SILENT KNIGHT IFP-2000, RPS-2000 Installation And Operation Manual

MODEL
IFP-2000/
RPS-2000
Analog/Addressable
Fire System
Installation and Operations Manual
Part Number 151430 Rev A
Adherence to the following will aid in problem-free installation with long-term reliability:
Installation Precautions - Adherence to the following will aid in problem-free installation with long-term reliability: WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood. CAUTION - System Re-acceptance T est after Software Changes: To ensure proper system operation, this product must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Re-acceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified. This system meets NFP A requirements for operation wi thin the range of 0°C-49°C (32°F-120°F) or humidity within the range of 10%-93% at 30°C (86°F) noncondensing. However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27º C/60-80º F. V erify that wir e sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage. Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered. Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits. Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, or printed circuit board location. Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal. Silent Knight fire alarm control panels contain static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment.
FACP operation and reliability depend upon proper installation. While installing a fire alarm system may make lower insurance rates possible, it is not a
substitute for fire insurance! An automatic fire alarm system - typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control with remote notification capability - can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire. Any fire alarm system may fail for a variety of reasons: Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second floor detector, for example, may not sense a first floor or basement fire. Furthermore, all types of smoke detectors, including ionization and photoelectric types, have sensing limitations. No type of smoke detector can sense every kind of fire caused by carelessness and safety hazards like smoking in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children playing with matches, or arson.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire. Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time. Rate-of-Rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment listed for service with your control panel. Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. The most common cause of fire alarm malfunctions, however, is inadequate maintenance. All devices and system wiring should be tested and maintained by professional fire alarm installers following written procedures supplied with each device. System inspection and testing should be scheduled monthly or as required by National and/or local fire codes. Adequate written records of all inspections should be kept.

