Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to
familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws,
and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required
to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
Identifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Allen-Bradley, CompactLogix, ControlFLASH, ControlLogix, HPK-Series, Kinetix, Logix5000, MP-Series, PanelView, POINT I/O, RDD-Series, RSLinx, RSLogix, Stratix 5700, Studio 5000, Studio 5000 Automation
Engineering an d Design Environment, Studio 5 000 Logix Desig ner, Rockwell Automation, Ro ckwell Software, and T L-Series are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Summary of Changes
This manual contains new and updated information.
TopicPag e
Replaced catalog number string 2198-Hxxx-ERS with 2198-Hxxx-ERSx when there’s no need to
distinguish between -ERS or -ERS2.
Added footnotes and other text to note that STO connector does no t apply to 2198-Hxxx-ERS2 drives.
Added references to the Hiperface-to-DSL (series B) feedback converter kit as needed.
10Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
Preface
About This Publication
Audience
Conventions Used in This
Manual
This manual provides detailed installation instructions for mounting, wiring, and
troubleshooting the Kinetix® 5500 servo drives, and system integration for your
drive and motor/actuator combination with a Logix5000™ controller.
This manual is intended for engineers or technicians directly involved in the
installation and wiring of the Kinetix 5500 drives, and programmers directly
involved in the operation, field maintenance, and integration of these drives with
the EtherNet/IP communication module or controller.
If you do not have a basic understanding of Kinetix 5500 servo drives, contact
your local Rockwell Automation sales representative for information on available
training courses.
These conventions are used throughout this manual:
• Bulleted lists such as this one provide information, not procedural steps.
• Numbered lists provide sequential steps or hierarchical information.
• Catalog number string 2198-Hxxx-ERSx is used when there’s no need to
distinguish between -ERS or -ERS2 servo drives.
Studio 5000 Environment
The Studio 5000 Automation Engineering and Design Environment™ combines
engineering and design elements into a common environment. The first element
in the Studio 5000® environment is the Logix Designer application. The Logix
Designer application is the rebranding of RSLogix™ 5000 software and continues
to be the product to program Logix5000 controllers for discrete, process, batch,
motion, safety, and drive-based solutions.
The Studio 5000 environment is the foundation for the future of Rockwell
Automation® engineering design tools and capabilities. The Studio 5000
environment is the one place for design engineers to develop all of the elements
for their control system.
Rockwell Automation Publication 2198-UM001D-EN-P - May 201411
Preface
Additional Resources
These documents contain additional information concerning related products
from Rockwell Automation.
ResourceDescription
Kinetix 5500 servo drives Installation Instructions, publication 2198-IN001Information on mounting and wiring the Kinetix 5500 servo drive.
ControlFLASH Firmware Upgrade Kit User Manual, publication 1756-QS105
National Electrical Code, published by the National Fire Protection Association of Boston, MAAn article on wire sizes and types for grounding electrical equipment.
Rockwell Automatio n Industrial Automation Glossary, publication AG-7. 1
Information on installing and wiring the Kinetix 5500 motor feedback connector kit.
Information on installing and wiring the Kinetix5500 AC line filters.
Information on installing and wiring the Kinetix 5500 capacitor module.
Information on installing and wiring Kinetix 300 shunt resistors.
Information, examples, and techniques designed to minimize system failures caused
by electrical noise.
Overview of Kinetix servo drives, motors, actuators, and motion accessories designed
to help make initial decisions for the motion control products best suited for your
system requirements.
System design guide to select the required (drive specific) drive module, power
accessory, feedback connector kit, and motor cable catalog numbers for your
Kinetix 5500 drive and Kinetix VP motor motion control system.
Product specifications for Kinetix VP (Bulletin VPL, VPF, and VPS), MP-Series™
(Bulletin MPL, MPM, MPF, and MPS), Kinetix 6000M (Bulletin MDF), TL-Series™,
RDD-Series™, and HPK-Series™ rotary motors.
Product specifications for MP-Series (Bulletin MPAS ballscrew, MPAR, and MPAI) and
LDAT-Series linear actuators.
Product specifications for Kinetix Integrated Motion over the EtherNet/IP network,
Integrated Motion over sercos interface, EtherNet/IP networking, and component
servo drive families.
Product specifications for Bulletin 2090 motor and interface cables, low-profile
connector kits, drive power components, and other servo drive accessory items.
Motion Analyzer application analysis software for drive/motor sizing.
Online product selection and system configuration tools, including AutoCAD (DXF)
drawings.
For declarations of conformity (DoC) currently available from Rockwell Automation.
Information on configuring and troubleshooting your ControlLogix® and
CompactLogix™ EtherNet/IP network modules.
Information on designing, installing, programming, or troubleshooting control
systems that use GuardLogix 5570 controllers.
Information for development, operation, or maintenance of a GuardLogix 5570
controller-based safety system that uses the Studio 5000 Logix Designer™ application.
Information regarding Allen-Bradley safety products, including safety relays, light
curtain, and gate interlock applications.
For ControlFLASH™ information not specific to any drive family.
A glossary of industrial automation terms and abbreviations.
You can view or download publications at
http://www.rockwellautomation.com/literature
technical documentation, contact your local Allen-Bradley distributor or
Rockwell Automation sales representative.
12Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
. To order paper copies of
Chapter 1
Start
Use this chapter to become familiar with the design and installation requirements
for Kinetix 5500 drive systems.
Top icPa ge
About the Kinetix 5500 Servo Drive System14
Typical Ha rdware Configurations15
Typical Communication Configurations20
Safe Torque-off Configurations23
Catalog Number Explanation26
Agenc y Compliance27
Rockwell Automation Publication 2198-UM001D-EN-P - May 201413
Chapter 1Start
About the Kinetix 5500
Servo Drive System
The Kinetix 5500 servo drives are designed to provide a Kinetix Integrated
Motion solution for your drive and motor/actuator application.
Table 1 - Kinetix 5500 Drive System Overview
Drive System
Component
Kinetix 5500
Servo Drives
Kinetix 5500
Capacitor Module
Shared-bus
Connector Kits
Feedba ck
Connector Kit
Hiperface to DSL
Converter Kit
I/O Connector Kits
Connector Sets
Logix5000
Controller Platform
Studio 5000
Environment
Rotary Servo
Motors
Linear Actuators
Induction motorsN/AInduction motors with open loop volts/hertz frequency control are also supported.
Cables
AC Line Filters
24V DC Power
Supply
External Shunt
Resistors
Cat. No.Description
2198-Hxxx-ERS
2198-Hxxx-ERS2Same power structures with standalone and multi-axis bus-sharing capability. Safe torque-off via the EtherNet/IP network.
2198-CAPMOD-1300
2198-H040-x-xInput wiring connectors and DC bus T-connector for frame 1 and 2 servo drives.
2198-H070-x-xInput wiring connectors and DC bus T-connector for frame 3 servo drives.
2198-KITCON-DSLReplacement feedback connector kit with 2-pin connector plug and grounding plate inside the connector housing.
2198-H2DCK
2198-KITCON-IOSPReplacement I/O connector kit (spring clamp) for I/O (IOD) connector.
2198-KITCON-IOSCReplacement I/O connector kit (screw terminal) for I/O (IOD) connector.
2198-KITCON-PWR40Replacement connector set, 40 A, for frame 1 and frame 2 drives.
2198-KITCON-PWR70Replacement connector set, 70 A, for frame 3 drives.
2198-KITCON-CAP1300Replacement connector set, 40 A, for capacitor module.
2090-CSxM1DF-xxAxxxBulletin 2090 single-cable for motor power, feedback, and 24V DC brake power with Kinetix VP motors.
2090-CFBM7DF-CEAxxx Bulletin 2090 motor feedback cables for MP-Series motors and actuators.
2090-CPxM7DF-xxAxxxBulletin 2090 motor power/brake cables for MP-Series motors and actuators.
1585J-M8CBJM-xEthernet cables are available in standard lengths. Shielded cable is recommended.
2198-DB08-F
2198-DB20-F
2198-DB42-F
1606-XLxxxBulletin 1606 24V DC power supply for control circuitry, digital inputs, safety, and motor brake.
2097-R6 and 2097-R7Bulletin 2097 external passive shunt resistors for when the drive’s internal shunt capability is exceeded.
200V-class (single-phase or three-phase) and 400V-class (three-phase) drives operate in standalone and multi-axis shared AC,
shared DC, shared AC/DC, and shared AC/DC hybrid configurations. Modules are zero-stacked from drive-to-drive and use the sharedbus connection system to extend power in multi-axis configurations. Safe torque-off via hardwired (STO) connector.
Use for energy storage and/or to improve performance in applications producing regenerative energy and requiring shorter duty
cycles (1360 μf). Modules are zero-stacked side-by-side with servo drives and use the shared-bus connection system to extend
power.
Use for Hiperface-to-DSL feedback conversion with 400V-class MP-Series (Bulletin MPL, MPM, MPF, and MPS) rotary motors and
MP-Series (Bulletin MPAS ballscrew, MPAR, MPAI) linear actuators. Series B or later converter kit is required for LDAT-Series linear
thrusters and 200V-class MP-Series motors and actuators.
CompactLogix 5370 controllers with Integrated Motion on the EtherNet/IP network. Linear, ring, and star topology is supported.
ControlLogix 1756-L7x and GuardLogix 1756-L7xS controllers with Integrated Motion on EtherNet/IP networks. Linear, device-level
ring (DLR), and star topology is supported.
Studio 5000 Logix Designer application, version 21.00 or later, provides support for programming, commissioning, and maintaining
the CompactLogix and ControlLogix controller families. Version 24.00 or later is required for 2198-Hxxx-ERS2 servo drives.
Compatible rotary motors include 200V and 400V-class Kinetix VP (Bulletin VPL, VPF, and VPS).
C
ompatible rotary motors include 200V and 400V-class MP-Series (Bulletin MPL, MPM, MPF, and MPS) when used with the
Hiperface-to-DSL feedback converter kit.
Compatible linear actuators include 200V and 400V-class MP-Series (Bulletin MPAS ballscrew, MPAR, and MPAI) and LDAT-Series
when used with the Hiperface-to-DSL feedback converter kit.
Bulletin 2198 three-phase AC line filters are required to meet CE and available for use in all Kinetix 5500 drive systems.
14Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
StartChapter 1
Single-phase or
Three-p hase
Input Power
Bulletin 2090
Single Motor Cable
Line
Disconnect
Device
Input
Fusin g
2198-Hxxx-ERSx Drive
(front view)
2097-Rx
Shunt Resistor
(optional component)
Kinetix VP (Bulletin VPL, VPF,
and VPS) Rotary Motors
(VPL-Bxxxx motor is shown)
2198-Hxxx-ERSx Drive
(top view)
AC Input Power
Bonded Cabinet
Ground Bus
2198-KITCON-DSL (shown)
Motor Feedback Connector Kit
or 2198-H2DCK Hiperface-to-DSL
Feedback Converter Kit
Mains AC and 24V input
wired to standard input
connectors.
2198-DBxx-F
AC Lin e Filter
(required for CE)
Shared DC (DC common bus)
Shared 24V (control power input)
2198-Hxxx-ERSx Drive (top view)
with 2198-CAPMOD-1300
Capacitor Module
2198-H0x0-x-x shared-bus
connection system for bussharing configurations.
Mains AC input wired to
standard input connector.
Digital Inputs
to Sensors and Control String
1606-XLxxx
24V DC Control, Digital Inputs,
and Motor Brake Power
(customer-supplied)
MP-Series (Bulletin MPAS, MPAR, MPAI) Linear Actuators
In this example, three-phase AC power and 24V control power is shared in a
multi-axis configuration. All drives must have the same power rating (catalog
number).
Figure 2 - Typical Shared AC Installations
(1) Requires the 2198-H2DCK Hiperface-to-DSL feedback converter kit. LDAT-Series linear thrusters and MP-Series (200V-class) motors
and actuators require the 2198-H2DCK (series B or later) converter kit.
In shared AC configurations, all drives must have the same power rating.
Shared AC configurations do not support Bulletin 2198 capacitor modules.
16Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
2097-Rx
Shunt Resistor
(optional component)
Line
Disconnect
Device
Input
Fusing
Three-phase
Input Power
AC Input Power
Bonded Cabinet
Ground Bus
Induction
Rotary Motors
2198-DBxx-F
AC Lin e Filter
(required for CE)
Bulletin 2090
Single Motor Cables
Kinetix 5500 Servo Drives (top view)
(2198-H015-ERS drives shown)
Kinetix 5500 Servo Drives (front view)
(2198-H015-ERS drives shown)
Shared AC (mains AC input)
Shared DC (DC common bus)
Shared 24V (control power input)
In this example, three-phase AC input power, 24V control power, and DC bus
power are shared in a multi-axis configuration. All drives must be the same power
rating (catalog number).
Figure 3 - Typical Shared AC/DC Installations
Allen-Bradley
1606-XL
Power Supply
Input
(1) Requires the 2198-H2DCK Hiperface-to-DSL feedback converter kit. LDAT-Series linear thrusters and MP-Series (200V-class) motors
and actuators require the 2198-H2DCK (series B or later) converter kit.
In shared AC/DC configurations, all drives must have the same power rating
(catalog number).
Rockwell Automation Publication 2198-UM001D-EN-P - May 201417
Chapter 1Start
1606-XL
Power Supply
Input
Allen-Bradley
Kinetix 5500 Servo Drive System (top view)
2097-Rx
Shunt Resistor
(optional component)
Line
Disconnect
Device
Input
Fusin g
Three-phase
Input Power
2198-H040-ERS
Common-bus Leader Drive
AC Input Power
Bonded Cabinet
Ground Bus
Kinetix 5500 Servo Drive System (front view)
2198-H008-ERS
Common-bus
Followe r Drives
2198-DBxx-F
AC Lin e Filter
(required for CE)
Bulletin 2090 Single Motor Cables
Shared DC (DC common bus)
Shared 24V (control power input)
Shared-bus connection system
for bus-sharing configurations.
Digital Inputs
to Sensors and Control String
1606-XLxxx
24V DC Control, Digital Inputs,
and Motor Brake Power
(customer-supplied)
2198-KITCON-DSL (shown)
Motor Feedback Connector Kit
or 2198-H2DCK Hiperface-to-DSL
Feedback Converter Kit
MP-Series (Bulletin MPAS, MPAR, MPAI) Linear Actuators
(1)
MPAS-B9xxx (ballscrew) Linear Stage is Shown
MP-Series (Bulletin MPL, MPM, MPF, MPS) Rotar y Motors
(1)
(MPL-Bxxxx rotary motor is shown)
Kinetix VP (Bulletin VPL, VPF,
and VPS) Rotary Motors
(VPL-Bxxxx motor is shown)
LDAT-Series Linear Thrusters
(1)
(LDAT-Sxxxxxx-xDx linear thruster is shown)
IMPORTANT
Shared DC Common-bus Configurations
In this multi-axis example, the common-bus leader (sourcing) drive receives
three-phase AC input power and supplies DC power to common-bus follower
(sinking) drives. The common-bus leader drive power rating is greater than or
equal to the power rating of each follower drive.
