Schneider Electric ATV61, ATV71 Instruction Bulletin

30072-451-38 (Rev. 01)
DANGER
09/2009
Instruction Bulletin
Replaces 30072-451-38C dated 07/2008
Raleigh, NC, USA
Altivar® 61 and 71 Supplementary Ratings
Retain for future use.
Before you Begin Read and follow these precautions before performing any procedure with
this drive.
The word “drive” as used in this bulletin refers to the controller portion of the adjustable speed drive as defined in the National Electrical Code
.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Read and understand this manual before installing or operating the Altivar 61 or 71 drive. Installation, adjustment, repair, and maintenance must be performed by qualified personnel.
• The user is responsible for compliance with all international and national electrical code requirements with respect to grounding of all equipment.
• Many parts of this drive, including the printed circuit boards, operate at the line voltage. DO NOT TOUCH. Use only electrically insulated tools.
• DO NOT touch unshielded components or terminal strip screw connections with voltage present.
• DO NOT short across terminals PA/+ and PC/– or across the DC bus capacitors.
• Before servicing the drive:
— Disconnect all power, including external control power that may be
present.
— Place a “DO NOT TURN ON” label on all power disconnects.
— Lock all power disconnects in the open position.
— WAIT 15 MINUTES to allow the DC bus capacitors to discharge.
Then follow the “DC Bus Voltage Measurement Procedure” on page 2 to verify that the DC voltage is less than 42 V. The drive LED is not an indicator of the absence of DC bus voltage.
• Install and close all covers before applying power or starting and stopping the drive.
(NEC).
© 2005–2009 Schneider Electric All Rights Reserved
Failure to follow these instructions will result in death or serious injury.
Released for Manufacturing
Printed on 2009/10/09
Altivar® 61 and 71 Supplementary Ratings 30072-451-38 (Rev. 01)
DANGER
Introduction 09/2009
Introduction This document provides:
Information regarding short circuit current rating (SCCR) and
overcurrent protection device (OCPD) for the 200–240 Vac, 380–480 Vac, and 500–600 Vac three-phase Altivar and Altivar 71 (ATV71) drives.
Information on drives in single-phase installations with and without
line reactors.
Use this information in addition to the ATV61 and ATV71 Simplified Manuals and as a supplement to the recommendations listed on the drive nameplate. Only the ATV61 and ATV71 drive part numbers available for each supplementary rating type are listed in this document.
®
61 (ATV61)
DC Bus Voltage Measurement Procedure
Measuring the DC bus voltage
Before working on the drive, turn it off and wait 15 minutes to allow the DC bus to discharge. Then measure the DC bus voltage.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Read and understand the instructions on page 1 before performing this procedure.
Failure to follow these instructions will result in death or serious injury.
The DC bus voltage can exceed 1,000 Vdc. Use a properly rated voltage­sensing device when performing this procedure. To measure the DC bus voltage:
1. Disconnect the drive power supply.
2. Wait 15 minutes to allow the DC bus to discharge.
3. Measure the voltage of the DC bus between the PA/+ and PC/– terminals to ensure that the voltage is less than 42 Vdc.
4. If the DC bus capacitors do not discharge completely, contact your local Schneider Electric representative. Do not repair or operate the drive.
© 2005–2009 Schneider Electric All Rights Reserved2
Released for Manufacturing
Printed on 2009/10/09
30072-451-38 (Rev. 01) Altivar® 61 and 71 Supplementary Ratings 09/2009 100 kA SCCR with Fuses and a Minimum 3% Impedance Line Reactor
100 kA SCCR with Fuses and a Minimum 3% Impedance Line Reactor
380–480 V Ratings For drives with a three-phase input line voltage of 380–480 V, a
This section provides fuse values for a drive installed as a Type 1 drive (open drive with a conduit box) with a 3% line reactor, or for a drive that is installed in a metallic enclosure with a 3% line reactor.
®
Bussmann
Class J Time Delay or Non-time Delay 600 V Fuse is
required. Table 1 lists the maximum fuse values for a 100 kA SCCR. For installations requiring an enclosure, the minimum enclosure volume is also specified in Table 1.
