(Cat. No. 1747-L20, 1747-L30,
and 1747-L40 Processors)
Installation and
Operation Manual
Important User Information
Solid state equipment has operational characteristics differing from those of
electromechanical equipment. “Safety Guidelines for the Application,
Installation and Maintenance of Solid State Controls” (Publication SGI-1.1)
describes some important differences between solid state equipment and
hard–wired electromechanical devices. Because of this difference, and also
because of the wide variety of uses for solid state equipment, all persons
responsible for applying this equipment must satisfy themselves that each
intended application of this equipment is acceptable.
In no event will the Allen-Bradley Company be responsible or liable for
indirect or consequential damages resulting from the use or application of
this equipment.
The examples and diagrams in this manual are included solely for illustrative
purposes. Because of the many variables and requirements associated with
any particular installation, the Allen-Bradley Company cannot assume
responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Allen-Bradley Company with respect to use
of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without
written permission of the Allen-Bradley Company is prohibited.
Throughout this manual we use notes to make you aware of safety
considerations.
ATTENTION: Identifies information about practices or
circumstances that can lead to personal injury or death, property
!
damage, or economic loss.
Attentions help you:
• identify a hazard
• avoid the hazard
• recognize the consequences
Important: Identifies information that is especially important for successful
application and understanding of the product.
PLC and PLC 5 are registered trademarks of Allen-Bradley Company, Inc.
SLC, SLC 500, Dataliner, and DTAM are trademarks of Allen-Bradley Company, Inc.
IBM is a registered trademark of International Business Machines, Incorporated.
Tandy is a trademark of the Tandy Corporation.
Gateway 2000 is a trademark of Gateway 2000, Inc.
Toshiba is a trademark of Toshiba America, Inc.
Compaq is a registered trademark of Compaq Computer Corporation.
Deskpro is a trademark of Compaq Computer Corporation.
Summary of Changes
Summary of Changes
The information below summarizes the changes to this manual since the last
printing as 1747-NI001 in November, 1993.
To help you find new information and updated information in this release of
the manual, we have included change bars as shown to the right of this
paragraph.
New Information
The table below lists sections that document new features and additional
information about existing features, and shows where to find this new
information.
Contact Output Circuits AC or DC 5-2
Solid-State
Sourcing
Sinking Device with Sourcing Input Module Circuit 5-3
Sinking Device with Sourcing Output Module Circuit 5-3
Sourcing
Preparing Your Wiring Layout 5-4
Features
Recommendations for Wiring I/O Devices 5-6
Wiring Your I/O Modules 5-7
Using Removable Terminal Blocks (RTBs) 5-8
DH-485 Network Protocol A-1
DH-485 Token Rotation A-2
DH-485
Devices that Use the DH-485 Network A-3
1747-AIC Isolated Link Coupler for DH-485 A-4
Example System Configuration A-5
Important Planning Considerations A-6
DH-485
Network Initialization
Hardware Considerations A-6
Number of Devices and Length of Communication Cable A-6
Planning Cable Routes A-6
Software Considerations A-7
Number of Nodes A-7
Setting Node Addresses A-8
Setting Processor Baud Rate A-8
Maximum Node Address Setting A-8
Network Installation
DH-485 Communication Cable and Isolated Link Coupler A-9
Installing the DH-485 Communication Cable A-10
Connecting the Communication Cable to the Isolated Link Coupler A-11
À C-6
1747-KE to a Modem (Hardware Handshaking Enabled) C-7
1747-KE to a 5/03 Processor
1773-KA, 5130-RM, or PLC-5
(Hardware Handshaking Disabled) À C-7
1746-BAS to a Modem (Hardware Handshaking Enabled) C-8
1746-BAS to a 5/03 Processor
1773-KA, 5130-RM, or PLC-5 (Hardware Handshaking
Disabled)À C-8
1770-KF3 to a Modem (Hardware Handshaking Enabled) C-8
2760-RB to a Modem (Hardware Handshaking Enabled) C-9
2760-RB to a 5/03 Processor
1773-KA, 5130-RM, or PLC-5
(Hardware Handshaking Disabled) À C-9
1771-KGM to a Modem (Hardware Handshaking Enabled) C-10
1771-KGM to a 5/03 Processor
1775-KA, 1773-KA, 5130-RM, or PLC-5
(Hardware Handshaking Disabled) À C-10
1775-KA to a Modem (Hardware Handshaking Enabled) C-11
1775-KA to a 5/03 Processor
5130-RM, or PLC-5 (Hardware Handshaking Disabled) À C-11
PLC-5 (Channel 0) to a Modem
(Hardware Handshaking Enabled) C-12
PLC-5 (Channel 0) to a 5/03 Processor
1773-KA, 5130-RM, PLC-5, 1747-KE, or 1746-BAS
(Hardware Handshaking Disabled) À C-12
5130-RM to a Modem (Hardware Handshaking Enabled) C-13
Read this preface first. It provides an overview of the entire manual and will
acquaint you with the information that is provided throughout these pages.
