Rockwell Automation 1756-EN2TXT User Manual

Page 1
Installation Instructions
ControlLogix-XT EtherNet/IP Bridge Module
Catalog Number 1756-EN2TXT
Top ic Page
Important User Information 2 About ControlLogix-XT Systems 8
ControlLogix-XT with Traditional ControlLogix Compone
Before You Begin 9
Determine Module Slot Location 9 Set the Network Address 10
nts 8
Page 2
2 ControlLogix-XT EtherNet/IP Bridge Module
WARNING
IMPORTANT
ATTENTION
SHOCK HAZARD
BURN HAZARD

Important User Information

Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at
http://literature.rockwellautomation.com
equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
Identifies information that is critical for successful application and understanding of the product.
) describes some important differences between solid state
Publication
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the consequences.
Labels may be on or inside the equipment (for example, drive or motor) to alert people that dangerous voltage may be present.
Labels may be on or inside the equipment (for example, drive or motor) to alert people that surfaces may reach dangerous temperatures.
1756-IN635A-EN-P - March 2009
Page 3
ControlLogix-XT EtherNet/IP Bridge Module 3
WARNING
AVERTISSEMENT

North American Hazardous Location Approval

The following information applies when operating this equipment in hazardous locations.
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating na meplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest "T" number) m ay be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority H aving Jurisdiction at the time of installation.
EXPLOSION HAZARD -
• Do not disconnect eq uipment unless power has been removed or the area is known to be nonhazardous.
• Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
• Substitution of components may impair suitability for Class I, Division 2.
• If this product contains batteries, they must only be changed in an area known to be nonhazardous.
Informations sur l’utilisation de cet équipement en environnements dangereux.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marqua ges sur sa plaque d'identification qui indiquent le code de température pour les environneme nts dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (co de de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les comb inaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.
RISQUE D’EXPLOSION –
• Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher l'équipement.
• Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
• La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.
• S'assurer que l'environnement est classé non dangereux avant de changer les piles.
Publication
1756-IN635A-EN-P - March 2009
Page 4
4 ControlLogix-XT EtherNet/IP Bridge Module
ATTENTION
Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11. Without appropriate precautions, there may be difficulties with electromagnetic compatibility in residential and other environments due to conducted and radiated disturbances.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if non-metallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see:
Industrial Automation Wiring and Grounding Guidelines, for
additional installation requirements, publication 1770-4.1
NEMA Standards 250 and IEC 60529, as applicable, for explanations
of the degrees of protection provided by different types of enclosure.
.
Publication
1756-IN635A-EN-P - March 2009
Page 5
ControlLogix-XT EtherNet/IP Bridge Module 5
ATTENTION
WARNING
Preventing Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe packaging when not in
use.
Safety-related Programmable Electronic Systems
Personnel responsible for the application of safety-related programmable electronic systems (PES) shall be aware of the safety requirements in the application of the system and shall be trained in using the system.
Publication
1756-IN635A-EN-P - March 2009
Page 6
6 ControlLogix-XT EtherNet/IP Bridge Module
ATTENTION
WARNING
European Hazardous Location Approval
European Zone 2 Certification (The following applies when the product bears the Ex or EEx Marking)
This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC and has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in potentially explosive atmospheres, given in Annex II to this Directive.
Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 60079-15 and EN 60079-0.
This equipment is not resistant to sunlight or other sources of UV radiation.
This equipment must be installed in an enclosure providing at least
IP54 protection when applied in Zone 2 environments.
This equipment shall be used within its specified ratings defined by
Allen-Bradley.
Provision shall be made to prevent the rated voltage from being
exceeded by transient disturbances of more than 40% when applied in Zone 2 environments.
This equipment must be used only with ATEX certified backplanes.
Secure any external connections that mate to this equipment by
using screws, sliding latches, threaded connectors, or other means provided with this product.
Do not disconnect equipment unless power has been removed or
the area is known to be nonhazardous.