Table 1: Maximum Fuse Values for 100 kA SCCR With a 3% Line
Reactor
Type 1 (Open Drive With Conduit Box)
Drive Catalog
hp
Number
Maximum Fuse Value (A)
A T V 6 1 H 0 7 5 N 4
1
ATV71H075N4
ATV61HU15N4
2
ATV71HU15N4
A T V 6 1 H U 2 2 N 4
3
ATV71HU22N4
A T V 6 1 H U 3 0 N 4
ATV71HU30N4
A T V 6 1 H U 4 0 N 4
5
ATV71HU40N4
A T V 6 1 H U 5 5 N 4
7.5 ATV71HU55N4
A T V 6 1 H U 7 5 N 4
10
ATV71HU75N4
ATV61HD11N4
15
ATV71HD11N4
A T V 6 1 H D 1 5 N 4
20
ATV71HD15N4
ATV61HD18N4
25
ATV71HD18N4
ATV61HD22N4
30
ATV71HD22N4
A T V 6 1 H D 3 0 N 4
40
ATV71HD30N4
A T V 6 1 H D 3 7 N 4
50
ATV71HD37N4
A T V 6 1 H D 4 5 N 4
60
ATV71HD45N4
A T V 6 1 H D 5 5 N 4
75
ATV71HD55N4
A T V 6 1 H D 7 5 N 4
100
ATV71HD75N4
1
Minimum enclosure volume allows the specified SCCR. Application specific thermal requirements may require a larger enclosure.
2
There is no supplementary rating for an ATV61HD11N4 or ATV71HD11N4 drive installed with a Type 1 conduit box or in a Type 1 enclosure. For the ATV61HD11N4 or ATV71HD11N4 drive installed in a metallic enclosure, a 100 kA short circuit current rating is possible only in a Type 12 enclosure.
6 6 1078
12 12 1078
15 15 1078
17.5 17.5 1550
25 25 1551
40 40 1987
40 40 1987
2
60 2719
2
70 70 4036
70 70 4036
80 80 4900
90 90 7230
110 110 7230
150 150 12044
175 175 12044
225 225 12045
Drive Installed in a Metallic Enclosure
Maximum Fuse Value (A)
Minimum Enclosure Volume (in³)
1
© 2005–2009 Schneider Electric All Rights Reserved
3
Released for Manufacturing
Printed on 2009/10/09
Altivar® 61 and 71 Supplementary Ratings 30072-451-38 (Rev. 01) 100 kA SCCR with Fuses and a Minimum 3% Impedance Line Reactor 09/2009
600 V Ratings For drives with a three-phase input line voltage of 600 V, a
Ferraz Shawmut® Class J Non-time Delay 600 V Fuse is required.
Table 2 lists the maximum fuse value for a 100 kA SCCR. For installations requiring an enclosure, the minimum enclosure volume is also specified.
Table 2: Maximum Fuse Value for 100 kA SCCR With a 3% Line
Reactor
Type 1 (Open Drive With Conduit Box)
Drive Installed in a Metallic Enclosure
1
hp Drive Catalog Number
Maximum Fuse Value (A)
ATV61HD22Y
25
ATV71HD22Y
ATV61HD30Y
30
ATV71HD30Y
ATV61HD37Y
40
ATV71HD37Y
ATV61HD45Y
50
ATV71HD45Y
ATV61HD55Y
60
ATV71HD55Y
ATV61HD75Y
75
ATV71HD75Y
1
Any NEMA type enclosure can be used.
2
Minimum enclosure volume allows the specified SCCR. Application specific thermal requirements may require a larger enclosure.
60 60 8640
60 60 8640
90 90 9792
110 110 9792
125 125 9792
150 150 9792
Maximum Fuse Value (A)
Minimum Enclosure Volume
2
(in³)
© 2005–2009 Schneider Electric All Rights Reserved4
Released for Manufacturing
Printed on 2009/10/09
Loading...
+ 8 hidden pages