In this preface, you will learn about:
• who should use this manual
• how to use this manual
• related publications
• conventions used in this manual
• Allen–Bradley support
Who Should Use this Manual
The tasks and procedures in this manual require you to have some knowledge
of programmable controller installation and electrical wiring. We also
assume that you have a “working” knowledge of SLCt products. If you do
not have this knowledge base, obtain the proper training before attempting
any of the tasks and/or procedures detailed in this manual.
P–1
Preface
How to Use this Manual
As much as possible, we organized this manual to explain, in a task–by–task
manner, how to install and operate (preliminary start–up operations) the SLC
500 fixed programmable controller. This manual also provides some system
design information.
Before using this manual, read over the table below and familiarize yourself
with the general content of the chapters and appendixes. If you already have
a topic in mind that you want to find specific information about, turn to the
index at the back of the manual.
If You WantSee
An overview of the manualThe Preface
Information on how to select certain components
for your SLC 500 control system
A guide on how to prepare for the installation of
your control system
Mounting dimensions of your fixed controller,
DTAM
t, and/or 1747-AIC
Procedures on how to install your hardware
components
Information on how to wire the components of
your SLC 500 control system
A guide on how to start up your control systemChapter 6 Starting Up Your Control System
Chapter 1 Selecting Your Hardware Components
Chapter 2 System Installation Recommendations
Chapter 3 Mounting Your SLC 500 Control System
Chapter 4 Installing Your Hardware Components
Chapter 5 Wiring Your Control System
Information on how to maintain your control
system
To identify error messages generated by your
control system
To replace parts of your SLC 500 control system
or purchase other SLC components
Information on setting up the DH-485 networkAppendix A Setting Up the DH-485 Network
Information on the 1771-Remote I/O networkAppendix B The 1771-Remote I/O Network
Information on configuring the RS-232 networkAppendix C RS-232 Communication Interface
Information on how to calculate the heat
dissipation of your controller
Wiring and circuit diagrams and voltage ranges
Definitions of terms used in this manualThe Glossary
Chapter 7 Maintaining Your Control System
Chapter 8 Troubleshooting
Chapter 9 Replacement Parts
Appendix D Calculating Heat Dissipation for the
SLC 500 Control System
Appendix E Wiring and Circuit Diagrams and
Voltage Ranges for Your Fixed Controller
P–2
Preface
Related PublicationsRelated Publications
The table below provides a listing of publications that contain important
information about Allen–Bradley Small Logic Controllers and their
installation and application. You may want to reference them while you are
installing the SLC 500 controller. (To obtain a copy of one of these
publications, contact your local Allen–Bradley office or distributor.)
