Rockwell Automation 2707-L8PxX, 2707-L40PxX, 2707-V40PxX User Manual

DTAM Plus Operator Interface

(Catalog Nos. 2707-L8PxX, -L40PxX, -V40PxX) Installation Instructions
This document describes how to install a DTAM Plus terminal and connect power.
Wiring and Safety Guidelines
Enclosures
Equipment Required
Mounting Dimensions
Installation
Wire and Cable Length Restrictions
Connecting Power
Powerup Sequence
Upload/Download DIP Switch Settings
Upload/Download Connections
Connecting to Devices
Specifications
Agency Ratings
European Union Directive Compliance
For more information on the DTAM Plus terminal, refer to the following publications.
DTAM Plus User Manual 2707-UM001B–EN–P
Intrinsically Safe DTAM Plus (2707-L40P4) 2707-800.6
DTAM Plus DeviceNet Operator Interface 2707-800.7
These publications are available for viewing and download from the Rockwell Automation/Allen-Bradley Website at www.ab.com.
2

Wiring Guidelines

Safety Guidelines

Here are some recommendations on how to reduce electromagnetic noise on the communications connections:
Careful wire routing helps reduce or minimize electrical noise.
Route incoming power to the terminal by a separate path from the communications cables.
Do not run communications wiring and power wiring in the same
conduit.
Where communications and power wiring must cross, make their
intersection perpendicular.
Proper grounding helps to reduce the effects of noise due to
Electromagnetic Interference (EMI). To avoid problems caused by EMI, all cables must be shielded and grounded at one end. Grounding is also an important safety measure in electrical installations. A source for grounding recommendations is the National Electrical Code published by the National Fire protection Association of Boston Massachusetts.
Install the DTAM Plus using publication NFPA 70E, Electrical Safety Requirements for Employee Workplaces as a guide.
Be certain to follow all directions for installing and connecting power to the DTAM Plus.
When used in a hazardous environment, the ultimate enclosure must be in accordance with Class 1, Division 2 wiring methods as described in the National Electrical Code (ANSI/NFPA 70) and the Canadian Electrical Code.
All peripheral equipment must be suitable for the location in which it is used.
For P1 powered units, use only a Class 2 power source as described in the National Electrical Code (ANSI/NFPA 70) and the Canadian Electrical Code.
3
ATTENTION: EXPLOSION HAZARD: SUBSTITUTION OF
!
!
!
COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS 1, DIVISION 2.
RISQUE D’EXPLOSION: LA SUBSTITUTION DE COMPOSANTS PEUT RENDRE CE MATÉRIEL INACCEPTABLE POUR LES EMPLACEMENTS DE CLASSE 1, DIVISION 2.
ATTENTION: USE P1 POWERED UNITS ONLY WITH CLASS 2 POWER SOURCE LIMITED TO 30 VDC OPEN CIRCUIT AND 8A SHORT CIRCUIT.
ATTENTION: UTILISER AVEC UNE TENSION DALIMENTATION CLASSE 2 DE 30 VCC MAXI EN CIRCUIT OUVERT AVEC UN COURANT DE COURT-CIRCUIT DE 8A MAXI.
ATTENTION: EXPLOSION HAZARD: DO NOT CONNECT OR
DISCONNECT EQUIPMENT WHILE CIRCUIT IS LIVE UNLESS AREA IS KNOWN TO BE NON-HAZARDOUS.

Enclosures

RISQUE D’EXPLOSION: NE PAS BRANCHER OU DEBRANCHER TANT QUE LE CIRCUIT EST SOUS TENSION, A MOINS QU’IL NE S’AGISSE DUN EMPLACEMENT NON DANGEREUX.
The terminal must be mounted in a panel or enclosure to protect the internal circuitry. The terminal meets NEMA Type 4, 12, 13 (indoor use only) or 4X (indoor 2707-V40P2N, -V40P2NR) ratings only when mounted in a panel or enclosure with the equivalent rating.
Allow enough spacing within an enclosure for adequate ventilation. For some applications, you may have to consider heat produced by other devices within a panel. The ambient temperature around the terminal must be maintained as specified. See Specifications Section for ratings.
Make sure that provisions are made for accessing the back panel of the terminal for wiring, routine maintenance, and troubleshooting.
4