Figure 4 - Typical Shared DC Common-bus Installations
(1) Requires the 2198-H2DCK Hiperface-to-DSL feedback converter kit. LDAT-Series linear thrusters and MP-Series (200V-class) motors
and actuators require the 2198-H2DCK (series B or later) converter kit.
In shared DC common-bus configurations, the leader drive power rating must
be greater than or equal to the power rating of the follower drives.
18Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
StartChapter 1
Kinetix 5500 Servo Drive System (top view)
2097-Rx
Shunt Resistor
(optional component)
Line
Disconnect
Device
Input
Fusing
Three-phase
Input Power
Digital Inputs
to Sensors and Control String
2198-H040-ERS
Common-bus (converter)
Leader Drives
1606-XLxxx
24V DC Control, Digital Inputs,
and Motor Brake Power
(customer-supplied)
AC Input Power
Bonded Cabinet
Ground Bus
Kinetix 5500 Servo Drive System (front view)
2198-H008-ERS
Common-bus (inverter)
Follower Drives
2198-DBxx-F
AC Lin e Filter
(required for CE)
Bulletin 2090 Single Motor Cables
Share d AC (mains AC input)
Shared DC (DC common bus)
Shared 24V (control power input)
Shared-bus connection system for
bus-sharing configurations.
In this multi-axis example, three-phase AC input power is supplied to two
converter drives. The converter drive ratings must be the same, and greater than
or equal to the power ratings of the inverter drives. This parallel converter
configuration increases the DC power supplied to the inverter drives.
Figure 5 - Typical Shared AC/DC Bus Hybrid Installations
Allen-Bradley
1606-XL
Power Supply
Input
(1) Requires the 2198-H2DCK Hiperface-to-DSL feedback converter kit. LDAT-Series linear thrusters and MP-Series (200V-class) motors
and actuators require the 2198-H2DCK (series B or later) converter kit.
Rockwell Automation Publication 2198-UM001D-EN-P - May 201419
In shared AC/DC hybrid configuration, the converter drives must have the same
power rating and must be greater than or equal to the power ratings of the
inverter drives.
Chapter 1Start
CompactLog ix 5370 Cont roller
Logix Designer
Application
1585J-M8CBJM-x
Ethernet (shielded) Cable
1734-AENTR POINT I/O™
EtherNet/IP Adapter
CompactLogix Controller Programming Network
Panel View™ Pl us
Display Terminal
1585J-M8CBJM-OM3
0.3 m (1.0 ft) Ethernet cable
for drive-to-drive connections.
Kinetix 5500 Servo Drive System
Typical Communication
Configurations
The Kinetix 5500 drives support any Ethernet topology including linear, ring,
and star.
These examples feature the CompactLogix 5370 programmable automation
controllers (catalog number 1769-L36ERM) with support for Integrated Motion
over the EtherNet/IP network. Controller features include the following:
• Supports up to 16 axes
• Supports up to 48 devices in linear configurations
• Dual-port connectivity to support device-level ring (DLR) topology
Refer to CompactLogix Controllers Specifications Technical Data, publication
1769-TD005
, for more information on CompactLogix 5370 L1, L2, and L3
controllers.
Linear Topology
In this example, all devices are connected in linear topology. The Kinetix 5500
drives include dual-port connectivity, however, if any device becomes
disconnected, all devices downstream of that device lose communication. Devices
without dual ports must include the 1783-ETAP module or be connected at the
end of the line.
00:00:BC:2E:69:F6
1 (Front)
2 (Rear)
Figure 6 - Kinetix 5500 Linear Communication Installation
1734-AENTR
02
0
POINT I O
Module
Status
Network
Activity
Network
Status
Point Bus
Status
Link 1
Activity/
System
Status
Power
Field
Power
Link 2
Activity/
Status
20Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
StartChapter 1
1 (Front)
2 (Rear)
00:00:BC:2E:69:F6
02
0
1734-AENTR
Module
Status
Network
Activity
Network
Status
Point Bus
Status
System
Power
Field
Power
POINT I O
Link 1
Activity/
Status
Link 2
Activity/
Status
1734-AENTR POINT I/O
EtherNet/IP Adapter
CompactLogix Controller Programming Network
1783-ETAP
Module
1585J-M8CBJM-OM3
0.3 m (1.0 ft) Ethernet cable
for drive-to-drive connections.
Panel View Plus
Display Terminal
Kinetix 5500 Servo Drive System
CompactLogix 5370 Controller
Logix Designer
Application
1585J-M8CBJM-x Ethernet
(shielded) Cable
Ring Topology
In this example, the devices are connected by using ring topology. If only one
device in the ring is disconnected, the rest of the devices continue to
communicate. For ring topology to work correctly, a device level ring (DLR)
supervisor is required (for example, the Bulletin 1783 ETAP device). DLR is an
ODVA standard. For more information, refer to the EtherNet/IP Embedded
Switch Technology Application Guide, publication ENET-AP005
Devices without dual ports, for example the display terminal, require a
1783-ETAP module to complete the network ring.
Figure 7 - Kinetix 5500 Ring Communication Installation
.
Rockwell Automation Publication 2198-UM001D-EN-P - May 201421
Chapter 1Start
1 (Front)
2 (Rear)
00:00:BC:2E:69:F6
1585J-M8CBJM-x
Ethernet (shielded) Cable
1734-AENTR POINT I/O
EtherNet/IP Adap ter
CompactLogix Controller Programming Network
PanelView Plus
Display Terminal
1783-BMS
Stratix 5700™
Switch
1585J-M8CBJM-OM3
0.3 m (1.0 ft) Ethernet cable
for drive-to-drive connections.
Kinetix 5500 Servo Drive System
CompactLogix 5370 Controller
Logix Designer
Application
Star Topology
In this example, the devices are connected by using star topology. Each device is
connected directly to the switch.
Kinetix 5500 drives have dual ports, so linear topology is maintained from driveto-drive, but Kinetix 5500 drives and other devices operate independently. The
loss of one device does not impact the operation of other devices.
Figure 8 - Kinetix 5500 Star Communication Installation
22Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
StartChapter 1
1 (Front)
2 (Rear)
00:00:BC:2E:69:F6
1606-XL
Power Supply
Input
Allen-Bradley
1585J-M8CBJM-x
Ethernet (shielded) Cable
CompactLogix 5370 Controller,
ControlLogix 1756-L7x Controller, or
GuardLogix 1756-L7xS Safety Controller
(CompactLogix controller is shown)
Logix Designer
Application
(version 21.0 or later)
AC Input Power
Safety
Device
2198-Hxxx-ERS Servo Drives
(top view)
2198-Hxxx-ERS Servo Drives
(front view)
Digital Inputs to Sensors and Control String
1606-XLxxx
24V DC Control, Digital Inputs,
and Motor Brake Power
(customer-supplied)
Kinetix VP
Servo Motors
2198-CAPMOD-1300 Capacitor Module
(optional component)
Module Definition
Configured with
Motion-only
Connection
Safe Torque-off
(STO) Connectors
Safe Torque-off
Configurations
Kinetix 5500 servo drives are available with safe torque-off via hardwired
connections or integrated over the EtherNet/IP network. These examples
illustrate the safe torque-off configuration options.
Hardwired Safety Configuration
The 2198-Hxxx-ERS drives use the safe torque-off (STO) connector for
cascading hardwired safety connections from drive-to-drive.
Rockwell Automation Publication 2198-UM001D-EN-P - May 201423
Chapter 1Start
IMPORTANT
1606-XL
Power Supply
Input
Allen-Bradley
LNK1LNK2NET OK
EtherNet/IP
1
2
1585J-M8CBJM-x
Ethernet (shielded) Cable
GuardLogix 1756-L7xS Safety Controller
Logix Designer
Application
(version 24.0 or later)
AC Inp ut Power
2198-Hxxx-ERS2 Servo Drives
(top view)
2198-Hxxx-ERS2 Servo Drives
(front view)
Digital Inputs to Sensors and Control String
1606-XLxxx
24V DC Control, Digital Inputs,
and Motor Brake Power
(customer-supplied)
Kinetix VP
Servo Motors
2198-CAPMOD-1300 Capacitor Module
(optional component)
1783-BMS
Stratix 5700
Switch
Module Definition
Configured with
Motion and Safety
Conne ction
1734-AENTR
POINT Guard I/O
EtherNet/IP Adapter
Safety
Device
Integrated Safety Configurations
The 1756-L7xS GuardLogix safety controller issues the safe torque-off (STO)
command over the EtherNet/IP network and the 2198-Hxxx-ERS2 integrated
safety drive executes the command.
In this example, a single GuardLogix safety controller makes a Motion and Safety
connection with the 2198-Hxxx-ERS2 integrated safety drives.
If only one controller is used in an application with Motion and Safety
connections, it must be a 1756-L7xS GuardLogix safety controller.
Figure 10 - Motion and Safety Configuration (single controller)
24Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
StartChapter 1
IMPORTANT
1585J-M8CBJM-x
Ethernet (shielded) Cable
GuardLogix 1756-L7xS Controller
Logix Designer
Application
(version 24.0 or later)
AC Inp ut Power
2198-Hxxx-ERS2 Servo Drives
(top view)
2198-Hxxx-ERS2 Servo Drives
(front view)
Digital Inputs to Sensors and Control String
1606-XLxxx
24V DC Control, Digital Inputs,
and Motor Brake Power
(customer-supplied)
Kinetix VP
Servo Motors
2198-CAPMOD-1300 Capacitor Module
(optional component)
1734-AENTR
POINT Guard I/O
EtherNet/IP Adapter
1783-BMS
Stratix 5700
Switch
CompactLogix 5370 Controller or
ControlLogix 1756-L7x Controller
(ControlLogix controller is shown)
Motion Program
Module Definition
Configured with
Motion only
Conne ction
Safety Program
Module Definition
Configured with
Safety only
Conne ction
Safety
Device
In this example, a non-safety controller makes the Motion-only connection and a
separate GuardLogix safety controller makes the Safety-only connection with
2198-Hxxx-ERS2 integrated safety drives.
If two controllers are used in an application with Motion-only and Safetyonly connections, the Safety-only connection must be a 1756-L7xS
GuardLogix safety controller and the Motion-only connection must be a
ControlLogix 1756-L7x or CompactLogix 5370 controller.
Figure 11 - Motion and Safety Configuration (multi-controller)
LNK1LNK2NET OK
EtherNet/IP
EtherNet/IP
LNK1LNK2NET OK
2
1
2
1
Allen-Bradley
1606-XL
Power Supply
Input
Rockwell Automation Publication 2198-UM001D-EN-P - May 201425
Chapter 1Start
Catalog Number Explanation
Drive Cat. No.
(hardwired STO)
2198-H003-ERS2198-H003-ERS2
2198-H008-ERS2198-H008-ERS2
2198-H015-ERS2198-H015-ERS2
2198-H025-ERS2198-H025-ERS2
2198-H040-ERS2198-H040-ERS2
2198-H070-ERS2198-H070-ERS23
Capacitor Module
Cat. No.
2198-CAPMOD-13002650V DC, nom1360 μF, min
Kinetix 5500 drive catalog numbers and performance descriptions.
26Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
StartChapter 1
Agency Compliance
If this product is installed within the European Union and has the CE mark, the
following regulations apply.
ATT EN TI ON : Meeting CE requires a grounded system, and the method of
grounding the AC line filter and drive must match. Failure to do this renders the
filter ineffective and can cause damage to the filter. For grounding examples,
refer to Grounded Power Configurations
on page 69.
For more information on electrical noise reduction, refer to the System Design
for Control of Electrical Noise Reference Manual, publication GMC-RM001
.
To meet CE requirements, these requirements apply:
• Install an AC line filter (catalog number 2198-DBxx-F) for input power as
close to the Kinetix 5500 drive as possible.
• Bond drive, capacitor module, and line filter grounding screws by using a
braided ground strap as shown in Figure 39 on page 73
.
• Use Bulletin 2090 single motor cables with Kinetix VP servo motors. Use
Bulletin 2090 motor power/brake and feedback cables for other
compatible Allen-Bradley® motors and actuators.
• Combined motor cable length for all axes on the same DC bus must not
exceed 250 m (820 ft). Drive-to-motor cables must not exceed 50 m
(164 ft); however, use of continuous-flex cable and 2198-H2DCK
converter kit limits the maximum length.
Table 5 - Drive-to-Motor Maximum Cable Length
Kinetix VP Servo MotorsOther Compatible Rotary Motors and Linear Actuators
Kinetix 5500 Servo Drive
Cat. No.
2198-H003-ERSx
2198-H008-ERSx
2198-H015-ERSx
2198-H025-ERSx
2198-H040-ERSx
2198-H070-ERSx50 (164)
(1) Requires use of the 2198-H2DCK Hiperface- to-DSL feedback converter kit.
(2) Can b e used to repla ce Bulletin 2090 motor po wer/brake cabl es in 2198-H2 DCK convert er kit applic ations to inc rease the maxi mum length up to 50 m (164 ft). Applie s to only power /brake cables. Refer to
Motor Power/Brake Cable Preparation
Standard (non-flex) Cables
(cat. no. 2090-CSxM1DF-xxAAxx)
• Install the Kinetix 5500 system inside an approved enclosure. Run input
power wiring in conduit (grounded to the enclosure) outside of the
enclosure. Separate signal and power cables.
• Segregate input power wiring from control wiring and motor cables.
Refer to Appendix A on page 189
for input power wiring and drive/motor
interconnect diagrams.
Rockwell Automation Publication 2198-UM001D-EN-P - May 201427
Chapter 1Start
Notes:
28Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
Chapter 2
Planning the Kinetix 5500 Drive
System Installation
This chapter describes system installation guidelines used in preparation for
mounting your Kinetix 5500 drive components.
Top icPa ge
System Design Guidelines30
Electrical Noise Reduction36
ATT EN TI ON : Plan the installation of your system so that you can perform all
cutting, drilling, tapping, and welding with the system removed from the
enclosure. Because the system is of the open type construction, be careful to
keep metal debris from falling into it. Metal debris or other foreign matter can
become lodged in the circuitry and result in damage to the components.
Rockwell Automation Publication 2198-UM001D-EN-P - May 201429
Chapter 2Planning the Kinetix 5500 Drive System Installation
IMPORTANT
System Design Guidelines
Use the information in this section when designing your enclosure and planning
to mount your system components on the panel.
