Description of terminal __________________________________________________________________________________ 18
Description of the graphic screen__________________________________________________________________________ 19
First power-up - [5. LANGUAGE] menu _____________________________________________________________________ 22
Subsequent power ups__________________________________________________________________________________ 23
Programming: Example of accessing a parameter_____________________________________________________________ 24
Quick navigation_______________________________________________________________________________________ 25
Functions of the display and the keys_______________________________________________________________________ 28
Accessing menus ______________________________________________________________________________________ 29
Read and understand these instructions bef ore performing any procedure on this drive.
DANGER
HAZARDOUS VOLTAGE
• Read and understand the Installation Manual before i nstalling or operating the ATV71 drive. Instal lation, adjustment,
repair, and maintenance must be performed by qualified personnel.
• The user is responsible for compliance with all international and national electrical standards in force concerning
protective grounding of all equipment.
• Many parts of this variable speed drive, including the printed circuit boards, operate at the line voltage. DO NOT
TOUCH.
Use only electrically insulated tools.
• DO NOT touch unshielded components or terminal strip screw connections with volta ge present.
• DO NOT short across terminals PA/+ and PC/- or across the DC bus capacitors.
• Install and close all the covers before applying power or starting and stopping the drive.
• Before servicing the variable speed drive
- Disconnect all power.
- Place a “DO NOT TURN ON” label on the variable speed drive disconnect.
- Lock the disconnect in the open position.
• Disconnect all power including external control power that may be present before servicing the drive. WAIT 15
MINUTES to allow the DC bus capacitors to discharge. Then follow the DC bus voltage measurement procedure
given in the Installation Manual to verify that the DC voltage is less than 42 V. The drive LEDs are not accurate
indicators of the absence of DC bus voltage.
Failure to follow these instructions will result in death or serious injury.
CAUTION
DAMAGED EQUIPMENT
Do not operate or install any drive that appears damaged.
Failure to follow this instruction can result in equipment damage.
41755855 12/2009
Documentation structure
The following Altivar 71 technical documents are available on the Telemecanique website (www.telemecanique.com) as well as on the
CD-ROM supplied with the drive.
Installation Manual
This bulletin contains complete mounting and wiring instructions.
Programming manual
This describes the functions, parameters and use of the drive terminal (integrated display terminal and graphic display terminal).
The communication functions are not described in this manual, but in the manual for the bus or network used.
Communication Parameters Manual
This manual describes:
• The drive parameters with specific information for use via a bus or communication network.
• The operating modes specific to communication (state chart).
• The interaction between communication and local control.
Manuals for Modbus, CANopen, Ethernet, Profibus, INTERBUS, Uni-Telway, FIPIO
and Modbus Plus, etc.
These manuals describe the assembly, connection to the bus or network, signaling, diagnostics, and configuration of the communicationspecific parameters via the integrated display terminal or the graphic display terminal.
They also describe the communication services of the protocols.
ATV 58-58F/ATV 71 Migration Manual
This manual describes the differences between the Altivar 71 and the Altivar 58/58F and explains how to replace an Altivar 58 or 58F,
including how to replace drives communicating on a bus or a network.
ATV 78/ATV 61/71 Migration Manual
This manual describes the differences between the Altivar 61/71 and Altivar 78 and explains how to replace an Altivar 78.
1755855 12/20095
Software enhancements
Since the Altivar ATV 71 was first launched, it has benefited from the addition of several new functions. The software version has been
updated to V3.3. The old versions can be replaced by this new one without any modifications.
Al
though this documentation relates to v ersion V3.3, it can still be used with earlier versions, as the updates merely involve t
values and parameters, and none of the parameters of the previous versions have been modified or removed.
Enhancements made to version V1.2 in comparison to V1.1
Factory setting
Note 1: In version V1.1, the analog input was 0 ± 10 V. For safety reasons, in the new version this inpu t has been set t o 0 + 10 V.
Note 2: In version V1.1, analog output AO1 was assigned to the motor f requency. In the new version, this output is not assigned
at
all.
With the exception of these two parameters, the factory settings of version V1.1 remain the same in the new version. The new functi
are factory-set to disabled.
Motor frequency range
The maximum output frequency has been extended from 1000 to 1600 Hz (depending on the drive rating and control profile).
New parameters and functions
Menu [1.2 MONITORING](SUP-)
Addition of internal states and values relating to the new functions described below.
he addition of
ons
Menu [1.3 SETTINGS](SEt-)
• [High torque thd.](ttH) page 66.
• [Low torque thd.](tt
• [Pulse warning thd.](FqL) page
• [Freewheel st
L) page 66.
67.
op Thd.](FFt) page67.
Menu[1.4 MOTOR CONTROL](drC-)
• [rpm increment](InSP) page 69.
• Extension of the following configurations to all drive ratings; previously limited to 45 kW (60 HP) for ATV71
(100 HP) for ATV71
• Input Al1 can now be configured to 0 +10 V or 0 ± 10 V via [AI1 Type] (AI1t) page 94.
• [AI net. channel] (
• New methods of assigning relays and logic outputs page
forward rotation, motor in reverse rotation, measured speed threshold reached, load variation detection.
• Analog output AO1 can now be used as a logic output and assigned to relay functions and logic outputs, page
• New method of modifying the scale of analog outputs page
max](ASHx).
