Rockwell Automation 1785-Lx0E User Manual

Contents

Installation Instructions
Ethernet PLC-5 Programmable Controllers
Catalog Numbers 1785-L20E, 1785-L40E, 1785-L80E, Series F
For This Topic See Page
About This Publication 1
Related User Manual 5
About the Controllers 6
Install the System Hardware 13
Troubleshoot the Controller 20
Controller Specifications 24
Rockwell Automation Support Back cover

About This Publication

This document describes how to install and troubleshoot your Ethernet PLC-5 programmable controller. For more information, see the documents listed on the following page or contact your local Rockwell Automation representative.
These installation instructions:
provide the basic information you need to get your system up and running.
provide specific bit and switch settings for modules.
include high-level procedures with cross-references to other manuals for
more detail.
IMPORTANT
In this document, we assume you are using a Series F Ethernet PLC-5 programmable controller.
1 Publication 1785-IN063B-EN-P - January 2006
2 Ethernet PLC-5 Programmable Controllers

Important User Information

Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.ab.com/manuals/gi) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc. is prohibited.
Throughout this manual we use notes to make you aware of safety considerations.
WARNINGWARNINGWARNINGWARNING
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
IMPORTANT
ATTENTION
SHOCK HAZARD
BURN HAZARD
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you:
identify a hazard
avoid a hazard
recognize the consequence
Labels may be located on or inside the equipment to alert people that dangerous voltage may be present.
Labels may be located on or inside the equipment to alert people that surfaces may be dangerous temperatures.
Publication 1785-IN063B-EN-P - January 2006
Environment and Enclosure
Ethernet PLC-5 Programmable Controllers 3
ATTENTION
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance.
This equipment is supplied as “open type” equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
Besides this publication, see:
– Industrial Automation Wiring and Grounding Guidelines,
Allen-Bradley publication 1770-4.1, for additional installation requirements.
– NEMA Standards publication 250 and IEC publication
60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure.
Prevent Electrostatic Discharge
ATTENTION
This equipment is sensitive to electrostatic discharge that can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment.
Touch a grounded object to discharge potential static.
Wear an approved grounding wrist strap.
Do not touch connectors or pins on component
boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe
packaging when not in use.
Publication 1785-IN063B-EN-P - January 2006
4 Ethernet PLC-5 Programmable Controllers
North American Hazardous Location Approval
The following information applies when operating this equipment in hazardous locations:
Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest “T” number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.
EXPLOSION HAZARD
WARNING
Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
Substitution of components may impair suitability for Class I, Division 2.
If this product contains batteries, they must only be changed in an area known to be nonhazardous.
Informations sur l’utilisation de cet équipement en environnements dangereux :
Les produits marqués “CL I, DIV 2, GP A, B, C, D” ne conviennent qu’à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d’identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d’équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l’installation.
RISQUE D’EXPLOSION
AVERTISSEMENT
Couper le courant ou s’assurer que l’environnement est classé non dangereux avant de débrancher l'équipement.
Couper le courant ou s'assurer que l’environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.
S’assurer que l’environnement est classé non dangereux avant de changer les piles.
Publication 1785-IN063B-EN-P - January 2006
Ethernet PLC-5 Programmable Controllers 5