Equipment Required

Clearances

Other than the tools required to make the panel cutout, the tools required for installation are:
7mm (M4) deep well socket wrench or nut driver
small slotted screwdriver
torque wrench (in. / lbs).
The terminal is tightened against the panel with six self-locking nuts.
Make sure that you leave adequate room, as shown in Figure 1, for mounting, air flow, cabling and access to DIP switches.
Figure 1 Recommended Clearances
Leave 3 inches (76.2 mm)
for Mounting, Air Flow, and
access to DIP Switches.
Leave 3 inches (76.2 mm) for
communications port connectors.
5

Mounting Dimensions

7.876
(200.1)
Figure 2 shows the mounting dimensions of the terminal.
Figure 2 Mounting Dimensions in Inches (Millimeters)
Back View
8.50
(215.9)
2.0
(50.8)
5.5
(139.7)
6.9
(175.3)
Bottom View
5.5
(139.7)
2.35
(59.7)
Remote I/O and DN VersionsRS-232 / RS-485 Versions
6

Installation

To install the DTAM Plus Operator Module:
ATTENTION:
!
1. Using the cutout template shown in Figure 3, cut an opening in the panel. Remove any sharp edges or burrs.
2. Make sure the sealing gasket is properly positioned on the DTAM Plus. This gasket forms a compression type seal. Do not use sealing compounds.
Disconnect all electrical power from the panel before making cutout.
Make sure that area around panel cutout is clear. Take precautions so that metal filings or other debris do not
fall into the DTAM Plus ventilation slots or enter any components that may already be installed in panel.
Make sure that no objects are inserted or fall into the terminal through the ventilation slots or DIP switch access hole.
Failure to follow these warnings may result in personal injury or damage to the panel components.
3. Place the DTAM Plus in the panel cutout.
ATTENTION:
!
4. Install the six self locking mounting nuts hand tight.
5. Alternately tighten the mounting nuts until the DTAM Plus is held firmly against the panel. Tighten mounting nuts to a torque of 8 to 10 inch-pounds. Do not over-tighten nuts.
Mounting nuts must be tightened to a torque of 8 to 10 inch pounds to provide a proper seal and to prevent potential damage to the terminal. Allen-Bradley assumes no responsibility for water or chemical damage to the terminal or other equipment within the panel enclosure because of improper installation.
Figure 3 Panel Cutout Dimensions in Inches (Millimeters)
7
8

Wire and Cable Length Restrictions

Connecting Power

The following wire and cable length restrictions apply to DTAM products that are CE marked when used in installations that require compliance to European EMC Directive 89/336:
DC Power Wiring 10 meters Ground Terminal Wire 3 meters Communication Cables 30 meters
These restrictions apply to catalog numbers 2707–L8P1 Series D, 2707–L40P1 Series D and 2707–V40P1 Series D.
The DTAM Plus accepts supply voltages in the following ranges depending upon the power supply designation.
Versions with P1 power supply, accept 15-23V AC (47 to 440 Hz)
or 20-30V DC
Series D versions with P1 Power supply only, accepts 20–30 V
DC
Versions with P2 power supply, accept 85-265V AC (47 to 440
Hz) or 110-300V DC
Versions with P4 power supply, accept 11-13V DC
To connect the DTAM Plus to a power source:
ATTENTION: Verify that the power is disconnected from the
power source before wiring. Failure to disconnect power may
!
result in electrical shock. Make sure that the supply voltage to the DTAM Plus is correct,
refer to the voltage label on back of unit. The incorrect voltage may damage the DTAM Plus.
Do not overtighten the power connector screw terminals. Overtightening the terminals may damage the DTAM Plus.
1. Make sure that the voltage source is not turned on.
2. Use AWG#16 or #14 stranded wire to connect the DTAM Plus screw terminals to the power source (see below).
Note: The power supply terminal block on the DTAM Plus is not removeable.
Figure 4 Power Connections
9
(40K Remote I/O Version Shown, Others Are Similar)
DTAM Plus
For DC connections, connect the Positive Lead to Hot and the Negative lead to NEU.
3. Connect communications cabling as described in Connecting to Devices section on page 15.
4. Apply voltage and verify the DTAM Plus powerup sequence as described in the next section.
10
ÎÎÎ
ÎÎÎ