For on-line product selection and system configuration tools, including
AutoCAD (DXF) drawings of the product, refer to
http://www.rockwellautomation.com/en/e-tools
.
System Mounting Requirements
• To comply with UL and CE requirements, the Kinetix 5500 drive systems
must be enclosed in a grounded conductive enclosure offering protection
as defined in standard EN 60529 (IEC 529) to IP54 such that they are not
accessible to an operator or unskilled person. A NEMA 4X enclosure
exceeds these requirements providing protection to IP66.
• The panel you install inside the enclosure for mounting your system
components must be on a flat, rigid, vertical surface that won’t be subjected
to shock, vibration, moisture, oil mist, dust, or corrosive vapors.
• Size the drive enclosure so as not to exceed the maximum ambient
temperature rating. Consider heat dissipation specifications for all drive
components.
• Combined motor power cable length for all axes on the same DC bus must
not exceed 250 m (820 ft). Drive-to-motor cables must not exceed 50 m
(164 ft), however use of continuous-flex cable and 2198-H2DCK
converter kit limits the maximum length. Refer to Ta b l e 5
specifications by frame size.
on page 27 for
System performance was tested at these cable length specifications.
These limitations also apply when meeting CE requirements.
• Ethernet cable lengths connecting drive-to-drive, drive-to-controller, or
drive-to-switch must not exceed 100 m (328 ft).
• Registration and digital input cables greater than 30 m (98.4 ft) must be
shielded.
• Segregate input power wiring from control wiring and motor cables.
• Use high-frequency (HF) bonding techniques to connect the modules,
enclosure, machine frame, and motor housing, and to provide a lowimpedance return path for high-frequency (HF) energy and reduce
electrical noise.
Bond drive, capacitor module, and line filter grounding screws by using a
braided ground strap as shown in Figure 39 on page 73
Refer to the System Design for Control of Electrical Noise Reference Manual,
publication GMC-RM001
reduction.
, to better understand the concept of electrical noise
.
30Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
Planning the Kinetix 5500 Drive System InstallationChapter 2
IMPORTANT
IMPORTANT
IMPORTANT
EXAMPLE
IMPORTANT
Transformer Selection
The servo drive does not require an isolation transformer for three-phase input
power. However, a transformer can be required to match the voltage
requirements of the drive to the available service.
To size a transformer for the main AC power inputs, refer to the Kinetix 5500
power specifications in the Kinetix Servo Drives Technical Data, publication
GMC-TD003
.
When using an autotransformer, make sure that the phase to neutral/ground
voltage does not exceed the input voltage ratings of the drive.
Use a form factor of 1.5 for three-phase power (where form factor is used to
compensate for transformer, drive module, and motor losses, and to account
for utilization in the intermittent operating area of the torque speed curve).
150 KVA, max and 3% impedance, min
Sizing a transformer to the voltage requirements of this drive:
2198-H040-ERSx = 8.4 kW = 12.6 KVA transformer.
Circuit Breaker/Fuse Selection
The Kinetix 5500 drives use internal solid-state motor short-circuit protection
and, when protected by suitable branch circuit protection, are rated for use on a
circuit capable of delivering up to 200,000 A.
While circuit breakers offer some convenience, there are limitations for their use.
Circuit breakers do not handle high current inrush as well as fuses.
UL has not approved circuit breakers for use as branch circuit protection for
Kinetix 5500 drive systems.
Make sure the selected components are properly coordinated and meet
acceptable codes including any requirements for branch circuit protection.
Evaluation of the short-circuit available current is critical and must be kept below
the short-circuit current rating of the circuit breaker.
Refer to Power Wiring Examples
ATT EN TI ON : Do not use circuit protection devices on the output of an AC drive
as an isolating disconnect switch or motor overload device. These devices are
designed to operate on sine wave voltage and the drive’s PWM waveform does
not allow it to operate properly. As a result, damage to the device occurs.
Rockwell Automation Publication 2198-UM001D-EN-P - May 201431
, on page 190, for the wiring diagram.
Chapter 2Planning the Kinetix 5500 Drive System Installation
(1) UL has not approved circuit breakers for use as branch circuit protection for Kinetix 5500 drive systems.
Rockwell Automation Publication 2198-UM001D-EN-P - May 201433
Chapter 2Planning the Kinetix 5500 Drive System Installation
A =
0.38Q
1.8T - 1.1
A =
4.08Q
T - 1.1
A =
0.38 (416)
1.8 (30) - 1.1
= 2.99 m
2
Enclosure Selection
This example is provided to assist you in sizing an enclosure for your
Kinetix 5500 drive system. You need heat dissipation data from all components
planned for your enclosure to calculate the enclosure size (refer to Ta b l e 1 4
With no active method of heat dissipation (such as fans or air conditioning)
either of the following approximate equations can be used.
MetricStandard English
).
Where T is temperature difference between inside air and
outside ambient (°C), Q is heat generated in enclosure
(Watts), and A is enclosure surface area (m
surface of all six sides of an enclosure is calculated as
A = 2dw + 2dh + 2wh A = (2dw + 2dh + 2wh) /144
Where d (depth), w (width), and h (height) are in meters. Where d (depth), w (width), and h (height) are in inches.
2
). The exterior
Where T is temperature difference between inside air and
outside ambient (°F), Q is heat generated in enclosure
(Watts), and A is enclosure surface area (ft2). The exterior
surface of all six sides of an enclosure is calculated as
If the maximum ambient rating of the Kinetix 5500 drive system is 50 °C
(122 °F) and if the maximum environmental temperature is 20 °C (68 °F), then
T=30. In this example, the total heat dissipation is 416 W (sum of all
components in enclosure). So, in the equation below, T=30 and Q=416.
2
In this example, the enclosure must have an exterior surface of at least 2.99 m
. If
any portion of the enclosure is not able to transfer heat, do not include that value
in the calculation.
Because the minimum cabinet depth to house the Kinetix 5500 system (selected
for this example) is 300 mm (11.8 in.), the cabinet needs to be approximately
1500 x 700 x 300 mm (59.0 x 27.6 x 11.8 in.) HxWxD.
1.5 x (0.300 x 0.70) + 1.5 x (0.300 x 2.0) + 1.5 x (0.70 x 2.0) = 3.31 m
2
Because this cabinet size is considerably larger than what is necessary to house the
system components, it can be more efficient to provide a means of cooling in a
smaller cabinet. Contact your cabinet manufacturer for options available to cool
your cabinet.
34Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
Table 14 - Power Dissipation Specifications
Clearance right of the
drive is not required.
Clearance left of the
drive is not required.
Kinetix 5500
Servo Drive
40 mm (1.57 in.) clearance below
drive for airflow and installation.
40 mm (1.57 in.) clearance above
drive for airflow and installation.
Refer to the Kinetix Servo Drives
Technical Data, publication GMC-TD003
,
for Kinetix 5500 drive dimensions.
IMPORTANT
Planning the Kinetix 5500 Drive System InstallationChapter 2
Kinetix 5500 Drive
Cat. No.
2198-H003-ERSx
2198-H008-ERSx
2198-H015-ERSx
2198-H040-ERSx
2198-H070-ERSx364128192256320
Frame
Size
20%40%60%80%100%
11225375062
240801201602002198-H025-ERSx
Usage as % of Rated Power Output
(watts)
Minimum Clearance Requirements
This section provides information to assist you in sizing your cabinet and
positioning your Kinetix 5500 drive:
• Additional clearance is required for cables and wires or the shared-bus
connection system connected to the top of the drive.
• Additional clearance is required if other devices are installed above and/or
below the drive and have clearance requirements of their own.
• Additional clearance left and right of the drive is required when mounted
adjacent to noise sensitive equipment or clean wire ways.
• The recommended minimum cabinet depth is 300 mm (11.81 in.).
Figure 12 - Minimum Clearance Requirements
Mount the drive in an upright position as shown. Do not mount the drive on its side.
Rockwell Automation Publication 2198-UM001D-EN-P - May 201435
Chapter 2Planning the Kinetix 5500 Drive System Installation
Zero-stack Tab and
Cutout Aligned
Shared-bus connection system for
bus-sharing configurations is not
shown for clarity.
In multi-axis shared-bus configurations, drives must be spaced by aligning
the zero-stack tab and cutout.
Electrical Noise Reduction
This section outlines best practices that minimize the possibility of noise-related
failures as they apply specifically to Kinetix 5500 system installations. For more
information on the concept of high-frequency (HF) bonding, the ground plane
principle, and electrical noise reduction, refer to the System Design for Control
of Electrical Noise Reference Manual, publication GMC-RM001
.
Bonding Modules
Bonding is the practice of connecting metal chassis, assemblies, frames, shields,
and enclosures to reduce the effects of electromagnetic interference (EMI).
Unless specified, most paints are not conductive and act as insulators. To achieve
a good bond between power rail and the subpanel, surfaces need to be paint-free
or plated. Bonding metal surfaces creates a low-impedance return path for highfrequency energy.
To improve the bond between the power rail and subpanel, construct your
subpanel out of zinc plated (paint-free) steel.
Improper bonding of metal surfaces blocks the direct return path and allows
high-frequency energy to travel elsewhere in the cabinet. Excessive highfrequency energy can effect the operation of other microprocessor controlled
equipment.
36Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
Planning the Kinetix 5500 Drive System InstallationChapter 2
Stud-mounting the Subpanel
to the Enclosure Back Wall
Stud-mounting a Ground Bus
or Chassis to the Subpanel
SubpanelWel ded S tud
Scrape Paint
Flat Washer
If the mounting bracket is coated with
a non-conductive material (anodized
or painted), scrape the material around
the mounting hole.
Star Washer
Nut
Nut
Flat Washer
Mounting Bracket or
Ground Bus
Use a wire brush to remove paint from
threads to maximize ground connection.
Back Wall of
Enclosure
Weld ed St ud
Subpanel
Star Washer
Use plated panels or scrape paint on
front of panel.
Subpanel
Nut
Nut
Star Washer
Flat Washer
Star Washer
Star Washer
Scrape paint on both sides of
panel and use star washers.
Tapped Hole
Bolt
Flat Washer
Ground Bus or
Mounting Bracket
If the mounting bracket is coated with
a non-conductive material (anodized
or painted), scrape the material around
the mounting hole.
Bolt-mounting a Ground Bus or Chassis to the Back-panel
These illustrations show details of recommended bonding practices for painted
panels, enclosures, and mounting brackets.
Figure 14 - Recommended Bonding Practices for Painted Panels
Rockwell Automation Publication 2198-UM001D-EN-P - May 201437
Chapter 2Planning the Kinetix 5500 Drive System Installation
Wire B raid
25.4 mm (1.0 in.) by
6.35 mm (0.25 in.)
Paint removed
from cabinet.
Cabinet ground bus
bonded to the subpanel.
Wire B raid
25.4 mm (1.0 in.) by
6.35 mm (0.25 in.)
Bonding Multiple Subpanels
Bonding multiple subpanels creates a common low impedance exit path for the
high frequency energy inside the cabinet. Subpanels that are not bonded together
do not necessarily share a common low impedance path. This difference in
impedance can affect networks and other devices that span multiple panels:
Figure 15 - Multiple Subpanels and Cabinet Recommendations
• Bond the top and bottom of each subpanel to the cabinet by using
25.4 mm (1.0 in.) by 6.35 mm (0.25 in.) wire braid. As a rule, the wider
and shorter the braid is, the better the bond.
• Scrape the paint from around each fastener to maximize metal-to-metal
contact.
38Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
Planning the Kinetix 5500 Drive System InstallationChapter 2
(1)
Dirty Wireway
Clean Wireway
Single Motor Cables
(2)
Circuit
Breakers
24V DC
Power Supply
AC Lin e Filter
(required for CE)
Kinetix 5500 Servo Drive System
(1)
(1)
Very Dirty Filter/AC Input Connections
Segregated (not in wireway)
Digital Inputs and
Ethernet Cables
Route single motor cables
in shielded cable.
Route registration and communication
signals in shielded cables.
Safety Cable
(2198-Hxxx-ERS drives only)
Module Status
24V Input
Establishing Noise Zones
Observe these guidelines when routing cables used in the Kinetix 5500 system:
• The clean zone (C) is beneath the drive system and includes the digital
inputs wiring and Ethernet cable (gray wireway).
• The dirty zone (D) is above and below the drive system (black wireways)
and includes the circuit breakers, 24V DC power supply, safety, and motor
cables.
• The very dirty zone (VD) is limited to where the AC line (EMC) filter
VAC output jumpers over to the drive (or first drive in multi-axis systems).
Shielded cable is required only if the very dirty cables enter a wireway.
Figure 16 - Noise Zones
D
D
D
C
VD
C
D
C
(1) When space to the right of the drive does not permit 150 mm (6.0 in.) segregation, use a grounded steel shield instead. For
examples, refer to the System Design for Control of Electrical Noise Reference Manual, publication GMC-RM001
(2) When 2198-H2DCK converter kit is used, feedback cable routes in the clean wireway.
Rockwell Automation Publication 2198-UM001D-EN-P - May 201439
.
Chapter 2Planning the Kinetix 5500 Drive System Installation
Cable Categories for Kinetix 5500 Systems
These tables indicate the zoning requirements of cables connecting to the
Kinetix 5500 drive components.
Table 15 - Kinetix 5500 Drive
Wire/CableConnector
L1, L2, L3 (shielded cable)
L1, L2, L3 (unshielded cable)X
DC-/DC+ (DC bus)DCBus-bar only, no wiring connector.
DC+/SH (shunt)RCX
U, V, W ( motor power)
Motor feedback
Motor brake
24V DCCPX
Safety enable for safe torque-off
Registration input, greater than 30 m (98.4 ft)
Registration input, less than 30 m (98.4 ft)X
Ethernet
(1)
ZoneMethod
Very
Dirty
IPD
MP
MF
BC
(2)
STOX
IOD
PORT1
PORT2
DirtyClean
XX
X
X
X
XX
XX
Ferrite
Sleeve
Shielded
Cable
X
X
X
(1) When the 2198-H2DCK converter kit is used, the feedback cable routes in the clean wireway.
(2) STO connector applies to only 2198-Hxxx-ERS (hardwired) servo drives.
Table 16 - Capacitor Module
ZoneMethod
Wire/CableConnector
DC-/DC+ (DC bus)DCBus-bar only, no wiring connector.
24V DCCPBus-bar only, no wiring connector.
Module statusMSX
Very
Dirty
DirtyClean
Ferrite
Sleeve
Shielded
Cable
40Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
Planning the Kinetix 5500 Drive System InstallationChapter 2
IMPORTANT
Noise Reduction Guidelines for Drive Accessories
Refer to this section when mounting an AC (EMC) line filter or external shunt
resistor for guidelines designed to reduce system failures caused by excessive
electrical noise.