Related User Manual

The related user manual contains detailed information about configuring, programming, and using an Ethernet PLC-5 controller. To obtain a copy of the Enhanced and Ethernet PLC-5 Programmable Controllers User Manual, publication 1785-UM012, you can:
view or download an electronic version from the Internet at www.rockwellautomation.com/literature.
contact your local distributor or Rockwell Automation representative to place an order.
Additional Related Documentation
The following documents contain additional information related to the products described in this document.
For More Information About See This Publication Number
Ethernet PLC-5 programmable controllers Enhanced and Ethernet PLC-5 Programmable Controllers User
Manual
Universal 1771 I/O chassis Universal I/O Chassis Installation Instructions 1771-2.210
Power supply Power Supply Modules (1771-P4S, -P6S, -P4S1, -P6S1)
Installation Instructions
DH+ network, extended-local I/O Enhanced and Ethernet PLC-5 Programmable Controllers User
Manual
Data Highway/Data Highway Plus/Data Highway II/Data Highway-485 Cable Installation Instructions
Communication cards 1784-KTx Communication Interface Card User Manual 1784-6.5.22
Cables Enhanced and Ethernet PLC-5 Programmable Controllers User
Manual
Batteries Allen-Bradley Guidelines for Lithium Battery Handling and
Disposal
Grounding and wiring Allen-Bradley programmable controllers
Terms and definitions Allen-Bradley Industrial Automation Glossary AG-7.1
Allen-Bradley Programmable Controller Wiring and Grounding Guidelines
1785-UM012
1771-2.135
1785-UM012
1770-6.2.2
1785-UM012
AG-5.4
1770-4.1
Publication 1785-IN063B-EN-P - January 2006
6 Ethernet PLC-5 Programmable Controllers