Contents

Contents
Section 1
Introduction ..............................................................................................................................................1-1
1.1 Overview of Basic System ....................................................................................................................... 1-1
1.1.1 Hardware Features ............................ ................................................................................................ 1-1
1.1.2 Network System Hardware Features ................................................................................................1-2
1.1.3 Software Features ............................................................................................................................. 1-2
1.2 About this Manual .................................................................................................................................... 1-3
1.2.1 Terms Used in this Manual ............................................................................................................... 1-3
1.3 Compatible Products ................................................................................................................................ 1-4
1.4 How to Contact Silent Knight .................................................................................................................. 1-5
Section 2
Agency Listings, Approvals, and Requirements ...................................2-1
2.1 Federal Communications Commission (FCC) ......................................................................................... 2-1
2.2 Underwriters Laboratories (UL) ..............................................................................................................2-2
2.2.1 Requirements for All Installations .................................................................................................... 2-2
2.2.2 Requirements for Central Station Fire Alarm Systems .................................................................... 2-3
2.2.3 Requirements for Local Protected Fire Alarm Systems ...................................................................2-3
2.2.4 Requirements for Remote Station Protected Fire Alarm Systems - Digital Alarm Communicator Transmitter (DACT) 2-3
Section 3
Before You Begin Installing ...............................................................................................3-1
3.1 What’s in the Box? ................................................................................................................................... 3-1
3.2 Environmental Specifications .................................................................................................................. 3-1
3.3 Electrical Specifications ........................................................................................................................... 3-2
3.4 Wiring Specifications ........................................................ ....................................................................... 3-4
3.5 Board Assembly Diagram ........................................................................................................................ 3-6
3.6 Calculating Current Draw and Standby Battery ......................................................................................3-7
3.6.1 Current Draw Worksheet Requirements ................................ ........................................................... 3-7
3.6.2 Current Draw Worksheet for IDP SLC Devices ...............................................................................3-7
3.6.3 Maximum Battery Standby Load ....................................................................................................3-10
3.7 Installation Tasks Overview ................................................................................................................... 3-10
Section 4
Control Panel Installation ......................................................................................................4-1
4.1 Mounting the Control Panel Cabinet .......................................................................................................4-1
4.1.1 Preventing Water Damage ................................................................................................................4-1
4.1.2 Removing the IFP-2000 Assembly from the Housing ...................................................................... 4-1
4.1.3 Ethernet Connection ......................................................................................................................... 4-1
151430 i
Contents
4.2 AC Connection ......................................................................................................................................... 4-2
4.3 Battery Connection .................................................................................................................................. 4-3
4.3.1 Battery Accessory Cabinets .............................................................................................................. 4-4
4.3.1.1 Installing the RBB or AB-55 Accessory Cabinet and Batteries ............................................ 4-4
4.4 SBUS Wiring ........................................................................................................................................... 4-7
4.4.1 Calculating Wiring distance for SBUS modules ..............................................................................4-7
4.4.2 Wiring Configurations ............................ .......................................................................................... 4-9
4.5 Configuring SBUS Modules ..................................................................................................................4-11
4.5.1 Assigning SBUS Module IDs ......................................................................................................... 4-11
4.5.2 SBUS Bandwidth Considerations ................................................................................................... 4-12
4.6 RA-2000 Remote Annunciator Installation ........................................................................................... 4-13
4.6.1 Mounting the RA-2000 ................................................................................................................... 4-14
4.6.1.1 Flush Mounting .................................................................................................................... 4-14
4.6.1.2 Surface Mounting .................................................................................................................4-16
4.6.2 Model RA-2000 Connection to the Panel ....................................................................................... 4-17
4.7 5815XL Installation ............................................................................................................................... 4-18
4.7.1 5815XL Connection to the Panel ....................................................................................................4-19
4.8 5824 Serial/Parallel Interface Module Installation ................................................................................ 4-20
4.8.1 Selecting 5824 Options ...................................................................................................................4-21
4.9 5880 LED I/O Module ...........................................................................................................................4-23
4.9.1 5880 Board Layout ......................................................................................................................... 4-23
4.9.2 FACP Connection ........................................................................................................................... 4-24
4.9.3 LED Wiring ....................................................... ............................................................................. 4-25
4.9.4 Dry Contact Wiring ........................................................................................................................4-26
4.10 5865-3 / 5865-4 LED Annunciator Installation ..................................................................................... 4-27
4.10.1 FACP Connection ...........................................................................................................................4-28
4.10.2 5865 Mounting ................................................................................................................................4-29
4.11 Vip Module Installation ...................................... ... ................................................................................ 4-30
4.12 Telephone Connection ......................................................................................................
4.13 Flexputs
I/O Circuits ...........................................................................................................................4-31
.....................4-30
4.13.1 Conventional Notification Appliance ............................................................................................. 4-31
4.13.1.1 Regulated Class B Notification Wiring ............................................................................... 4-31
4.13.1.2 Class A Notification Wiring ...............................................................................................4-33
4.13.2 Conventional Input Switch Circuits ................................................................................................4-34
4.13.2.1 Class B Inputs ................................................. ..................................................................... 4-34
4.13.2.2 Class A Inputs ...................................................................................................................... 4-35
4.13.3 Installing 2-Wire Smoke Detectors .................................................................................................4-36
4.13.3.1 Installing 2-Wire Class B Smoke Detectors ........................................................................ 4-36
4.13.3.2 Installing 2-Wire Class A Smoke Detector .........................................................................4-37
4.13.4 Installing 4-Wire Smoke Detectors .................................................................................................4-38
4.13.4.1 Installing a Class B 4-Wire Smoke Detector ....................................................................... 4-38
4.13.4.2 Installing 4-Wire Class A Smoke Detectors ........................................................................ 4-39
4.13.5 Auxiliary Power Installation ...........................................................................................................4-40
4.13.5.1 Door Holder Power ..............................................................................................................4-40
4.13.5.2 Constant Power .................................................................................................................... 4-41
4.13.5.3 Resettable Power ........................................................................................ .......................... 4-41
4.14 On-Board Relays (Conventional) ........................................................................................................... 4-41
4.14.1 Trouble Relay ................................................................................................................................. 4-41
4.14.2 Programmable Relays ..................................................................................................................... 4-41
4.15 Remote Station Applications .................................................................................................................4-42
4.15.1 Keltron Model 3158 Installation ..................................................................................................... 4-42
4.15.2 City Box Connection Using the 5220 Module ................................................................................4-44
4.15.3 Using the IDP-Relay Addressable Relay Module for City box Connecti on .................................. 4-45
4.15.4 NFPA 72 Polarity Reversal .............................................................................................................4-46
151430 ii
Contents
4.15.4.1 Using the 5220 Module ........................................................................................................4-46
4.15.4.2 Using the 7644 Module ........................................................................................................4-47
4.15.5 Transmitter Activated by Dry Contacts .......................................................................................... 4-48
Section 5
Networking ................................................................................................................................................ 5-1
5.1 Network System Hardware Features ........................................................................................................ 5-1
5.1.1 Networked Sites ................................................................................................................................ 5-1
5.1.2 Wiring Options to Connect Networked Panels .................................................................................5-1
5.2 Model RPS-2000 ...................................................................................................................................... 5-1
5.3 Direct Connect Wiring Option ................................................................................................................. 5-2
5.3.1 Installing using Direct Connection within a Site: .............................................................................5-2
5.4 Repeater Wiring Options ......................................................................................................................... 5-4
5.4.1 Network Repeater Types ...................................... ............................................................................ 5-5
5.4.2 Network Repeater Installation .......................................................................................................... 5-6
5.4.2.1 Network Repeater Cable Requirements ................................................................................. 5-8
5.4.2.2 Unshielded Twisted Pair Wiring between Multiple Panels ................................................ ...5-8
5.4.2.3 Fiber Optic Repeater Wiring ..................................................................................................5-9
5.4.2.4 Fiber Optic and Twisted Pair Repeater Wiring between Multiple Panels ...........................5-10
5.5 Using Both Repeaters and Direct Connect Wiring on a Networked System ......................................... 5-11
5.5.1 Setting the Network Terminators at Panel DIP Switches and Repeater Jumpers ........................... 5-12
5.6 Setting the Network ID for each Panel ..................................................................................................5-13
Section 6
Network Management ................................................................................................................. 6-1
6.1 Network Diagnostics ................................................................................................................................6-1
6.1.1 Ping Panel .........................................................................................................................................6-1
6.1.2 Network Status .................................................................................................................................. 6-1
6.2 Network Programming ............................................................................................................................. 6-1
6.2.1 Learn Network ..................................................................................................................................6-1
6.2.2 Edit Network ............................. ........................................................................................................6-2
6.2.2.1 Edit Panel ................................................................. ... ...........................................................6-2
6.2.2.2 Edit Site Name ....................................................................................................................... 6-3
6.2.3 Edit Panel ID ..................................................................................................................................... 6-3
6.2.4 Computer Account ............................................................................................................................ 6-3
6.2.5 Access Codes ....................................................................................................................................6-4
6.2.5.1 Edit Name .............................. ................................................................................................6-6
6.2.5.2 Edit Access Code ................................................................................................................... 6-6
6.2.5.3 Panel Functions ...................................................................................................................... 6-6
6.2.6 Dialer ................................................................................................................................................6-6