•
New methods of assigning logic outputs page
• New methods of assigning alarm groups page
threshold reached, load variation detection.
AIC1) page 98.
103 : rope slack, high torque threshold, low torque threshold, motor in
110 using the parameters [Scaling AOx min](ASLx) and [Scaling AOx
111: signed motor torque and measured motor speed.
• The summing, subtraction and multiplication reference fu nctions can now be assigned to virtual input [Network AI] (AIU1) page 136.
• New parameter [Freewheel stop Thd.] (FFt) page 141 used to set a threshold for switching to freewheel at the end of a stop on ramp
or fast stop.
• Brake engage at regulated zero speed [Brake engage at 0] (bECd) page 162.
• Weight [Weight sensor ass.] (PES) page 167 can now be assigned to virtual input [Network AI] (AIU1).
• New "rope slack" function page 171, with the parameters [Rope slack config.] (rSd) and [Rope slack trq level] (rStL).
• Use of the ramp [Acceleration 2] (AC2) page 179 when starting and "waking up" the PID function.
• The torque limitation [TORQUE LIMITATION] (tOL-) page 186 can now be configured in whole % or in 0.1% increments using [Torque
increment] (IntP) and assigned to virtual input [Network AI] (AIU1).
• New "stop at distance calculated after deceleratio n limit swi tch" funct ion page 195, with the parameters [St op distance] (Std),[Rated
linear speed] (nLS) and [Stop corrector] (SFd).
• Positioning by sensors or limit switch [POSITIONING BY SENSORS] (LPO-) page 196 can now be configured in positive logic or
negative logic using [Stop limit config. (SAL) and [Slowdown limit cfg.] (dAL).
• Parameter set switching [PARAM. SET SWITCHING] (MLP-) page 199 can now be assigned to the frequency thresholds attained
[Freq. Th. att.] (FtA) and [Freq. Th. 2 at ta in . ] (F2A).
• New half-floor: menu [HALF FLOOR] (HFF-) page 213.
Menu [1.8 FAULT MANAGEMENT](FLt)
• Possibility of reinitializing the drive without turning it off, via [Product reset] (rP) page 220.
• Possibility of reinitializing the drive via a logic input without turning it off, using [Product reset assig.] (rPA) page 220.
• The possibility of configuring the "output phase loss" fault [Output Phase Loss] (OPL) page 224 to [Output cut] (OAC) has been
extended to all drive ratings (previously limited to45 kW (60 HP) for ATV71pppM3X and 75 kW (100HP) for ATV71pppN4).
• The external fault [EXTERNAL FAULT] (EtF-) page 227 can now be configured in positive or negat ive logic via [External fault config.]
(LEt).
• New monitoring function based on speed measurement via "Pulse input" page 234, via the [FREQUENCY METER] menu (FqF-).
• New function for detecting load variation page 236, via the [DYNAMIC LOAD DETECT] menu (dLd-).
• Short-circuit faults on the braking unit can now be configured via[Brake res. fault Mgt] bUb) page 238.
Menu [7 DISPLAY CONFIG.]
•In [7.4 KEYPAD PARAMETERS]page 261, the [KEYPAD CONTRAST] and [KEYPAD STAND-BY] parameters to adjust the contrast
and stand-by mode of the graphic display unit.
Enhancements made to version V1.6 in comparison to V1.2
Extension of the range with the addition of ATV71ppppY drives for 500 to 690 V supplies.
There are no new parameters, but the adjust ment ranges and fa ctory sett ings of some parame ters have b een adapted to the new vol tages.
Menu [1.5 INPUTS / OUTPUTS CFG](I-O-)
Increased adjustment range for the relay and logic output delay parameters: 0 to 60000 ms instead of 0 to 9999 ms.
Enhancements made to version V2.5 in comparison to V1.6
Menu [1.3 SETTINGS](SEt-)
• New parameters [Skip Frequency](JPF), [Skip Frequency 2] (JF2) and [3rd Skip Frequency](JF3) page 67 allow to avoid critical
speed which generate resonances.
• New parameter [Skip.Freq.Hysteresis](JFH) page 67 to adjust the range of skip frequency.
• Possibility to adjust the parameter [Torque ratio] (trt) page 67 (visible too in [TORQUE CONTROL] (tOr-) menu page 183).
Important:
For V2.5 version, the behaviour of the following functions is different from the previous version when type of stop "freewheel" is selected
(factory value):
• [LIMIT SWITCHES](LSt-) function,
• [POSITIONING BY SENSORS](LPO-) function,
• "shutdown" command by communication (see CiA402 state chart in communication parameters manual).
Actually, on previous versions, type of stop "freewheel" was not well done.
1755855 12/20097
Software enhancements
Enhancements made to version V2.7 in comparison to V2.5
Menu [7 DISPLAY CONFIG.]
• Addition in [7.4 KEYPAD PARAMETE RS ]page 261 of [Power up menu]. This parameter allows to choose the menu which di spl ays
on the drive on power up.
Menu [1.3 SETTINGS](SEt-)
The adjustment range of [Time to restart] (ttr) page 163 can now be configured between 0.00 and 15.00 seconds.