About the Controllers

Keyswitch - Selects Controller Mode
Channel 2 Ethernet Status Indicator (green when functioning normally; red when not functioning)
Channel 2, Ethernet Transmit Indicators (green when the channel is communicating at either 100M or 10M communication rate)
Ethernet Channel 2 Communication Port - RJ45 Connector
Channel 1A Status Indicator (lights green and red)
The following illustrations indicate the controller’s front panel components.
PLC-5/20E, -5/40E and -5/80E, Controller Front Panel
Battery Indicator (red when the battery is low)
Controller RUN/FAULT Indicator (green when running; red when faulted)
Force Indicator (amber when I/O forces are enabled)
Channel 0 Communication Status Indicator (green when the channel is communicating)
STAT
100M
10M
ETHERNET
Channel 0-25-pin D-shell serial port. Supports standard CEIA RS-232C and RS-423 and is RS-422A compatible.
Use this port with ASCII or DF1 full-duplex, half-duplex master, and half-duplex slave protocols. The port's default configuration supports controller programming:
DF1 point-to-point 2400 bps No parity
Channel 1B Status Indicator (lights green and red)
One stop-bit BCC error check No handshaking
8-pin Mini-DIN, DH+ Programming Terminal Connection Parallel to Channel 1A
Channel 1A Communication Port - Default Configuration Is DH+ Communication
Channel 1B Communication Port - Default Configuration Is Remote I/O Scanner
Install Battery Here
Install Memory Module Here
Use these labels to write information about the channel, such as communication mode and station addresses.
PLC-5/40E
Programmable
Controller
PLC-5 Family Member Designation
43909
Additional System Components
Along with your controller, you need the following components to complete a basic system.
Product Cat. No.
Lithium battery 1770-XYC
I/O chassis 1771-A1B, -A2B, -A3B, -A3B1, -A4B
Power supply 1771-P4S, -P6S, -P4S1, -P6S1
Personal computer
Publication 1785-IN063B-EN-P - January 2006
Ethernet PLC-5 Programmable Controllers 7
New Features
The controllers contain an RJ-45 connector for the Channel 2 communication port.
The controllers provide additional Channel 2 port configuration and status:
ENET Status
ENET Transmit
RJ45 Connector
STAT
100M
10M
BOOTP, DHCP, or Static entry of IP address
Auto Negotiate speed selection
Full/Half Duplex port setting
10/100 speed selection
Email client functionality
Enable/Disable HTTP Web Server
Enable/Disable SNMP functionality
To see or activate the new configuration and status features:
1. Open or create a project in RSLogix 5 software, version 7.1 or later.
2. Click on the Channel Configuration menu.
You see the Edit Channel Properties menu.
3. Click on the Channel 2 tab.
BOOTP, DHCP, or Static Entry of IP Address
As shown in the following screen capture, you can select between a static or dynamic network configuration.
The default is Dynamic Network Configuration Type and Use BOOTP to obtain network configuration.
If you choose a dynamic network configuration, you can change the default BOOTP to DHCP.
If you choose a static network configuration type, you must enter the IP address.
Publication 1785-IN063B-EN-P - January 2006
8 Ethernet PLC-5 Programmable Controllers
Similarly, if you have a dynamic network configuration, DHCP or BOOTP assigns the controller’s hostname. With a static configuration, you assign the hostname.
When you create a hostname, consider these naming conventions.
The hostname can be a text string up to 24 characters.
The hostname can contain alpha (A to Z) numeric (0 to 9) and may
contain a period and minus sign.
The first character must be an alpha character.
The last character must not be a minus sign.
You cannot use blank spaces or space characters.
The hostname is not case-sensitive.
Auto Negotiate Speed Selection
In the Edit Channel 2 properties box, you can either leave the Auto Negotiate box unchecked, which forces the port setting to a particular speed and duplex port setting, or you may check the Auto Negotiate box, which lets the controller negotiate a speed and duplex port setting.
If you check Auto Negotiate, the port setting lets you select the range of speed and duplex settings that the controller negotiates. The default port setting with Auto Negotiate checked is 10/100 Mbps Full Duplex/Half Duplex, which lets the controller negotiate any of it’s four available settings. The following table lists the order of negotiation for each setting.