6.2.6.1 Dialer Assignments ................................................................................................................ 6-7
6.2.6.2 Dialer Miscellaneous .............................................................................................................. 6-7
6.2.6.3 Receiver Configuration ..........................................................................................................6-7
6.2.6.4 Dialer Report Table ................................................................................................................6-7
6.3 Network Management Quick Reference .................................................................................................. 6-8
Section 7
IDP SLC Device Install ............................................................................................................... 7-1
151430 iii
Contents
7.1 List of IDP SLC Devices ......................................................................................................................... 7-1
7.2 Maximum Number of Devices ................................................................................................................. 7-2
7.3 Wiring Requirements for SLC Devices ..................................... .............................................................. 7-2
7.3.1 Wiring 5815XL in Style 4 (Class B) Configuration ......................................................................... 7-2
7.3.2 Wiring 5815XL in Style 6 & 7 (Class A) Configuration .................................................................. 7-4
7.4 Wiring IDP SLC Detectors ...................................................................................................................... 7-5
7.5 Addressing IDP SLC Devices .................................................................................................................. 7-6
Section 8
Programming Overview ...........................................................................................................8-1
8.1 JumpStart AutoProgramming .................................................................................................................. 8-1
8.1.1 Input Points ....................................................................................................................................... 8-1
8.1.2 Output Points ..................................................... ............................................................................... 8-2
8.1.3 Running JumpStart AutoProgramming ............................................................................................8-2
8.2 Mapping Overview ..................................................................................................................................8-4
8.2.1 Input Point Mapping .........................................................................................................................8-5
8.2.2 Output Circuit Mapping ............................................................................................. ....................... 8-6
8.2.3 Event Mapping ............................................................. .................................................................... 8-7
8.2.4 Mapping LED Points ...................................................................................................................... 8-11
8.2.5 Mapping LED Points for a Networked System ..............................................................................8-12
8.3 Programming Using the 5655 Silent Knight Software Suite-2 .............................................................. 8-13
8.4 Programming Using an Annunciator ....................................................... ... ...........................................8-13
8.4.1 Entering & Exiting Panel Programming ......................................................................................... 8-13
8.4.1.1 Moving through the Menus ..................................................................................................8-13
8.4.1.2 Selecting Options and Entering Data ................................................................................... 8-14
8.4.1.3 Editing Keys ......................................................................................................................... 8-15
8.5 Programming Menu Quick Reference ...................................................................................................8-16
Section 9
Programming ......................................................................................................................................... 9-1
9.1 UL 864 Programming Requirements .......................................................................................................9-1
9.2 Modules ....................................................................................................................................................9-2
9.2.1 Edit Modules .....................................................................................................................................9-2
9.2.1.1 Naming Modules .............................................................. ......................................................9-2
9.2.1.2 Setting the 5815XL Wiring Class .......................................................................................... 9-3
9.2.2 Adding a Module ............................................ .................................................................................. 9-4
9.2.3 Deleting a Module .................................... ........................................................................................ 9-4
9.2.4 View Module List ............................. .............................................................. ..................................9-5
9.3 Zone .........................................................................................................................................................9-5
9.3.1 Edit Zone ........................................... .............................................................. .................................. 9-5
9.3.1.1 Edit Zone Name ...................................... .............................................................. ... .............. 9-5
9.3.1.2 Edit Zone Properties ...............................................................................................................9-6
9.3.1.3 Zone Accessory Options ........................................................................................................9-8
9.3.2 Add Zone ..................................................... ..................................................................................... 9-8
9.3.3 Delete Zone ......................... ... .............................................................. .............................................9-9
9.3.4 View Zone Points ....................................................................................................... ....................... 9-9
9.4 Group ..................................................................................................................................................... 9-10
9.4.1 Edit Group ............................................ .............................................................. ............................. 9-10
9.4.1.1 Edit Group Name ................................................................................................................. 9-10
151430 iv
Contents
9.4.1.2 Edit Group Properties ......................................... ......................................................... ......... 9-11
9.4.2 Add Group ...................................................... ................................................................................ 9-12
9.4.3 Delete Group ...................................................................................................................................9-13
9.4.4 View Group Points .......................................................................................................................... 9-14
9.5 Point ....................................................................................................................................................... 9-15
9.5.1 Point Programming For 5815XL Module .......................................................................................9-15
9.5.2 Point Programming For Internal or External Power Module (RPS-1000) .....................................9-18
9.5.3 Point Programming For 5880, and 5865 Modules .......................................................................... 9-20
9.5.3.1 Assigning a Name to Points .................................................................................................9-21
9.5.4 Point Programming For VIP-50/VIP-CE4 ......................................................................................9-21
9.6 System Options ......................................................................................................................................9-23
9.6.1 Auto Test Time ............................................................................................................................... 9-23
9.6.2 Phone Lines .....................................................................................................................................9-23
9.6.2.1 Dialing Prefix ....................................................................................................................... 9-24
9.6.2.2 Number of Answer Rings ....................................................................................................9-25
9.6.2.3 Dial Option (TouchTone or Pulse) .......................................................................................9-25
9.6.2.4 Rotary Format ...................................................................................................................... 9-25
9.6.2.5 Line Monitor ........................................................................................................................ 9-25
9.6.2.6 Answering Machine Bypass ........................................... ......................................................9-26
9.6.2.7 Phone Line Unused ..............................................................................................................9-26
9.6.3 Daytime/Nighttime Sensitivity ....................................................................................................... 9-26
9.6.4 Holiday Days ..................................................... ............................................................................. 9-28
9.6.5 Miscellaneous Options 1 ................................................................................................................. 9-28
9.6.5.1 Water Flow Delay ............................. ................................................................................... 9-28
9.6.5.2 Low AC Report Time ..........................................................................................................9-30
9.6.5.3 Automatic Daylight Savings Adjustment ............................................................................ 9-30
9.6.5.4 Clock Display Format (AM/PM or Military) .......................................................................9-30
9.6.5.5 Change AC Line Frequency .................................................................................................9-31
9.6.6 Miscellaneous Options 2 ................................................................................................................. 9-32
9.6.6.1 Strobes Active when Silenced ..............................................................................................9-32
9.6.6.2 Auto Display Oldest Event .................................................................................................. 9-32
9.6.6.3 IFP-RPT Repeater Installed .................................. ...............................................................9-32
9.6.6.4 Both Ports Used ...................................................................................................................9-33
9.6.7 Miscellaneous Options 3 ................................................................................................................. 9-33
9.6.7.1 Alarm Verification Time ......................................................................................................9-33
9.6.7.2 Daylight Saving Time Start and End ................................................................................... 9-34
9.6.8 Edit Banner Message ...................................................................................................................... 9-35
9.6.9 Edit Voice Commands .................................................................................................................... 9-36
9.7 JumpStart Autoprogramming ................................................................................................................. 9-36
9.8 Restore Defaults ....................................... .............................................................................................. 9-37
9.9 VIP-VCM Maintenance .........................................................................................................................9-38
9.9.1 PC Connection ........................................................................................ ........................................9-38
9.9.2 Local Recording .............................................................................................................................. 9-38
Section 10
System Operation ..........................................................................................................................10-1
10.1 User and Installer Default Codes ........................................................................................................... 10-1
10.2 Annunciator Description ................................................. ....................................................................... 10-2
10.2.1 LCD Displays ................................................................................................................................. 10-3
10.2.2 Banner ............................................................................................................................................. 10-3
10.3 Menu System ..........................................................................................................................................10-4
151430 v
Contents
10.3.1 Main Menu Overview ..................................................................................................................... 10-4
10.3.2 Using the Menus ............................................. ... ............................................................................. 10-5
10.4 Basic Operation ...................................................................................................................................... 10-5
10.4.1 Setting Time and Date ....................................................................................................................10-5
10.4.2 Disable / Enable a Point ............................................. ..................................................................... 10-5
10.4.3 Disable / Enable NACs by Group ................................................................................................... 10-5
10.4.4 View Event History ...................................................... .................................................................. 10-6
10.4.4.1 To clear the event history ..................................................................................................... 10-6
10.4.5 Conduct a Fire Drill ........................................................................................................................ 10-6
10.4.6 Conduct an Indicator Test ............................................................................................................... 10-6
10.4.7 Conduct a Walk Test ....................................................................................................................... 10-7
10.4.8 Conduct a Dialer Test ..................................................................................................................... 10-7
10.4.9 Silence Alarms or Troubles ............................................................................................................10-8
10.4.10 Reset alarms ................................................................ ... ...............................................................10-8
10.4.11 Check Detector Sensitivity Through Point Status ........................................................................ 10-8
10.4.12 View Status of a Point .................................................................................................................. 10-9
10.4.13 View Alarms or Troubles ............................................................................................................. 10-9
10.4.14 View System Information ............................................................................................................. 10-9
10.4.15 Communicating with a Remote Computer ................................................................................. 10-10
10.5 Operation Mode Behavior .................................................................................................................... 10-11