Enhancements made to version V3.3 in comparison to V2.7
[1.7 APPLICATION FUNCT.](Fun-) menu
New parameters and functions
• New parameter [REGEN CONNECTION] (AFE) page 215 . With this parameter it is possible to retun the braking energy to the mains
and reduce the harmonics
81755855 12/2009
Steps for setting up
INSTALLATION
v 1 Consult the Installation Manual
PROGRAMMING
Procedure applicable if the factory configuration, page 10, and use of the
[SIMPLY START](SIM-) menu only are sufficient for the application.
b 2 Power up without run command
v If you are using a separate power
supply for the control section, follow
the instructions on page 15.
b 3 Select the language, if the drive
has a graphic display terminal
b 4 Configure the [SIMPLY START]
(SIM-) menu
v 2-wire or 3-wire control
v Macro configuration
v Motor parameters
) Perform an auto-tuning
operation
v Motor thermal current
v Acceleration and deceleration
ramps
v Speed variation range
Tips:
• Before you start programming, complete
the user setting tables, page 274
.
• Perform an auto-tuning operation to
optimize performance, page 43
.
• If you get lost, return to the factory
settings, page 250
.
Note: Check that the wiring of the
drive is compatible with its
configuration.
b 5 Start
1755855 12/20099
Factory configuration
Drive factory settings
The Altivar 71 is factory-set for the most common operating conditions:
• Macro configuration: Start/Stop
• Motor frequency: 50 Hz
• Constant torque application with asynchronous motor and sensorless flux vector control
• Normal stop mode on deceleration ramp
• Stop mode in the event of a fault: freewheel
• Linear, acceleration and deceleration ramps: 3 seconds
• Low speed: 0 Hz
• High speed: 50 Hz
• Motor thermal current = rated drive current
• Standstill injection braking current = 0.7 x rated drive current, for 0.5 seconds
• No automatic starts after a fault
• Switching frequency 2.5 kHz or 4 kHz depending on drive rating
• Logic inputs:
- LI1: forward, LI2: Forward (2 operating direction), 2-wire control on transition
- L13, L14, LI5, LI6: inactive (not assigned)
• Analog inputs:
- AI1: speed reference 0 +10 V
- AI2: 0-20 mA, inactive (not assigned)
• Relay R1: The contact opens in the event of a fault (or drive off).
• Relay R2: Inactive (not assigned)
• Analog output AO1: 0-20 mA, inactive (not assigned)
If the above values are compatible with the application, the drive can be used without changing the settings.
Option card factory settings
The option card inputs/outputs are not factory-set.
101755855 12/2009
Application functions
The tables on the following pages show the most common combinations of functions and applications, in order to guide your selection.
The applications in these tables relate to the foll owing machines in particular:
• High inertia: centrifuges, mixers, unbalanced machines (beam pumps, presses)
• Process
Each machine has its own special features, and the combinations listed here are neither mandatory nor exhaustive.
Some functions are designed specifically for a particular application. In this case, the application is identified by a tab in the
margin on the relevant programming pages.
Motor control functions
Applications
FunctionsPage
V/f ratio
Sensorless flux vector control
Flux vector control with sensor
2-point vector control
Open-loop synchronous motor
Output frequency of up to 1600 Hz
Motor overvoltage limiting
DC bus connection (see User's Manual)
Motor fluxing using a logic input
Switching frequency of up to 16 kHz
Auto-tuning
71
71
71
71
71
69
83
-
154
82
70
Hoisting
Lifts
Handling
Packing
Textiles
Wood
High inertia
bbb
bbbbbbbb
bbbbbbbb
bb
b
bb
bb
bb
bbb
bbb
bbbbbbbb
Process
1755855 12/200911
Application functions
Functions on speed references
FunctionsPage
Applications
Differential bipolar reference91
Reference delinearization (magnifying glass effect)93
Frequency control input125
Reference switching
Reference summing134
Reference subtraction134
Reference multiplication134
S ramps137
Jog operation145
Preset speeds146
+ speed / - speed using single action pushbuttons
Fast stop141
Limit switch management155
Brake control157
Load measurement166
High-speed hoisting168
Rope slack171
PID regulator173
Torque monitoring182
Motor/generator torque limit185
Load sharing85
Line contactor control189
Output contactor control191
Positioning by limit switches or sensors193
Stop at distance calculated after deceleration limit switch195
ENA system (mechanical with unbalanced load)80
Parameter switching198
Motor or configuration switching201
Traverse control205
Stop configuration141
Evacuation212
Half floor213
Hoisting
Lifts
Handling
Packing
Textiles
Wood
High inertia
bb
bbb
bbb
bb
b
b
bbb
bbbb
bb
bbb
b
bb
bb
b
bbbbbbbb
bbb
b
bbbb
b
b
Process
b
1755855 12/200913
Application functions
Safety functions/fault management
FunctionsPage
Applications
Power Removal (safety function, see User's Manual)
Deferred stop on thermal alarm226
Alarm handling115
Fault management218 to 240
IGBT tests229
Catch a spinning load222
Braking resistor thermal protection238
Motor protection with PTC probes218
Undervoltage management228
4-20mA loss230
Uncontrolled output cut (output phase loss)224
Automatic restart221
Use of the "Pulse input" input to measure the speed of
rotation of the motor.
