Rockwell Automation 2707-M232P3xX, 2707-M485P3X User Manual

DTAM Micro Operator Interface
(Catalog Nos. 2707-M232P3xX, -M485P3X) Installation Instructions
This document describes how to install a DTAM Micro terminal and connect power.
Wiring and Safety Guidelines
Enclosures
Clearances
Mounting Dimensions
Installation
Wire and Cable Length Restrictions
Connecting Power
Powerup Sequence
Upload/Download DIP Switch Settings
Upload/Download Connections
Connecting to Devices
Specifications
Agency Ratings
European Union Directive Compliance
For more information on the DTAM Micro terminal, refer to the following publications.
DTAM Micro User Manual
2707-803
DTAM Micro DeviceNet Operator Interface 2707-803.5
These publications are available for viewing and download from the Rockwell Automation/Allen-Bradley Website at www.ab.com.
DTAM Micro Operator Interface2

Wiring Guidelines

Safety Guidelines

Here are some recommendations on how to reduce electromagnetic noise on the communications connections:
Careful wire routing helps reduce or minimize electrical noise.
Route incoming power to the terminal by a separate path from the communications cables.
Do not run communications wiring and power wiring in the same
conduit.
Where communications and power wiring must cross, make their
intersection perpendicular.
Proper grounding helps to reduce the effects of noise due to
Electromagnetic Interference (EMI). To avoid problems caused by EMI, all cables must be shielded and grounded at one end. Grounding is also an important safety measure in electrical installations. A source for grounding recommendations is the National Electrical Code published by the National Fire protection Association of Boston Massachusetts.
Install the DTAM Micro terminal using publication NFPA 70E, Electrical Safety Requirements for Employee Workplaces as a guide.
Be certain to follow all directions for installing and connecting DC power to the DTAM Micro.
When used in a hazardous environment, the ultimate enclosure must be in accordance with Class 1, Division 2 wiring methods as described in the National Electrical Code (ANSI/NFPA 70) and the Canadian Electrical Code.
All peripheral equipment must be suitable for the location in which it is used.
Use only a Class 2 power source as described in the National Electrical Code (ANSI/NFPA 70) and Canadian Electrical Code. The recommended AC to DC adapters (Catalog No. 1747-NP1 and Catalog No. 1747-NP2) meet this requirement.
The DTAM Micro contains no user serviceable parts.
ATTENTION: EXPLOSION HAZARD: SUBSTITUTION OF
!
COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS 1, DIVISION 2.
RISQUE D’EXPLOSION: LA SUBSTITUTION DE COMPOSANTS PEUT RENDRE CE MATÉRIEL INACCEPTABLE POUR LES EMPLACEMENTS DE CLASSE 1, DIVISION 2.
DTAM Micro Operator Interface 3
ATTENTION CAUTION: USE ONLY WITH CLASS 2 POWER
!
!
SOURCE LIMITED TO 30 VDC OPEN CIRCUIT AND 8A SHORT CIRCUIT.
ATTENTION: UTILISER AVEC UNE TENSION D’ALIMENTATION CLASSE 2 DE 30 VCC MAXI EN CIRCUIT OUVERT AVEC UN COURANT DE COURT-CIRCUIT DE 8A MAXI.
DANGER EXPLOSION HAZARD: DO NOT CONNECT OR
DISCONNECT EQUIPMENT WHILE CIRCUIT IS LIVE UNLESS AREA IS KNOWN TO BE NON-HAZARDOUS RISQUE D’EXPLOSION: NE PAS BRANCHER OU DEBRANCHER TANT QUE LE CIRCUIT EST SOUS TENSION, A MOINS QU’IL NE S’AGISSE D’UN EMPLACEMENT NON DANGEREUX.

Enclosures

The terminal must be mounted in a panel or enclosure to protect the internal circuitry. The terminal meets NEMA Type 4, 12, 13 (indoor use only) ratings only when mounted in a panel or enclosure with the equivalent rating.
Allow enough spacing within an enclosure for adequate ventilation. For some applications, you may have to consider heat produced by other devices within a panel. The ambient temperature around the terminal must be maintained between 32_ – 131_ F (0_ – 55_ C).
Make sure that provisions are made for accessing the back panel of the terminal for wiring, routine maintenance, and troubleshooting.
DTAM Micro Operator Interface4

Equipment Required

Clearances

Other than the tools required to make the panel cutout, the tools required for installation are:
7mm (M4) deep well socket wrench or nut driver
small slotted screwdriver
torque wrench (in. / lbs).
The terminal is tightened against the panel with six self-locking nuts.
Make sure that you leave adequate room, as shown in Figure 1, for mounting, air flow, cabling, and access to DIP switches.
Figure 1 Recommended Clearances
Leave 3 inches (76.2 mm)
for Mounting, Air Flow, and
access to DIP Switches.
Leave 3 inches (76.2 mm) for
communications port connector.
DTAM Micro Operator Interface 5

Mounting Dimensions

Figure 2 shows the mounting dimensions of the terminal.
Figure 2 Mounting Dimensions in Inches (Millimeters)
Back View
3.9
(99.1)
6.9
(175.3)
Bottom View
5.4
(137.2)
5.4
(137.2)
1.8
(45.7)
Loading...
+ 11 hidden pages