Schneider Electric ATV61, ATV71 option cards

1/4
00175448019096
Electrical equipment should be installed, operated, serviced, and maintained only by qualifed personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this product. © 2010 Schneider Electric. All Rights Reserved.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Read and understand this manual and the manuals of the drive before installing this option.
• The user is responsible for compliance with all international and national electrical code requirements with respect
to grounding of all equipment.
• Many parts of this drive, including the printed circuit boards, operate at the line voltage. DO NOT TOUCH. Use only
electrically insulated tools.
• DO NOT touch unshielded components or terminal strip screw connections with voltage present.
• DO NOT short across terminals PA/+ and PC/– or across the DC bus capacitors.
• Before servicing the drive:
- Disconnect all power, including external control power that may be present.
- Place a “DO NOT TURN ON” label on all power disconnects.
- Lock all power disconnects in the open position.
- WAIT 15 MINUTES to allow the DC bus capacitors to discharge.
- Measure the voltage of the DC bus between the PA/+ and PC/– terminals to ensure that the voltage is less than 42 Vdc.
- If the DC bus capacitors do not discharge completely, contact your local Schneider Electric representative. Do not repair
or operate the drive.
• Install and close all covers before applying power or starting and stopping the drive.
Failure to follow these instructions will result in death or serious injury.
DANGER
VW3 A3 301, 309, 310
ATV71 u V1.1 IE04
VW3 A3 312, 313, 315, 318, 319
ATV61 u V1.2
W9 1754480 01 19 A09
09 - 2010
Altivar
VW3 A3 20p, 3pp, 5 pp
2/4
2)
3)
4)
1)
Loading...