Load variation detection236
-
234
Hoisting
Lifts
Handling
Packing
Textiles
Wood
High inertia
bbbbbbbb
b
bbbbbbbb
bbbbbbbb
bbbbbbbb
bbb
bbbb
bbbbbbbb
bbb
bbbbbb
b
b
bbb
b
Process
141755855 12/2009
Setup - Preliminary recommendations
DANGER
UNINTENDED EQUIPMENT OPERATION
• Before turning on and configuring the Altivar 71, check that the PWR (POWER REMOVAL) input is dea ctivat ed (at
state 0) in order to prevent unintended operation.
• Before turning on the drive, or when exiting the configuration menus, check that the inputs assigned to the run
command are deactivated (at state 0) since they can cause the motor to start immediately.
Failure to follow these instructions will result in death or serious injury.
CAUTION
INCOMPATIBLE LINE VOLTAGE
Before turning on and configuring the drive, ensure that the li ne voltage is compatible with the sup ply voltage range shown
on the drive nameplate. The drive may be damaged if the line voltage is not compatible.
Failure to follow this instruction can result in equipment damage.
CAUTION
RISK OF EQUIPMENT DAMAGE
• Avoid operating the contactor frequently (premature ageing of the f ilter capacitors).
• Cycle times < 60 s may result in damage to the pre-charge resistor.
Failure to follow these instructions can result in equipment damage.
DANGER
UNINTENDED EQUIPMENT OPERATION
• Check that changes made to the settings during operation do not present any danger.
• We recommend stopping the drive before making any changes.
Failure to follow these instructions will result in death or serious injury.
Turning on and configuring the drive
Separate control section power supply
Only supply power to the power section the next time the drive is powered up when:
A) The drive control section is powered independently of the power section (P24 and 0V te rminals).
B) Whenever an option card is added or replaced.
Power switching via line contactor
User adjustment and extension of functions
• The display unit and buttons can be used to modify the settings and to extend the functions described in the following pages.
• Return to factory settings is made easy by the [1.12 FACTORY SETTINGS](FCS-) menu, see page 248.
• There are three types of parameter:
- Display: Values displayed by the drive
- Adjustment: Can be changed during operation or when stopped
- Configuration: Can only be modified when stopped and no braking is taking place. Can be displayed during operation.
1755855 12/200915
Setup - Preliminary recommendations
CAUTION
UNINTENDED EQUIPMENT OPERATION
Motor thermal protection will not be provide d by the drive if th e motor current i s less t han 0.2 ti mes the rated drive current.
Provide an alternative means of thermal protection.
Failure to follow this instruction can result in equipment damage.
CAUTION
UNINTENDED EQUIPMENT OPERATION
Motor thermal protection is no longer provided by the drive. Provide an alternative means of thermal protection on every
motor.
Failure to follow this instruction can result in equipment damage.
Starting
Important:
• In factory settings mode, the motor can only be supplied wit h power once the “forward”, “reverse” an d “DC injection st op” commands
have been reset:
- On power-up or a manual fault reset or after a stop command
If they have not been reset, the drive will display "nSt" but will not start.
• If the automatic restart function has been configured ([Automatic restart](Atr) parameter in the [1.8-FAULT MANAGEMENT](FLt-)
menu, see page
Test on a low power motor or without a motor
• In factory settings mode, [Output Phase Loss] detection (OPL) page 224 is active (OPL = YES). To check the drive in a test or
maintenance environment without having to switch to a moto r with the same rating as the drive (part icularly useful in the case of high
power drives), deactivate [Output Phase Loss] (OPL = no).
• Configure [Motor control type] (Ctt) = [V/F 2pts](UF2) or [V/F 5pts](UF5) ([1.4-MOTOR CONTROL](drC-) menu, see page 71)
221), these commands are taken into account without a reset being necessary.
Using motors in parallel
• Configure [Motor control type] (Ctt) = [V/F 2pts](UF2) or [V/F 5pts](UF5) ([1.4-MOTOR CONTROL](drC-) menu, see page 71)
161755855 12/2009
Setup - Preliminary recommendations
CAUTION
UNINTENDED EQUIPMENT OPERATION
• To protect a motor which has a nominal voltage lower than drive supply voltage, it is mandatory to use
[Vector Control 2pt](UC2) function in order to limit maximal voltage of the motor lower than network voltage.
• Nevertheless, it is necessary to check that instantaneous voltage applied to the motor (link to DC bus voltage) are
compatible with characteristics of this one.
Failure to follow these instructions can result in equipment damage.
ATV71pppY - Network which presents often under voltage
To assure an optimal running of an ATV71pppY used on network which pre sent s ofte n und er volt ag e (netwo rk vol tage cont ai ned betwe en
425 V and 446 V), it is necessary to adjust [Prevention level](UPL) = 383 V ([1.8-FAULT MANAGEMENT](FLt-) menu, see page
Using motor with nominal voltage lower than drive supply voltage
• Configure [Vector Control 2pt](UC2) = [Yes](YES) ([1.4-MOTOR CONTROL] (drC-) menu, see page 73)
229).
1755855 12/200917
Graphic display terminal
1 Graphic display
2 Function keys
F1, F2, F3, F4,
see page 19
.