ForRead this Document
An overview of the SLC 500 family of productsSLC 500 System Overview1747-2.30
A description on how to install and use your Modular SLC 500
programmable controller
A procedural manual for technical personnel who use APS to develop
control applications
A reference manual that contains status file data, instruction set, and
troubleshooting information about APS
An introduction to APS for first-time users, containing basic concepts but
focusing on simple tasks and exercises, and allowing the reader to begin
programming in the shortest time possible
A procedural and reference manual for technical personnel who use the
APS import/export utility to convert APS files to ASCII and conversely
ASCII to APS files
A procedural and reference manual for technical personnel who use an
HHT to develop control applications
An introduction to HHT for first-time users, containing basic concepts but
focusing on simple tasks and exercises, and allowing the reader to begin
programming in the shortest time possible
Installation & Operation Manual for Modular Hardware
Style Programmable Controllers
Advanced Programming Software (APS) User Manual9399-APSUM
SLC 500t and MicroLogixt 1000 Instruction Set
Reference Manual
APS Quick Start for New Users9399-APSQS
APS Import/Export User Manual9399-APSIE
Allen-Bradley Hand-Held Terminal User Manual1747-NP002
Getting Started Guide for HHT1747-NM009
Document
Number
1747-6.2
1747-6.15
In-depth information on grounding and wiring Allen-Bradley
programmable controllers
A description on how to install a PLC-5r system
A description of important differences between solid-state programmable
controller products and hard-wired electromechanical devices
An article on wire sizes and types for grounding electrical equipmentNational Electrical Code
A complete listing of current Automation Group documentation, including
ordering instructions. Also indicates whether the documents are
available on CD-ROM or in multi-languages.
A glossary of industrial automation terms and abbreviationsAllen-Bradley Industrial Automation GlossaryAG-7.1
Allen-Bradley Programmable Controller Grounding and
Wiring Guidelines
PLC-5 Family Programmable Controllers Hardware
Installation Manual
Application Considerations for Solid-State ControlsSGI-1.1
Allen-Bradley Publication IndexSD499
1770-4.1
1785-6.6.1
Published by the
National Fire
Protection
Association of
Boston, MA.
P–3
Preface
Conventions Used in this
Manual
Allen-Bradley Support
The following conventions are used throughout this manual:
• Bulleted lists such as this one provide information, not procedural steps.
• Numbered lists provide sequential steps or hierarchical information.
• Italic type is used for emphasis.
• Dimensions are in millimeters. (Dimensions in parentheses are in
inches.)
• Text in this
Allen–Bradley offers support services worldwide, with over 75 Sales/Support
offices, 512 authorized Distributors and 260 authorized Systems Integrators
located throughout the United States alone, plus Allen–Bradley
representatives in every major country in the world.
font
indicates words or phrases you should type.
Local Product Support
Contact your local Allen–Bradley representative for:
• sales and order support
• product technical training
• warranty support
• support service agreements
P–4
Technical Product Assistance
If you need to contact Allen–Bradley for technical assistance, please review
the information in the Troubleshooting chapter first. Then call your local
Allen–Bradley representative.
Your Questions or Comments on this Manual
If you find a problem with this manual, please notify us of it on the enclosed
Publication Problem Report.
If you have any suggestions for how this manual could be made more useful
to you, please contact us at the address below:
Allen–Bradley Company, Inc.
Automation Group
Technical Communication, Dept. 602V, T122
P.O. Box 2086
Milwaukee, WI 53201–2086
Chapter
1
Selecting Your Hardware Components
This chapter provides general information on what your SLC 500 controller
can do for you and an overview of the fixed control system. It also explains
how to select:
• 2–slot chassis
• discrete I/O modules
• specialty I/O modules
• enclosures
• operator interfaces
• memory modules
• isolation transformers
• suppressors
• output contact protection
What Your SLC 500 Controller
Can Do for You
There is also a section on special considerations for controller installations.
This chapter does not provide you with all the information that you need to
select a complete SLC 500 control system. To do this, we recommend that
you use the latest version of the system overview, SLC 500 Family of SmallProgrammable Controllers, Publication Number 1747–2.30.
The SLC 500 programmable controller has features that previously could
only be found in large programmable controllers. It has the flexibility and
power of a large controller with the size and simplicity of a small controller.
The SLC 500 controller offers you more control options than any other
programmable controller in its class.
These programmable controllers make up a technologically advanced control
system having inherent flexibility and advantages characteristic of other
programmable controllers, but with one important difference — simplicity!