Powerup Sequence

The powerup sequence is automatic. The sequence depends upon the setting of DIP switch position SW-1 (upload / download enable). The DTAM Plus is shipped with SW-1 On.
Powerup Sequence (DIP Switch SW-1 ON)
The following steps show the powerup sequence if DIP switch SW-1 is ON.
1. The DTAM Plus verifies the system memory checksum, program checksum, and system RAM. When done, the result is displayed with the current DIP switch settings.
Memory Check: pass
DIP Switch: 101000 40K User Memory
2. The display is tested, every pixel of the display is turned on.
Use this display to verify that all pixels are operational.
3. The firmware version number and type of communication port(s) is displayed (PPort, RS-232, RS-485 or Remote I/O).
Operator Interface Core: X.XX RS-485 PPORT
4. The DTAM Plus waits for an application download.
Programming Mode
Waiting Up/Download
You cannot operate the DTAM Plus keypad while in the upload/download mode. The DTAM Plus is waiting for upload/download operations with a personal computer running the DTAM Programming Software (DPS).
11
Powerup Sequence (DIP Switch SW-1 OFF)
The following steps show the powerup sequence if DIP switch SW-1 is OFF.
1. The DTAM Plus verifies the system memory checksum, program checksum, and system RAM. After the test is completed, the result is displayed with the current DIP switch settings.
Checksum: passed DIP Switch: 001000 RAM: pass 40K User Memory
2. The display is tested, every pixel of the display is turned on.
Use this display to verify that all pixels are operational.
3. The operating system firmware release number and protocol is displayed (PLC5-DF1 or AB DH-485 or Remote I/O).
Allen-Bradley Operator Interface DTAM Plus (c) 1996 FRN: 01.20 AB-RIO
4. On 40K versions with a clock, the current time setting is displayed.
DATE: W ed Aug 12 98 TIME: 01:12:47
Diagnostics Complete
5. The first application screen displays. When the DTAM Plus is powered up for the first time you see:
Bul. 2707 DTAM Plus
No Program Loaded
12

Upload / Download DIP Switch Settings

Before you can upload or download an application, you must verify that DIP switch SW-1 is ON. (DTAM Plus is shipped in this position).
To access the DIP switch, remove the cover from the access hole on the back of the DTAM Plus (align cover tabs with notches in hole to remove). The DTAM Plus is shipped without the cover installed, you can find it in the hardware bag.
On versions with both a Comm and a Printer port, you can transfer applications using the communication port or the printer port:
Set DIP switch position SW-6 ON to select the Comm port
Set DIP switch position SW-6 OFF to select the Printer port
Note: Turn DIP switch SW-6 ON after downloading through the printer port. This allows communications to occur with the controller.
All other versions of the DTAM Plus use a single port to transfer applications; either the Comm port or the Printer port.
If using the Comm port, make sure DIP switch SW-2 is in the correct position (OFF = RS-232 download, ON = RS-485 download).
Side View
ON =
DIP Switch SW-1
must be ON.
When using the RS-485 / RS-232 Comm Port for file download, set SW-2 to the correct port selection.
ON = RS-485 OFF = RS-232
123456
OPEN
On Versions with a Printer Port DIP Switch SW-6 must be:
ON to download using the Comm port.
OFF to download using the Printer port (only if the Comm port is connected to a host).
13

Upload / Download RS-232 Connections

Remote I/O Version With
Printer Port RS-232 Connector
(9 Pin Male)
Gender Adapter
Cable
(2707-NC2)
T o Computer RS-232 Port
Comm 1 or 2
Printer Port
Power Connector
Remote I/O Connector
To connect a DTAM Plus RS-232 port to a computer, use the RS-232 Upload/Download cable (Catalog No. 2707-NC2). Use the communications or printer port (see below). You may need a 9-to-25 pin adapter to connect the cable to your computer. A male to female gender adapter is required to connect the cable to the printer port or you can create your own cable. Appendix B of the DTAM Plus User Manual (2707-UM001B–EN–P).
(T erminal Block)
Remote I/O Version With
Comm Port
Remote I/O Connector
(T erminal Block)
Cable
(2707-NC2)
Power Connector
Comm Port Connector
(9 Pin Female)
To Computer RS-232 Port
Comm 1 or 2
Versions with a Comm Port Only Versions with a Comm Port
and Printer Port
Cable
(2707-NC2)
Power Connector
Comm Port Connector
(9 Pin Female)
T o Computer RS-232 Port
Printer Port RS-232 Connector
(9 Pin Male)
Gender Adapter
Cable
(2707-NC2)
Power Connector
Cable
(2707-NC2)
Comm 1 or 2
T o Computer RS-232 Port
Comm 1 or 2
Comm Port Connector
(9 Pin Female)
Use Either Port
(Set DIP Switch #6 to
correspond)
14