About the EtherNet/IP Bridge Module

Configure and use the 1756-EN2TXT module as you would a traditional 1756-EN2T module. For more information about configuring and using the 1756-EN2TXT and 1756-EN2T modules, see the EtherNet/IP Modules in Logix5000 Control Systems User Manual, publication
Publication
ENET-UM001.
1756-IN635A-EN-P - March 2009
Page 7
ControlLogix-XT EtherNet/IP Bridge Module 7
Top
Front
Side
Bottom
31919-M
1
2
3
4
5
6
Use this figure to identify the external features of the module.
Item Description
1 Alphanumeric display provides module status 2 USB port for temporary workstation connection 3 Backplane connector 4 MAC ID 5 Ethernet port for RJ45 connection 6 Rotary switches that may be used to set the IP address
Publication
1756-IN635A-EN-P - March 2009
Page 8
8 ControlLogix-XT EtherNet/IP Bridge Module
IMPORTANT

About ControlLogix-XT Systems

The ControlLogix-XT products include control and communication system components that, when used with FLEX I/O-XT products, provide a complete control system solution that can be used in environments where temperatures range from -20...70 °C (-4...158 °F).
When used independently, the ControlLogix-XT system can withstand
ironments where the temperature ranges from -25...70 °C
env (-13...158 °F).
ControlLogix-XT with Traditional ControlLogix Components
ControlLogix-XT system components are rated for extreme environmental conditions only when used properly with other Logix-XT system components. The use of ControlLogix-XT components
with traditional ControlLogix system components nullifies extreme-environment ratings.
If a ControlLogix-XT module is used with traditional ControlLogix products, that is, ControlLogix products not designed for extreme environments, the ControlLogix-XT module can withstand only the environments specified for the traditional ControlLogix version of the module. For example, if a 1756-EN2TXT module is used in a standard 1756-A10 chassis, the 1756-EN2TXT module can withstand only the environment specified for the traditional 1756-EN2T module.
The ControlLogix-XT system components are designed to meet the same
greater operational and environmental requirements as traditional
and ControlLogix products.
When a ControlLogix-XT component is traditional ControlLogix component, the functional and environmental specifications of the traditional ControlLogix component apply.
used as a replacement for a
For more information about standard ControlLogix component specifications and installation requirements, see the resources listed in the Additional Resources table on page
Publication
1756-IN635A-EN-P - March 2009
24.
Page 9
ControlLogix-XT EtherNet/IP Bridge Module 9
Slot 0
Slot 1
Slot 2
Slot 3
31818-M
Slot 4

Before You Begin

Complete these tasks by using the resources listed as references before you install your module.
Task Resource
Install a ControlLogix-XT chassis ControlLogix-XT Chassis, Series B Installation
Instructions, publication 1756-IN637
Install a ControlLogix-XT power supply ControlLogix-XT Power Supply Installation
Instructions, publication 1756-IN639
Determine Module Slot Location
Install the module in any open slot of the ControlLogix-XT chassis. You can install multiple 1756-EN2TXT modules in the same chassis.
Publication
1756-IN635A-EN-P - March 2009
Page 10
10 ControlLogix-XT EtherNet/IP Bridge Module
Rotary Switches
31587
Set the Network Address
The module ships with the rotary switches set to 999 and BOOTP enabled. You can set the network Internet Protocol (IP) address by using one of these methods:
• Use the rotary switches on the top of the module.
Use a BOOTP server or Dynamic Host Configuration Protocol
• (DHCP) server, such as Rockwell Automation’s BootP-DHCP Server tool.
• Use Rockwell Automation’s RSLinx or RSLogix 5000 software.
The module first reads the rotary switches to determine if the last
tion of the IP address specified is a valid number. Valid numbers
por range from 001…254.
When the switches are set to a valid number, the module’s IP address
92.168.1.xxx (where xxx represents the number set on the
is 1 switches). The module’s subnet mask is 255.255.255.0 and the gateway address is set to 0.0.0.0. The module does not have a host name assigned, or use any Domain Name System when using the rotary switch settings.
BOOTP, DHCP, and the Module IP Address
If BOOTP or DHCP is Then the module
Enabled Asks for an address from a DHCP/BOOTP server. The server also
Not enabled Uses the IP address (along with other TCP configurable
Publication
1756-IN635A-EN-P - March 2009
ssigns other Transport Control Protocol (TCP) parameters.
a
arameters) stored in nonvolatile memory.
p
Page 11
ControlLogix-XT EtherNet/IP Bridge Module 11
IMPORTANT
Reset the Module to Initial Settings
To reset the module to its initial out-of-the-box settings, reset the switches to 888 and cycle power.
Do not use the 888 switch setting during normal module operation.
After cycling power with the switches set to 888, remove the module
set the switches to their final value. When you set the rotary
and switches to a value other than 888, or to the valid IP address values 001…254, the software configuration determines the IP address.
Publication
1756-IN635A-EN-P - March 2009
Page 12
12 ControlLogix-XT EtherNet/IP Bridge Module
WARNING
X T
LINK
NET
OK
10/100/BASE T
X T