Setting 100 Mbps
Full Duplex
10/100 Mbps Full Duplex/Half Duplex 1st 2nd 3rd 4th
100 Mbps Full Duplex or 100 Mbps Half Duplex 1st 2nd 3rd
100 Mbps Full Duplex or 10 Mbps Full Duplex 1st 2nd 3rd
100 Mbps Half Duplex or 10 Mbps Full Duplex 1st 2nd 3rd
100 Mbps Full Duplex 1st 2nd
100 Mbps Half Duplex 1st 2nd
10 Mbps Full Duplex 1st 2nd
10 Mbps Half Duplex Only 1st
100 Mbps Half Duplex
10 Mbps Full Duplex
10 Mbps Half Duplex
Publication 1785-IN063B-EN-P - January 2006
Ethernet PLC-5 Programmable Controllers 9
The unchecked Auto Negotiate box and corresponding port settings are shown below.
The checked Auto Negotiate box and corresponding port settings are shown below.
Email Client Functionality
The controller is an email client that sends an email triggered by a message instruction via a mail relay server. The controller uses standard SMTP protocol to forward the email to the relay server. The controller does not receive email.
You must enter the SMTP Server’s IP address into the text box as shown in the following dialog.
The controller supports login authentication. If you want the controller to authenticate to the SMTP server, check the SMTP authentication box. If you select authentication, you must also use a username and password for each email.
Publication 1785-IN063B-EN-P - January 2006
10 Ethernet PLC-5 Programmable Controllers
To create an email:
1. Create a message instruction similar to the one below.
The destination (to), the reply (from), and the body (text) are stored as strings in elements of separate ASCII string files.
If you want to send an email to a specific recipient when a controller application generates an alarm or reaches a certain condition, program the controller to send the message instruction to the destination of the email.
2. Verify the r ung.
3. Click on Setup Screen.
A dialog appears like the one below.
Publication 1785-IN063B-EN-P - January 2006
The three Data fields display the string values of the ST file element addresses.
Ethernet PLC-5 Programmable Controllers 11
4. To send email, enter the appropriate information into the Data fields and Username and Password, if Authentication is enabled.
Examine the Error Code (denoted in Hex) and Error Description areas within the General tab to see if the message was successfully delivered.
Error Code (hex) Description
0x000 Delivery successful to the mail relay server.
0x002 Resource unavailable. The email object was unable to obtain memory resources to initiate the SMTP session.
0x101 SMTP mail server IP address not configured.
0x102 To (destination) address not configured or invalid.
0x103 From (reply) address not configured or invalid.
0x104 Unable to connect to SMTP mail server.
0x105 Communication error with SMTP server.
0x106 Authentication required.
0x017 Authentication failed.
Channel 2 Status
To check the status of channel 2:
1. In your RSLogix 5 software project, click on Channel Status.
You see the Channel Status menu.
2. Click on the Channel 2 tab.
3. Click on the Port tab.
You see the status for each port configuration.
Publication 1785-IN063B-EN-P - January 2006
12 Ethernet PLC-5 Programmable Controllers
SNMP Server Enabled
Enable/Disable HTTP Web Server
You can disable the HTTP web server functionality from within the Channel 2 Configuration by unchecking the HTTP Server Enable check box shown below
.
HTTP Server Enabled
The default (checked box) lets you connect to the controller using a web browser. Although this parameter can be downloaded to the controller as part of a program download or changed and applied while online with the controller, you must cycle power to the controller for the change to take affect.
Enable/Disable Simple Network Management Protocol (SNMP)
You can disable the controller’s SNMP functionality from within the Channel 2 Configuration by unchecking the SNMP Server Enable check box as shown above.
The default (checked box) lets you connect to the controller using an SNMP client. Although this parameter can be downloaded to the controller as part of a program download or changed and applied while online with the controller, you must cycle power to the controller for the change to take affect.
Publication 1785-IN063B-EN-P - January 2006
Ethernet PLC-5 Programmable Controllers 13