1–1
Chapter 1
Selecting Your Hardware Components
Overview of Your Fixed
Control System
Fixed Hardware Components
Fixed Hardware Controller
The basic fixed controller consists of a processor with 1,024 (1K) instruction
capacity, a power supply, and a fixed number of I/O contained in a single
package. The figure below shows typical hardware components for a fixed
controller.
Input Module
Output Module
Fixed
Controller with 2-slot Expansion Chassis
Operator Interface
2-Slot Expansion Chassis
for I/O Modules
1–2
Chapter 1
Selecting Your Hardware Components
Fixed Controller
Specifications
This section provides the specifications for the SLC 500 Fixed Controller.
Capacitor Memory Back-up TimeRefer to curve on page 1-4.
Battery Life5 years
Typical Scan Time
➀
Bit Execution (XIC)4 microseconds
Program Scan Hold-up Time after
Loss of Power
Power Supply Operating Voltage
Power Supply Fuse Protection
Power Supply Inrush Rating30 Amperes maximum
Maximum Power Requirement
24 VDC User Power Output Current
24 VDC User Power Output Voltage
Wire Size#14 AWG Max.
8 milliseconds/1K
20 milliseconds to 700 milliseconds (dependent on loading)
AC units: 85-265 VAC 47-63 Hz
DC units: 21.6-26.4 VDC (24 VDC ± 10%)
AC units: 120/240 VAC 1.25A
DC units: 24 VDC1.6A
➁
50 VA
➂
200mA
➂
20.4 - 27.6 VDC (24 VDC ± 15 %)
I/O Electrical-Optical Isolation1500 VAC at 1 minute
1747-AIC Link Coupler
Electrical-Optical Isolation
LED Indicators
1500 VDC
POWER, PC RUN, CPU FAULT, FORCED I/O, and
BATTERY LOW
Noise ImmunityNEMA Standard ICS 2-230
Ambient Temperature Rating
Operating: 0°C to +60°C (+32°F to +140°F)
Storage: 40°C to +85°C (-40°F to +185°F)
Humidity5 to 95% without condensation
Displacement: .015 inch, peak-to-peak @ 5-57 Hz
Vibration
Certification
➀
The scan times are typical for a 1K ladder logic program consisting of simple ladder logic and communication
servicing. Actual scan times depend on your program size, instructions used, and the DH-485
communication.
➁
This specification does not include input and output values. (See page
➂
This applies only to fixed controllers that have AC line power and DC input circuits.
Acceleration: 2.5 Gs @ 57-2000 Hz
Duration: 1 hr per axis (x, y
, z)
UL listed/
CSA approved
1-6.)
1–3
Chapter 1
Selecting Your Hardware Components
30
25
20
Time
(Days)
15
Memory Backup for the SLC 500 Fixed Controller
The curve below illustrates the ability of the memory back–up capacitor to
maintain the contents of the RAM in a fixed controller. To back up the
memory for a longer period of time, a lithium battery, Catalog Number
1747–BA, is required.
Capacitor Memory Back-up Time
VS
Temperature
10
5
2530354045505560
(77°)(86°)(95°)(104°)(113°)(122°)(131°)(140°)
Temperature °
C (
°F)
1–4
Chapter 1
Catalog
High-Speed
Selecting Your Hardware Components
Configuration Options
The following table provides configuration options for 20, 30, or 40 I/O
points.