10.6 Multi-Site Annunciator and Multi-Site user Access 10-14

10.7 Releasing Operations ................................................... ........................................................................ 10-15
10.7.1 Single Interlock Zone Releasing ...................................... ............................................................. 10-16
10.7.2 Double Interlock Zone Releasing .................................................................................................10-17
10.8 Smoke Alarm Verification ................................................................................................................... 10-18
10.9 Function Keys ..................................................................................................................................... 10-18
10.9.1 Recording an F-Key macro: .................................. ........................................................................ 10-18
10.9.2 Aborting an F-Key macro recording session: ............................................................................... 10-19
10.9.3 Erasing an F-Key macro: ................................................. .............................................................10-19
10.9.4 Using a recorded F-Key macro: ....................................................................................................10-19
Section 11
Reporting ................................................................................................................................................... 11-1
11.1 Receivers Compatible with the Control Panel .......................................................................................11-1
11.2 Reporting Formats Table .......................................................................................................................11-1
11.3 SIA - Intelliknight / IFP-2000 Panels PI Modifier Reporting: ........................................................ ....... 11-6
11.4 SIA – IFP-2000 Panel Dialer: ................................................................................................................11-7
Section 12
Testing and Troubleshooting ......................................................................................... 12-1
12.1 Troubleshooting .....................................................................................................................................12-1
12.2 Common Problems ................................................................................................................................. 12-1
12.2.1 Periodic Testing And Maintenance .................................................................................................12-2
12.2.2 Event History .................................................................................................................................. 12-3
12.3 Built-in Troubleshooting and Testing Tools ..........................................................................................12-3
12.3.1 SLC Device Locator .......................................................................................................................12-3
12.3.2 SLC Multi Device Locator ............................................................................................................. 12-4
12.3.3 I/O Point Control ............................................................................................................................ 12-5
151430 vi
Contents
12.3.4 Earth Fault Resistance .................................................................................................................... 12-6
Section 13
Installation Records ....................................................................................................................13-1
13.1 Detector and Module Point Record ........................................................................................................13-1
13.2 Conventional Output Point Record ........................................................................................................13-6
Appendix A
Compatible Devices ....................................................................................................................14-1
Appendix B
Special Characters Lists .........................................................................................................B-1

Silent Knight Fire Product Warranty and Return Policy

151430 vii
IFP-2000 Installation Manual
viii
Introduction

Section 1 Introduction

The IFP-2000 Fire Alarm Control/Communicator is an analog addressable fire control system that meets the requirements of UL 864. The RPS-2000 is used in a networked system where there is at least one IFP-2000 in the system. The RPS-2000 is the same as the IFP-2000 without the display. When using the RPS-2000 as a stand alone local unit, one RA-2000 must be connected, and the RA-2000 must be wired in conduit within 20’ of the RPS-2000.

1.1 Overview of Basic System

The IFP-2000 base system is packaged as an assembled stack of 3 circuit boards mounted to an aluminum housing.