Install the Module

When you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding. Repeated electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance that can affect module operation.
Complete these steps to install the module.
1. Align the circuit board with top and bottom guides in the ssis.
cha
2. Slide the module into the chassis.
Make sure the module backplane connector properly connects to the chassis backplane. The module is properly installed when it is flush with the power supply or other installed modules.
Publication
1756-IN635A-EN-P - March 2009
Page 13
ControlLogix-XT EtherNet/IP Bridge Module 13
WARNING
IMPORTANT
X T
LINK
NET
OK
10/100
/BASE
T
X T
Connect the Module to the EtherNet/IP Network
If you connect or disconnect the communication cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
Attach the RJ45 connector to the Ethernet port on the bottom of the module as shown.
We recommend connecting the module to the network via a 100 MB Ethernet switch, which will reduce collisions and lost packets and increase network bandwidth. For detailed EtherNet/IP connection information, see the EtherNet/IP Performance and Application Guide, publication ENET-AP001
.
Publication
1756-IN635A-EN-P - March 2009
Page 14
14 ControlLogix-XT EtherNet/IP Bridge Module
WARNING
ATTENTION
Connect to the Module Via the USB Port
The USB port is intended for only for temporary local programming purposes and is not intended for permanent connection. If you connect or disconnect the USB cable with power applied to this module or any device on the USB network, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding. A Samtec Inc. RSP-119350 USB cable is required to maintain hazardous
location certifications.
Components Required for USB Connection
The EtherNet/IP module has a USB device port that uses a Type B receptacle. The port is USB 1.1-compatible and runs at 12 Mbps. To
the USB port with this 1756-EN2TXT module, you must have
use RSLinx software, version 2.55 or later, installed on your workstation.
Connect the USB Cable
USB cable length must be less than 3 m (9.84 ft) and must not contain hubs.
Use a USB cable to connect your computer to the USB port. The connection lets you download programs to controllers and configure Ethernet modules directly from your computer.
If your installation of RSLinx software has not had a USB driver set
you will be prompted to install the required software. For more
up, information about setting-up a USB driver, see the EtherNet/IP Modules in Logix5000 Control Systems User Manual, publication
ENET-UM001.
Publication
1756-IN635A-EN-P - March 2009
Page 15
ControlLogix-XT EtherNet/IP Bridge Module 15
Power Supply Status
Alphanumeric Status Indicator
Module Status Indicators