AC Line Filters
Observe these guidelines when mounting your AC (EMC) line filter (refer to the
figure on page 39
• Mount the AC line filter on the same panel as the Kinetix 5500 drive and
as close to the power rail as possible.
• Good HF bonding to the panel is critical. For painted panels, refer to the
examples on page 37
• Segregate input and output wiring as far as possible.
for an example):
.
CE test certification applies to only the AC line filter used with a single drive or
the line filter used in multi-axis drive configurations. Sharing a line filter with
more than one multi-axis drive configuration can perform satisfactorily, but
the customer takes legal responsibility.
Rockwell Automation Publication 2198-UM001D-EN-P - May 201441
Chapter 2Planning the Kinetix 5500 Drive System Installation
C
C
D
D
VD
D
D
C
VD
Dirty Wireway
Clean Wireway
Single Motor Cable
Very Dirty Connections Segregated
(not in wireway)
Customer-supplied
Metal Enclosure
150 mm (6.0 in.)
clearance (min) on all four
sides of the shunt resistor.
Enclosure
Metal Conduit (where
required by local code)
No sensitive
equipment within
150 mm (6.0 in.).
Shunt Power Wiring Methods:
Twisted pair in conduit (1st choice).
Shielded twisted pair (2nd choice).
Twisted pair, two twists per foot (min) (3rd choice).
Circuit
Breaker
Digital Inputs
and Ethernet Cables
Route single motor cables
in shielded cable.
Route registration and communication
signals in shielded cables.
Kinetix 5500 Servo Drive System
24V DC
Power Su pply
AC Line Fi lter
(required for CE)
Module Status
Safety Cable
(2198-Hxxx-ERS drives only)
External Shunt Resistor
Observe these guidelines when mounting your external shunt resistor outside of
the enclosure:
Figure 17 - External Shunt Resistor Outside the Enclosure
• Mount shunt resistor and wiring in the very dirty zone or in an external
shielded enclosure.
• Mount resistors in a shielded and ventilated enclosure outside of the
cabinet.
• Keep unshielded wiring as short as possible. Keep shunt wiring as flat to
the cabinet as possible.
42Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
Planning the Kinetix 5500 Drive System InstallationChapter 2
C
C
D
D
VD
D
D
C
VD
Dirty Wireway
Clean Wireway
Single Motor Cable
Very Dirty Connections Segregated
(not in wireway)
Enclosure
No sensitive
equipment within
150 mm (6.0 in.).
Shunt Power Wiring Methods:
Twisted pair in conduit (1st choice).
Shielded twisted pair (2nd choice).
Twisted pair, two twists per foot (min) (3rd choice).
Circuit
Breaker
Digital Inputs and
Ethernet Cables
Route single motor cables
in shielded cable.
Route registration and communication
signals in shielded cables.
Kinetix 5500 Servo Drive System
24V DC
Power Supply
AC Line Filter
(required for CE)
Module Status
150 mm (6.0 in.)
clearance (min) on all four
sides of the shunt resistor.
Safety Cable
(2198-Hxxx-ERS drives only)
When mounting your shunt resistor inside the enclosure, follow these additional
guidelines:
• Mount metal-clad modules anywhere in the dirty zone, but as close to the
Kinetix 5500 drive as possible.
• Route shunt power wires with other very dirty wires.
• Keep unshielded wiring as short as possible. Keep shunt wiring as flat to
the cabinet as possible.
• Separate shunt power cables from other sensitive, low voltage signal cables.
Figure 18 - External Shunt Resistor Inside the Enclosure
Rockwell Automation Publication 2198-UM001D-EN-P - May 201443
Chapter 2Planning the Kinetix 5500 Drive System Installation
Notes:
44Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
Chapter 3
Mounting the Kinetix 5500 Drive System
This chapter provides the system installation procedures for mounting your
Kinetix 5500 drives to the system panel.
Top icPa ge
Determining Mounting Order46
Drilling Hole Patterns49
Mount Your Kinetix 5500 Drive56
This procedure assumes you have prepared your panel and understand how to
bond your system. For installation instructions regarding equipment and
accessories not included here, refer to the instructions that came with those
products.
SHOCK HAZARD: To avoid hazard of electrical shock, perform all mounting and
wiring of the Kinetix 5500 drives prior to applying power. Once power is
applied, connector terminals can have voltage present even when not in use.
ATT EN TI ON : Plan the installation of your system so that you can perform all
cutting, drilling, tapping, and welding with the system removed from the
enclosure. Because the system is of the open type construction, be careful to
keep metal debris from falling into it. Metal debris or other foreign matter can
become lodged in the circuitry and result in damage to the components.
Rockwell Automation Publication 2198-UM001D-EN-P - May 201445
Shared-bus Connection System
(required in shared-bus configurations)
Determining Mounting Order
Mount drives in order (left to right) according to power rating (highest to
lowest) starting with the highest power rating. If power rating is unknown,
position drives (highest to lowest) from left to right based on amp rating.
Zero-stack Tab and Cutout
Engaging the zero-stack tab and cutout from drive-to-drive makes efficient use of
panel space for installations with multiple drives.
Engaging the zero-stack tab and cutout from drive-to-drive is required for
shared-bus multi-axis drive systems. This is done to make sure the drive
connectors are spaced properly to accept the shared-bus connection system.
Figure 19 - Zero-stack Tab and Cutout Example
For the zero-stack feature to engage properly (when more than one frame size
exists in the drive system) frame 3 drives must mount left of frame 1 or 2 drives,
and frame 2 drives must mount left of frame 1 drives.
Capacitor modules can mount to the right of any frame size, but are always
rightmost in any drive configuration.
Mount drives in descending order, left to right, according to frame size with
capacitor modules always mounted on the far right.
Figure 20 - Shared-bus Connection System Example
46Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
Mounting the Kinetix 5500 Drive SystemChapter 3
IMPORTANT
Input Wiring Connector
(1)
(mains AC input shown)
AC T-connectors
Bus-bar Connectors
(2)
(AC bus-bars shown)
Input Wiring
(AC input wiring is shown)
Zero-stack Tab
and Cutout Engaged
2198-Hxxx-ERSx Drive System (top view)
Frame 2 drives are shown.
Drive with largest amp rating must be
leftmost drive.
DC Bus Connector Latch
DC Bus T-connector
(3)
Shared-bus Connection System
The shared-bus connection system is used to extend the mains AC input, 24V
control input, and the DC bus power from drive-to-drive in shared-bus multiaxis configurations.
When the shared-bus connection system is used, the zero-stack tab and
cutout must be engaged between adjacent drives.
The connection system is comprised of three components:
• Input wiring connectors that plug into the leftmost drive and receive input
wiring for mains AC and 24V DC.
• AC bus, DC bus, and 24V DC T-connectors that plug into the drives
downstream from the first where AC, DC, and/or 24V control power is
shared. DC bus T-connectors also plug into the first drive where DC bus
power is shared.
• Bus bars that connect between drives to extend the mains AC bus, DC bus,
and 24V DC control power from drive-to-drive.
Figure 21 - Connection System Example
(1) Due to the higher amp rating of frame 3 drives, input wiring connectors for frame 3 drives (catalog number 2198-H070-ADP-IN) are
slightly larger than connectors for frame 1 and 2 drives (catalog number 2198-H040-ADP-IN).
(2) Due to the extra width of frame 3 drives, bus-bar connectors between frame 3 drives are slightly longer (85 mm) than connectors
between frame 3, frame 2, and frame 1 drives (55 mm).
(3) DC bus T-connectors latch on both sides when inserted into the drive. To remove the DC bus T-connector, at least one latch must be
pried away with a non-conductive probe.
The three components assemble from left to right across the drive system.
1. Attach wiring to input wiring connectors.
2. Insert input wiring connectors and T-connectors into the appropriate
drive connectors.
3. Insert bus-bars to connect between wiring connectors and T-connectors.
Rockwell Automation Publication 2198-UM001D-EN-P - May 201447
Chapter 3Mounting the Kinetix 5500 Drive System
Single-axis Configurations
The following restrictions exist for standalone (single-axis) configurations:
• Standalone (single-axis) drives can be mounted to the panel individually or
by using the zero-stack tab and cutout (refer to Figure 21 on page 47
• The shared-bus connection system does not apply and must not be used
For a single-axis example configuration, refer to Typical Kinetix 5500 Standalone
Installation on page 15.
)
Multi-axis Configurations
Each multi-axis configuration has restrictions that apply:
• The shared-bus connection system must be used. Do not attach discrete
wires from drive-to-drive.
• The maximum number of drives in Shared AC bus power-sharing groups
cannot exceed 5.
• The maximum number of drives in any other bus power-sharing group
cannot exceed 8.
For a multi-axis example configuration, refer to Typical Shared AC/DC Bus
Hybrid Installations on page 19.
48Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
Mounting the Kinetix 5500 Drive SystemChapter 3
Drilling Hole Patterns
Hole patterns for drives mounted in zero-stack or shared-bus configuration are
provided for mounting your drives to the panel. Drives with the highest power
rating are always mounted to the left of any drive with a lower power rating in
shared-bus configurations:
• Frame 1 drives can be followed by only another frame 1 drive.
• Frame 2 drives can be followed by frame 1 drives or another frame 2 drive.
• Frame 3 drives can be followed by frame 1, frame 2, or another frame 3
drive.
• Mount Bulletin 2198 capacitor modules in the rightmost position.
– Capacitor modules have the same hole pattern as frame 2 drives.
– Only Shared DC, Shared AC/DC, and Shared AC/DC, hybrid
configurations are compatible with Bulletin 2198 capacitor modules.
Table 17 - Hole Pattern Overview
Drive Cat. No.Frame SizeFrame Size PatternsPage
2198-H003-ERSx
2198-H008-ERSx
2198-H015-ERSx
2198-H025-ERSx
2198-H040-ERSx
2198-H070-ERSxFrame 3
Frame 1As many as eight frame 1 drives
As many as 8 frame 2 drives
Frame 2
One frame 2 drive followed by as many as seven frame 1 drives52
As many as 8 frame 3 drives53
One frame 3 drive followed by as many as seven frame 1 drives54
One frame 3 drive followed by as many as seven frame 2 drives55
51
Table 18 - Capacitor Module Support
Three-phase Operation
Drive Cat. No.
Frame Size
2198-H003-ERSx
2198-H008-ERSx
2198-H015-ERSx
2198-H040-ERSx
2198-H070-ERSx34
(1) Catalog number 2198-H003-ERS and any drive in standalone single-p hase operation is not compatible with the Kinetix 5500
capacitor module.
(1)
1
(1)
(1)
0
242198-H025-ERSx
N/A
StandaloneShared DCShared AC/DC
Standalone
Single Phase
Operation
Number of capacitor modules connected, max
0
1
3
2
Shared AC/DC
Hybrid
Rockwell Automation Publication 2198-UM001D-EN-P - May 201449
These hole patterns apply when all drives in the system are frame 1 or frame 2.
There is 50 mm (2.0 in.) between mounting holes (A-to-A and B-to-B).
Figure 23 - Frame 1 and Frame 2 Hole Patterns
Axis 8
Axis 7
Axis 6
Axis 5
Axis 4
A
A
A
A
A
B
B
B
B
B
Axis 3
Axis 2
Axis 1
Frame 1
A
A
A
(7.6)
193.68
16x
Frame 2
243.84
50.0 (2.0)
ØM4 (#8-32)
(9.6)
50.0 (2.0)
B
B
B
0
0
Rockwell Automation Publication 2198-UM001D-EN-P - May 201451
Chapter 3Mounting the Kinetix 5500 Drive System
4x
ØM4 (#8-32)
Axis 1
(frame 2)
243.84
(9.6)
0
0
5.00
(0.2)
57.00
(2.2)
52.50
(2.1)
50.15
(2.0)
Axis 2
(frame 1)
243.83
(9.6)
Dimensions are in mm (in.)
This hole pattern applies when transitioning from frame 2 drives to frame 1
drives. To mount additional frame 1 drives to the right of Axis 2 in this figure,
refer to the frame 1 hole pattern in Figure 23
Figure 24 - Frame 2 to Frame 1 Hole Pattern
.
52Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
Mounting the Kinetix 5500 Drive SystemChapter 3
Dimensions are in
mm (in.)
This hole pattern applies when all drives in the system are frame 3 drives. There is
85.20 mm (3.4 in.) between mounting holes, as shown.
Figure 25 - Frame 3 Hole Pattern
(25.5)
648.90
(24.8)
630.40
(23.5)
596.40
(22.2)
563.70
(21.5)
545.20
(20.1)
511.20
(18.8)
478.50
460.0
(18.1)
426.0
(16.8)
Axis 5Axis 6Axis 7Axis 8
Axis 1Axis 2Axis 3Axis 4
(14.8)
374.80
(11.4)
289.60
(8.0)
204.40
(4.7)
119.20
(1.3)
34.00
85.20 (3.4)
32x
ØM4 (#8-32)
85.20 (3.4)
85.20 (3.4)
(15.5)
393.30
(13.4)
340.80
(12.1)
308.10
(10.1)
255.60
(8.8)
222.90
(6.7)
170.40
(5.4)
137.70
85.20
(2.1)
52.50
0
(3.4)
0
(10.8)
273.70
Rockwell Automation Publication 2198-UM001D-EN-P - May 201453
Chapter 3Mounting the Kinetix 5500 Drive System
273.70
(10.8)
0
52.50
(2.1)
0
6x
ØM4 (#8-32)
Axis 1
(frame 3)
Axis 2
(frame 1)
272.23
(10.7)
78.55
(3.1)
92.70
(3.7)
97.20
(3.8)
34.00
(1.3)
Dimensions are in mm (in.)
This hole pattern applies when transitioning from frame 3 drives to frame 1
drives. To mount additional frame 1 drives to the right of Axis 2 in this figure,
refer to the frame 1 hole pattern in Figure 23
Figure 26 - Frame 3 to Frame 1 Hole Pattern
.
54Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
Mounting the Kinetix 5500 Drive SystemChapter 3
Dimensions are in mm (in.)
This hole pattern applies when transitioning from frame 3 drives to frame 2
drives. To mount additional frame 2 drives to the right of Axis 2 in this figure,
refer to the frame 2 hole pattern in Figure 23
Figure 27 - Frame 3 to Frame 2 Hole Pattern
Axis 1
(frame 3)
.
(frame 2)
Axis 2
6x
ØM4 (#8-32)
273.70
(10.8)
34.00
(1.3)
272.24
(10.7)
100.00
(3.9)
28.40
(1.1)
0
0
Rockwell Automation Publication 2198-UM001D-EN-P - May 201455
52.50
(2.1)
95.00
(3.7)
Chapter 3Mounting the Kinetix 5500 Drive System
IMPORTANT
2
1
Kinetix 5500 Servo Drives
(frame 1 drives shown)
Top Scre ws
(bottom screws not shown)
Zero-s tack Tab
and Cutout Engaged
Mount Your Kinetix 5500
Drive
This procedure assumes you have prepared your panel and understand how to
bond your system. For installation instructions regarding other equipment and
accessories, refer to the instructions that came with those products.