Upload / Download RS-485 Connections

Versions with a Comm Port
Power Connector
RS-485 / RS-232 Connector
(9 Pin Female)
Its recommended that you use the RS-232 port for transferring applications. On DTAM Plus versions with a Comm (RS-485 / RS-232) port, you can also download applications using an RS-485 connection.
Versions with a Comm Port
and Printer Port
Power Connector
Printer Port RS-485 / RS-232 Connector
(9 Pin Female)
Create your own cable
To Computer RS-485 Port or Converter
Remote I/O Version With
Comm Port
Remote I/O Connector
(T erminal Block)
Power Connector
RS-485 / RS-232 Connector
(9 Pin Female)
To download through the RS-485 port, you must:
set DIP switch position SW-2 ON
create a communication cable. The RS-485 port connections are:
DTAM Plus Comm Port
RS-485/RS-232 Connector
Pin 1 = Tx485 ­Pin 2 = Tx485 + Pin 3 = Rx485 ­Pin 4 = Rx485 +
15

Connecting to Devices

To connect the DTAM Plus to an RS-232 device:
1. Make sure that the DTAM Plus is not connected to a voltage source.
2. Use the proper cabling to connect the DTAM Plus Comm port to the port of the controller (PLC-5 channel 0 or SLC 5/03, 5/04 or 5/05 RS-232 port).
Use cable, Catalog No. 2707-NC3 for PLC-5 channel 0
connection.
Use cable, Catalog No. 1747-CP3 for SLC 5/03, 5/04 or 5/05
port connection. This cable requires a 9-pin female to male gender adapter.
If you need to make your own cable, refer to the cable diagrams in Appendix B of the DTAM Plus User Manual (2707–UM001B–EN–P). The maximum recommended cable length is 50 feet (15.2 meters).
3. Make sure that the communication parameters of the DTAM Plus match the host device.
4. Apply power and verify that communications are established.
To connect the DTAM Plus terminal to an RS-485 device:
1. Make sure that the power to the DTAM Plus is off.
2. Use the proper cabling to connect the DTAM Plus communications port to the port of the controller (PLC-5 channel 0 or SLC 5/03, 5/04 or 5/05 RS-232 port).
Use cable, Catalog No. 2707-NC4 for PLC-5 channel 0
RS-422 connection
Use cable, Catalog No. 2707-NC5 for PLC-5 channel 0
RS-232 connection. The 2707-NC5 cable converts the signals from the RS-485 port to RS-232 levels.
Use cable, Catalog No. 1747-CP3 for SLC 5/03, 5/04 or 5/05
port connection
If you need to make your own cable, refer to the connection diagrams in Appendix B of the DTAM Plus User Manual (2707–UM001B–EN–P). The maximum cable length is 200 feet (60.8 meters).
Important: The DH-485 network cable requires proper shielding, grounding, and termination. Refer to Data Highway / Data Highway Plus / Data Highway-485 Cable Installation Manual (1770-6.2.2).
3. The DH-485 connectors are not electrically isolated. If electrical isolation is required, use Link Couplers (Catalog No. 1747-AIC).
ATTENTION: Electrical isolation using Link Couplers (Catalog No. 1747-AIC) is required in applications where the distance
!
between the DTAM Plus terminal and the SLC is greater than 6.5 feet (2 meters).
16
4. Make sure that the communication parameters of the DTAM Plus terminal match the host device.
5. Apply power and verify that communications are established.
To connect the DTAM Plus terminal to Remote I/O:
1. Make sure that the power to the DTAM Plus is off.
2. The Remote I/O port of the DTAM Plus provides access via a Remote I/O link directly to a controller or subscanner. Use cable (Catalog No. 1770–CD) Belden 9463 for all Remote I/O connections. Refer to Publication 1770–4.1 for detailed grounding and wiring guidelines. The User Manual for your controller or subscanner will also provide cabling instructions.
3. Make sure that the communication parameters of the DTAM Plus terminal match the host device.
4. Apply power and verify that communications are established.
17