Apply Chassis Power

Apply power to the ControlLogix-XT power supply to supply power to the EtherNet/IP module installed in the chassis.
Check Power Supply and Module Status
After power is applied, check the:
• power supply status indicator.
• module status indicators.
• module alphanumeric display.
These indicators indicate if the module is operating properly.
Use these sections as references when checking the status:
• Alphanumeric Display Start-up Indications, on page 16
• Status Indicators, page 18
Publication
1756-IN635A-EN-P - March 2009
Page 16
16 ControlLogix-XT EtherNet/IP Bridge Module
Alphanumeric Display Start-up Indications
Upon installation and powerup, the alphanumeric display of the module cycles through these states:
1. TEST
2. PASS
3. OK
4. REV X.X (X.X is the mod
Once that cycle is complete, the display alternates between OK and the module’s
EtherNet/IP address.
ule’s current firmware revision).
Install the EDS File
The EDS file can be uploaded directly from the module. This feature lets you register the EDS file for your module from within RSLinx software by following the steps listed below.
1. Open RSLinx software, version 2.55 (or later), and browse for
the module.
2. Right-click the module and select Upload EDS file from device.
The Upload EDS wizard opens.
3. Complete the EDS wizard to register the EDS file.
The EDS file can also be downloaded from
www.ab.com/networks/eds.html and installed with the RSLinx EDS
Hardware Installation Tool.
Publication
1756-IN635A-EN-P - March 2009
Page 17
ControlLogix-XT EtherNet/IP Bridge Module 17
WARNING
IMPORTANT
X T
LINK
NET
OK
10/100
/BASE
T
X T

Remove the Module

When you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding. Repeated electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance that can affect module operation.
You can remove and re-install this module while chassis power is applied. Complete these steps to remove the module.
1. Push on upper and lower module tabs to disengage them.
2. Slide the module out of the chassis.
If you want to replace an existing module with an identical one, and you want to resume identical system operation, you must install the new module in the same slot.
Publication
1756-IN635A-EN-P - March 2009
Page 18
18 ControlLogix-XT EtherNet/IP Bridge Module

Status Indicators

Use these tables to interpret the status indicators.
NET Status Indicator
State Description
Off The module is not powered. Verify that there is chassis power and
that the module is completely inserted into the chassis and backplane.
The module does not have a valid IP address. Make sure the module
has been configured with a valid IP address. Flashing green The module has an IP address, but has no established connections. Green The module has an IP address and at least one established
connection. Flashing red One or more of the connections in which the module is the target has
timed out. Red The module is attempting to use an IP address already in use on the
network. Assign a unique IP address to the module.
LNK Status Indicator
State Description
Off The module is not ready to communicate. Verify that the
module is on. Green The module is ready to communicate. Flashing green The module is communicating over the network.
Publication
1756-IN635A-EN-P - March 2009
Page 19
ControlLogix-XT EtherNet/IP Bridge Module 19
OK Status Indicator
State Description
Off Verify that the module has 24V DC chassis power and that
Flashing green The module is not configured. Green The module is operating correctly. Flashing red The module detected a recoverable fault. A configuration
Red The module detected an unrecoverable fault. Cycle power
Red and alphanumeric display scrolls 'Image Update Needed'
Flashing red and green The module is performing a power-up self-test.
the module is completely inserted into chassis and
backplane.
error may have caused the fault. Check the module
configuration. If necessary, reconfigure the module.
to the module. If this does not clear the fault, replace the
module.
Update the firmware image. Once the image is updated,
cycle power. If this does not clear the fault, replace the
module.
Publication
1756-IN635A-EN-P - March 2009
Page 20
20 ControlLogix-XT EtherNet/IP Bridge Module

