Devices in Style 6 & 7 (Class A)
Configuration
The following figure illustrates how to wire the SLC loop for Style 6 or Style 7 Class A installations.
Note: Style 6 does not use short circuit isolator devices.
Figure 5-3 Class A SLC Configuration
Note: No t-taps allowed on class A SLC loops.
Caution
For proper system supervision do not use looped wire under terminals marked SLC + and – of the SLC device connectors. Break wire runs to provide supervision of connections.
5-6 151295
Page 79
SK and Hochiki SLC Device Installation
Caution: Do not loop wire under Terminal 1 or 2.
Break wire run to provide supervision of connec tions.
Class A wiring: Class B wiring:
...............
5.5 Wiring SK SLC Detectors
This section describes how to install heat and smoke detectors. All detectors ship with installation instructions. Refer to the detector’s installation instructions for more detailed information.
This information applies to the following SK models:
SK-Photo Photoelectric Smoke Detector
SK-Photo-T Photoelectric Smoke Detector with Thermal
SK-Acclimate Photoelectric Smoke Detector with Thermal
SK-Heat Fixed Temperature Detector
SK-Heat-T High Temperature Thermal Detector
SK-Heat-ROR Rate-of-Rise Thermal Detector
SK-Ion Ionization Smoke Detector
To wire SK detectors:
1. Wire device bases as shown in Figure 5-4.
2. Set the address for each device as described in Section 5.6.
Figure 5-4 Heat and Smoke Detector Connection to the Panel.
151295 5-7
Page 80
Model 5700 Installation and Operation Manual
Example 1: Device Set to 01.
Example 2: Device Set to 42.
All dials labeled for ONES
or TENS position.
5.6 Addressing SK SLC Devices
All SK devices are addressed using the two rotary dials that appear on the device board. Use the ONES rotary dial to set the ones place in a one or two digit number, and use the TENS rotary dial to set the tens place in a two digit number.
SK device addresses are handled differently than Hochiki device addresses. The control panel recognizes when an SK detector or SK module is installed. For this reason, SK detectors can be assigned any unique address from 1 to 50, and SK modules can be assigned any unique address from 1 to 50. Unlike Hochiki detectors and modules which share addresses 1 through 50, there can be an SK detector using address 1 and an SK module using address 1. 0 is an invalid address.
Example 1: To select device address 1, turn the ONES rotary dial to 1 and the TENS rotary dial to 0 as shown in Figure 5-5.
Example 2: To select device address 42, turn the ONES rotary dial to 2 and the TENS rotary dial to 4 as show in Figure 5-5.
Figure 5-5 SK SLC Device Addressing Using Rotary Dials
5-8 151295
Page 81
SK and Hochiki SLC Device Installation
5.7 Wiring Hochiki Detectors
The information in this section applies to the following Hochiki models: SD505-AHS Heat Detector, SD505-AIS Ionization Smoke Detector, and SD505-APS Photoelectric Smoke Detector.
To wire SD505-APS, SD505-AHS, or SD505-AIS detectors:
1. Wire device bases as shown in Figure 5-6.
2. Set the address for each device as described in Section 5.8.
Figure 5-6 Heat or Smoke Detector Connection to the FACP (Class B)
151295 5-9
Page 82
Model 5700 Installation and Operation Manual
ENTER
2
3
ENTER
SILENCE
1
2
5.8 Addressing Hochiki Devices
This section tells how to address detectors and modules.
5.8.1 SD505-APS, SD505-AHS, & SD505-AIS
The SD505-APS photoelectric smoke detector, SD505-AHS heat detector, and SD505-AIS ionization smoke detector are easily addressed at the FACP. The Installer Code is required to perform this task.
To address a SD505-APS, SD505-AHS, or SD505-AIS:
1. Connect a detector base temporarily to the programming terminals as shown in Figure 5-7. (You can use the same base for each detector.)
Figure 5-7 Temporary Connection of Detector Base to Panel for Addressing
2. Enter the Installer code, then press .
3. Select for Point Functions.
4. Select for Set SLC Dev Addr.
5. Select “Yes” by pressing the up arrow, then press . (The panel will go into trouble at this point. You can use the key to stop the PZT. The trouble will clear
automatically when the panel reinitializes when you finish programming.)