Catalog
Number
1747-L20A(12) 120 Volts AC(8) AC/DC RelayNo
1747-L30A(18) 120 Volts AC(12) AC/DC RelayNoNA
1747-L40A(24) 120 Volts AC(16) AC/DC RelayNoNA
1747-L20B(12) 120 Volts AC(8) AC TriacNoNA
1747-L30B(18) 120 Volts AC(12) AC TriacNoNA
1747-L40B(24) 120 Volts AC(16) AC TriacNoNA
1747-L20C(12) 24 Volts DC Sink(8) AC/DC RelayYe s24V-200mA
1747-L30C(18) 24 Volts DC Sink(12) AC/DC RelayYe s24V-200mA
1747-L40C(24) 24 Volts DC Sink(16) AC/DC RelayYe s24V-200mA
1747-L20D(12) 24 Volts DC Sink(8) AC TriacYes24V-200mA
1747-L30D(18) 24 Volts DC Sink(12) AC TriacYes24V-200mA
1747-L20E
1747-L40E(24) 24 Volts DC Sink
1747-L20L
1747-L30L
1747-L40L
1747-L20R(12) 240 Volts AC(8) AC/DC RelayNoNA
Line Power
120/240 VAC
(12) 24 Volts DC Sink
(12) 24 Volts DC
Source
(18) 24 Volts DC
Source
(24) 24 Volts DC
Source
I/O Configuration
InputOutput
(8) DC Transistor
Source
(16) DC Transistor
Source
(8) DC Transistor
Sink
(12) DC Transistor
Sink
(16) DC Transistor
Sink
High-Speed
Counter
Yes24V-200mA
Yes24V-200mA
Yes24V-200mA
Yes24V-200mA
Yes24V-200mA
User Power
NA
1747-L20P(12) 240 Volts AC(8) AC TriacNoNA
1747-L30P(18) 240 Volts AC(12) AC TriacNoNA
1747-L40P(24) 240 Volts AC(16) AC TriacNoNA
1747-L20F(12) 24 Volts DC Sink(8) AC/DC RelayYesNA
1747-L40F(24) 24 Volts DC Sink(16) AC/DC RelayYesNA
1747-L20G
1747-L20N
24 VDC±
10%
(12) 24 Volts DC Sink
(12) 24 Volts DC
Source
(8) DC Transistor
Source
(8) DC Transistor
Sink
YesNA
YesNA
1–5
Chapter 1
Selecting Your Hardware Components
Input Specifications
The following table details the input specifications for SLC 500 Fixed I/O
units. See the glossary for a definition of specifications.
InputsSpecifications
120 VACInrush Current0.8A peak
On-State Voltage85-132 VAC
Frequency
Off-State Voltage30 VAC (maximum)
Nominal Input Current12mA at 120 VAC
Turn-On Time35 milliseconds (maximum)
Turn-Off Time45 milliseconds (maximum)
Maximum Off-State Current2mA
On-State Voltage170-265 VAC
47-63 Hz
Frequency47-63 Hz
Off-State Voltage50 VAC (maximum)
240 VACInrush Current1.6A peak
Nominal Input Current12mA at 240 VAC
Turn-On Time35 milliseconds (maximum)
Turn-Off Time45 milliseconds (maximum)
Maximum Off-State Current2mA
On-State Voltage10-30 VDC
4 VDC maximum for input 0 (HSC)
5 VDC for all others
20mA at 24 VDC (for input 0 only)
8mA at 24 VDC (all others inputs)
DC Sink & Source
Off-State Voltage
Nominal Input Current
Turn-On Time8 milliseconds (maximum)
Turn-Off Time8 milliseconds (maximum)
Maximum Off-State Current1mA
1–6
Chapter 1
Triac
➂
Selecting Your Hardware Components
Output Specifications
The following table details the output specifications for SLC 500 Fixed I/O
Units.
OutputsSpecifications
Output Voltage85-265 VAC
Triac
Transistor Sink &
Source
Continuous Current (per output)
0.5 Amp at +30°C
0.25 Amp at +60°C (maximum)
Minimum Load Current10mA
Turn-On Time
0.1 milliseconds (maximum)
Turn-Off Time10 milliseconds (maximum)
Maximum Off-State Leakage Current2mA
Maximum On-State Voltage Drop1.5V @ 0.5 Amps
Maximum Surge Current
10 Amps for 25 milliseconds
Output Voltage10-50 VDC
Continuous Current (per output)
0.5 Amp at +30°C
0.25 Amp at +60°C (maximum)
Minimum Load Current1mA
Turn-On Time0.1 millisecond (maximum)
Turn-Off Time
1 millisecond (maximum)
Maximum Off-State Leakage Current1mA
Maximum On-State Voltage Drop1.5V @ 0.5 Amps
Maximum Surge Current
3.0 Amps for 25 milliseconds
Output Voltage Range5-265 VAC, 5-125 VDC
➀
➀
Continuous Current (per output)2.5 Amps (maximum)
Relay
Continuous Current (per group)
➂
Maximum Load (per chassis)1440 VA
➁
8 Amps (maximum)
Turn-On Time10 milliseconds (maximum)
Turn-Off Time10 milliseconds (maximum)
Maximum Off-State Leakage Current0mA
Minimum Load Current at 5 VDC10mA
➀
Repeatability is once every 1 second at +30°C. Repeatability is once every 2 seconds at +60°C.
