Before you BeginRead and follow these precautions before performing any procedure with
this drive.
The word “drive” as used in this bulletin refers to the controller portion of the
adjustable speed drive as defined in the National Electrical Code
.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Read and understand this manual before installing or operating the
Altivar 61 or 71 drive. Installation, adjustment, repair, and maintenance
must be performed by qualified personnel.
• The user is responsible for compliance with all international and national
electrical code requirements with respect to grounding of all equipment.
• Many parts of this drive, including the printed circuit boards, operate at
the line voltage. DO NOT TOUCH. Use only electrically insulated tools.
• DO NOT touch unshielded components or terminal strip screw
connections with voltage present.
• DO NOT short across terminals PA/+ and PC/– or across the DC bus
capacitors.
• Before servicing the drive:
— Disconnect all power, including external control power that may be
present.
— Place a “DO NOT TURN ON” label on all power disconnects.
— Lock all power disconnects in the open position.
— WAIT 15 MINUTES to allow the DC bus capacitors to discharge.
Then follow the “DC Bus Voltage Measurement Procedure” on
page 2 to verify that the DC voltage is less than 42 V. The drive LED
is not an indicator of the absence of DC bus voltage.
• Install and close all covers before applying power or starting and
stopping the drive.
Failure to follow these instructions will result in death or serious
injury.
Released for Manufacturing
Printed on 2009/10/09
Altivar® 61 and 71 Supplementary Ratings 30072-451-38 (Rev. 01)
DANGER
Introduction09/2009
IntroductionThis document provides:
•Information regarding short circuit current rating (SCCR) and
overcurrent protection device (OCPD) for the 200–240 Vac,
380–480 Vac, and 500–600 Vac three-phase Altivar
and Altivar 71 (ATV71) drives.
•Information on drives in single-phase installations with and without
line reactors.
Use this information in addition to the ATV61 and ATV71 Simplified Manuals
and as a supplement to the recommendations listed on the drive nameplate.
Only the ATV61 and ATV71 drive part numbers available for each
supplementary rating type are listed in this document.
®
61 (ATV61)
DC Bus Voltage Measurement
Procedure
Measuring the DC bus voltage
Before working on the drive, turn it off and wait 15 minutes to allow the DC
bus to discharge. Then measure the DC bus voltage.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Read and understand the instructions on page 1 before performing this
procedure.
Failure to follow these instructions will result in death or serious
injury.
The DC bus voltage can exceed 1,000 Vdc. Use a properly rated voltagesensing device when performing this procedure. To measure the DC bus
voltage:
1. Disconnect the drive power supply.
2. Wait 15 minutes to allow the DC bus to discharge.
3. Measure the voltage of the DC bus between the PA/+ and PC/–
terminals to ensure that the voltage is less than 42 Vdc.
4. If the DC bus capacitors do not discharge completely, contact your local
Schneider Electric representative. Do not repair or operate the drive.
30072-451-38 (Rev. 01) Altivar® 61 and 71 Supplementary Ratings
09/2009100 kA SCCR with Fuses and a Minimum 3% Impedance Line Reactor
100 kA SCCR with Fuses and a
Minimum 3% Impedance Line
Reactor
380–480 V RatingsFor drives with a three-phase input line voltage of 380–480 V, a
This section provides fuse values for a drive installed as a Type 1 drive
(open drive with a conduit box) with a 3% line reactor, or for a drive that is
installed in a metallic enclosure with a 3% line reactor.
®
Bussmann
Class J Time Delay or Non-time Delay 600 V Fuse is
required. Table 1 lists the maximum fuse values for a 100 kA SCCR. For
installations requiring an enclosure, the minimum enclosure volume is also
specified in Table 1.
Table 1:Maximum Fuse Values for 100 kA SCCR With a 3% Line
Reactor
Type 1
(Open Drive With
Conduit Box)
Drive Catalog
hp
Number
Maximum Fuse
Value
(A)
A T V 6 1 H 0 7 5 N 4
1
ATV71H075N4
ATV61HU15N4
2
ATV71HU15N4
A T V 6 1 H U 2 2 N 4
3
ATV71HU22N4
A T V 6 1 H U 3 0 N 4
—
ATV71HU30N4
A T V 6 1 H U 4 0 N 4
5
ATV71HU40N4
A T V 6 1 H U 5 5 N 4
7.5
ATV71HU55N4
A T V 6 1 H U 7 5 N 4
10
ATV71HU75N4
ATV61HD11N4
15
ATV71HD11N4
A T V 6 1 H D 1 5 N 4
20
ATV71HD15N4
ATV61HD18N4
25
ATV71HD18N4
ATV61HD22N4
30
ATV71HD22N4
A T V 6 1 H D 3 0 N 4
40
ATV71HD30N4
A T V 6 1 H D 3 7 N 4
50
ATV71HD37N4
A T V 6 1 H D 4 5 N 4
60
ATV71HD45N4
A T V 6 1 H D 5 5 N 4
75
ATV71HD55N4
A T V 6 1 H D 7 5 N 4
100
ATV71HD75N4
1
Minimum enclosure volume allows the specified SCCR. Application specific thermal
requirements may require a larger enclosure.
2
There is no supplementary rating for an ATV61HD11N4 or ATV71HD11N4 drive installed with
a Type 1 conduit box or in a Type 1 enclosure. For the ATV61HD11N4 or ATV71HD11N4 drive
installed in a metallic enclosure, a 100 kA short circuit current rating is possible only in a Type
12 enclosure.