3 STOP/RESET
button
4 RUN button
5 Navigation button:
• Press (ENT):- To save the current value
- To enter the selected menu or parameter
• Turn CW/
CCW:
- To increment or decrement a value
- To go to the next or previous line
- To increase or decrease the reference if control via
the terminal is activated
7 ESC key: Aborts a value, a
parameter or a menu to return
to the previous selection
6 Button for reversing the directi on
of rotation of the motor
HMI Modbus
Green LED:
DC bus ON
Red LED:
Fault
Although the graphic display terminal is optional for low-power drives, it is a standard component on high-power drives (see catalog). The
graphic display terminal can be disconnected and connected remotely (on the door of an enclosure for example) using the cables and
accessories available as options (see catalog).
Description of terminal
Note: Buttons 3, 4, 5 and 6 can be used to control the drive directly, if control via the terminal i s ac tivated.
Disconnected terminal
When the terminal is disconnected, 2 LEDs become visible:
181755855 12/2009
Graphic display terminal
F1F2F3F4
RDYTerm+0.00 Hz0A
1 DRIVE MENU
1.1 SIMPLY START
1.2 MONITORING
1.3 SETTINGS
1.4 MOTOR CONTROL
1.5 INPUTS / OUTPUTS CFG
Code<<>>Quick
1
2
3
4
6
5
• Code F1
•HELP F1
• << F2
• >> F3
• Quick F4
Description of the graphic screen
1. Display line. Its content can be configured; the factory settings show:
• The drive state (see page 20)
• The active control channel:
- Term: Terminals
- HMI: Graphic display terminal
- MDB: Integrated Modbus
- CAN: Integrated CANopen
- NET: Communication card
- APP: Controller Inside card
• Frequency reference
• Current in the motor
2. Menu line. Indicates the name of the current menu or submenu.
3. Menus, submenus, parameters, values, bar charts, etc., are displayed in drop-down window format on a maximum of 5 lines.
The line or value selected by the navigation button is displayed in reverse video.
4. Section displaying the functions assigned to the F1 to F4 keys and aligned with them, for example :
The function keys are dynamic and contextual.
Other functions (application functions) can be assigned to these keys via the [1.6 COMMAND] menu.
If a preset speed is assigned to a function key and if the f uncti on key is p ressed, the mot or will run a t this preset spe ed until anoth er preset
speed or JOG is pressed, speed reference is changed, or Stop key is pressed.
5. Indicates that there are no more levels below this display window.
Indicates that there are more levels below this display window.
6. Indicates that this display window does not scroll further up.
Indicates that there are more levels above this display window.
: Displays the code of the selected parameter, i.e., the code corresponding to the 7-segment display.
: Contextual help
: Navigate horizontally to the left, or go to previous menu/submenu or, for a value, go to the next di gi t up, di spl ayed
in reverse video (see the example on page
: Navigate horizontally to the right or go to next menu/submenu (going to the [2 ACCESS LEVEL] menu in this
example) or, for a value, go to the next digit down, displayed in reverse video (see the example on page
: Quick navigation, see page 25.
21).
21).
1755855 12/200919
Graphic display terminal
Drive state codes:
- ACC: Acceleration
- CLI: Current limit
- CTL: Controlled stop on input phase loss
- DCB: DC injection braking in progress
-DEC: Deceleration
- FLU: Motor fluxing in progress
-FST: Fast stop
- NLP: No line power (no line supply on L1, L2, L3)
- NST: Freewheel stop
- OBR: Auto-adapted deceleration
- PRA: Power Removal function active (drive locked)
When only one selection is possible, the selection made is indicated by
Example: Only one language can be chosen.
When multiple selection is possible, the selections made are indicated by
Example: A number of parameters can be chosen to form the [USER MENU].
Example configuration window for one value:
The << and >> arrows (keys F2 and F3) are used to select the digit to be modified, and the navigation button is rotated to increase or
decrease this number.
1755855 12/200921
Graphic display terminal
ATV31HU22N4
2.2kW/3HP 380/480V
Config. n°1
5 LANGUAGE
English
Français
Deutsch
Español
Italiano
Chinese
Russian
Turkish
RDY Term +0.00Hz 0.0A
2 ACCESS LEVEL
Basic
Standard
Advanced
Expert
RDY Term +0.00Hz 0.0A
1 DRIVE MENU
1.1 SIMPLY START
1.2. MONITORING
1.3. SETTINGS
1.4. MOTOR CONTROL
1.5. INPUTS / OUTPUTS CFG
Code<<>>Quick
RDY Term +0.00Hz 0.0A
MAIN MENU
1 DRIVE MENU
2 ACCESS LEVEL
3 OPEN / SAVE AS
4 PASSWORD
5 LANGUAGE
CodeQuick
First power-up - [5. LANGUAGE] menu
The first time the drive is powered up, the user will automatically be guided through the menus as far as [1. DRIVE MENU].
The parameters in the [1.1 SIMPLY START] submenu must be configured and auto-tuning performed before the motor is started up.
Display for 3 seconds following power-up
3 seconds
Automatically switches to [5 LANGUAGE]
menu 3 seconds later.
Select the language and press ENT.
ESC
Switches to [2 ACCESS LEVEL] menu
(see page
31)
Select the access level and press ENT.