Install the System Hardware

This illustration shows a basic Ethernet PLC-5 programmable controller system.
Data Highway
Plus or Serial
Cable
PC with Programming Software
Ethernet PLC-5 Controller
Internal Power Supply
43910
For more information, see the Enhanced and Ethernet PLC-5 Programmable Controllers User Manual, publication 1785-UM012.
WARNINGWARNINGWARNINGWARNING
WARNINGWARNINGWARNINGWARNING
If you connect or disconnect any communications cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
The local programming terminal port (circular mini-DIN style programming terminal connection) is intended for temporary use only and must not be connected or disconnected unless the area is assured to be nonhazardous.
Publication 1785-IN063B-EN-P - January 2006
14 Ethernet PLC-5 Programmable Controllers
Prepare to Install the Controller
Installing the controller is one part of setting up the hardware in your system.
To properly install the controller, you must follow these procedures in the order described in this section.
1. Install an I/O Chassis.
2. Configure the I/O Chassis.
3. Install the Power Supply.
4. Install the PLC-5 Programmable Controller.
5. Apply Power to the System.
6. Connect the Personal Computer to the PLC-5 Programmable
Controller.
Install an I/O Chassis
Install an I/O chassis according to the Universal I/O Chassis Installation Instructions, publication 1771-IN075.
Publication 1785-IN063B-EN-P - January 2006
Ethernet PLC-5 Programmable Controllers 15
Configure the I/O Chassis
Configure the I/O chassis by following this procedure.
1. Set the backplane switches.
Pressed In At Top ON (closed)
Pressed In At Bottom OFF (open)
O
N
O
F
F
12345678
Always Off
Switch
1
on
off
Outputs of this I/O chassis remain in their last state when a hardware failure occurs.
Outputs of this I/O chassis are turned off when a hardware failure occurs.
Switches
45
off off
off on
on off
on on
Switches
67
off off
on on
on off
Last State
1
(1)
(1)
Addressing
2 - slot
1 - slot
1/2 - slot
Not allowed
EEPROM Transfer
EEPROM memory transfer to controller memory at power-up.
(2), (3)
EEPROM memory transfers to controller memory if controller memory not valid.
EEPROM memory does not transfer to controller memory.
(4)
Switch
8
off
on
(1)
Regardless of this switch setting, outputs are turned off when any of the following occurs:
Processor Memory Protection
Controller memory protection disabled.
Controller memory protection enabled.
(5)
- controller detects a runtime error
- an I/O chassis backplane fault occurs
- you select program or test mode
- you set a status file bit to reset a local rack
(2)
If an EEPROM module is not installed and controller memory is valid, the controller's PROC LED indicator blinks, and the processor sets S:11/9, bit 9 in the major fault status word. To clear this fault, change the controller from program mode to run mode and back to program mode.
(3)
If the controller's keyswitch is set in REMote, the controller enters remote RUN after it powers up and has its memory updated by the EEPROM module.
(4)
A processor fault (solid red PROC LED) occurs if processor memory is not valid.
(5)
You cannot clear processor memory when this switch is on.
Publication 1785-IN063B-EN-P - January 2006
43912
16 Ethernet PLC-5 Programmable Controllers
2. Set the power-supply configuration jumper and set the keying bands as shown below
Are you using a power supply module in the chassis?
N
Y
.
2 4 6 8 10 12 14 16
Keying Bands
YN
18 20 22 24 26 28 30 32 34 36 38 40 42
Between
44 46
- 40 & 42
48 50 52
- 54 & 56
54 56
43912
Install the Power Supply
Install a power supply according to one of the following corresponding installation instructions.
Install This Power Supply According to this Publication
