Rockwell Automation 1734-APB User Manual

POINT I/O PROFIBUS Adapter Module
Cat. No. 1734-APB
User Manual

Important User Information

Because of the variety of uses for the products described in this publication, those responsible for the application and use of this control equipment must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards.
The illustrations, charts, sample programs and layout examples shown in this guide are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Allen-Bradley does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication.
Allen-Bradley publication SGI-1.1, Safety Guidelines for the
Application, Installation and Maintenance of Solid-State Control
(available from your local Allen-Bradley office), describes some important differences between solid-state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication.
Reproduction of the contents of this copyrighted publication, in whole or part, without written permission of Rockwell Automation, is prohibited.
Throughout this manual we use notes to make you aware of safety considerations:
ATTENTION
Identifies information about practices or circumstances that can lead to personal injury or death, property damage or economic loss
!
Attention statements help you to:
identify a hazard
avoid a hazard
recognize the consequences
IMPORTANT
Allen-Bradley, RSNetworx and POINT I/O are trademarks of Rockwell Automation
PROFIBUS is a trademark of PROFIBUS Trade Organization
Identifies information that is critical for successful application and understanding of the product.
About This User Manual

Preface

Purpose of This Manual

Who Should Use This Manual

This manual describes how to install, configure and troubleshoot your PROFIBUS Adapter module.
For information about: See:
What is the PROFIBUS Adapter Chapter 1
Installing the PROFIBUS Adapter Chapter 2
Configuring the POINT I/O System Chapter 3
Communication and I/O Table Mapping Chapter 4
Grouped Modules Chapter 5
Troubleshooting the PROFIBUS Adapter Chapter 6
Specifications Appendix A
Default Data Maps Appendix B
You must be able to use your selected configuration software to set up and calibrate these modules. You must have the capability to download and use files.

Related Products and Documentation

Description Cat. No. Publication
POINT I/O Technical Data 1734-Series 1734-2.1
Sink Input Module Installation Instructions 1734-IB2, -IB4 1734-IN051
Source Output Module Installation Instructions 1734-IV2, -IV4 1734-IN052
220V ac Input Module Installation Instructions 1734-IM 1734-IN008
120V ac Input Module Installation Instructions 1734-IA2 1734-IN010
120/220V ac Output Module Installation Instructions 1734-OA2 1734-IN009
Analog Current Input Module Installation Instructions 1734-IE2C 1734-IN053
We assume you know how to do this in this manual. If you do not, refer to your software user manuals or online help before attempting to use these modules.
The following table lists related 1734 products and documentation.
1 Publication 1734-UM005B-EN-P - June 2001
Preface 2
Description Cat. No. Publication
Analog Current Output Module Installation Instructions 1734-OE2C 1734-IN054
Analog Voltage Input Module Installation Instructions 1734-IE2V 1734-IN001
Analog Voltage Output Module Installation Instructions 1734-OE2V 1734-IN002
Very High Speed Counter Module Installation Instructions 1734-VHSC24 1734-IN003
Very High Speed Counter Module Installation Instructions 1734-VHSC5 1734-IN004
5V Encoder/Counter Module Installation Instructions 1734-IJ 1734-IN005
24V Encoder/Counter Module Installation Instructions 1734-IK 1734-IN006
Relay Output Module Installation Instructions 1734-OW2 1734-IN055
Protected Output Module Installation Instructions 1734-OB2E, -OB4E 1734-IN056
DeviceNet Communication Interface Installation Instructions 1734-PDN 1734-IN057
POINT I/O 24V dc Expansion Power Supply Installation Instructions 1734-EP24DC 1734-IN058
Field Potential Distributor Installation Instructions 1734-FPD 1734-IN059
General Installation Instructions All 1734 1734-IN510
Wiring Base Assembly Installation Instructions 1734-TB, -TBS 1734-5.11
Wiring Base Assembly Installation Instructions 1734-TB3, -TB3S 1734-IN013A
Cold Junction Wiring Base Assembly Installation Instruction 1734-TBCJC 1734-IN583
8 dc Input/8 Output Module Installation Instructions 1734D-IB8XOB8 1734-5.20
8 dc Input/8 Relay Output Module Installation Instructions 1734D-IB8XOW8 1734-5.21
8 ac Input/8 OutputModule Installation Instructions 1734D-IA8XOA8 1734-5.22
8 ac Input/8 Relay Output Module Installation Instructions 1734D-IA8XOW8 1734-5.23
16 ac Input Module Installation Instructions 1734D-IA16 1734D-IN001
16 dc Input Module Installation Instructions 1734D-IB16 1734D-IN002
Publication 1734-UM005B-EN-P - June 2001
Preface 3

European Communities (EC) Directive Compliance

If this product has the CE mark it is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.