Follow these steps to mount your Kinetix 5500 drives to the panel.
1. Lay out the hole pattern for each Kinetix 5500 drive in the enclosure.
Refer to Establishing Noise Zones
on page 39 for panel layout
recommendations.
To improve the bond between the Kinetix 5500 drive and subpanel,
construct your subpanel out of zinc plated (paint-free) steel.
2. Drill holes in the panel for mounting your drive system.
Hole patterns, by frame size, are shown in Drilling Hole Patterns
beginning on page 49
.
3. Loosely attach the mounting hardware to the panel.
The recommended mounting hardware is M4 (#8-32) steel bolts. Observe
bonding techniques as described in Bonding Modules
on page 36.
4. Attach the leftmost drive to the cabinet panel.
5. Attach additional drives (if any) just to the right of the previous drive by
using the same method, but also making sure the zero-stack tabs and
cutouts are engaged.
Zero-stack mounting is required based on configuration, refer to the Zero-
56Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
stack Tab and Cutout Example on page 46.
6. Tighten all mounting fasteners.
Apply 2.0 N•m (17.7 lb•in) maximum torque to each fastener.
Chapter 4
Connector Data and Feature Descriptions
This chapter illustrates drive connectors and indicators, including connector
pinouts, and provides descriptions for Kinetix 5500 drive features.
Top icPa ge
Kinetix 5500 Connector Data58
Understanding Control Signal Specifications62
Feedback Specifications65
Safe Torque-off Safety Features66
Rockwell Automation Publication 2198-UM001D-EN-P - May 201457
Chapter 4Connector Data and Feature Descriptions
21
20
19
18
17
1
2
L3
L2
L1
1
2
+
–
1
8
3
4
13
5
6
11
10
9
12
16
7
7
U
V
W
2
1
15
14
2
1
2
Kinetix 5500 Drive, Front View
(2198-H003-ERSx drive is shown)
Kinetix 5500, Top View
(2198-H003-ERS drive is shown)
Kinetix 5500, Top View
(2198-Hxxx-ERS2 drives)
Protect ive
Knock-out
Shared-bus AC Input
Wiring Co nnector
Shared-bus 24V Input
Wiring Co nnector
Kinetix 5500 Connector Data
Use these illustrations to identify the connectors and indicators for the
Kinetix 5500 servo drives.
Figure 28 - Kinetix 5500 Drive Features and Indicators
ItemDescriptionItemDescriptionItemDescription
1Motor cable shield clamp8Module status indicator15Motor brake (BC) connector
4Digital inputs (IOD) connector11Navigation pushbuttons18AC mains input power (IPD) connector
5Ethernet (PORT1) RJ45 connector12Link speed status indicators19DC bus (DC) connector (under cover)
6Ethernet (PORT2) RJ45 connector13Link/Activity status indicators2024V control input power (CP) connector
7Zero-stack mounting tab/cutout14Motor power (MP) connector21
(1) Protective knock-out covers the 2198-H2DCK Hiperface-to-DSL feedback converter kit mou nting hole. Remove knock-out for use with the converter kit.
(2) DC bus connector ships with protective knock-out cover that can be removed for use in shared-bus configurations.
(3) Protective knock-out cover is removed on 2198-Hxxx-ERS (hardwired STO) drives.
58Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
Converter kit mounting hole
(under cover)
(1)
9Network status indicator16Ground terminal
(2)
Safe torque-off (STO) connector
(3)
(does not apply to 2198-Hxxx-ERS2 drives)
Connector Data and Feature DescriptionsChapter 4
Safe Torque-off Connector Pinout
For the hardwired safe torque-off (STO) connector pinouts, feature descriptions,
and wiring information, refer to Chapter
9 beginning on page 157.
Input Power Connector Pinouts
Table 19 - Mains Input Power Connector
IPD PinDescriptionSignal
Chassis ground
L3
L2L2
L1L1
Three-phase input power
L3
Table 20 - 24V Input Power Connector
CP PinDescriptionSignal
124V power supply, customer supplied24V+
224V common24V-
DC Bus and Shunt Resistor Connector Pinouts
Table 21 - DC Bus Power Connector
DC PinDescriptionSignal
1
2DC+
DC bus connections
Table 22 - Shunt Resistor Connector
RC PinDescriptionSignal
1
2SH
1
2DC+
Shunt connections (frames 2 and 3)
Shunt connections (frame 1)
DC-
DC+
SH
Rockwell Automation Publication 2198-UM001D-EN-P - May 201459
Chapter 4Connector Data and Feature Descriptions
1
8
Digital Inputs Connector Pinout
IOD PinDescriptionSignal
1
2I/O common for customer-supplied 24V supply.COM
3
4I/O cable shield termination point.SHLD
(1) This signal has dual-functionality. You can use IN1 (IOD-1) as registration or Home input.
Figure 29 - Pin Orientation for 4-pin Digital Inputs (IOD) Connector
High speed registration/home position input. A low/high or high/low transition
triggers a registration event. This is a dual-function input.
High speed registration input. A low/high or high/low transition triggers a
registration event.
Pin 1IN1
COM
IN2
SHLD
IN1
IN2
(1)
Ethernet Communication Connector Pinout
PinDescriptionSignal
1Transmit+TD+
2Transmit-TD-
3Receive+RD+
4Reserved–
5Reserved–
6Receive-RD-
7Reserved–
8Reserved–
Figure 30 - Pin Orientation for 8-pin Ethernet PORT1 and PORT2 Connectors
60Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
Connector Data and Feature DescriptionsChapter 4
IMPORTANT
IMPORTANT
Motor Power, Brake, and Feedback Connector Pinouts
Table 23 - Motor Power Connector
MP PinDescriptionSignalColor
U
VVBlack
WWBlue
Three-phase motor power
Chassis groundGreen
Drive-to-motor power cables must not exceed 50 m (164 ft).
System performance was tested at this cable length. These limitations also
apply when meeting CE requirements.
Table 24 - Motor Brake Connector
BC PinDescriptionSignal
1
2MBRK-
Motor brake connections
UBrown
MBRK+
Motor Feedback Connector Pinout
MF PinDescriptionSignal
1
2D-
SHIELD
Bidirectional data and power for digital encoder interface
Cable shield and grounding plate (internal to 2198-KITCON-DSL connector kit)
termination point.
Drive-to-motor power cables must not exceed 50 m (164 ft).
System performance was tested at these cable length specifications. These
limitations also apply when meeting CE requirements.
Figure 31 - Pin Orientation for 2-pin Motor Feedback (MF) Connector
Pin 1
Pin 2
D+
SHIELD
Rockwell Automation Publication 2198-UM001D-EN-P - May 201461
Chapter 4Connector Data and Feature Descriptions
IMPORTANT
Understanding Control
Signal Specifications
FunctionDescriptionDefault Behavior
Home/Reg1
Registration 1An inactive-to-active transition (also known as a positive transition) or
Registration 2
This section provides a description of the Kinetix 5500 digital inputs, Ethernet
communication, power and relay specifications, encoder feedback specifications,
and safe torque-off features.
Digital Inputs
Two digital inputs are available for the machine interface on the IOD connector.
Digital inputs require a 24V DC @ 15 mA supply. These are sinking inputs that
require a sourcing device. A common and cable shield connection is provided on
the IOD connector for digital inputs.
The Registration 1 input is capable of dual functionality. You can also use this as
the Home input. Configuration for dual functionality is not needed.
To improve registration input EMC performance, refer to the System Design for
Control of Electrical Noise Reference Manual, publication GMC-RM001
Table 25 - Understanding Digital Input Functions
An active state indicates to a homing sequence that the referencing
sensor has been seen. Typically, a transition of this signal is used to
establish a reference position for the machine axis.
active-to-inactive transition (also known as a negative transition) is
used to latch position values for use in registration moves.
.
The function is always inactive. You can enable in the Logix
Designer application.
Table 26 - Digital Input Specifications
AttributeValue
TypeActive high, single-ended, current sinking (EN 61131-2 Type 1)
Windowed registration invalid-to-valid event delay125 μs, min
62Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
Connector Data and Feature DescriptionsChapter 4
INPUT
24VCOM
24VPWR
IOD-1 or IOD-3
IOD-2
Kinetix 5500 Drive
24V DC
Figure 32 - Digital Input Circuitry
Ethernet Communication Specifications
The PORT1 and PORT2 (RJ45) Ethernet connectors are provided for
communication with the Logix5000 controller.
AttributeValue
Communication
Cyclic update period500 μs, min
Embedded switch features
Auto MDI/MDIX crossover detection/
correction
Port-to-port time synchronization
variation
CablingCAT5e shielded, 100 m (328 ft) max
The drive auto-negotiates speed and duplex modes. These modes can be
forced through the Logix Designer application. 100BASE-TX, full duplex is
recommended for maximum performance.
Three-port, cut-through, time correction on IEEE-1588 packets, limited
filtering, quality of service with four priority levels
Yes
100 ns, max
Rockwell Automation Publication 2198-UM001D-EN-P - May 201463
Chapter 4Connector Data and Feature Descriptions
ISP772
MBRK+ (BC-1)
MBRK– (BC-2)
24V PWR
24V COM
INT PWR
Kinetix 5500
Servo Drive
Control
Board
Noise
Suppression
Device
IMPORTANT
IMPORTANT
Motor Brake Circuit
The customer-supplied 24V power supply drives the motor parking-brake output
through a solid-state relay. The solid-state brake driver circuit provides the
following:
• Brake thermal-overload protection
• Brake current-overload protection
• Brake over-voltage protection
Two connections (BC-1 and BC-2) are required for the motor brake output.
Connections are rated for 2.0 A @ +24V (refer to Figure 33
Control of the solid-state relay to release the motor brake is configurable in the
Logix Designer application. An active signal releases the motor brake. Turn-on
and turn-off delays are specified by the brake-active delay and brake-inactive delay
(configurable in the Logix Designer application). Refer to Kinetix 5500 Drive
and Motor/Actuator Wiring Examples beginning on page 195
examples.
).
for wiring
Figure 33 - Motor Brake Circuit
Motor parking-brake switching frequency must not exceed 10 cycles/min.
Control Power
The Kinetix 5500 drive requires 24V DC input power for control circuitry.
SELV and PELV rated power supplies must be used to energize external safety
devices connected to the Kinetix 5500 safety inputs.
The National Electrical Code and local electrical codes take precedence over the
values and methods provided. Implementation of these codes is the
responsibility of the machine builder.
Table 27 - Control Power Input Power Specifications
AttributeFrame 1Frame 2Frame 3
Input voltage21.6…26.4V DC
Control power AC input current
64Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
Nom @ 24V DC
Inrush, max
(1) Plus BC connector (MBRK+) current.
(1)
400 mA
2.0 A
800 mA
3.0 A
1.3 A
3.0 A
Connector Data and Feature DescriptionsChapter 4
TIP
Posit ion at Power Down
2048 Turns, MP-Series and LDAT-Series Motors/Actuators
4096 Turns, Kinetix VP Motors
Feedback Specifications
The Kinetix 5500 drive accepts motor feedback signals from Stegmann
Hiperface digital-servo-link (DSL) encoders.
Kinetix 5500 drive and Kinetix VP motor combinations use single motor-cable
technology with motor power, feedback, and brake wires (when specified)
housed in a single cable. Feedback and brake wires are shielded separately and
each provide a shield braid for grounding in the motor cable clamp.
Auto-configuration in the Logix Designer application of intelligent absolute,
high-resolution encoders is possible with only Allen-Bradley motors.
Table 28 - Stegmann Hiperface DSL Specifications
AttributeValue
ProtocolHiperface DSL
Memory supportProgrammed with Allen-Bradley motor data
Hiperface data communication9.375 Mbits/s
Other Allen-Bradley motors and actuators with Stegmann Hiperface single-turn
or multi-turn high-resolution absolute encoders are also accepted, but only when
using drive firmware revision 2.002 or later and the 2198-H2DCK Hiperface-toDSL feedback converter kit for Hiperface-to-DSL conversion.
Absolute Position Feature
The drive’s absolute position feature tracks the position of the motor, within the
multi-turn retention limits, while the drive is powered off. The absolute position
feature is available with only multi-turn encoders.
Rockwell Automation Publication 2198-UM001D-EN-P - May 201465
Chapter 4Connector Data and Feature Descriptions
Safe Torque-off Safety
Features
Kinetix 5500 servo drives have safe torque-off (STO) capability and can safely
turn off the inverter power transistors in response to a monitored digital input,
according to Category 0 Stop behavior.
Servo Drives with Hardwired Safety
2198-Hxxx-ERS (hardwired) servo drives support parallel input terminals for
cascading to adjacent drives over duplex wiring. For applications that do not
require the STO safety function you must install jumper wires to bypass the safe
torque-off feature.
Refer to Chapter
wiring information.
9 on page 157 for the STO connector pinout, installation, and
Servo Drives with Integrated Safety
For 2198-Hxxx-ERS2 (integrated safety) servo drives, the 1756-L7xS
GuardLogix safety controller issues the STO command via the EtherNet/IP
network and the 2198-Hxxx-ERS2 servo drives execute the command.
Refer to Chapter
configuring motion and safety connections, motion direct commands, and the
STO bypass feature.
10 on page 167 for integrated safety drive specifications,
66Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
Chapter 5
Connecting the Kinetix 5500 Drive System
This chapter provides procedures for wiring your Kinetix 5500 system
components and making cable connections.
Top icPa ge
Basic Wiring Requirements68
Determine the Input Power Configuration69
Removing the Grounding Screws in Ungrounded Power Configurations71
Grounding the Drive System73
Wiring Requirements75
Wiring Guidelines76
Wiring the Power Connectors77
Wiring the Digital Input Connectors79
Wiring Kinetix VP Motors80
Wiring Other Allen-Bradley Motors and Actuators86
Capacitor Module Connections95
External Shunt Resistor Connections96
Ethernet Cable Connections97
Rockwell Automation Publication 2198-UM001D-EN-P - May 201467
Chapter 5Connecting the Kinetix 5500 Drive System
IMPORTANT
Basic Wiring Requirements
This section contains basic wiring information for the Kinetix 5500 drives.
ATT EN TI ON : Plan the installation of your system so that you can perform all
cutting, drilling, tapping, and welding with the system removed from the
enclosure. Because the system is of the open type construction, be careful to
keep metal debris from falling into it. Metal debris or other foreign matter can
become lodged in the circuitry and result in damage to components.