➁
Refer to the wiring diagrams for output groupings on the fixed I/O chassis.
➂
Surge suppression across the output device is recommended to protect relay contacts.
1–7
Chapter 1
Selecting Your Hardware Components
Relay Contact Ratings
Selecting the 2-Slot Chassis
Maximum
Volts
240 VAC
120 VAC
125 VDC0.22A1.0A28 VA
24 VDC1.2A2.0A28 VA
7.5A
15A
Amperes
Make Break
0.75A
1.5A
Amperes
Continuous
2.5A1800 VA180 VA
Voltamperes
Make Break
To calculate make and break ratings for other load voltages, divide the
voltampere rating by the load voltage; for example:
28 VA/48 VDC = 0.583 A
For the 20, 30, and 40 I/O fixed controllers, an optional 2–slot expansion
chassis lets you add two additional I/O modules providing even more
versatility. The power supply provides backplane power for the modules in
the optional expansion chassis.
Refer to chapter 3 for chassis dimensions and chapter 4 for mounting
directions.
Selecting Discrete I/O
Modules
Selecting Speciality I/O
Modules
There are three types of I/O modules: input, output, and combination I/O.
They are available in a wide variety of densities including 4, 8, 16, and 32
point and can interface to AC, DC, and TTL voltage levels. Output modules
are available with solid–state AC, solid–state DC, and relay contact type
outputs.
For a complete, up–to–date listing of discrete I/O modules and their
specifications, contact your Allen–Bradley sales office for the latest product
data entitled Discrete Input and Output Modules, Publication Number
1746–2.35.
Refer to chapter 4 for installation directions.
The SLC 500 family offers specialty I/O modules that enhance your control
system. These modules range in function from analog interface to motion
control, from communication to high–speed counting.
For a complete, up–to–date listing of specialty I/O modules and their
specifications, contact your Allen–Bradley sales office for the latest System
Overview entitled SLC 500 Family of Small Programmable Controllers,
Publication Number 1747–2.30, or for a related product data.
1–8
Refer to chapter 4 for installation directions.
Chapter 1
Selecting Your Hardware Components
Selecting Enclosures
Selecting Operator Interfaces
The enclosure protects the equipment from atmospheric contamination.
Standards established by the National Electrical Manufacturer’s Association
(NEMA) define enclosure types, based on the degree of protection an
enclosure will provide. Use a fan to circulate the air of sealed enclosures that
use convection cooling to dissipate heat. Select a NEMA–rated enclosure
that suits your application and environment. The enclosure should be
equipped with a disconnect device. To calculate the heat dissipation of your
controller, see appendix D.
Use an operator interface to program and/or monitor your SLC 500
controller. You can choose from several Allen–Bradley operator interface
devices.
Programming with a Hand-Held Terminal (1747-PT1)
Use the Hand–Held Terminal (HHT) to configure the SLC 500 controller,
enter/modify a user program, download/upload programs, monitor control
operation, and test/troubleshoot. When equipped with a battery (1747–BA),
the HHT retains a user program in memory for storage and later use.
The display area accommodates 8 lines x 40 characters. You can display five
rungs of a user program. The top row of keys are the menu function keys.
Important: Using the HHT, you can program the SLC 5/01t and 5/02t
processors and the SLC 500 fixed controllers. You cannot,
however, program the SLC 5/03 processor.
Refer to the Hand–Held Terminal User Manual, Catalog Number
1747–NP002, for information on programming your fixed controller with the
HHT.