Switches to [1 DRIVE MENU]
(see page
27)
Press ESC to return to [MAIN MENU]
221755855 12/2009
Graphic display terminal
3 seconds later, switches to
[1. DRIVE MENU] or to
[1.14 PROGRAMMABLE CARD].
If no operator inputs are made,
switches to "Display" automatically
10 seconds later (the display will
vary depending on the selected
configuration).
Users can return to [MAIN MENU]
by pressing ENT or ESC.
3 seconds
10 seconds
ESC
ATV71HU22N4
2.2kW/3HP 380/480V
Config. n°1
RDY Term+38Hz0A
1. DRIVE MENU
1.1 SIMPLY START
1.2 MONITORING
1.3 SETTINGS
1.4 MOTOR CONTROL
1.5 INPUTS / OUTPUTS CFG
Code<<>>Quick
RDY Term+38Hz0A
Frequency ref.
Min=0Max=60
Quick
RDY Term+38Hz0A
MAIN MENU
1 DRIVE MENU
2 ACCESS LEVEL
3 OPEN / SAVE AS
4 PASSWORD
5 LANGUAGE
CodeQuick
38 Hz
RDY Term +0.00Hz0A
1.14 PROGRAMMABLE CARD
Modbus add Prg C. :17
DATE/TIME SETTINGS
<<>>Quick
RDY Term +0.00Hz0A
1.3 SETTINGS
Ramp increment: 01
Acceleration9.51 s
Deceleration: 9.67 s
Acceleration 2: 12.58 s
Deceleration 2: 13.45 s
Code<<>>Quick
Menu selected in
[Power up menu]
page 265
ENT
or, if the Controller Inside card is present
Subsequent power ups
1755855 12/200923
Graphic display terminal
RDY Term +0.00Hz0A
1 DRIVE MENU
1.1 SIMPLY START
1.2 MONITORING
1.3 SETTINGS
1.4 MOTOR CONTROL
1.5 INPUTS / OUTPUTS CFG
Code<<>>Quick
ENT
ESC
RDY Term +0.00Hz0A
1.3 SETTINGS
Ramp increment: 01
Acceleration9.51 s
Deceleration: 9.67 s
Acceleration 2: 12.58 s
Deceleration 2: 13.45 s
Code<<>>Quick
ENT
ENT or
ESC
RDY Term +0.00Hz0A
Acceleration
9.51 s
Min = 0.01 Max = 99.99
<<>>Quick
Programming: Example of accessing a parameter
Accessing the acceleration ramp
Note:
• To select a parameter:
- Turn the navigation button to scroll vertically.
• To modify a parameter:
- Use the << and >> keys (F2 and F3) to scroll horizontally and select the digit to be modified (the selected di git chan ges to white
on a black background).
- Turn the navigation button to modify the digit.
• To cancel the modification:
-Press ESC.
• To save the modification:
- Press the navigation button (ENT).
241755855 12/2009
Graphic display terminal
RDY Term +0.00Hz0A
1.4 MOTOR CONTROL
Standard mot. freq: 5 0Hz IEC
Rated motor power: 0.37 kW (0.5 HP)
Rated motor volt.: 206 V
Rated mot. current: 1.0 A
Rated motor freq.: 50.0 Hz
Code<<>>Quick
ENT
RDY Term +0.00Hz0A
QUICK NAVIGATION
RETURN TO MAIN MENU
DIRECT ACCESS TO...
10 LAST MODIFICATIONS
GOTO MULTIPOINT SCREEN
Code
See page 266
RDY Term +0.00Hz0A
MAIN MENU
1 DRIVE MENU
2 ACCESS LEVEL
3 OPEN / SAVE AS
4 PASSWORD
5 LANGUAGE
CodeQuick
RDY Term +0.00Hz0A
DIRECT ACCESS TO...
1.3
SETTINGS
<<>>
ENT
RDY Term +0.00Hz0A
1.3 SETTINGS
Ramp increment: 01
Acceleration9.51 s
Deceleration: 9.67 s
Acceleration 2: 12.58 s
Deceleration 2: 13.45 s
Code<<>>Quick
RDY Term +0.00Hz0A
10 LAST MODIFICATIONS
Acceleration: 10 s
ENA prop.gain: 1.2
Rated mot. current: 15 A
Preset speed 4: 20 Hz
Preset speed 5: 30 Hz
Code
ESC
ENT
RDY Term +0.00Hz0A
Rated mot. current
15.0 A
<<>>
Quick navigation
If the "Quick" function is displayed above the F4 key, you can gain quick access to a parameter from any screen.
Example:
Press F4 to access the Quick screen, which contains
4 selection options.
• [HOME]: Return to [MAIN MENU].
• [DIRECT ACCESS TO...] : Opens the direct access window, which
will contain the text "1". The function keys << and >> (F2 and F3)
can be used to select each of the numbers and the navigation
button to increment or decrement the numbers: 1.3 in the example
below.
• [10 LAST MODIFICATIONS]: Opens a window in which the l ast 10
parameters modified can be accessed directly.