1.1.1 Hardware Features

The basic IFP-2000 panel contains one built in signaling line circuit (SLC), which can
support up to 159 IDP sensors and 159 IDP modules. Additional SLC loops can be added using the model 5815XL SLC expander to increase overall point capacity to a maximum of 636 points. The SLC(s) supports Intelligent Device Protocol (IDP) analog addressable sensors and modules.
Each SLC supports 159 IDP sensors and 159 IDP modules to a maximum of 636 points
per IFP-2000 Control panel.
9.0A of output power is available through 8 sets of terminals for notification and auxiliary
applications. Each circuit is power limited per UL 864 and can source up to 3.0A (total output power must not exceed 9.0A). When used as a constant auxiliary power, must not exceed 6.0A.
Built-in dual phone line, digital alarm communicator/transmitter (DACT).
Reports events to central station by point or by zone.
UL Listed for pre-action and deluge releasing systems.
Dedicated Form C trouble relay and two general purpose Form C programmable relays.
Can be used with Model RA-2000 Remote Annunciators (sold separately).
Supports the 5865-3, 5865-4, and 5880 LED annunciator. See sections 4.9 and 4.10 for
additional information on these models.
Printing of event log available through the Model 5824 Serial/Parallel Printer Interface
Module (sold separately).
151430 1-1
IFP-2000 Installation Manual
Supports conventional 2-wire & 4-wire detectors using the 8 Flexput™ circuits or SLC
zone modules.
999 software zones, 999 output groups.
Add 4 notification/auxiliary power circuits with each 5496 Intelligent Power Module.
Add 6 Flexput™ circuits with each RPS-1000 Remote Power Supply.
Interconnection capability for up to 8 panels.

1.1.2 Network System Hardware Features

Up to 8 IFP-2000 panels can be connected within a networked system providing a
maximum addressable point capacity of 5,088.
The networked system can be configured to emulate a large virtual system or can be
segmented into separate sites for multiple building applications.
Each building is referred to as a “site”. All panels in a site operate as a single panel.
Panels can be interconnected using a BUS or CLASS A (style 7) topology.
Panels can be connected cost effectively via shielded twisted pair copper wire within
conduit when the panels are located no more than 20 feet apart and within the same room.
Panels separated by more than 20 feet or located in multiple buildings use IFP-RPT
network repeater hardware to provide up to 3000 ft. of separation with twisted pair copper wire or up to 8dB loss of signal separation for fiber optic cable. All 3 methods of panel connectivity can be used within the same networked system.
The network architecture provides true peer to peer capability allowing network
survivability for all hardware that remains operational in the event of partial system failure.

1.1.3 Software Features

Advanced analog smoke detector features:
Three sensitivity settings (high, medium, low) Automatic drift compensation Maintenance alert region Point status eliminates calibrated smoke test requirements for NFPA 72 Automatic day/night sensitivity adjustment
“JumpStart AutoProgramming” feature for easy programming
Non-volatile event history stores 1000 events per panel
A choice of output patterns available for notification outputs, including ANSI 3.41
temporal signal
®
Built-in synchronization appliance support for AMSECO, Gentex
Wheelock®.
1-2 151430
, System Sensor®, and
Introduction

1.2 About this Manual

This manual is intended to be a complete reference for all installation and operation tasks for the IFP-2000 and RPS-2000. Please let us know if the manual does not meet your needs in any way. We value your feedback!

1.2.1 Terms Used in this Manual

The following terminology is used with the above mentioned control panels:
Table 1-1 Manual Terminology
Term Description
SLC Signaling line circuit Module The term module is used for all hardware devices except for SLC
addressable devices and notification appliances. This includes the IFP­2000/RPS-2000 panels itself and the built-in power supply. It also refers to any (optional) 5815XL SLC expansion modules.
Input Point An addressable sensing device, such as a smoke or heat detector or a contact
monitor device. Input Zone A protected area made up of input points. Output Point
(or Output Circuit) Group (or “Output Group”) A group of output points. Operating characteristics are common to all
Mapping Mapping is the process of specifying which outputs are activated when
Networking Up to 8 panels can be networked to sites that act like one panel.
A notification point or circuit for notification appliances. Relay circuits and
auxiliary power circuits are also considered output points.
output points in the group.
certain events occur in the system. Section 8.2 explains mapping in detail.
151430 1-3
IFP-2000 Installation Manual

1.3 Compatible Products

Table 1-1 lists the products available from Silent Knight for use with the IFP-2000.
Table 1-2: IFP-2000 Compatible Products
Ty pe of
Device
IDP
Addressable
SLC Devices
Other
Modules
Misc. 7860 Telephone Cord RJ31X cord for connecting phone line to the IFP-2000.
See Section 7.1 for a list of compatible devices.
5815XL SLC Expander Each 5815XL allows up to 159 IPD sensors and 159 IDP modules to be added to the system.
5824 Serial/Parallel Printer Interface Module
RPS-1000 Intelligent Power Module
5496 Intelligent Power Module
RA-2000 Remote Fire Alarm Annunciator
5865-3 and 5865-4 LED Annunciator
5880 LED I/O Module Driver for up to 40 LEDs. Interfaces with customized annunciator boards. In addition the
5883 General Purpose Relay Module
VIP-VCM Voice Control Module used with the IFP-2000VIP. Refer to the VIP-Series VIP-SW16 16 switch expander with the IFP-2000VIP. VIP-50 50 watt audio amplifier VIP-CE4 Provides four additional audio circuits for the VIP-50 VIP-RM2000 Remote Microphone used with the IFP-2000VIP.
Silent Knight Software Suite (SKSS-2)
RBB Remote Battery Box for mounting backup batteries up to 35AH that are too large to fit into
AB-55 Remote Battery Box for mounting backup batteries up to 55AH that are too large to fit into
Model Description
The number of 5815XLs that can be added to the system is limited only by the maximum number of SBUS devices. However the maximum point count is limited to 636 per panel. This allows the installer to distribute the 636 points on more than two SLC loops and also allows all 636 points to be all sensors or all modules or any combination of sensors and modules.
Allows a printer to be attached for the on-site event logging. Maximum of two 5824s per control panel Provides additional power, six Flexput™ circuits, and two Form C relays. See Model RPS-
1000 Installation Instructions P/N 151024. Provides four additional Notification Appliance Circuits/Auxiliary power.
Same operation, similar appearance as on-board annunciator.
LED annunciator can display up to 30 LEDs (15 red and 15 yellow). 5865-4 has key switches for silence and reset, and a system trouble LED.
5880 has eight generic switch input points. Provides 10 Form C relays. Designed to be driven by the 5880. Up to four, 5883s can be
used with each 5880 module.
For communication and panel programming with a Windows-based computer and *modem (not sold by Silent Knight, see Table 1-3 for compatible modems). Enables remote viewing of detector status and event history.
the main control panel cabinet. Dimensions: 16" W x 10" H x 6" D (40.64 cm W x 25.4 cm H x 15.24 cm D)
the main control panel cabinet. Dimensions: 20" W x 12" H x 7.5" D (50.8 cm W x 30.48 cm H x 19.05 cm D)
Installation Manual P/N 151286 for more information on these accessories. VIP series is not FM approved for use with IFP-2000
1-4 151430
Introduction
The following modems have been tested by Silent Knight for compatibility with the Silent Knight Software Suite software packages:
Table 1-3: Compatible Modems
Manufacturer Model
US Robotics 28.8
LifeStyle
Motorola
MultiTech MT19321ZDX
28.8, 3400 series Premier 33.6