DTAM Plus Specifications

Display
Column and Character 4 lines x 20 characters Display Technology
LCD (2707-L versions) Twisted-nematic type with adjustable
LED (yellow) backlighting
VFD (2707-V versions) Vacuum Fluorescent Display with viewing
distance that exceeds 25 feet (7.6 meters)
Backlight Settings for LCD Version
(via Keypad) Four (0,33,66 and 100%)
Contrast Ratio 10:1 Contrast/Brightness Settings (Keypad)
LCD (2707-L versions) 4 settings VFD (2707-V versions) 2 settings
Display Size (H x W)
LCD (2707-L versions) 1.0 x 3.0 in (25.2 x 76.0 mm) VFD (2707-V versions) 1.3 x 3.9 in (33.0 x 99.0 mm)
Character Size (H x W) 0.19 x 0.12 in (4.75 x 2.95 mm)
Keypad
Keypad Type Embossed, sealed membrane Tactile Feedback Stainless steel dome Operation Force 12 oz. ± 3 oz. (340 grams ± 85 grams) Operational Life 1 million cycles
Electrical
Comm Port RS-485 or RS-232C (configurable) Printer Port (40K memory units) RS-232C Serial Communication Distances
RS-485 4,000 ft (1219 meters) maximum with the
Link Coupler (Catalog No. 1747-AIC) RS-232C 50 ft (15 meters) maximum RS-422 200 ft (61 meters) maximum to a PLC-5
Remote I/O Communication Distances
57.6K 10,000 ft (2800 meters) maximum
115.2K 5,000 ft (1400 meters) maximum
230.4K 2,500 ft (700 meters) maximum
Voltage, Current, Fusing Requirements
Power Supply
P1 15 - 23V AC, 47 - 440 Hz or 20 - 30V DC 800 mA max. 1 amp P2 85 - 265V AC, 47 - 440 Hz or 110 - 300V DC 300 mA max. 1/2 amp P4 11 - 13V DC 250 mA max. 1/2 amp
Port Isolation
Communication Port 500V isolation Printer Port 500V isolation
Voltage Current Fuse
18
Environmental
Ambient Temperature Rating
Operating
LCD Display 0 to VFD Display 0 to
+45° C (32 to 113° F) +60° C (32to 140° F)
Storage -20 to +85° C (-4 to 185° F)
Relative Humidity 5 to 95%, noncondensing
Mechanical
Dimensions (Approximate)
Height: 7.6 inch (193.0 mm) Width: 5.5 inch (139.7 mm) Depth:
RS-232 / RS 485 Versions 1.8 inch (45.7 mm) Remote I/O Versions 2.35 inch (59.7 mm)
Front Panel Size:
Height: 8.5 inch (215.9 mm) Width: 6.5 inch (165.1 mm)
Weight
All except 2707-V40P2N,
-V40P2NR 2.1 lbs (0.95 kg) 2707-V40P2N, -V40P2NR 4.6 lbs (2.09 kg)

Agency Ratings

LED Indicators
RUN LED Green Alarm LED Red Function LED Yellow
NEMA Type 4, 12, 13 (indoor use only) NEMA Type 4X (2707-V40P2N, 2707-V40P2NR only)
Class 1 Division 2 Groups A, B, C, D, hazardous locations
Class 1 Division 2 Groups A, B, C, D, hazardous locations
Class 1 Division 2 Groups C & D, hazardous locations Temperature Code T3C (2707–L40P4 only)
Series B or higher – Cat. Nos. 2707–L8P1R, –L8P2R, –L40P1R, –L40P2R, –V40P1R, –V40P2R, –V40P2NR, –L40P4, –L8P1D, –L8P2D, –L40P1D, –L40P2D, –V40P1D, –V40P2D, –V40P2ND Series C or higher – Cat. Nos. 2707–L8P1, –L8P2, –L40P1, –L40P2, –V40P2, –VP40P1, –VP40P2, –V40P2N Series D Only – Cat. Nos. 2707–L8P1, –L40P1, –V40P1
19
European Union Directive Compliance
If this product is installed within the European Union or EFTA regions, the following regulations apply:
This apparatus is tested to meet Council Directive 89/336 Electromagnetic Compatibility (EMC) standards:
EN50081–2 Class A (Industrial) Emissions
EN50082–2 Class A (Industrial) Immunity
EN61000–6–2 Class A (Industrial) Immunity (Series D Only;
2707L8P1, L40P1, V40P1: Series C Only; 2707L8P2,L40P2, V40P2, V40P2N)
According to these Standards, the factor which determines, for EMC pruposes, whether an apparatus is deemed to be “Industrial” or Residential, commercial and light industrial, is given in Clause 1 of EN50081–2 as follows:
Apparatus covered by this standard is not intended for connection to a public mains network, but is intended to be connected to a power network supplied from a high– or medium–voltage transformer dedicated for the supply of an installation feeding a manufacturing or similar plant.
The product described in this document is intended solely for use in an industrial environment as defined above. When installed in Europe, any other application is in contravention of the European Union Directives, and a breach of those laws.
Publication 2707-IN005C-EN-P - July 2002 PN 41061-113-01(3)
Supersedes Publication 41061-11 3-01(1) Copyright © 2002 Rockwell Automation. A ll rights reserved. Printed in the U.S.A.
Loading...