Programming with Advanced Programming Software (APS) on an IBM
Compatible Computer
The Advanced Programming Software (APS) can be used with an
Allen-Bradley T45, T47, or T50 terminal, an IBM
Portable, Portable II, Deskprot 286, 386/SX, 386, a Tandyt 3000HL,
Toshibat 3100E, or GATEWAY 2000t models 386DX/25, 386DX/33,
486DX/33, and 486DX2/50 personal computer. Your computer must have:
r-AT or XT, a Compaqr
• 640 Kbytes of RAM (extended or expanded memory is recommended, but
not required)
• 10 Mbyte fixed-disk drive (APS requires a minimum or 2.5 MBytes of
free disk space.)
• DOS version 3.1 or higher
1–9
Chapter 1
Selecting Your Hardware Components
Advanced Programming Software, 1747–PA2E
APS, Catalog Number 1747–PA2E, comes on 5–1/4 and 3–1/2 inch disks.
You must have DOS installed in your computer. You also must have at least
550 Kbytes of free memory to execute the APS software. Like the
Hand–Held Terminal, APS lets you configure the SLC 500 controller,
enter/modify a user program, restore/save programs to the SLC 500, monitor
controller operation, and test/troubleshoot. You can also:
• create and print ladder diagrams, data tables, instruction cross references,
and configurations
• use cut/copy/paste editor
• store multiple programs in the memory of the computer (on the hard disk)
Refer to the Advanced Programming Software User Manual, Catalog
Number 1747–NM002, and the Advanced Programming Software ReferenceManual, Catalog Number 1747–NR001, for information on programming
your fixed controller with APS.
DH–485 Interface Converter (1747–PIC)
For communication, use an RS–232/DH–485 Interface Converter between
the computer and SLC controller. The converter includes a 279.4 mm (11.0
in.) ribbon cable, already attached to the converter, for connection to the
computer serial port and a Catalog Number 1746–C10 cable for connection
to the controller.
Monitoring with a Data Table Access Module (1747-DTAM-E)
The Data Table Access Module (DTAM) is a plant floor device that lets you
access data file information, change operating modes, monitor and clear
processor faults, and transfer the user program between RAM and an
EEPROM memory module with any SLC 500 family processor. You cannot
use it to create new programs.
Important features of DTAM include:
• shorthand addressing, which provides easier access to data files
• display prompts in six, user–selectable languages: English, French,
German, Italian, Spanish, and Japanese
• UL listed, CSA Certified
• NEMA type 12 and 13 enclosures
• point–to–point interface to an SLC family processor, or as a network
device on a DH–485 network
Refer to the Data Table Access Module (DTAM) User Manual, Catalog
Number 1747–ND013, for information on monitoring your fixed controller
with the DTAM.
1–10
Chapter 1
Selecting Your Hardware Components
EEPROM and UVPROM
Memory Modules
These optional memory modules provide a non–volatile memory back–up in
a convenient modular form. The modules plug into a socket on the
controller.
You can store (save) your program in the EEPROM by inserting it into the
processor and using either the Hand–Held Terminal or Advanced
Programming Software.
Use of the UVPROM provides you with an extra degree of program security
because the user program cannot be altered while it is installed in the
controller. You can program the UVPROM with commercially available
UVPROM programming and erasing equipment. You can use an EEPROM
module as a master, or you can use an archived processor file as the source
by using the APS PROM translator utility.
Adapter sockets are required when inserting memory modules into
commercially available PROM programmer. The memory module fits into
the adapter socket and then into a PROM programmer.
ATTENTION: Make sure the adapter is inserted properly or
damage could result.
!
The following table lists the types of memory modules that are available for
the fixed controller. Also listed are the manufacturer part number for
determining compatibility with an external PROM burner.
DescriptionCatalog NumberManufacturerManufacturer's Part Number
NECuPD28C64 - 250
1K User Words EEPROM1747-M1
4K User Words EEPROM1747-M2
1K User Words UVPROM1747-M3FujitsuMBM27C64 - 25
4K User Words UVPROM1747-M4Not compatible with the fixed controller.
Adaptor Socket1747-M5NANA
-
OKIMSM28C64ARS - 20
XICORX28C64BP - 25
SEEQPE28C64 - 250
X28C256DI - 25
XICOR
X28256DI - 25
SEEQDE28C256 - 25
1–11
Loading...
+ 193 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.