6. When the wait message clears, the following options display:
for Read Address. Use to read (or check) a single detector’s address. for Write Address. Use to program a single detector’s address.
5-10 151295
Page 83
SK and Hochiki SLC Device Installation
3
for Seq. Programming. Use to program more than one detector in sequential order.
7. If you are changing addresses, write the programmed address on the back of the device.
8. To exit press left arrow until fully exited.
151295 5-11
Page 84
Model 5700 Installation and Operation Manual
5.8.2 Hochiki SLC Devices with Dip Switches
Input and relay module addresses are set using the dip switches on the module board. The chart below shows the available addresses. For example, to select address 3, place dip switches 1 and 2 in the up position. The range of valid addresses is 1-50. 0 is an invalid address.
Figure 5-8 Hochiki SLC Device Addressing Using Dip Switches
5-12 151295
Page 85
Section 6 Programming Overview
This section of the manual is intended to give you an overview of the programming process. Please read this section of the manual carefully , especially if you are programming the control panel for the first time.
The JumpStart feature automates many programming tasks and selects default options for the system. You will run JumpStart at least once when you are installing the system. See Section
6.1 for details. After you run JumpStart, you may need to do some additional programming
depending on your installation. Section 7 of this manual covers manual programmable options in detail.
Programming the panel can be thought of as a three part process. You must program:
System options. These are options that affect general operation of the panel (see Section
7.7 for details).
Options for input points and zones. These are primarily options that control detection behavior of devices (see Section 7.6 for details).
Options for output points and groups. This includes selecting characteristics for output groups and mapping output circuits to output groups (see Section 7.6 for details).
6.1 JumpStart Autoprogramming
The JumpStart feature allows for faster system setup. When you run JumpStart (immediately after addressing SLC devices), the system scans devices on all SLC loops and determines device type (for example, photoelectric smoke detector or heat sensor) and selects some system options based on the device type. This saves the installer from having to program options for each device. Depending on the application, the installer may need to make some changes after JumpStart completes.
See Section 6.1.3 for complete details about running JumpStart.
IMPORTANT!
JumpStart is intended to be run one time only, immediately after SLC devices have been addressed and connected. JumpStart will reset all manually programmed options to default settings. Do not run JumpStart after you have configured the system.
151295 6-1
Page 86
Model 5700 Installation and Operation Manual
7
6
6.1.1 Input Points
JumpStart will determine the number and type of input points (detectors or contact monitor modules) on each SLC loop. JumpStart assigns the correct detector type (heat, or photoelectric), so the installer does not need to edit device type for detectors. Any contact monitor modules on the system will be assigned type “Manual Pull.” The installer will need to manually change the switch type if manual pull is not correct.
JumpStart creates one zone (Zone 1) and assigns all input points to Zone 1. Zone 1 is mapped to Output Group 1. After JumpStart completes, you can re-map to configure a multiple zone/ output group system (see Section 7.4.1.3). For a general explanation of mapping, see Section
6.2.
6.1.2 Output Points
JumpStart creates three output groups and assigns output circuits as follows: Circuits 1-2:
Configured as Notification and assigned to Group 1. JumpStart automatically programs Zone 1 to activate Group 1 using constant on output.
Circuit 3 (Relay 1): Assigned to Group 124. JumpStart automatically programs Zone 1 to activate Group 124 using constant on output when a supervisory condition occurs.
Circuit 4 (Relay 2): Assigned to Group 125. JumpStart automatically programs Zone 1 to activate Group 125 using constant on output when an alarm occurs.
Addressable output points (Relay modules): All addressable relay devices will be configured as “Output Pt” (general purpose output point) and assigned to Group 1.
Note: Relay output is constant even if the zone activating the relay is programmed with an output pattern.
6.1.3 Running JumpStart
Run JumpStart immediately after addressing and connecting all input devices (detectors, pull stations, and so on) and output devices (notification appliances, relays, and so on).
Note: To install a few devices manually after running JumpStart, see Section 7.
To run JumpStart:
1. Press to view the Main Menu.
2. Select for Program Menu.
3. From the next menu, select for JumpStart.
4. When the message “W ARNING Will DELETE all system options” displays, select Yes. A series of messages displays for the next several seconds. JumpStart scans the SLC loops for devices and can take several minutes, depending on the number of devices attached.
