DTAM Micro Operator
Interface
(Catalog Nos. 2707-M232P3xX, -M485P3X)
Installation Instructions
This document describes how to install a DTAM Micro terminal and
connect power.
• Wiring and Safety Guidelines
• Enclosures
• Equipment Required
• Clearances
• Mounting Dimensions
• Installation
• Wire and Cable Length Restrictions
• Connecting Power
• Powerup Sequence
• Upload/Download DIP Switch Settings
• Upload/Download Connections
• Connecting to Devices
• Specifications
• Agency Ratings
• European Union Directive Compliance
For more information on the DTAM Micro terminal, refer to the
following publications.
• DTAM Micro User Manual
2707-803
• DTAM Micro DeviceNet Operator Interface 2707-803.5
These publications are available for viewing and download from the
Rockwell Automation/Allen-Bradley Website at www.ab.com.
DTAM Micro Operator Interface2
Wiring Guidelines
Safety Guidelines
Here are some recommendations on how to reduce electromagnetic
noise on the communications connections:
• Careful wire routing helps reduce or minimize electrical noise.
Route incoming power to the terminal by a separate path from the
communications cables.
• Do not run communications wiring and power wiring in the same
conduit.
• Where communications and power wiring must cross, make their
intersection perpendicular.
• Proper grounding helps to reduce the effects of noise due to
Electromagnetic Interference (EMI). To avoid problems caused
by EMI, all cables must be shielded and grounded at one end.
Grounding is also an important safety measure in electrical
installations. A source for grounding recommendations is the
National Electrical Code published by the National Fire
protection Association of Boston Massachusetts.
Install the DTAM Micro terminal using publication NFPA 70E,
Electrical Safety Requirements for Employee Workplaces as a guide.
Be certain to follow all directions for installing and connecting DC
power to the DTAM Micro.
When used in a hazardous environment, the ultimate enclosure must
be in accordance with Class 1, Division 2 wiring methods as
described in the National Electrical Code (ANSI/NFPA 70) and the
Canadian Electrical Code.
All peripheral equipment must be suitable for the location in which it
is used.
Use only a Class 2 power source as described in the National
Electrical Code (ANSI/NFPA 70) and Canadian Electrical Code.
The recommended AC to DC adapters (Catalog No. 1747-NP1 and
Catalog No. 1747-NP2) meet this requirement.
The DTAM Micro contains no user serviceable parts.
ATTENTION:
EXPLOSION HAZARD: SUBSTITUTION OF
!
COMPONENTS MAY IMPAIR SUITABILITY FOR
CLASS 1, DIVISION 2.
RISQUE D’EXPLOSION: LA SUBSTITUTION DE
COMPOSANTS PEUT RENDRE CE MATÉRIEL
INACCEPTABLE POUR LES EMPLACEMENTS DE
CLASSE 1, DIVISION 2.
DTAM Micro Operator Interface 3
ATTENTION
CAUTION: USE ONLY WITH CLASS 2 POWER
!
!
SOURCE LIMITED TO 30 VDC OPEN CIRCUIT
AND 8A SHORT CIRCUIT.
ATTENTION: UTILISER AVEC UNE TENSION
D’ALIMENTATION CLASSE 2 DE 30 VCC MAXI
EN CIRCUIT OUVERT AVEC UN COURANT DE
COURT-CIRCUIT DE 8A MAXI.
DANGER
EXPLOSION HAZARD: DO NOT CONNECT OR
DISCONNECT EQUIPMENT WHILE CIRCUIT IS
LIVE UNLESS AREA IS KNOWN TO BE
NON-HAZARDOUS
RISQUE D’EXPLOSION: NE PAS BRANCHER
OU DEBRANCHER TANT QUE LE CIRCUIT EST
SOUS TENSION, A MOINS QU’IL NE S’AGISSE
D’UN EMPLACEMENT NON DANGEREUX.
Enclosures
The terminal must be mounted in a panel or enclosure to protect the
internal circuitry. The terminal meets NEMA Type 4, 12, 13 (indoor
use only) ratings only when mounted in a panel or enclosure with the
equivalent rating.
Allow enough spacing within an enclosure for adequate ventilation.
For some applications, you may have to consider heat produced by
other devices within a panel. The ambient temperature around the
terminal must be maintained between 32_ – 131_ F (0_ – 55_ C).
Make sure that provisions are made for accessing the back panel of
the terminal for wiring, routine maintenance, and troubleshooting.
DTAM Micro Operator Interface4
Equipment Required
Clearances
Other than the tools required to make the panel cutout, the tools
required for installation are:
• 7mm (M4) deep well socket wrench or nut driver
• small slotted screwdriver
• torque wrench (in. / lbs).
The terminal is tightened against the panel with six self-locking nuts.
Make sure that you leave adequate room, as shown in Figure 1, for
mounting, air flow, cabling, and access to DIP switches.
Figure 1
Recommended Clearances
Leave 3 inches (76.2 mm)
for Mounting, Air Flow, and
access to DIP Switches.
Leave 3 inches (76.2 mm) for
communications port connector.
DTAM Micro Operator Interface 5
Mounting Dimensions
Figure 2 shows the mounting dimensions of the terminal.
Figure 2
Mounting Dimensions in Inches (Millimeters)
Back View
3.9
(99.1)
6.9
(175.3)
Bottom View
5.4
(137.2)
5.4
(137.2)
1.8
(45.7)