EMC Directive

This product is tested to meet the Council Directive 89/336/EC Electromagnetic Compatibility (EMC) by applying the following standards, in whole or in part, documented in a technical construction file:
EN 50081-2 EMC — Generic Emission Standard, Part 2 — Industrial
Environment
EN 50082-2 EMC — Generic Immunity Standard, Part 2 —
Industrial Environment
This product is intended for use in an industrial environment.

Environmental/Safety Protection

Open style devices must be provided with environmental and safety protection by proper mounting in enclosures designed for specific application conditions. See NEMA Standards publication 250 and IEC publication 529, as applicable, for explanations of the degrees of protection provided by different types of enclosures. Refer to Allen-Bradley publication 1770-4.1, Industrial Automation Wiring and Grounding Guidelines for more information.
Publication 1734-UM005B-EN-P - June 2001
Preface 4
Publication 1734-UM005B-EN-P - June 2001

Preface

What is the PROFIBUS Adapter

Table of Contents

Important User Information . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Purpose of This Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . P-1
Who Should Use This Manual . . . . . . . . . . . . . . . . . . . . . . P-1
Related Products and Documentation. . . . . . . . . . . . . . . . . P-1
European Communities (EC) Directive Compliance . . . . . . P-3
EMC Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-3
Environmental/Safety Protection . . . . . . . . . . . . . . . . . . P-3

Chapter 1

General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
PROFIBUS Adapter Overview . . . . . . . . . . . . . . . . . . . . . . 1-1
Communicating through the Adapter . . . . . . . . . . . . . . 1-2
I/O Module Removal and Insertion Under Power . . . . . 1-2
Startup Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Set the Adapter Node Address . . . . . . . . . . . . . . . . . . . 1-2
Configure the Adapter for PROFIBUS Communication . . 1-3 Configure the I/O Modules for PointBus Communication 1-3
Diagnostic Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Network Connector. . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Chapter Summary and What’s Next . . . . . . . . . . . . . . . . . . 1-4

Installing the PROFIBUS Adapter

Configuring the POINT I/O System

Chapter 2

General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Installing the PROFIBUS Adapter . . . . . . . . . . . . . . . . . . . . 2-2
Installing a Replacement PROFIBUS Adapter to an
Existing System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Wiring the PROFIBUS Adapter. . . . . . . . . . . . . . . . . . . . . . 2-6
Module Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Wiring Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
PROFIBUS Connection Plug Wiring . . . . . . . . . . . . . . . 2-9
Chapter Summary and What’s Next . . . . . . . . . . . . . . . . . . 2-9

Chapter 3

In This Chapter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Configuration Overview . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Installing the GSD File. . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Adding the Master to the Network . . . . . . . . . . . . . . . . . . . 3-3
Adding the Adapter to the Network . . . . . . . . . . . . . . . . . . 3-5
Adding I/O Modules to the Adapter. . . . . . . . . . . . . . . . . . 3-6
Configuring I/O Modules. . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
Enable/Disable Diagnostic Functionality for
your Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Configure Fault Action/Value for your Output Modules . 3-10
Configure Idle Action Value for your Output Modules . . 3-11
Download to Master System . . . . . . . . . . . . . . . . . . . . . . . 3-13
Chapter Summary and What’s Next . . . . . . . . . . . . . . . . . . 3-14
i Publication 1734-UM005B-EN-P - June 2001
Table of Contents ii

Communication and I/O Table Mapping

Grouped Mode

Chapter 4

In This Chapter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Image Table Mapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
How Data Communication Takes Place . . . . . . . . . . . . . . . 4-2
Set_Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Check_Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
Get_Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
Global_Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
Data_Exchange . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
Slave_Diag. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
Grouping Modules for Memory Management . . . . . . . . . . . 4-16
Chapter Summary and What’s Next . . . . . . . . . . . . . . . . . . 4-16

Chapter 5

In This Chapter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
How to Configure the Adapter for Grouped Mode . . . . . . . 5-2
Configuration Example. . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Chapter Summary and What’s Next . . . . . . . . . . . . . . . . . . 5-4

Troubleshooting the PROFIBUS Adapter

Specifications

Default Data Maps

Chapter 6

In This Chapter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Using the Status Indicators. . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Using PROFIBUS Diagnostics. . . . . . . . . . . . . . . . . . . . . . . 6-3
Chapter Summary and What’s Next . . . . . . . . . . . . . . . . . . 6-3