6-2 151295
Page 87
Programming Overview
1
1
223
3
211
212
121
2
4
4
5. When the message “Configuring System Done” displays, press any key to continue.
6. Select one of the following options from the menu that displays.
- Review System Press if you need to review the JumpStart configuration.
- Repeat JumpStart Press if you need to rerun JumpStart for any reason.
- Accept Configuration 1. If you are ready to make the JumpStar t c onfiguration permanent, select .
2. The system will ask you if the installation contains duct detectors. If there are none, select for No and skip to S tep 8. If the system co ntains duct detec­tors, select for Yes and continue with Step 3.
3. From the list, select the SLC device that contains the duct detectors.
4. The first photoelectric detector on the system will display. Select for DUCT and for NonDUCT.
5. Press to select the next detector. Select for DUCT and for Non­DUCT. Continue until all duct detectors have been selected. (Note: You can
move backwards through the list with .)
6. When you reach the last detector on this device, press .
7. The system will ask you if there are more duct detectors in the system. If there are, select for Yes and repeat from Step 3. If there are no more duct
detectors, select for No and continue with Step 8.
8. The system will restart in 10 seconds, or press to restart immediately. Do not select for System Diagnostics (This feature is for testing at the fac-
tory.)
9. After the system resets, it will use the new JumpStart configuration.
- Enter Programming To go directly to Program Mode to configure any devices, press . The Programming Menu appears and you can begin programming.
151295 6-3
Page 88
Model 5700 Installation and Operation Manual
6.2 Mapping Overview
This section of the manual is an overview of mapping. Details about how to select mapping options appear in the appropriate subsections in Section 7.
Mapping is an important concept with the control panel. In general terms, mapping is assigning or linking events to outputs that should activate when events occur. You do this by assigning input points to input zones, output points to output groups and then linking or mapping zones and output groups.
Figure 6-1 is a brief overview of the concept of mapping. The next several pages of the manual show these subjects in detail.
Figure 6-1 Mapping Overview
6-4 151295
Page 89
Programming Overview
6.2.1 Input Point Mapping
Input points are assigned to input zones. Any input point can be assigned to any input zone. (Input points can be assigned to one zone only . An input point can be designated as “Unused,” which means it has not been assigned to a zone.)
Figure 6-2 Input Point Assignment Example
151295 6-5
Page 90
Model 5700 Installation and Operation Manual
6.2.2 Output Circuit Mapping
Figure 6-3 is a simple example showing how to assign notification and relay output circuits to groups. For an example of a simple floor above/floor below application, see Figure 6-5.
Figure 6-3 Assigning Output Circuits to Groups (Example)
6-6 151295
Page 91
Programming Overview
6.2.3 Zone Event Mapping
There are 8 types of events that can occur in zones (see below). For each event type, you can activate up to 8 output groups and patterns. If it is necessary to map to more than 8 output groups, an output group template may be used (see Section 7.5.5 for information on output group templates). Event types are:
Manual Pull Alarm
Water Flow Alarm
Detector Alarm (heat or smoke detectors)
Aux 1 and Aux 2 Alarm (user-specified alarm types)
Pre-alarm
Supervisory
Trouble
Figure 6-4 Example of Zone Events Mapped to Output Groups and Patterns
151295 6-7
Page 92
Model 5700 Installation and Operation Manual
Figure 6-5 Example of Zone Events Mapped to Output Groups and Patterns
6-8 151295
Page 93
Programming Overview
6.2.4 Mapping LED Points
Figure 6-6 is a simple example showing how LED points are mapped to zones and output groups. Typically you would create two output groups for each zone, one for alarms and one for troubles. (LED points are available when Models 5865-3/4 and/or 5880 are used with the system.)
Figure 6-6 Example of LED Points Mapped to Output Groups
151295 6-9
(applies to Models 5865-3/4 and 5880)
Page 94
Model 5700 Installation and Operation Manual
6.3 Programming Using the 5660 Silent Knight Software Suite
You can use the 5660 Silent Knight Software Suite (SKSS) to program the control panel onsite or remotely. SKSS is an optional software package that lets you easily program the control panel using a Windows-based computer and a modem* (not sold by Silent Knight). When using SKSS, you can set up the programming options for the panel, save the options in a file, then download the file to the panel. You connect to the control panel directly using the control panel’s onboard serial port or remotely using a modem. If you need to connect to an older control panel that does not have a USB port, and your laptop does not have a serial port, use a USB to serial converter. SKSS includes an online help system and a manual. See the SKSS manual (PN 151240) for more information.