SHOCK HAZARD: To avoid hazard of electrical shock, perform all mounting and
wiring of the Bulletin 2198 drive modules prior to applying power. Once power
is applied, connector terminals can have voltage present even when not in use.
This section contains common PWM servo system wiring configurations, size,
and practices that can be used in a majority of applications. National Electrical
Code, local electrical codes, special operating temperatures, duty cycles, or
system configurations take precedence over the values and methods provided.
Routing the Power and Signal Cables
Be aware that when you route power and signal wiring on a machine or system,
radiated noise from nearby relays, transformers, and other electronic devices can
be induced into I/O communication, or other sensitive low voltage signals. This
can cause system faults and communication anomalies.
The Bulletin 2090 single motor cable contains the power, brake, and feedback
wires, but is properly shielded to protect the noise-sensitive feedback signals.
Refer to Electrical Noise Reduction
low voltage cables in wireways. Refer to the System Design for Control of
Electrical Noise Reference Manual, publication GMC-RM001
information.
on page 36 for examples of routing high and
, for more
68Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
Connecting the Kinetix 5500 Drive SystemChapter 5
L3
L2
L1
1
2
L3
L2
L1
1
2
Transformer
Three-phase
Input VAC
Phase Ground
Transformer (WYE) Secondary
Bonded Cabinet
Ground
Ground Grid or
Power Distribution Ground
Connect to ground st ud.
Three-phase
AC Line Filter
Input Fusing
Kinetix 5500 Servo Drive
(top view)
IMPORTANT
Determine the Input Power
Configuration
Before wiring input power to your Kinetix 5500 system, you must determine the
type of input power you are connecting to. The drive is designed to operate in
both grounded and ungrounded environments.
ATT EN TI ON : Ungrounded and corner-grounded input power configurations are
permitted, but you must remove the ground screws.
Refer to Removing the Grounding Screws in Ungrounded Power Configurations
on page 71
for more information.
Grounded Power Configurations
The grounded (WYE) power configuration lets you ground your three-phase
power at a neutral point. This type of grounded power configuration is preferred.
Figure 35 - Grounded Power Configuration (WYE Secondary)
The Kinetix 5500 drive has factory-installed grounding screws for grounded
power distribution.
If you determine that you have grounded power distribution in your plant, you
do not need to remove the grounding screws.
Refer to Power Wiring Examples
interconnect diagrams.
Rockwell Automation Publication 2198-UM001D-EN-P - May 201469
beginning on page 190 for input power
Chapter 5Connecting the Kinetix 5500 Drive System
L3
L1
L2
1
2
L3
L2
L1
1
2
Transformer (Delta) Secondary
Bonded Cabinet
Ground
Transformer
Ground Grid or
Power Distribution Ground
Connect to ground stud.
Three-phase
AC Line Fi lter
Input Fusing
Kinetix 5500 Servo Drive
(top view)
IMPORTANT
IMPORTANT
Figure 36 - Corner Grounded (B-phase) Power Configuration (Delta Secondary)
Even though corner-grounded power configurations have a ground
connection, treat them as ungrounded when installing Kinetix 5500 drive
systems.
Refer to Power Wiring Examples beginning on page 190 for input power
interconnect diagrams.
Ungrounded Power Configurations
The ungrounded power configuration (Figure 37) does not provide a neutral
ground point.
If you determine that you have ungrounded or high-impedance grounded
power distribution in your facility, you need to remove the grounding screws.
Refer to Removing the Grounding Screws in Ungrounded Power Configurations
on page 71
for more information.
70Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
Figure 37 - Ungrounded Power Configuration
Transformer
Three-phase
Input VAC
Chassis Ground
Bonded Cabinet
Ground
Ground Grid or
Power Distribution Ground
Connect to ground st ud.
Three-phase
AC Lin e Filter
Input Fusing
Kinetix 5500 Servo Drive
(top view)
IMPORTANT
IMPORTANT
L3
Connecting the Kinetix 5500 Drive SystemChapter 5
2
1
Removing the Grounding
Screws in Ungrounded Power
Configurations
L2
L1
L3
L2
L1
2
1
ATT EN TI ON : Ungrounded systems do not reference each phase potential to a
power distribution ground. This can result in an unknown potential to earth
ground.
Refer to Power Wiring Examples beginning on page 190 for input power
interconnect diagrams.
Removing the grounding screws is necessary only when using ungrounded or
corner-ground power configurations. Removing the screws involves gaining
access, opening the sliding door, and removing the screws.
If you have grounded power distribution, you do not need to remove the
grounding screws. Go to Grounding the Drive System
on page 73.
Removing the grounding screws can affect EMC performance.
Removing the grounding screws in multi-axis configurations is best done when
the drive is removed from the panel and placed on its side on a solid surface
equipped as a grounded static-safe workstation.
Rockwell Automation Publication 2198-UM001D-EN-P - May 201471
ATTENTION: By removing the grounding screws for ungrounded power
configurations, you no longer maintain line-to-neutral voltage protection.
Chapter 5Connecting the Kinetix 5500 Drive System
Ground screws installed
for grounded power configuration
(screws installed is default setting).
Remove screws for ungrounded power.
Grounding Screws
Access Door
Kinetix 5500 Drive
(side view)
Lift door to meet
arrow at left.
ATTENTION: This drive contains electrostatic discharge (ESD) sensitive parts
and assemblies. You are required to follow static-control precautions when you
install, test, service, or repair this assembly. If you do not follow ESD control
procedures, components can be damaged. If you are not familiar with static
control procedures, refer to Guarding Against Electrostatic Damage, publication
8000-4.5.2
Figure 38 - Removing the Ground Screws
, or any other applicable ESD awareness handbook.
ATTENTION: Risk of equipment damage exists. The drive ground configuration
must be accurately determined. Leave the grounding screws installed for
grounded power configurations (default). Remove the screws for ungrounded
power.
Table 30 - Grounding Screw Configurations
Ground ConfigurationExample DiagramGrounding Screw ConfigurationBenefits of Correct Configuration
• UL and EMC compliance
• Reduced electrical noise
Grounded (wye)Figure 35 on page 69
• B-phase corner ground
• AC fed ungrounded
Figure 36 on page 70
Figure 37 on page 71
Both screws installed (default setting)
Both screws removed
• Most stable operation
• Reduced voltage stress on components
and motor bearings
• Helps avoid severe equipment damage
when ground faults occurs
• Reduced leakage current
72Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
Connecting the Kinetix 5500 Drive SystemChapter 5
Braided Ground Straps
25.4 mm (1.0 in.) by 6.35 mm (0.25 in.).
Keep lengths as short as possible.
4
3
2
1
Kinetix 5500
Servo Drive
(standalone)
Kinetix 5500
Servo Drives
(shared-bus)
Grounding the Drive System
All equipment and components of a machine or process system must have a
common earth ground point connected to chassis. A grounded system provides a
ground path for protection against electrical shock. Grounding your drives and
panels minimize the shock hazard to personnel and damage to equipment caused
by short circuits, transient overvoltages, and accidental connection of energized
conductors to the equipment chassis.
ATT EN TI ON : The National Electrical Code contains grounding requirements,
conventions, and definitions. Follow all applicable local codes and regulations
to safely ground your system.
For CE grounding requirements, refer to Agency Compliance
on page 27.
Ground the System Subpanel
Ground Kinetix 5500 drives and 2198-CAPMOD-1300 capacitor modules to a
bonded cabinet ground bus with a braided ground strap or 4.0 mm2 (12 AWG)
copper wire.
Figure 39 - Connecting the Ground Terminal
ItemDescription
1Ground screw (green) 2.0 N•m (17.7 lb•in), max
2Braided ground strap (customer sup plied)
3Ground grid or power distribution ground
4Bonded cabinet ground bus (customer supplied)
Refer to the System Design for Control of Electrical Noise Reference Manual,
publication GMC-RM001
Rockwell Automation Publication 2198-UM001D-EN-P - May 201473
, for more information.
Chapter 5Connecting the Kinetix 5500 Drive System
Follow NEC and applicable
local codes.
Bonded Ground Bus
Ground Grid or Power
Distribution Ground
Ground Multiple Subpanels
In this figure, the chassis ground is extended to multiple subpanels.
Figure 40 - Subpanels Connected to a Single Ground Point
High-frequency (HF) bonding is not illustrated. For HF bonding information,
refer to Bonding Multiple Subpanels
on page 38.
74Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
Wires must be copper with 75 °C (167 °F) minimum rating. Phasing of main AC
power is arbitrary and earth ground connection is required for safe and proper
operation.
Refer to Power Wiring Examples
Table 31 - Power and I/O Wiring Requirements
Description
Mains input power
(single-axis IPD connector)
Motor power
PELV/SELV 24V power
(single-axis CP connector)
Brake power
DC Bus power
Shunt resistor
(frame 2 and 3)
Shunt resistor
(frame 1)
(5)
Safety
Digital inputs
(1)
(1)
on page 190 for interconnect diagrams.
The National Electrical Code and local electrical codes take precedence over
the values and methods provided.
Connects to Terminals
PinSignal
CP-1
CP-2
BC-1
BC-2
DC-1
DC-2
RC-1
RC-2
RC-1
RC-2
ST0-1
ST0-2
ST0-3
ST0-4
ST0-5
IOD-1
IOD-2
IOD-3
IOD-4
24V+
24V-
MBRK+
MBRK-
DCDC+
DC+
SH
SH
DC+
SB+
SBS1
SC
S2
(7)
IN1
COM
IN2
SHLD
Wire Size
2
mm
(AWG)
1.5…4
(16…12)
1.5…6
(16…10)
Motor power cable
depends on motor/
drive combination.
0.75…2.5
(2)
(18…14)
(2)
2.5…6
(14…10)
2.5…0.5
(14…20)
(3)
N/A
(4)
N/A
4…0.5
(12…20)
1.5…0.2
(16…24)
1.5…0.2
(16…24)
Strip Length
mm (in.)
8.0 (0.31)
10.0 (0.39)
8.0 (0.31)
10.0 (0.39)
7.0 (0.28)
(4)
N/A
8.0 (0.31)
10.0 (0.39)N/A
10.0 (0.39)N/A
Tor que V alue
N•m (lb•in)
0.5…0.6
(4.4…5.3)
0.5…0.6
(4.4…5.3)
0.22…0.25
(1.9…2.2)
(4)
N/A
0.5…0.6
(4.4…5.3)
(6)
(6)
(1) The wire size, strip length, and torque specifications shown here apply to the single-axis connector that ships with the drive. For the shared-bus connector specifications, refer to
Tab le 33
on page 77 (CP connector) and Tab le 35 on page 79 (IPD connector).
(2) Building your own cables or using third-party cables is not an optio n. Use single motor cable catalog number 2090-CSxM1DF-xxAAxx. Refer to the Kinetix Motion Accessories
Specifications Technical Data, publication GMC-TD004
(3) Motor brake wires are part of the 2090-CSBM1DF-xxAAxx motor cable.
(4) DC bus connections are always made from drive-to-drive over the bus bar connection system. These terminals do not receive discrete wires.
(5) These signals and the safe torque-off (STO) connector apply to only the 2198-Hxxx-ERS drives.
(6) This connector uses spring tension to hold wires in place.
(7) This signal has dual-functionality. You can use IN1 (IOD-1) as registration or Home input.
, for cable specifications.
Rockwell Automation Publication 2198-UM001D-EN-P - May 201475
Chapter 5Connecting the Kinetix 5500 Drive System
IMPORTANT
IMPORTANT
IMPORTANT
ATT EN TI ON : To avoid personal injury and/or equipment damage, observe the
following:
• Make sure installation complies with specifications regarding wire types,
conductor sizes, branch circuit protection, and disconnect devices. The National
Electrical Code (NEC) and local codes outline provisions for safely installing
electrical equipment.
• Use motor power connectors for connection purposes only. Do not use them to
turn the unit on and off.
• Ground shielded power cables to prevent potentially high voltages on the shield.
Wiring Guidelines
Use these guidelines as a reference when wiring the power connectors on your
Kinetix 5500 drive.
For connector locations of the Kinetix 5500 drives, refer to Kinetix 5500
Connector Data on page 58.
When removing insulation from wires and tightening screws to secure the
wires, refer to the table on page 75
To improve system performance, run wires and cables in the wireways as
established in Establishing Noise Zones
Follow these steps when wiring the connectors for your Kinetix 5500 drive.
1. Prepare the wires for attachment to each connector plug by removing
insulation equal to the recommended strip length.
Use caution not to nick, cut, or otherwise damage strands as you
remove the insulation.
2. Route the cable/wires to your Kinetix 5500 drive.
for strip lengths and torque values.
on page 39.
3. Insert wires into connector plugs.
Refer to connector pinout tables in Chapter
diagrams in Appendix
4. Tighten the connector screws.
5. Gently pull on each wire to make sure it does not come out of its terminal;
reinsert and tighten any loose wires.
6. Insert the connector plug into the drive connector.
76Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
A.
4 or the interconnect
Connecting the Kinetix 5500 Drive SystemChapter 5
24V-
24V+
1
2
Remove
For DC
Bus Only
Kinetix 5500 Drive
Top Vie w
24V (CP) Connector Plug
24V-
24V+
Kinetix 5500 Drives
Top Vi ew
24V DC Input
Wiring Connector
Wiring the Power Connectors
This section provides examples and guidelines to assist you in making
connections to the input power connectors.
Refer to Power Wiring Examples
on page 190 for an interconnect diagram.
Wire the 24V Control Power Input Connector
The 24V power (CP) connector requires 24V DC input for the control circuitry.
The single-axis connector ships with the drive, shared-bus connector kits are
purchased separately.
Figure 41 - CP Connector Wiring - Single Axis
Table 32 - Single Axis CP Connector Wiring Specifications
Drive Cat. No.CP PinSignal
2198-Hxxx-ERSx
CP-124V+
CP-224V-
Figure 42 - CP Connector Wiring - Shared Bus
Table 33 - Shared Bus CP Connector Wiring Specifications
Drive Cat. No.CP PinSignal
2198-Hxxx-ERSx
CP-124V+
CP-224V-
Input Current, max
A rms
328.4 (8)11.0 (0.43)
Recommended
Wire Size
2
(AWG)
mm
2.5…0.5
(14…20)
Recommended
Wire Size
2
mm
(AWG)
Strip Length
mm (in.)
7.0 (0.28)
Strip Length
mm (in.)
Tor que Val ue
N•m (lb•in)
0.22…0.25
(1.9…2.2)
Tor que V alue
N•m (lb•in)
1.7…1.8
(15.0…15.9)
Rockwell Automation Publication 2198-UM001D-EN-P - May 201477
Chapter 5Connecting the Kinetix 5500 Drive System
L3
L2
L1
Remove
For DC
Bus Only
Kinetix 5500 Drive
Top Vie w
Input Power (IPD)
Connector Plug
L3
L2
L1
L3
L2
L1
Wire the Input Power Connector
The input power (IPD) connector requires 195…528V AC (single-phase or
three-phase) for mains input power. The single-axis connector ships with the
drive, shared-bus connector kits are purchased separately.