1.4 How to Contact Silent Knight

If you have a question or encounter a problem not covered in this manual, contact Silent Knight Technical Support at 800-328-0103 or 763-493-6455. To order parts, contact Silent Knight Sales at 800-446-6444 or 763-493-6435 in Minnesota.
Flexput™ is a trademark of Silent Knight.
151430 1-5
IFP-2000 Installation Manual
Limitations of Fire Alarm Systems
Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer’s recommendations, State and local codes, and the recommendations contained in Guide for the Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off or give early warning in as many as 35% of all fires. While fire alarm systems are designed to provide warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons. For example:
Particles of combustion or smoke from a developing fire may not reach the sensing chambers of smoke detectors because:
Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
Smoke particles may become cold, stratify , and not reach the ceiling or upper walls where detectors are located.
Smoke particles may be blown away from detectors by air outlets Smoke particles may be drawn into air returns before reaching the detector.
In general, smoke detectors on one level of a structure cannot be expected to sense fires developing on another level.
The amount of smoke present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors are subject to false alarms and nuisance alarms and may have been disconnected by users. For example, a smoke detector located in or near a kitchen may go into nuisance alarm during normal operation of kitchen appliances. In addition, dusty or steamy environments may cause a smoke detector to falsely alarm. If the location of a smoke detector causes an abundance of false alarms or nuisance alarms, do not disconnect the smoke detector; call a professional to analyze the situation and recommend a solution.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially within bedrooms), smoking in bed, violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and are designed to alarm only when
1-6 151430
Introduction
heat on their sensors increases at a predetermined rate or reaches a predetermined level. Heat detectors are designed to protect property, not life.
Warning devices (including horns, sirens, and bells) may not alert people or wake up sleepers who are located on the other side of closed or partially open doors. A warning device that activates on a different floor or level of a dwelling or structure is less likely to awaken or alert people. Even persons who are awake may not notice the warning if the alarm is muffled by noise from a stereo, radio, air conditioner or other appliance, or by passing traffic. Audible warning devices may not alert the hearing-impaired (strobes or other devices should be provided to warn these people). Any warning device may fail to alert people with a disability, deep sleepers, people who have recently used alcohol or drugs, or people on medication or sleeping pills.
Please note that: i) Strobes can, under certain circumstances, cause seizures in people with conditions
such as epilepsy.
ii) Studies have shown that certain people, even when they hear a fire alarm signal, do not
respond or comprehend the meaning of the signal. It is the property owner’s responsi­bility to conduct fire drills and other training exercises to make people aware of fire alarm signals and instruct on the proper reaction to alarm signals.
iii) In rare instances, the sounding of a warning device can cause temporary or permanent
hearing loss.
Telephone lines needed to transmit alarm signals from a premises to a central station may be out of service or temporarily out of service. For added protection against telephone line failure, backup radio transmission systems are recommended.
System components, though designed to last many years, can fail at any time. As a precautionary measure, it is recommended that smoke detectors be checked, maintained, and replaced per manufacturer’s recommendations.
System components will not work without electrical power. If system batteries are not serviced or replaced regularly , they may not provide battery backup when AC power fails.
Environments with high air velocity or that are dusty or dirty require more frequent maintenance.
In general, fire alarm systems and devices will not work without power and will not function properly unless they are maintained and tested regularly.
While installing a fire alarm system may make the owner eligible for a lower insurance rate, an alarm system is not a substitute for insurance.
Property owners should continue to act prudently in protecting the premises and the people in their premises and should properly insure life and property and buy sufficient amounts of liability insurance to meet their needs.
151430 1-7
IFP-2000 Installation Manual
Requirements and recommendations for proper use of fire alarm systems in­cluding smoke detectors and other fire alarm devices:
Early fire detection is best achieved by the installation and maintenance of fire detection equipment in all rooms and areas of the house or building in accordance with the requirements and recommendations of the current edition of the National Fire Protection Association Standard 72, National Fire Alarm Code (NFPA 72), the manufacturer’s recommendations, State and local codes and the recommendations contained in Guide for the Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. For specific requirements, check with the local Authority Having Jurisdiction (ex. Fire Chief) for fire protection systems.
Requirements and Recommendations include:
Smoke Detectors shall be installed in sleeping rooms in new construction and it is
recommended that they shall also be installed in sleeping rooms in existing construction.
It is recommended that more than one smoke detector shall be installed in a hallway if it is
more than 30 feet long.
It is recommended that there shall never be less then two smoke detectors per apartment or
residence.
It is recommended that smoke detectors be located in any room where an alarm control is
located, or in any room where alarm control connections to an AC source or phone lines are made. If detectors are not so located, a fire within the room could prevent the control from reporting a fire.
All fire alarm systems require notification devices, including sirens, bells, horns, and/or
strobes. In residential applications, each automatic alarm initiating device when activated shall cause the operation of an alarm notification device that shall be clearly audible in all bedrooms over ambient or background noise levels (at least 15dB above noise) with all intervening doors closed.
It is recommended that a smoke detector with an integral sounder (smoke alarm) be
located in every bedroom and an additional notification device be located on each level of a residence.
To keep your fire alarm system in excellent working order, ongoing maintenance is
required per the manufacturer’s recommendations and UL and NFPA standards. At a minimum the requirements of Chapter 7 of NFPA 72 shall be followed. A maintenance agreement should be arranged through the local manufacturer’s representative. Maintenance should be performed annually by authorized personnel only.
The most common cause of an alarm system not functioning when a fire occurs is
inadequate maintenance. As such, the alarm system should be tested weekly to make sure all sensors and transmitters are working properly.
1-8 151430
Introduction
SURVIVABILITY:
Per the National Fire Alarm Code, NFPA 72, all circuits necessary for the operation of the notification appliances shall be protected until they enter the evacuation signaling zone that they serve. Any of the following methods shall be considered acceptable as meeting these requirements:
1) A 2-hour rated cable or cable system
2) A 2-hour rated enclosure
3) Performance alternatives approved by Authority Having Jurisdiction
151430 1-9
IFP-2000 Installation Manual
1-10 151430
Agency Listings, Approvals, and Requirements