1755855 12/200925
Graphic display terminal
RDY Term +0.00Hz0A
MAIN MENU
1 DRIVE MENU
2 ACCESS LEVEL
3 OPEN / SAVE AS
4 PASSWORD
5 LANGUAGE
CodeQuick
6 MONITORING CONFIG.
7 DISPLAY CONFIG.
RDY Term +0.00Hz0A
1 DRIVE MENU
1.1 SIMPLY START
1.2 MONITORING
1.3 SETTINGS
1.4 MOTOR CONTROL
1.5 INPUTS / OUTPUTS CFG
Code<<>>Quick
1.6 COMMAND
1.7 APPLICATION FUNCT.
1.8 FAULT MANAGEMENT
1.9 COMMUNICATION
1.10 DIAGNOSTICS
1.11 IDENTIFICATION
1.12 FACTORY SETTINGS
1.13 USER MENU
1.14 PROGRAMMABLE CARD
[MAIN MENU] - Menu mapping
Content of [MAIN MENU] menus
[1 DRIVE MENU]See next page
[2 ACCESS LEVEL]Defines which menus can be accessed (level of complexity)
[3 OPEN / SAVE AS]Can be used to save and recover drive configuration files
[4 PASSWORD]Provides password protection for the configuration
[5 LANGUAGE]Language selection
[6 MONITORING CONFIG.]Customization of information displayed on the graphic display terminal during operation
[7 DISPLAY CONFIG.] • Customization of parameters
• Creation of a customized user menu
• Customization of the visibility and protection mechanisms for menus and parameters
261755855 12/2009
Graphic display terminal
[1 DRIVE MENU]
RDY Term +0.00Hz0A
1.1 SIMPLY START
1.2 MONITORING
1.3 SETTINGS
1.4 MOTOR CONTROL
1.5 INPUTS / OUTPUTS CFG
1.6 COMMAND
1.7 APPLICATION FUNCT.
1.8 FAULT MANAGEMENT
1.9 COMMUNICATION
1.10 DIAGNOSTICS
1.11 IDENTIFICATION
1.12 FACTORY SETTINGS
1.13 USER MENU
1.14 PROGRAMMABLE CARD
1 DRIVE MENU
Code<<>>Quick
Content of [1. DRIVE MENU] menus:
[1.1 SIMPLY START]:Simplified menu for a quick start
[1.2 MONITORING]:Visualization of current, motor and input/output values
[1.3 SETTINGS]:Accesses the adjustment parameters, which can be modified during operation
[1.4 MOTOR CONTROL]:Motor parameters (motor nameplate, auto-tuning, switching frequency, control algorithms, etc.)
[1.5 INPUTS / OUTPUTS CFG]:I/O configuration (scaling, filtering, 2-wire control, 3-wire control, etc.)
[1.6 COMMAND]:Configuration of command and reference channels (graphic d ispl ay t erminal , t ermin als, bu s, e tc.)
[1.7 APPLICATION FUNCT.] :Configuration of application functions (e.g., preset speeds, PID, brake logic control, etc.)
[1.8 FAULT MANAGEMENT]:Configuration of fault management
[1.9 COMMUNICATION]:Communication parameters (fieldbus)
[1.10 DIAGNOSTICS]:Motor/drive diagnostics
[1.11 IDENTIFICATION]:Identifies the drive and the internal options
[1.12 FACTORY SETTINGS]:Access to configuration files and return to factory settings
[1.13 USER MENU]:Specific menu set up by the user in the [7. DISPLAY CONFIG.] menu
[1.14 PROGRAMMABLE CARD]: :Configuration of optional Controller Inside card
1755855 12/200927
Integrated display terminal
• Four 7-segment
displays
• Enters a menu or
parameter, or saves the
displayed parameter or
value
• Returns to the previous
menu or parameter, or
increases the
displayed value
• Exits a menu or parameter,
or aborts the displayed
value to return to the
previous value in the
memory
• Goes to the next menu
or parameter, or
decreases the
displayed value
• 2 CANopen status LEDs
• 2 Modbus status LEDs
Note:
Low-power Altivar 71 drives (see catalog) feature an integrated display terminal with a 7-segment 4-digit display. The graphic display
terminal described on the previous pages can also be connected to these drives as an option.
Functions of the display and the keys
• Pressing or does not store the selection.
• Press and hold down (>2 s) or to scroll through the data quickly.
Save and store the selection: ENT
The display flashes when a value is stored.
Normal display, with no fault present and no startup:
- 43.0 : Display of the parameter selected in the SUP menu (default selection: motor frequency)
- CLI: Current limit
- CtL: Controlled st op on in pu t phase loss
- dCb: DC injection braking in progress
- FLU: Motor fluxing in progress
- FSt: Fast stop.
- nLP: No line power (no line supply on L1, L2, L3)
- nSt: Freewheel stop
- Obr: Auto-adapted deceleration
- PrA: Power Removal function active (drive locked)
- rdY = Drive ready
- SOC: Controlled output cut in progress
- tUn: Auto-tuning in progress
- USA: Undervoltage alarm
The display flashes to indicate the presence of a fault.