1771-P4S 1771-P6S 1771-P4S1 1771-P6S1
1771-P7 Power Supply Module Installation Instructions,
Power Supply Modules Installation Instructions, publication 1771-2.135
publication 1771-IN056
Publication 1785-IN063B-EN-P - January 2006
Ethernet PLC-5 Programmable Controllers 17
Install the PLC-5 Programmable Controller
The controller is a modular component of the 1771 I/O system requiring a properly installed system chassis. Refer to publication 1771-IN075 for detailed information on acceptable chassis along with proper installation and grounding requirements. Limit the maximum adjacent slot power dissipation to 10 W.
1. Define the DH+ Station Address of Channel 1A by setting switch assembly SW-1 on the back of the controller.
See the side of the controller for a listing of DH+ switch settings.
Side View of Controller Switch Assembly SW1
1234567
Side View of Switch 7
Down
57.6 Kbps
Up 230 Kbps
Use Switch 7 to Set the Communication Rate
43913
2. Specify the Channel 0 port configuration. See the side of the controller for a listing of Channel 0 switch settings.
Bottom View of Controller
Side View
OFF
Switch Assembly SW2
123456789
Front of Controller
10
43914
Publication 1785-IN063B-EN-P - January 2006
18 Ethernet PLC-5 Programmable Controllers
3. To install the battery, attach the battery-side connector into the controller-side connector inside the battery compartment of the controller.
Locking Bar
Ejector Tab
Battery Connector is Mounted Inside the Battery Compartment
Battery
43916
WARNINGWARNINGWARNINGWARNING
Card Guides
When you connect or disconnect the battery, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. For safety information on the handling of lithium batteries, including handling and disposal of leaking batteries, see Guidelines for Handling Lithium Batteries, publication AG-5.4.
4. Install the controller.
For more information, see the Enhanced and Ethernet PLC-5 Programmable Controllers User Manual, publication 1785-UM012.
Apply Power to the System
When you apply power to a new controller, it is normal for the programming software to indicate a RAM fault.
Publication 1785-IN063B-EN-P - January 2006
Ethernet PLC-5 Programmable Controllers 19
See the following table to proceed. If the PROC LED is not off, turn to the next page for troubleshooting information.
If Your Keyswitch is in This Position
PROGRAM Clear memory. The PROC LED should turn off.
REMOTE Clear memory. The PROC LED should turn off.
RUN You see the message No access or privilege violation
Do This
The software is in Program mode.
The software is in Remote Program mode.
because you cannot clear memory in Run mode. Change the keyswitch position to Program or Remote and press Enter to clear memory.
To monitor your system as you configure and run it, check the controller’s indicators:
This Indicator Lights When
COMM You establish serial communication (CH 0)
BATT No battery is installed or the battery voltage is low
FORCE Forces are present in your ladder program
If your controller is operating correctly, the:
Ethernet STAT indicator remains solid green
Ethernet Transmit indicators (100 M and 10 M) briefly light green when
transmitting packets
If the indicators do not indicate the above normal operation, refer to the following table to troubleshoot the Ethernet indicators.
Publication 1785-IN063B-EN-P - January 2006
20 Ethernet PLC-5 Programmable Controllers
Connect the Personal Computer to the PLC-5 Programmable Controller
For more information, see:
Enhanced and Ethernet PLC-5 Programmable Controllers User Manual, publication 1785-UM012
the documentation provided with your communication card
Data Highway/Data Highway Plus/Data Highway II/Data Highway
485 Cable Installation Manual, publication 1770-6.2.2