Section 2 Agency Listings, Approvals, and Requirements

2.1 Federal Communications Commission (FCC)

1. The following information must be provided to the telephone company before the IFP-
2000 can be connected to the phone lines:
A Manufacturer: Silent Knight B Model Number: IFP-2000 and IFP-2000HV C FCC registration number: AC6AL11B6820
Ringer equivalence: 0.8B D Type of jack: RJ31X E Facility Interface Codes: Loop Start: 02LS2 F Service Order Code: 9.0F
This equipment complies with Part 68 of the FCC rules and the requirements adopted by ACTA. On the inside cover of this equipment is a label that contains, among other information, a product identifier. If requested, this information must be provided to the telephone company.
A plug and jack used to connect this equipment to the premises wiring and telephone network must comply with the applicable FCC Part 68 rules and requirements adopted by the ACTA. A compliant telephone cord (not provided) and modular jack must be utilized with this product. It is designed to be used with a modular jack that is also compliant.
The REN (ringer equivalence number) provided on this installation sheet is used to determine the number of devices that may be connected to the public switched telephone network. This number must not exceed 5.0. Since this product has an REN of 1.0, the number of devices is limited. The REN number is imbedded in the FCC registration number as 10B.
If the IFP-2000/IFP-2000HV causes harm to the telephone network, the telephone company will notify you in advance that the temporarily discontinuance of service may be required. But if advance notice is not practical, the telephone company will notify the customer as soon as possible. Also, you will be advised of your right to file a complaint with the FCC if you believe it is necessary.
The telephone company may make changes in its facilities, equipment, operations or procedures that could affect the operation of the equipment. If this happens the telephone company will provide advance notice in order for you to make necessary modifications to maintain uninterrupted service.
If trouble is experienced with the IFP-2000/IFP-2000HV, for repair or warranty information, please contact Silent Knight at 1-800-328-0103 or www.silentknight.com. If the equipment is causing harm to the telephone network, the telephone company may request that you disconnect the IFP-2000/IFP-2000HV until the problem has been resolved.
151430 2-1
IFP-2000 Installation Manual
This product cannot be adjusted or repaired in the field. It must be returned to the factory for service.
This equipment is not designed for use with party line service. Connection to party line service is subject to state tariffs. You may contact the state public utility commission, public service commission or corporation commission for information.
Since the IFP-2000/IFP-2000HV is a commercial fire alarm panel, it must be connected upstream of all other equipment utilizing the phone lines. If you have questions about the installation, contact your telephone company or a qualified installer.
Warning
This device has been verified to comply with FCC Rules Part 15. Operation is subject to the following conditions: (1) This device may not cause radio interference, and (2) This device must accept any interference received, including interference that may cause undesired operation.

2.2 Underwriters Laboratories (UL)

2.2.1 Requirements for All Installations

General requirements are described in this section. When installing an individual device, refer to the specific section of the manual for additional requirements. The following subsections list specific requirements for each type of installation (for example, Central Station Fire Alarm systems, Local Protected Fire Alarm systems, and so on). See Section 10.7 for information on releasing operation.
1. All field wiring must be installed in accordance with NFPA 70 National Electric Code.
2. Use the addressable smoke detectors specified in Section 7.1 (IDP devices) of this manual and or conventional detectors listed in the compatibility chart
3. Use UL listed notification appliances compatible with the IFP-2000 from those specified in the Appendix at the back of this manual.
4. A full system checkout must be performed any time the panel is programmed.
2-2 151430
Agency Listings, Approvals, and Requirements
Restricted Options:
The loss of AC signal is defaulted to 3 hours however the system allows settings from 0 ­30 hours. For UL certified installations this number must be set from 1 to 3 hours.
The system allows the use of non-latching spot type smoke detectors. This feature may not be used in commercial applications whereby a general alarm is sounded. It is intended for elevator recall, door holding applications, and hotel/motel room applications.
The system allows the Alarm Verification confirmation time to be set from 1 to 255 sec­onds. For UL certified installations the setting must be a minimum of 60 seconds.
Call forwarding shall not be used.
When two count is used detector spacing shall be cut in half, you shall not use the alarm verification feature, and no delay shall be used.
P.A.S feature shall be used only with automatic detectors.
2.2.2 Requirements for Central Station Fire Alarm
Systems
1. Use both phone lines. Enable phone line monitors for both lines.
2. You must program a phone number and a test time so that the IFP-2000 sends an auto­matic daily test to the central station.
3. The AC Loss Hours option must be set from 1-3 hours.
2.2.3 Requirements for Local Protected Fire Alarm
Systems
At least one UL listed supervised notification appliance must be used.
2.2.4 Requirements for Remote Station Protected Fire
Alarm Systems - Digital Alarm Communicator Transmitter (DACT)
1. Do not exceed the current load restrictions shown in Section 3.6.
2. The AC Loss Hours option must be set from 1-3 hours for UL installations.
151430 2-3
IFP-2000 Installation Manual
2-4 151430
Before You Begin Installing

Section 3 Before You Begin Installing

This section of the manual is intended to help you plan your tasks to facilitate a smooth installation. Please read this section thoroughly, especially if you are installing a IFP-2000 or RPS-2000 panel for the first time.