* See Section 1.3 for a list of modems that have been tested for compatibility with the control panel and SKSS.
6.4 Programming Using an Annunciator
You can program the control panel from a system annunciator, using either the control panel’s on-board annunciator or a Model 5860 Remote Annunciator.
The following subsections describe programming basics, including a description of editing keys available for programming and how to move through programming menus. Section 7 contains specific information about individual programming options.
6-10 151295
Page 95
Programming Overview
7
6.4.1 Entering / Exiting the Program Menu
To enter the Program Mode:
1. Press or to display the main menu.
2. Enter the installer code if requested.
3. Select for Program Menu.
Display reads: Initializing
Please wait . . .
The menus described in Section 7 of this manual will display . Section 7.7 of this manual is a quick reference listing all programmable options and JumpStart defaults.
To Exit Program Mode:
When you have completed working with the menus, press Left Arrow button several times until you are exited from programming mode. T wo prompts will display. The first prompt is to make sure you intended to leave the Program Menu (select Yes or No as appropriate). The second prompt is for accepting all changes. If you select No, any changes you have made since you entered the Program Menu will have no effect.
6.4.2 Moving through the Menus
Figure 6-7 shows how to move through Menu screens, using the System Options screen as an example.
Figure 6-7 Moving through Program Menu
(System Options Sub-Menu Used as an Example)
151295 6-11
Page 96
Model 5700 Installation and Operation Manual
6.4.3 Selecting Options and Entering Data
There are several ways to make programming selections using the control panel depending on which screen you are currently using. The chart below is a generic explanation.
To Press
Select from a menu. Enter the number of the option. Enter numeric data. Press the appropriate number on the annunciator. Enter text (alphanumeric data). Enter each letter individually by pressing and holding any numeric key until the
one you wish to select displays. Then press (right arrow) to select the letter.
Select from a scrolling list.
Use (up arrow) and (down arrow) to move through a list of available
options. When the option you want to select is displayed, press .
6.4.4 Editing Keys
The keys shown in Figure 6-8 are available for use when you are in the Program Menu.
Figure 6-8 Editing Keys Available from Program Menu
6-12 151295
Page 97
Programming Overview
6.5 Programming Menu Quick Reference
This section of the manual lists all Program Menu options in the order they appear on the sub­menus. Default settings are indicated in text or marked with an asterisk. The comments column provide quick information and a reference to a section (if applicable) which has more detailed information.
Menu Options/Defaults Comments
SLC Family
Module
Zone
Hochiki SK Edit Module Select Module Enter Module Name Select Class Section 7.3.1
5824-Ser/Par/IO 5860-LCD Ann
Add Module
Delete Module List of Modules Section 7.3.3 View Module List List of Modules
Edit Zone Select Zone to Edit
Add Zone Adds next available zone number. Section 7.4.2 Delete Zone
View Zone Points
5496-NAC Expand 5880-LED/IO Dev 5865-LED Annunc
Select Zone to Delete
List of all points in selected zone.