Troubleshoot the Controller

Indicator Color Description Probable Cause Recommended Action
BATT Red Battery low Battery low Replace battery within 10 days
Off Battery is good Normal operation No action required
PROC Green
(steady)
Green
BATT
PROC
FORCE
COMM
43918
(blinking)
Red (blinking)
Alternating Red and Green
Use the controller’s status indicators with the following tables for diagnostics and troubleshooting.
Processor is in Run mode and fully operational
Processor memory is being transferred to EEPROM
Major fault RSLogix 5
Processor in FLASH-memory Programming mode
Normal operation No action required
Normal operation No action required
During RSLogix 5 download, this download in progress
Run-time error
is normal operation - wait for
download to complete.
If not during RSLogix 5 download:
Check major fault bit in status file
(S:11) for error definition
Clear fault, correct problem, and
return to Run mode
Normal operation if processor's FLASH
No action required - allow flash
update to complete memory is being reprogrammed
Publication 1785-IN063B-EN-P - January 2006
Continued on next page
43919
BATT
PROC
FORCE
COMM
Ethernet PLC-5 Programmable Controllers 21
Indicator Color Description Probable Cause Recommended Action
PROC Red
Fault with memory loss
New controller
Use programming software to
clear and initialize memory
(steady)
Processor has failed internal diagnostics
Power cycle with
Install battery (to preserve failure
diagnostics), then power down,
reseat controller and cycle power;
then reload your program. If you
are unable to reload your
program, replace the controller.
If you are able to reload your
program and fault persists,
contact Technical Support at
440.646.3223 to diagnose the
problem.
Properly replace or install battery. battery problem.
Off Processor is in
program load or Test
Power supply or connections
Check power supply and
connections
mode or is not receiving power
FORCE Amber
SFC and/or I/O forces
Normal operation No action required
enabled
(steady)
Amber (blinking)
SFC and/or I/O forces present but not enabled
Off SFC and/or I/O forces
not present
COMM Off No transmission on
channel 0
Normal operation if channel is not being
No action required
used
Green (blinking)
Transmission on channel 0
Normal operation if channel is being used
Publication 1785-IN063B-EN-P - January 2006
22 Ethernet PLC-5 Programmable Controllers
Troubleshoot the Controller Communication Channels
Indicator Color Channel Mode Description Probable
A or B Green
(steady)
Remote I/O Scanner
Active Remote I/O link, all adapter modules are present and not faulted
Remote I/O Adapter
Communicating with scanner
DH+ Controller is transmitting
AB
Green (blinking
Remote I/O Scanner
or receiving on DH+ link
At least one adapter is faulted or has failed
rapidly or
A
43920
slowly)
Red (steady)
DH+ No other nodes on network
Remote I/O Scanner
Hardware fault Hardware error Turn power off, then
Remote I/O Adapter DH+
Red (blinking
Remote I/O Scanner
Faulted adapters detected Cable not
rapidly or slowly)
DH+ Bad communication on
DH+
Off Remote I/O
Scanner
Channel offline Channel is not
Remote I/O Adapter DH+
Cause
Normal operation
Power off at remote rack
Cable broken
connected or is broken
Power off at remote racks
Duplicate node detected
being used
Recommended Action
No action required
Restore power to the rack
Repair cable
on.
Check that the software configurations match the hardware set-up.
Replace the controller.
Repair cable
Restore power to racks
Correct station address
Place channel online if needed
Publication 1785-IN063B-EN-P - January 2006
Ethernet PLC-5 Programmable Controllers 23
Troubleshoot the Ethernet Status Indicators
Indicator Color Description Probable Cause Recommended
Action
ENET Status
ENET Transmit
STAT
100M
10M
STAT Solid red Critical hardware fault Controller requires
internal repair
Blinking red Hardware or software fault
(detected and reported via
Fault-code dependent
a code)
Off Module is functioning
Normal operation Attach the controller properly but it is not attached to an active Ethernet network
Solid Green Ethernet channel 2 is
Normal operation No action required functioning properly and has detected that it is connected to an active Ethernet network
100 M or 10 M
Green Lights (green) briefly when
the Ethernet port is transmitting a packet. It does not indicate whether or not the Ethernet port is receiving a packet.
Contact your local Allen-Bradley distributor
Contact Technical Support at
440.646.3223 to diagnose the problem.
and interface module to an active Ethernet network
Publication 1785-IN063B-EN-P - January 2006
24 Ethernet PLC-5 Programmable Controllers