ATT EN TI ON : Make sure the input power connections are correct when wiring
the IPD connector plug or input wiring connector and that the plug/connector is
fully engaged in the drive connector. Incorrect wiring/polarity or loose wiring
can cause explosion or damage to equipment.
This section provides guidelines to assist you in making digital input
connections.
Wire the Safe Torque-off Connector
For the hardwired safe torque-off (STO) connector pinouts, feature descriptions,
and wiring information, refer to Chapter
9 beginning on page 157.
Rockwell Automation Publication 2198-UM001D-EN-P - May 201479
Chapter 5Connecting the Kinetix 5500 Drive System
1
IN1
COM
IN2
SHLD
Digital Inputs (IOD) Connector Plug
Kinetix 5500 Servo Drive
(front view)
IMPORTANT
Wire the Digital Inputs Connector
The digital inputs (IOD) connector uses spring tension to hold wires in place.
Figure 45 - IOD Connector Wiring
Wiring Kinetix VP Motors
Table 36 - Digital Inputs (IOD) Connector Specifications
Recommended
Drive Cat. No.DC PinSignal
IOD-1
2198-Hxxx-ERSx
(1) This signal has dual-functionality. You can use IN1 (IOD-1) as registration or Home input.
(2) This connector uses spring tension to hold wires in place.
IOD-2
IOD-3
IOD-4
IN1
COM
IN2
SHLD
(1)
Wire Size
2
(AWG)
mm
1.5…0.2
(16…24)
Strip Length
mm (in.)
10.0 (0.39)N/A
Tor que Val ue
N•m (lb•in)
(2)
The Kinetix 5500 drives with Kinetix VP motors use a single cable that includes
conductors for motor power, brake, and encoder feedback. Standard and
continuous-flex (Bulletin 2090) cables are available with and without the motor
brake conductors.
Due to the unique characteristics of single cable technology, designed for
and tested with Kinetix 5500 drives and Kinetix VP motors, you cannot
build your own cables or use third-party cables.
Refer to the Kinetix Motion Accessories Specifications Technical Data,
publication GMC-TD004
, for cable specifications.
Table 37 - Single Cable Catalog Numbers
Motor FamilyFeedback Kit Cat. No.Motor Cat. No.
Kinetix VP2198-KITCON-DSL
80Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
Refer to Kinetix 5500 Drive and Motor/Actuator Wiring Examples on page 195
for an interconnect diagram.
Figure 46 - MP Connector Wiring
U
V
W
ATT EN TI ON : Make sure the motor power connections are correct when wiring
the MP connector plug and that the plug is fully engaged in the module
connector. Incorrect wiring/polarity or loose wiring can cause an explosion or
damage to equipment.
Table 38 - Motor Power (MP) Connector Specifications
Motor power cable
depends on motor/
drive combination.
0.75…2.5
(18…14) max
2.5…6
(14…10) max
Strip Length
mm (in.)
8.0 (0.31)
10.0 (0.39)
Tor que V alue
N•m (lb•in)
0.5…0.6
(4.4…5.3)
Rockwell Automation Publication 2198-UM001D-EN-P - May 201481
Chapter 5Connecting the Kinetix 5500 Drive System
Motor Cable
Shield Clamp
Motor Brake (BC) Connector Plug
Kinetix 5500 Servo Drive
(front view)
Motor Brake Connections
Figure 47 - BC Connector Wiring
2
1
MBRKMBRK+
Table 39 - Motor Brake (BC) Connector Specifications
Drive Cat. No.Pin
2198-Hxxx-ERSx
(1) Motor brake wires are part of the 2090-CSBM1DF-xxAAxx motor cable.
BC-1MBRK+/Black
BC-2MBRK-/White
Signal/
Wire Color
Recommended
Wire Size
(AWG)
N/A
Strip Length
mm (in.)
(1)
7.0 (0.28)
Tor que V alue
N•m (lb•in)
0.22…0.25
(1.9…2.2)
82Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
Connecting the Kinetix 5500 Drive SystemChapter 5
IMPORTANT
Motor Cable
Shield Clamp
Motor Feedback
Connector Kit
2198-KITCON-DSL
Feedback Connector Kit
Connector
Housing
Refer to Kinetix 5500 Feedback Connector
Kit Installation Instructions, publication
2198-IN002
, for connector kit specifications.
Internal
Grounding Plate
Clamp Screws (2)
Mounting Screws (2)
Exposed Shield
Feedback Cable
(EPWR+, EPWR-)
Cover
Kinetix 5500 Servo Drive
(front view)
2090-CSxM1DF-18AAxx
Motor Cable
IMPORTANT
IMPORTANT
Motor Feedback Connections
Single motor cable feedback connections are made by using the
2198-KITCON-DSL feedback connector kit.
When using the 2198-KITCON-DSL feedback connector kit, the ambient
temperature for the Kinetix 5500 drive enclosure is 0…50 °C (32…122 °F).
Figure 48 - MF Connector Wiring
Cable preparation and positioning that provides a high-frequency bond
between the shield braid and grounding plate is required to optimize
system performance.
Table 40 - Motor Feedback (MF) Connector Specifications
Drive Cat. No.Pin
2198-Hxxx-ERSx
Signal/
Wire Color
MF-1D+/Blue
MF-2D-/White/Blue
Wire Size
AWG
2210.0 (0.39)0.4 (3.5)
Strip Length
mm (in.)
Tor que V alue
N•m (lb•in)
The feedback bundle in 2090-CSxM1DF-18AAxx motor cables (typically used
with frame 1 drives) route around the shield clamp (as shown in Figure 48
The feedback bundle in 14 and 10 AWG cables (typically used with frame 2
Rockwell Automation Publication 2198-UM001D-EN-P - May 201483
and 3 drives) route with the power and brake wires inside the cable shield.
).
Chapter 5Connecting the Kinetix 5500 Drive System
TIP
Motor Cable
Shield Clamp
2198-KITCON-DSL
Motor Feedback
Connector Kit
Motor Power
(MP) Connector
Motor Brake
(BC) Connector
Exposed shield braid
under clamp.
Shield Clamp Screws (2)
2.0 N•m (17.7 lb•in), max
Kinetix 5500 Servo Drives,
Frame 1 or 2, Front View
(frame 1 is shown)
Feedback cable routed
around the shield clamp.
Bulletin 2090 Single Motor Cable
Apply the Single Motor Cable Shield Clamp
Factory-supplied 2090-Series single motor cables are shielded, and the braided
cable shield must terminate at the drive during installation. A small portion of the
cable jacket has been removed to expose the shield braid. The exposed area must
be clamped (with the clamp provided) at the bottom front of the drive.
SHOCK HAZARD: To avoid hazard of electrical shock, make sure shielded power
cables are grounded according to recommendations.
Cables for Kinetix VP motors (catalog numbers 2090-CBxM1DF-18AAxx) do not
route the feedback bundle under the shield clamp. The same cables with 14 or
10 AWG conductors have the feedback bundle within the cable shield braid.
This procedure assumes you have completed wiring your motor power, brake, and
feedback connectors and are ready to apply the cable shield clamp.
Follow these steps to apply the motor cable shield clamp.
1. Loosen the clamp screws and remove at least one of the screws.
Figure 49 - 18 AWG Cable Installation
When the drive/motor combination calls for 18 AWG cable, the feedback
cable routes around the motor cable shield clamp.
84Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
Figure 50 - 14 and 10 AWG Cable Installation
Motor Cable
Shield Clamp
Motor Power
(MP) Connector
Motor Brake
(BC) Connector
Exposed shield braid
under clamp.
Shield Clamp Screws (2)
Feedback cable routed
within the shield braid.
Kinetix 5500 Servo Drives,
Frame 2 or 3, Front View
(frame 2 is shown)
2198-KITCON-DSL
Motor Feedback
Connector Kit
Retention Screw
(loosen, do not remove)
Clamp features apply to all
frame sizes.
Torque clamp screws to
2.0 N•m (17.7 lb•in), max
Bulletin 2090 Single Motor Cable
Connecting the Kinetix 5500 Drive SystemChapter 5
When the drive/motor combination calls for 14 or 10 AWG cable, the
feedback cable routes along with the power and brake wiring.
2. Position the exposed portion of the cable braid directly in line with the
clamp.
3. Tighten the clamp screws. Torque value 2.0 N•m (17.7 lb•in) max.
4. Repeat step 1
through step 3 for each drive in multi-axis configurations.
Rockwell Automation Publication 2198-UM001D-EN-P - May 201485
Chapter 5Connecting the Kinetix 5500 Drive System
IMPORTANT
Wiring Other Allen-Bradley
Motors and Actuators
Kinetix 5500 drives are also compatible with other Allen-Bradley servo motors
and actuators when wired at the drive by using the Hiperface-to-DSL feedback
converter kit, catalog number 2198-H2DCK. The kit is required for converting
the 15-pin Hiperface feedback signals to 2-pin DSL feedback signals.
Table 41 - Compatible Motors and Actuators
Motor/Actuator Families
MP-Series low-inertia motors (Bulletin MPL)
MP-Series medium-inertia motors (Bulletin MPM)
MP-Series food-grade motors (Bulletin MPF)
MP-Series stainless-steel motors (Bulletin MPS)
MP-Series integrated linear stages (Bulletin MPAS/MPMA) ballscrew
MP-Series electric cylinders (Bulletin MPAR)
MP-Series heavy-duty electric cylinders (Bulletin MPAI)
LDAT-Series integrated linear thrusters
(1) The 2198-H2DCK converter kit is required for all 400V-class MP-Series motors and actuators. The 2198-H2DCK (series B or later)
converter kit is required for LDAT-Series linear thrusters and all 200V-class M P-Series motors and actuators.
(1)
Encoder Feedback Type
Single-turn or multi-turn
high-resolution, absolute
To configure these motors and actuators with your Kinetix 5500 servo drive,
you must have drive firmware 2.002 or later. Refer to Tab l e 42
to determine
if you need to install the Kinetix 5500 Add-on Profile.
Add-On profiles (AOP) are available for download at the Custom Downloads
Add-On Profiles website: https://download.rockwellautomation.com/esd/
download.aspx?downloadid=addonprofiles
Follow these steps to download the Kinetix 5500 Add-On profile.
1. Login to the Custom Download Add-On Profiles website.
86Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
Connecting the Kinetix 5500 Drive SystemChapter 5
The Custom Download Files dialog box opens.
2. Check AOP for 2198-Hxx CIP Motion Kinetix 5500.
3. Click Download Now and accept the user license agreement.
If prompted to install the Download Manager, allow the installation.
4. Click the Add-On Profile icon and follow the download instructions.
5. Extract the AOP zip file and run Setup.
Motor Power and Brake Connections
The motors and actuators in Ta b l e 4 1 have separate power/brake and feedback
cables. The motor power/brake cable attaches to the cable clamp on the drive and
wires to the MP and BC connectors, respectively.
Table 43 - Current Motor Power Cable Compatibility
MPAS-A/Bxxxx1-V05SxA, MPAS-A/Bxxxx2-V20SxA
MPAI-A/Bxxxx, MPAR-A/B3xxx,
MPAR-A/B1xxx and MPAR-A/B2xxx (series B)
LDAT-Sxxxxxx-xDxN/A
(1)
Motor Power Cat. No.
(with brake wires)
2090-CPBM7DF-xxAAxx
(standard) or
2090-CPBM7DF-xxAFxx
(continuous-flex)
(2)
Motor Power Cat. No.
(without brake wires)
2090-CPWM7DF-xxAAxx
(standard) or
2090-CPWM7DF-xxAFxx
(continuous-flex)
(2)
(1) The 2198-H2DCK converter kit is required for all 400V-class MP-Series motors and actuators. The 2198-H2DCK (series B or later)
converter kit is required for LDAT-Series linear thrusters and all 200V-class M P-Series motors and actuators.
(2) Refer to the Kinetix Motion Accessories Specifications Technical Data, publication GMC-TD004, for cable specifications.
Refer to Motor Power Connections on page 81 and Motor Brake Connections
on page 82
Rockwell Automation Publication 2198-UM001D-EN-P - May 201487
for the MP and BC connector specifications.
Chapter 5Connecting the Kinetix 5500 Drive System
IMPORTANT
Table 44 - Legacy Motor Power Cables
Motor CableDescriptionMotor Power Cat. No.
Standard
Continuous-flex
Power/brake, threaded2090-XXNPMF-xxSxx
Power-only, bayonet2090-XXNPMP-xxSxx
Power/brake, threaded2090-CPBM4DF-xxAFxx
Power-only, threaded2090-CPWM4DF-xxAFxx
Power-only, bayonet2090-XXTPMP-xxSxx
To use your existing Bulletin 2090 cables with Kinetix 5500 drives, some
preparation is necessary so that the cable shield, conductor, and strip lengths are
correct. Follow these cable preparation guidelines:
• Trim the shield flush so that no strands can short to adjacent terminals.
• Measure the conductor lengths and include a service loop.
• Remove just enough insulation to provide the proper strip length.
Maximum Cable Lengths
The power cable length for Kinetix 5500 drive and MP-Series motor/actuator
combinations is limited to 20 m (65.6 ft); however, you can replace the existing
motor power/brake cable with a 2090-CSBM1DF-xxAAxx single motor cable to
extend the length up to 50 m (164 ft).
When replacing your existing motor power/brake cable with a 2090CSBM1DF-xxAAxx single motor cable, only the motor power and brake
conductors are used. Cut off the feedback conductors in the single motor
cable and reuse the existing 2090-Series feedback cable.
88Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
Connecting the Kinetix 5500 Drive SystemChapter 5
Dimensions are in mm (in.)
Motor Conductors
Brake
Conduc tors
(1)
Electrical Tape
or Heat Shrink
8.0 (0.31) Frame 1 and 2 drives
10.0 (0.39) Frame 3 drives
Motor Power/Brake Cable Preparation
Power cable preparation on existing 16 and 14 AWG cables is sufficient to reuse
on Kinetix 5500 frame 1 and 2 drives, except for the brake conductors, which are
much longer than required.
However, for frame 3 drives with 14 or 10 AWG cables, the overall length of the
cable preparation area needs to be increased for the motor power conductors to
reach the MP connector and also provide a proper service loop.
Follow these steps to prepare your existing brake conductors and 14 or 10 AWG
power cable.
1. Remove a total of 325 mm (12.8 in.) of cable jacket from your existing
cable.
This exposes additional cable shield.