Edit Zone Name
Zone Properties
Zone Outputs
Zone Accessry Opt
Enter Name1 Section 7.4 Enter Number1 Enter Name2 Enter Number2
*1 Count 2 Count
Verification Type
Heat Temp Set 135° to 150°F
Smoke Sens
Manual Pull (MP)
Water Flow (WF)
Detector Alarm (DE)
Aux 1 (A1)
Pre-alarm (PR) Supervisory
(SU) Trouble (TR) no group Cadence 00-20 Local Zone Yes or No
Alarm Ver. PAS SNGL ILOCK DBL ILOCK
Low* Section 7.4 Medium High
(Groups 01 & 250, Pattern
00)
no groupAux 2 (A2)
(Group 249, Pattern 00)
Section 7.2
Section 7.3.2
Section 7.4
Section 7.4
Section 7.4.3
Section 7.4.4
151295 6-13
Page 98
Model 5700 Installation and Operation Manual
Menu Options/Defaults Comments
Enter Name1 Enter Number1 Enter Name2 Enter Number2
*SILENCE Silenceable NON-SIL Non-Silenceable
Auto
Silencing Options
Group Active With:
Yes No
PHOTO ION HEAT PHOT DUCT ION DUCT 2WIRE SMK SUP PHOTO LATCH
SUP ION LATCH
Unsilence SIL-INHIB Silence after inhib
SHUT­DOWN
Group Activates for all Man. Pull
Group Activates for Fire Drill
Group Activates for Aux 1
Group Activates for Aux 2
Ignore Global Cadence
Select zone
NLATCH
NLATCH
Section 7.5.1.1
Section 7.5.1 Auto Un-silenced
Section 7.5.1
delay. Section
7.5.1 Automatic
Shutdown Section 7.5.1
*No
*Yes
*No
*No
*No
Section 7.5.3
Section 7.6
Edit Group Select Group
1
Group
Add Group Section 7.5.2 Delete Group View Group Points Select Group Section 7.5.4
Edit OPG Template
Point SLC Loop Enter Pt
Select Group to Delete
Select Template Number
Group Name
Group Properties
Select Group Section 7.5.5 Include in template Select Pattern 0-20 0 = Constant. Refer to Figure 7-5
UNUSED
DETECTOR
SUP DET
6-14 151295
Page 99
Programming Overview
Menu Options/Defaults Comments
MAN_PULL
LATCH NLATCH
NLATCH
LATCH NLATCH LATCH NLATCH LATCH NLATCH LATCH NLATCH
LATCH NLATCH
Group or Zone selection will appear depending on the type is selected
Section 7.6
Section 7.6
Section 7.6
Point (cont.)
SLC Loop (cont.)
Internal Pwr and External Power
5880
5865
SWITCH
Enter Pt
RELAY
SLC LED LED No. 01–80 Select Group UNUSED B NOTIF
Select Type
Select Group or Zone Number
Edit Name Enter Name Enter Point # Select Group #
Edit Name Enter Name Enter Point # Select Group #
Edit Name Enter Name
A NOTIF
AUX PWR
NOTIF UNUSED
NOTIF UNUSED
WATERFLOW SUPERVSY LATCH
FIREDRILL SILENCE RESET PAS_ACK
ZN_AUX1
ZN_AUX2
SYS_AUX1
SYS_AUX2 DETECT SW TAMPER MAN REL
ILOCK OUTPUT PT Select Group AUX RESET AUX DOOR
Select Group CONSTANT
RESETABLE DOOR
151295 6-15
Page 100
Model 5700 Installation and Operation Manual
Menu Options/Defaults Comments
For each account (1-4), select:
Edit Account # *123456 Account # (6-digit
number, identifies account to central station) Section 7.7.1
Edit Format *Contact ID Reporting Format
(SIA, S20, Contact ID) Section 7.7.1
Y (Yes) *Yes Section 7.7.1
System Options
Edit Acct.
Reporting Accounts
Auto Test Time
Phone Lines Select Phone Line
Report Alarms
Rep. Alarm Restore
Report Troubles, Supervisories, Enable/Disable
Report Test
Report Resets
Switch attempts 3 - 5 *5 Section 7.7.2 Edit Phone #1 up to 24 digits blank Section 7.7.2 Set the Hour
Select AM/PM For each phone line (1 & 2), select: Dialing Prefix Up to 8 digits none Section 7.7.2.1 # of Answer Rings Range: 00-15 06 Number of rings
Select Dialing Option
Rotary Pulse Format
Line Monitor
Ground Start Answering Machine
Bypass
N (No) M (Must) Y (Yes) *No N (No) M (Must) Y (Yes) N (No) M (Must) Y (Yes) N (No) M (Must) Y (Yes) N (No) M (Must)
*02:00 AM Section 7.7.1.2Set the Minutes
before panel answers a call from a computer
Section 7.7.2.2 TT TT/PL TouchTone
TouchTone
PULSE Pulse dialing U = 60/40 E = 66/34 Yes No Yes = enabled No = disabled Yes = enabled No = disabled
*U
*Yes
*N = Disabled
*Y = Enabled
Touch Tone
alternating with
pulse
Section 7.7.2.3
Section 7.7.2.4
Section 7.7.2.5
Section 7.7.2.6
Section 7.7.2.7
6-16 151295
Loading...