Controller Specifications

Operating Temperature IEC 60068-2-1 (Test Ad, Operating Cold),
Nonoperating Temperature IEC 60068-2-1 (Test Ab, Un-packaged Nonoperating Cold),
Relative Humidity IEC 60068-2-30 (Test Db, Un-packaged Nonoperating
Vibration IEC 60068-2-6 (Test Fc, Operating):
Operating Shock IEC 60068-2-27:1987, (Test Ea, Unpackaged shock):
Nonoperating Shock IEC 60068-2-27:1987, (Test Ea, Unpackaged shock):
Emissions CISPR 11:
ESD Immunity IEC 61000-4-2:
Radiated RF Immunity IEC 61000-4-3:
EFT/B Immunity IEC 61000-4-4:
Surge Transient Immunity IEC 61000-4-5:
Conducted RF Immunity IEC 61000-4-6:
Enclosure Type Rating None (open style)
Power Consumption 3.6 A @5V dc max
Power Dissipation 18.9 W max
Isolation (continuous voltage rating)
Wire Size Ethernet: 802.3 compliant shielded or unshielded twisted pair
Wiring Category
Replacement Battery 1770-XYC
North American Temp Code T4A
Specifications continued on next page
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
(1)
IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0...60 oC (32...140 oF)
IEC 60068-2-2 (Test Bc, Un-packaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Un-packaged Nonoperating Thermal Shock):
–40...85 oC (–40...185 oF)
Damp Heat):
5...95% Noncondensing
2 g @ 10...500Hz
30 g
50 g
Group 1, Class A (with appropriate enclosure)
6 kV indirect contact discharges
10 V/m with 1 kHz sine-wave 80% AM from 30...2000 MHz 10 V/m with 200 Hz Pulse 50% AM from 100% AM at 900 MHz 10 V/m with 200 Hz Pulse 50% AM from 100% AM at 1890 MHz 1V/m with 1 kHz sine-wave 80%AM from 2000…2700 MHz
+2 kV at 5 kHz on communications ports
+2 kV line-earth (CM) on communications ports
10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
50V Basic Insulation between communication ports and between communication ports and backplane Tested to withstand 500V rms for 60 s
Remote I/O: 1770-CD cable Serial Ports: Belden 8342 or equivalent
2 - on communications ports
Publication 1785-IN063B-EN-P - January 2006
Ethernet PLC-5 Programmable Controllers 25
Controller Specifications (continued)
(1)
Time-of-day Clock/Calendar
Available Cartridges 1785-RC Relay Cartridge Memory Modules • 1785-ME16
I/O Modules Bulletin 1771 I/O, 1794 I/O, 1746 I/O, and 1791 I/O
Hardware Addressing 2-slot
Location 1771-A1B, -A2B, -A3B, -A3B1, -A4B chassis; leftmost slot Weight 3 lb, 1 oz (1.39 kg)
Certifications
(2)
(when product is marked)
(1)
The clock/calendar will update appropriately each year.
(2)
See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Maximum Variations at 60× C: ± 5 min per month Typical Variations at 20× C: ± 20 s per month Timing Accuracy: 1 program scan
• 1785-ME32
• 1785-ME64
• 1785-M100
including 8-, 16-, 32-pt, and intelligent modules
• Any mix of 8-pt modules
• 16-pt modules must be I/O pairs
• No 32-pt modules 1-slot
• Any mix of 8- or 16-pt modules
• 32-pt modules must be I/O pairs 1/2-slot—Any mix of 8-,16-, or 32-pt modules
UL UL Listed Industrial Control Equipment. See UL File E65584. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D
Hazardous Locations. See CSA File LR69960C.
CE European Union 2004/108/EC EMC Directive, compliant with:
EN 50082-2; Industrial Immunity EN 61326; Meas./Control/Lab.,Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions
C-Tick Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
EtherNet/IP ODVA conformance tested to EtherNet/IP specifications
Publication 1785-IN063B-EN-P - January 2006
26 Ethernet PLC-5 Programmable Controllers
In This Controller: At This
PLC-5/20E, -5/40E,
-5/80E
(1)
The battery indicator (BATT) warns you when the battery is low. These durations are based on the battery supplying the only
power to the controller (power to the chassis is off) once the LED first lights.
Battery Type
Ethernet PLC-5 programmable controllers use 1770-XYC batteries that contain 0.65 grams of lithium.
Average Battery Lifetime Specifications
Worst-case Battery Life Estimates
Power Off
Temperature
100%
60 °C 84 days 150 days 5 days
25 °C 1 year 1.2 years 30 days
Power Off 50%
Battery Duration After The LED lights
Memory and Channel Specifications
(1)
Cat. No. Max User
Memory (words)
1785-L20E 16 k 512 any mix or
1785-L40E 48 k 2048 any mix or
1785-L80E 100 k 3072 any mix or
Total I/O Max Channels Max Number of I/O Chassis Power
512 in + 512 out (complement)
2048 in + 2048 out (complement)
3072 in + 3072 out (complement)
This table lists memory and channel specifications of each Ethernet PLC-5 programmable contoller.
To tal Extended
1 Ethernet 1 DH+ 1 DH+/remote I/O
1 Ethernet 2 DH+/remote I/O
1 Ethernet 2 DH+/remote I/O
Allen-Bradley, Data Highway, Data Highway II, DH+, PLC-5, and RSLogix 5 are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
13 0 12 0 19 W 3.6 A
61 0 60 0 19 W 3.6 A
65 0 64 0 19 W 3.6 A
-Local
Remote ControlNet
Dissipation, Max
Backplane Current Load
Publication 1785-IN063B-EN-P - January 2006

Notes

Ethernet PLC-5 Programmable Controllers 27
Publication 1785-IN063B-EN-P - January 2006
Rockwell Automation Support
Rockwell Automation provides technical information on the web to assist you in using our products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration and troubleshooting, we offer TechConnect Support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com.
Installation Assistance
If you experience a problem with a hardware module within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your module up and running:
United States 1.440.646.3223
Monday – Friday, 8am – 5pm EST
Outside United States Please contact your local Rockwell Automation representative for any technical support issues.
New Product Satisfaction Return
Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned:
United States Contact your distributor. You must provide a Customer Support case number (see phone number
above to obtain one) to your distributor in order to complete the return process.
Outside United States Please contact your local Rockwell Automation representative for return procedure.
Publication 1785-IN063B-EN-P - January 2006 28 PN 957988-67
Supersedes Publication 1785-IN063A -EN-P - May 2005 Copyright © 2006 Rockwell Automation, Inc . All rights reserved. Printed in the U.S.A.
Loading...