281755855 12/2009
Integrated display terminal
XXX
CtL-
FUn-
SIM-
I-O-
SEt-
SUP-
ESC
ESC
ESC
ESC
ESC
ESC
ESC
ESC
ENT
ENT
ESC
ENT
ESC
ENT
ESC
ENT
ESC
ENT
ESC
ENT
ESC
ENT
ESC
FCS-
LAC-
CON-
FLt-
ESC
ESC
ESC
ESC
ENT
ESC
ENT
ESC
ENT
ESC
ENT
ESC
ENT
ESC
SPL-
ESC
ENT
ESC
drC-
COd-
USr-
ESC
ENT
ESC
Displays the state of the drive
SETTINGS
APPLICATION FUNCT.
INPUTS / OUTPUTS CFG
FAULT MANAGEMENT
SIMPLY START
Menus
MONITORING
MOTOR CONTROL
COMMAND
Power-up
FACTORY SETTINGS
PASSWORD
ACCESS LEVEL
COMMUNICATION
(page 54) Adjustment parameters, can be modified during
operation
(page 129
)Configuration of application functions (e.g., preset
) Visualization of current, motor and i nput/output values
(page 70
) Motor parameters (motor nameplate, auto-tuning,
switching frequency, control algorithms, etc.)
(page 116
) Configuration of command and reference channels
(graphic display terminal, terminals, bus, etc.)
(page 248
) Access to configuration files and return to factory
settings
(page 255
)
(page 31
)
(page 241
) Communication parameters (fieldbus)
(page 251
) Specific menu, set up by the user using the graphic
display terminal.
USER MENU
PROGRAMMABLE CARD
(page 252
) Menu for the Controller Inside card, if present.
Accessing menus
A dash appears after menu and submenu codes to differentiate them from parameter codes.
Examples: FUn- menu, ACC parameter.
1755855 12/200929
The grayed-out menus may not be accessible depending on the control access (LAC) configuration.
Integrated display terminal
ENT
ACC15.0
ENT
ESC
ENT
ESC
26.026.0
ESC
dEC
ENT
SEt-
Menu
Value or assignment
1 flash
(save)
Parameter
(Next parameter)
ENT
ESC
1
st
n
th
last
Menu
ENT
ESC
I-O-
Alarm not selected
Alarm selected
Accessing menu parameters
Save and store the displayed selection :
The display flashes when a value is stored.
All the menus are "drop-down" type menus, which means that after the last pa rameter, if
you continue to press, you will return to the first parameter an d, conve rsely, you can
switch from the first parameter to the last parameter by pressing.
Selection of multiple assignments for one parameter
Example: List of group 1 alarms in [INPUTS / OUTPUTS CFG]
menu (I-O-)
A number of alarms can be selected by "checking" them as
follows.
The digit on the right indicates: selected
not selected.
The same principle is used for all multiple select ions.
301755855 12/2009
[2. ACCESS LEVEL](LAC-)
RDY Term +0.00Hz0A
2 ACCESS LEVEL
Basic
Standard
Advanced
Expert
<<>>Quick
RDY Term +0.00Hz0A
MAIN MENU
1 DRIVE MENU
2 ACCESS LEVEL
3 OPEN / SAVE AS
4 PASSWORD
5 LANGUAGE
Code<<>>Quick
RDY Term +0.00Hz0A
1. DRIVE MENU
1.1 SIMPLY START
1.2. MONITORING
1.3. SETTINGS
1.11. IDENTIFICATION
1.12. FACTORY SETTINGS
Code<<>>Quick
1.13 USER MENU
RDY Term +0.00Hz0A
MAIN MENU
1 DRIVE MENU
2 ACCESS LEVEL
3 OPEN / SAVE AS
4 PASSWORD
5 LANGUAGE
CodeQuick
6 MONITORING CONFIG.
RDY Term +0.00Hz0A
1 DRIVE MENU
1.1 SIMPLY START
1.2 MONITORING
1.3 SETTINGS
1.4 MOTOR CONTROL
1.5 INPUTS / OUTPUTS CFG
Code<<>>Quick
1.6 COMMAND
1.7 APPLICATION FUNCT.
1.8 FAULT MANAGEMENT
1.9 COMMUNICATION
1.10 DIAGNOSTICS
1.11 IDENTIFICATION
1.12 FACTORY SETTINGS
1.13 USER MENU
1.14 PROGRAMMABLE CARD
RDY Term +0.00Hz0A
MAIN MENU
1 DRIVE MENU
2 ACCESS LEVEL
3 OPEN / SAVE AS
4 PASSWORD
5 LANGUAGE
CodeQuick
6 MONITORING CONFIG.
7 DISPLAY CONFIG.
RDY Term +0.00Hz0A
MAIN MENU
1 DRIVE MENU
2 ACCESS LEVEL
3 OPEN / SAVE AS
4 PASSWORD
5 LANGUAGE
CodeQuick
6 MONITORING CONFIG.
7 DISPLAY CONFIG.
With graphic display terminal
Basic
Access to 5 menus only, and access to 6 submenus only in the
[1. DRIVE MENU] menu.
A single function can be assigned to each input.
Standard
This is the factory-set level. Access to 6 menus only, and access to all
submenus in the [1. DRIVE MENU] menu.
A single function can be assigned to each input.
1755855 12/200931
Advanced
Access to all menus and submenus.
Several functions can be assigned to
each input.
Expert
Access to all menus and submenus as for [Advanced] level, and access to
additional parameters.
Several functions can be assigned to each input.
Loading...
+ 262 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.