3.1 What’s in the Box?

The IFP-2000 or RPS-2000 ships with the following hardware:
A cabinet with all hardware assembled
Two keys for the front door
Ten 4.7K ohm end-of-line resistors
A battery cable for batteries wired in series

3.2 Environmental Specifications

It is important to protect the IFP-2000 control panel from water. To prevent water damage, the following conditions should be AVOIDED when installing the units:
Intended for indoor use in dry locations only
Do not mount directly on exterior walls, especially masonry walls (condensation)
Do not mount directly on exterior walls below grade (condensation)
Protect from plumbing leaks
Protect from splash caused by sprinkler system inspection ports
Do not mount in areas with humidity-generating equipment (such as dryers, production machinery)
When selecting a location to mount the IFP-2000 control panel, the unit should be mounted where it will NOT be exposed to temperatures outside the range of 0°C-49°C (32°F-120°F) or humidity not exceeding 93% noncondensing.
151430 3-1
IFP-2000 Installation Manual

3.3 Electrical Specifications

Terminal Label Description Rating
Voltage Current
B AC input (hot)
G Earth ground N/A N/A N/A
W AC input (neutral)
X
*I/O 1 Flexput™ Circuits 24 VDC
O
X
*I/O 2 Flexput™ Circuits 24 VDC
O
X
*I/O 3 Flexput™ Circuits 24 VDC
O
X
*I/O 4 Flexput™ Circuits 24 VDC
O
X
*I/O 5 Flexput™ Circuits 24 VDC
O
X
*I/O 6 Flexput™ Circuits 24 VDC
O
X
*I/O 5 Flexput™ Circuits 24 VDC
O
X
*I/O 8 Flexput™ Circuits 24 VDC
O B
A +
-
SBUS1 OUT
SBUS communication 5 VDC 100 mA
SBUS power 24 VDC 1.0 A
120/240 VAC, 50/60 Hz
120/240 VAC, 50/60 Hz
5A for the IFP-2000,
2.5A for the IFP-2000HV
5A for the IFP-2000,
2.5A for the IFP-2000HV
3.0 Amp Notification and Aux power Circuits
100 mA for initiation circuits
3.0 Amp Notification and Aux power Circuits
100 mA for initiation circuits
3.0 Amp Notification and Aux power Circuits
100 mA for initiation circuits
3.0 Amp Notification and Aux power Circuits
100 mA for initiation circuits
3.0 Amp Notification and Aux power Circuits
100 mA for initiation circuits
3.0 Amp Notification and Aux power Circuits
100 mA for initiation circuits
3.0 Amp Notification and Aux power Circuits
100 mA for initiation circuits
3.0 Amp Notification and Aux power Circuits
100 mA for initiation circuits
Earth Ground
Faults
N/A
N/A
0Ω
0Ω
0Ω
0Ω
0Ω
0Ω
0Ω
0Ω
0Ω
* Regulated for NAC circuits * Special application when used for releasing or auxiliary power circuits.
3-2 151430
Before You Begin Installing
Terminal Label Description Rating
Voltage Current
B
+
­B A +
­B A +
­A
GND N.C.
N.O. N.C.
N.O. N.C.
N.O. S­S+ SC­SC+ Ring Phone Line 1 Telco Ring Tip Phone Line 1 Telco Tip Ring Phone Line 1 Premises Ring Tip Phone Line 1 Premises Tip Ring Phone Line 2 Telco Ring Tip Phone Line 2 Telco Tip Ring Phone Line 2 Premises Ring Tip Phone Line 2 Premises Tip + –
SBUS1 IN
SBUS2 OUT
SBUS2 IN Used for Class A installations 0Ω
NETWORK
RELAY 2 General Purpose Relay 2 24 VDC 2.5 A, resistive N/AC
RELAY 1 General Purpose Relay 1 24 VDC 2.5 A, resistive N/AC
TROUBLE Trouble Relay 24 VDC 2.5 A, resistive N/AC
SLC OUT SLC terminals 32 VDC 150 mA 0Ω
SLC IN Used for Class A installations 0Ω
Battery Battery Connection 24 VDC 1.12 A N/A
Used for Class A installations 0ΩA
SBUS communication 5 VDC 100 mA
SBUS power 24 VDC 1.0 A
NETWORKING CONNECTION
5V 100mA N/AB
N/A 0Ω
N/A 0Ω
Earth Ground
Faults
0Ω
151430 3-3
IFP-2000 Installation Manual

3.4 Wiring Specifications

Induced noise (transfer of electrical energy from one wire to another) can interfere with telephone communication or cause false alarms. To avoid induced noise, follow these guidelines:
Isolate input wiring from high current output and power wiring. Do not pull one multi­conductor cable for the entire panel. Instead, separate the wiring as follows:
High voltage AC power terminal SLC loops SLC In/Out Terminals Audio input/output Phone line circuits, Ring Tip Telco,
Phone Terminals Notification circuits I/01-I/08 Terminals SBUS SBUS1 In/Out Terminals, SBUS 2
In/Out Terminals Relay circuits Trouble, Relay 1, Relay 2
Terminals
Do not pull wires from different groups through the same conduit. If you must run them together, do so for as short a distance as possible or use shielded cable. Connect the shield to earth ground at the panel. You must route high and low voltages separately.
Route the wiring around the inside perimeter of the cabinet. It should not cross the circuit board where it could induce noise into the sensitive microelectronics or pick up unwanted RF noise from the high speed circuits. See Figure 3-1 for an example.
High frequency noise, such as that produced by the inductive reactance of a speaker or bell, can also be reduced by running the wire through ferrite shield beads or by wrapping it around a ferrite toroid.
3-4 151430
Loading...
+ 208 hidden pages