General Specifications - 1756-EN2TXT

Attribute Value
Module location Any slot in the ControlLogix-XT chassis Backplane current (mA) at
5V.1V DC Backplane current (mA) at
24V DC Enclosure Type Rating None (open-style) Isolation voltage 30 V (continuous), Basic Insulation Type
Power consumption 17.1 BTU/hr Power dissipation 5.1 W Wire size Ethernet connections:
Wiring category
North American temp code T4A IEC temp code T4 Recommended USB cable
for USB port USB port USB 1.1
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
1 A
3 mA
No isolation between USB and system.
Type tested at 853V AC for 60 s, Ethernet to system.
RJ45 connector according to IEC 60603-7, 2 or 4 pair
Category 5e minimum cable according to TIA 568-B.1 or
Category 5 cable according to ISO/IEC 24702.
2 - on communications ports
(1)
Samtec cable, PN RSP-119350
USB device
USB series B receptacle
.
Publication
1756-IN635A-EN-P - March 2009
Page 21
ControlLogix-XT EtherNet/IP Bridge Module 21

Environmental Specifications - 1756-EN2TXT

Attribute Value
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
Vibration
IEC 60068-2-6 (Test Fc, Operating)
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Emissions
CISPR 11
ESD immunity
IEC 61000-4-2
Radiated RF immunity
IEC 61000-4-3
-25…70 °C (-13…158 °F)
-40…85 °C (-40…185 °F)
5…95% noncondensing
2 g @ 10…500 Hz
30 g
50 g
Group 1, Class A
6 kV contact discharges
8 kV air discharges
10V/m with 1 kHz sine-wave
80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse
100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse
100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80%
AM from 2000…2700 MHz
Publication
1756-IN635A-EN-P - March 2009
Page 22
22 ControlLogix-XT EtherNet/IP Bridge Module
Attribute Value
EFT/B immunity
IEC 61000-4-4
Surge transient immunity
IEC 61000-4-5
Conducted RF immunity
IEC 61000-4-6
±2 kV at 5 kHz on Ethernet port
±2 kV line-earth (CM) on Ethernet port
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Publication
1756-IN635A-EN-P - March 2009
Page 23
ControlLogix-XT EtherNet/IP Bridge Module 23

Certifications - 1756-EN2TXT

Certification
c-UL-us UL Listed Industrial Control Equipment, certified for US and
CE European Union 2004/108/EC EMC Directive, compliant with:
C-Tick AS/NZS CISPR 11; Industrial Emissions Ex European Union 94/9/EC ATEX Directive, compliant with:
TÜV TÜV Certified for Functional Safety: up to and including SIL 2 EtherNet/IP ODVA conformance tested to EtherNet/IP specifications
(1)
When the product is marked.
(2)
See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
(1) (2)
Value
Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous
Locations, certified for U.S. and Canada. See UL File E194810.
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A
& B)
EN 60079-15; Potentially Explosive Atmospheres,
Protection "n" (II 3 G Ex nA IIC T4 X)
EN 60079-0; General Requirements (Zone 2)
Publication
1756-IN635A-EN-P - March 2009
Page 24

Additional Resources

Resource Description
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
ControlLogix-XT Chassis, Series B Installation Instructions, publication 1756-IN637
ControlLogix-XT Power Supply Installation Instructions, publication 1756-IN639
EtherNet/IP Modules in Logix5000 Control Systems User Manual, publication
ENET-UM001
EtherNet/IP Performance and Application Guide, publication ENET-AP001
Open DeviceNet Vendor Association (ODVA) website, http://www.odva.org
You can view or download publications at
http://literature.rockwellautomation.com. To order paper copies of
technical documentation, contact your local Rockwell Automation distributor or sales representative.
Provides general guidelines for installing a Rockwell Automation industrial system
Contains installation procedures and specifications for the ControlLogix-XT chassis
Contains installation procedures and specifications for the ControlLogix-XT power supply
Contains information on how to use EtherNet/IP modules with various Logix5000 controllers
Provides detailed EtherNet/IP connection information
Provides information on implementing EtherNet/IP technology
Allen-Bradley, ControlLogix, ControlLogix-XT, FLEX I/O-XT, RSLinx, RSLogix 5000, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 1756-IN635A-EN-P - March 2009 PN-36861
Copyright © 2009 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Loading...