2. Remove all but 63.5 mm (2.5 in.) of the shield.
3. Cover 12.5 mm (0.5 in.) of the shield ends and an equal length of the
conductors with 25 mm (1.0 in.) of electrical tape or heat shrink.
Do the same on the other side of the cable shield. This keeps the shield
ends from fraying and holds the conductors together.
4. Cut the brake conductors back to 163 mm (6.4 in.) and trim the shield
braid at the base of the jacket.
The shield braid covering the brake conductors is not needed.
5. Remove the specified length of insulation from the end of each wire.
This example applies to existing 2090-Series cables and 2090-Series single motor
cables. If you are using a 2090-CSBM1DF-xxAAxx single motor cable, you can
remove the shield braid covering the brake conductors.
Figure 51 - Power/brake Cable (14 and 10 AWG)
325 (12.8)
262 (10.3)
25.0 (1.0)
284 (11.2)
155 (6.1)
221 (8.7)
7.0 (0.28)
51.0 (2.0)
(1) The overall shield braid covering the brake conductors can be removed.
Rockwell Automation Publication 2198-UM001D-EN-P - May 201489
Chapter 5Connecting the Kinetix 5500 Drive System
IMPORTANT
Clamp Compressed
Around Shield
(no spacer required)
Insert the clamp spacer when
the cable diameter is smaller
than the drive clamp alone.
Servo Drive
Clamp Spacer (if needed)
Shield Clamp
Clamp Screws
2.0 N•m (17.7 lb•in)
Service Loops
Frame 1
Servo Drive
Frame 2
Servo Drive
Frame 3
Servo Drive
Clamp Spacer Added
(small diameter cable)
Apply the Motor Power/brake Shield Clamp
The power/brake cable shield attaches to the drive cable clamp. A clamp spacer is
included with the kit for cable diameters that are too small for a tight fit within
the drive clamp alone.
• Routing the conductors with service loops provides stress relief to the
motor power and brake conductors.
• Make sure the cable clamp tightens around the cable shield and provides a
good bond between the cable shield and the drive chassis.
If the power/brake cable shield has a loose fit inside the shield clamp, insert
the clamp spacer between the shield clamp and the drive to reduce the
clamp diameter. When the clamp screws are tight, 2.0 N•m (17.7 lb•in), the
result must be a high-frequency bond between the cable shield and the
drive chassis.
Figure 52 - Cable Clamp Attachment
90Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
Connecting the Kinetix 5500 Drive SystemChapter 5
IMPORTANT
IMPORTANT
Motor Feedback Connections
The feedback cable attaches to the 2198-H2DCK converter kit and is wired to
the 10-pin connector. Bulletin 2090 feedback cables require preparation to make
sure the shield clamp attaches properly and conductors route smoothly to the
10-pin connector terminals.
When using the 2198-H2DCK feedback connector kit and Bulletin 2090
feedback cables listed in Tab le 45
the Kinetix 5500 drive enclosure is derated to 0…40 °C (32…104 °F).
All of the current and legacy feedback cables listed below are compatible with the
2198-H2DCK converter kit.
Only Allen-Bradley motors and actuators with single-turn or multi-turn
high-resolution absolute encoders are compatible.
MPAR-A/B1xxxx-V and MPAR-A/B2xxxx-V (series B)
MPAR-A/B3xxxx-M
MPAI-A/BxxxxxM3
LDAT-Sxxxxxx-xDx
(1) The 2198-H2DCK converter kit is required for all 400V-class MP-Series motors and actuators. The 2198-H2DCK (series B or later)
converter kit is required for LDAT-Series linear thrusters and all 200V-class M P-Series motors and actuators.
(1)
Feedback Kit
Cat. No.
2198-H2DCK
Feedback Cable Cat. No.
2090-CFBM7DF-CEAAxx
2090-CFBM7DD-CEAAxx
2090-CFBM7DF-CERAxx
(standard) or
2090-CFBM7DF-CEAFxx
2090-CFBM7DD-CEAFxx
2090-CFBM7DF-CDAFxx
(continuous-flex)
Table 46 - Legacy Motor Feedback Cables
Motor CableDescriptionFeedback Cable Cat. No.
2090-XXNFMF-Sxx
2090-UXNFBMF-Sxx
2090-UXNFBMP-Sxx
2090-XXNFMP-Sxx
Standard
Continuous-flex
Encoder feedback, threaded
Encoder feedback, bayonet
Encoder feedback, bayonet2090-XXTFMP-Sxx
Encoder feedback, threaded2090-CFBM4DF-CDAFxx
Rockwell Automation Publication 2198-UM001D-EN-P - May 201491
Chapter 5Connecting the Kinetix 5500 Drive System
Ter min al
Signal
Wire Color
Strip Length
mm (in.)
Tor que V alue
N•m (lb•in)
1 SIN+ Black
5.0 (0.2)
0.22…0.25
(1.9…2.2)
2 SIN–White/Black
3 COS+Red
4 COS–White/Red
5DATA+ Green
6 ECOM
(1)
(1) The ECOM and TS- connections are tied together and connect to the cable shield.
White/Gray
7EPWR_9V
(2)
(2) The converter kit generates 5V and 9V from a 12V supply coming from the drive. The 5V supply is
used by 5V encoders in 230V motors. The 9V supply is used by 9V encoders in 460V motors.
Orange
10DATA– White/Green
11TS+White/Orange
14EPWR_5V
(2)
Gray
10-pin
Conne ctor
IMPORTANT
Cable Jacket
Cable Shield
Dimensions are in mm (in.)
1
2
3
4
5
6
7
10
11
14
Figure 53 - 2198-H2DCK Converter Kit Pinout
Motor Feedback Cable Preparation
Follow these steps to prepare feedback cables.
1. Remove 115 mm (4.5 in.) of cable jacket and 103 mm (4.0 in.) of cable
shield.
This length of wire is needed to provide a service loop for the longest
wires terminated at the 10-pin connector. However, most wires need to
be trimmed shorter, depending on the terminal they are assigned to.
2. Determine the length for each of the 10 wires and trim as necessary.
3. Remove 5.0 mm (0.2 in.) of insulation from the end of each wire.
92Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
12.0 (0.5)
103 (4.0)
5.0 (0.2)
115 (4.5)
Connecting the Kinetix 5500 Drive SystemChapter 5
IMPORTANT
Shield Clamp
Apply the Converter Kit Shield Clamp
Follow these steps to apply the converter kit shield clamp.
1. Apply the shield clamp to the 12 mm (0.5 in.) of exposed cable shield to
achieve a high-frequency bond between the shield braid and clamp.
Cable preparation and positioning that provides a high-frequency
bond between the shield braid and clamp is required to optimize
system performance.
Apply 0.30 N•m (2.6 lb•in) torque to each screw.
2. Route and insert each wire to its assigned terminal.
Include a service loop, as shown in Figure 54
pinout in Figure 53
.
, and refer to the connector
3. Tighten each terminal screw.
Apply 0.22…0.25 N•m (1.9…2.2 lb•in) torque to each screw.
4. Gently pull on each wire to make sure it does not come out of its terminal;
reinsert and tighten any loose wires.
5. Attach the tie wrap for added stress relief.
Rockwell Automation Publication 2198-UM001D-EN-P - May 201493
Chapter 5Connecting the Kinetix 5500 Drive System
14
11
10
7
6
5
4
3
2
1
2
1
Shield Clamp
Clamp Screws (2)
Service Loops
Tie Wrap for Stress Relief
and Wire Management
Mounting Screws (2)
Mounting Bracket
Frame 2 Mounting Position
(catalog numbers 2198-H015-ERSx,
2198-H025-ERS, and 2198-H040-ERSx)
Frame 1 Mounting Position
Frame 3 Mounting Position
(catalog number 2198-H070-ERSx)
(catalog numbers 2198-H003 ERSx
and 2198-H008-ERSx)
Refer to Hiperface to DSL Feedback Converter Kit Installation Instructions,
publication 2198-IN006
, for converter kit specifications.
10-pin
Connector
Converter Kit Mounting Hole
with Protective Cover Removed
(frame 1 drive example shown)
1. Place exposed cable shield
in the channel.
2. Place the shield clamp over
the exposed shield.
94Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
(1) The ECOM and TS- connections are tied together and connect to the cable shield.
A mounting bracket is included with the 2198-H2DCK converter kit to secure
the kit to the drive. Install the mounting bracket in the mounting position
specific to the frame size of your drive.
Figure 54 - Wiring the 2198-H2DCK Feedback Converter Kit
Connecting the Kinetix 5500 Drive SystemChapter 5
IMPORTANT
2
1
3
4
1
2
Kinetix 5500 Capacitor Module
Top Vie w
Kinetix 5500 Capacitor Module
Front View
ItemDescription
1Module status (MS) connector (relay output)
2Module status indicator
3DC bus (DC) connector (under cover)
(1) (2)
(1) The DC bus connector ships with a protective knock-out cover
that can be removed for use in shared-bus configurations.
(2) The shared-bus connector set for the capacitor module, catalog
number 2198-KITCON-CAP1300, is included for connection to the
upstream drive. Replacement kits are also available.
424V control input power (CP) connector
(2)
Capacitor Module
Connections
Follow these guidelines when wiring the 2198-CAPMOD-1300 capacitor
module:
• Wire relay output (MS) connections to the Logix5000 controller
(optional).
• Refer to Kinetix 5500 Capacitor Module
• Refer to Kinetix 5500 Capacitor Module Status Indicators
wiring example on page 191.
on page 147 for
troubleshooting the module status indicator and relay output.
• Refer to the installation instructions provided with your Bulletin 2198
capacitor module, publication 2198-IN004
.
To improve system performance, run wires and cables in the wireways as
established in Chapter
2.
Connections to the DC bus and 24V control power must be made with the
shared-bus connection system.
You must disconnect the internal shunt wires at the RC connector before
connecting the Bulletin 2097 shunt resistor wires.
Table 50 - Shunt Resistor Selection
Drive Cat. No.
2198-H003-ERSx
2198-H008-ERSx
2198-H015-ERSx
2198-H025-ERSx
2198-H040-ERSx
2198-H070-ERSx
Bulletin 2097 Shunt Resistor
Cat. No.
2097-R7
2097-R6
2
(AWG)
Strip Length
mm (in.)
8.0 (0.31)
Tor que Val ue
N•m (lb•in)
0.5…0.6
(4.4…5.3)
96Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
Connecting the Kinetix 5500 Drive SystemChapter 5
1 (Front)
2 (Rear)
00:00:BC:2E:69:F6
1
2
LNK1LNK2NE T OK
1
2
ControlLogix Controller
1756-ENxTR EtherNet/IP module is shown.
ControlLogix Ethernet Ports
The 1756-EN2T modules have only one port,
1756-EN2TR and 1756-EN3TR modules have two.
Bottom View
Front Views
CompactLogix 5370 L1, L2, and L3 Controllers
1769-L36ERM controller is shown.
Port 1, Front
Port 2, Rear
IMPORTANT
Ethernet Cable Connections
This procedure assumes you have your CompactLogix 5370 controller or
ControlLogix EtherNet/IP module and Kinetix 5500 drives mounted and are
ready to connect the network cables.
The EtherNet/IP network is connected by using the PORT 1 and PORT 2
connectors. Refer to page 58
to locate the Ethernet connectors on your
Kinetix 5500 drive. Refer to the figure below to locate the connectors on your
Logix5000 controller.
Shielded Ethernet cable is available in several standard lengths. Refer to the
Kinetix Motion Accessories Specifications Technical Data, publication
GMC-TD004
, for more information.
Ethernet cable lengths connecting drive-to-drive, drive-to-controller, or drive-toswitch must not exceed 100 m (328 ft).
Figure 57 - ControlLogix and CompactLogix Ethernet Port Locations
These Logix5000 controllers accept linear, ring (DLR), and star network
configurations. Refer to Typical Communication Configurations
on page 20 for
linear, ring, and star configuration examples.
When using an external Ethernet switch for routing traffic between the
controller and the drive, switches with IEEE-1588 time synchronization
capabilities (boundary or transparent clock) must be used to make sure switch
delays are compensated.
Rockwell Automation Publication 2198-UM001D-EN-P - May 201497
Chapter 5Connecting the Kinetix 5500 Drive System
Notes:
98Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
Chapter 6
TIP
Configure and Start the
Kinetix 5500 Drive System
This chapter provides procedures for configuring your Kinetix 5500 drive system
with a Logix5000 controller.
Top icPa ge
Understanding the Kinetix 5500 Display100
Configure the Drive104
Configure the Logix Designer Application Project105
Apply Power to the Kinetix 5500 Drive129
Test and Tune the Axes131
Understanding Bus Sharing Group Configuration135
Before you begin, make sure you know the catalog number for each
drive component, the Logix module and /or controller, and the servo
motor used in your motion control application.
Rockwell Automation Publication 2198-UM001D-EN-P - May 201499
Chapter 6Configure and Start the Kinetix 5500 Drive System
Soft Menu
Navigation Buttons
Status Indicators (see page 146
)
Menu Buttons
Setup Buttons
MAIN MENU
MOTOR INFO
ESC
DRIVE INFO
Each soft menu item is executed by pressing the
navigation button directly below the item, as
shown in this example.
HOME
LOG
TEXT
INFO
HELP
Understanding the
Kinetix 5500 Display
The Kinetix 5500 drive has two status indicators and an LCD status display. The
indicators and display are used to monitor the system status, set network
parameters, and troubleshoot faults. Four navigation buttons are directly below
the display and are used to select items from a soft menu.
Figure 58 - Kinetix 5500 Drive LCD Display and Status Indicators
PRECHARGE
192.168.1.1
DC BUS: 0.3V
SETUP
MENU
PRECHARAGE
192.168.1.1
DC BUS: 0.3V
SETUP
MENU
This is the Home screen. The SETUP selections are tied to the two left-side
buttons and the MENU selections are tied to the two right-side buttons.
PRECHARAGE
192.168.1.1
DC BUS: 0.3V
SETUP
MENU
100Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
The soft menu provides a changing selection that corresponds to the current
screen. Use the navigation buttons to perform the following.
ESC
(1) Refer to Faul t Code s beginning on page 140 to review the troubleshooting tables.
Press to go back. Pressing enough times results in the HOME screen.
Pressing either arrow moves the selection to the next (or previous) item. When changing values,
pressing the up arrow increments the highlighted value. Values rollover after reaching the end of
the list.
Press to select values to change, moving from right to left. Values rollover when reaching the end
of the list.
Press to select a menu item.
Press to return to the Home screen.
Press to display the list of active fault codes.
Press to display the fault text (exception code in troubleshooting tables).
Press to display the fault details (the problem in troubleshooting tables).
Press to display the fault help (possible solutions in troubleshooting tables).
(1)
(1)
(1)
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.