Appendix A

Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-1

Appendix B

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
1734-IB2 Sink Input Module . . . . . . . . . . . . . . . . . . . . . . . B-2
Product Code: 0081h . . . . . . . . . . . . . . . . . . . . . . . . . . B-2
Data Map: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-2
Configuration Data: . . . . . . . . . . . . . . . . . . . . . . . . . . . B-2
Diagnostic Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-2
1734-IB4 Sink Input Module . . . . . . . . . . . . . . . . . . . . . . . B-3
Product Code: 0082h . . . . . . . . . . . . . . . . . . . . . . . . . . B-3
Data Map: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-3
Configuration Data: . . . . . . . . . . . . . . . . . . . . . . . . . . . B-3
Diagnostic Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-3
Publication 1734-UM005B-EN-P - June 2001
Table of Contents iii
1734-IV2 Source Input Module. . . . . . . . . . . . . . . . . . . . . . B-4
Product Code: 0083h . . . . . . . . . . . . . . . . . . . . . . . . . . B-4
Data Map: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-4
Configuration Data: . . . . . . . . . . . . . . . . . . . . . . . . . . . B-4
Diagnostic Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-4
1734-IV4 Source Input Module. . . . . . . . . . . . . . . . . . . . . . B-5
Product Code: 0084h . . . . . . . . . . . . . . . . . . . . . . . . . . B-5
Data Map: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-5
Configuration Data: . . . . . . . . . . . . . . . . . . . . . . . . . . . B-5
Diagnostic Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-5
1734-OB2E Electronically Protected Output Module . . . . . . B-6
Product Code: 0085h . . . . . . . . . . . . . . . . . . . . . . . . . . B-6
Data Map: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-6
Configuration Data: . . . . . . . . . . . . . . . . . . . . . . . . . . . B-6
Diagnostic Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-6
1734-OB4E Electronically Protected Output Module . . . . . . B-7
Product Code: 0086h . . . . . . . . . . . . . . . . . . . . . . . . . . B-7
Data Map: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-7
Configuration Data: . . . . . . . . . . . . . . . . . . . . . . . . . . . B-7
Diagnostic Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-7
1734-OW2 Relay Sink/Source Output Module. . . . . . . . . . . B-8
Product Code: 0087h . . . . . . . . . . . . . . . . . . . . . . . . . . B-8
Data Map: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-8
Configuration Data: . . . . . . . . . . . . . . . . . . . . . . . . . . . B-8
Diagnostic Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-8
1734-IE2C Analog Current Input Module . . . . . . . . . . . . . . B-9
Product Code: 0018h . . . . . . . . . . . . . . . . . . . . . . . . . . B-9
Data Map: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-9
Configuration Data: . . . . . . . . . . . . . . . . . . . . . . . . . . . B-9
Diagnostic Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-10
1734-OE2C Analog Current Output Module . . . . . . . . . . . B-11
Product Code: 0019h . . . . . . . . . . . . . . . . . . . . . . . . . B-11
Data Map: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-11
Configuration Data: . . . . . . . . . . . . . . . . . . . . . . . . . . B-11
Diagnostic Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-11
1734-IE2V Analog Voltage Input Module . . . . . . . . . . . . . B-12
Product Code: 0018h . . . . . . . . . . . . . . . . . . . . . . . . . B-12
Data Map: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-12
Configuration Data: . . . . . . . . . . . . . . . . . . . . . . . . . . B-12
Diagnostic Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-13
1734-OE2V Analog Voltage Output Module . . . . . . . . . . . B-14
Product Code: 0019h . . . . . . . . . . . . . . . . . . . . . . . . . B-14
Data Map: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-14
Configuration Data: . . . . . . . . . . . . . . . . . . . . . . . . . . B-14
Diagnostic Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-14
Publication 1734-UM005B-EN-P - June 2001
Table of Contents iv
Publication Problem Report Index Back Cover
1734-IA2 120V ac Input Module. . . . . . . . . . . . . . . . . . . . B-15
Product Code: 1111h . . . . . . . . . . . . . . . . . . . . . . . . . B-15
Data Map: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-15
Configuration Data: . . . . . . . . . . . . . . . . . . . . . . . . . . B-15
Diagnostic Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-15
1734-IM2 220V ac Input Module . . . . . . . . . . . . . . . . . . . B-16
Product Code: 1112h . . . . . . . . . . . . . . . . . . . . . . . . . B-16
Data Map: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-16
Configuration Data: . . . . . . . . . . . . . . . . . . . . . . . . . . B-16
Diagnostic Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-16
1734-OA2 120/220V ac Output Module . . . . . . . . . . . . . . B-17
Product Code: 1113h . . . . . . . . . . . . . . . . . . . . . . . . . B-17
Data Map: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-17
Configuration Data: . . . . . . . . . . . . . . . . . . . . . . . . . . B-17
Diagnostic Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-17
Publication 1734-UM005B-EN-P - June 2001

What is the PROFIBUS Adapter

Chapter
1

General

PROFIBUS Adapter Overview

This chapter describes the purpose of the POINT I/O PROFIBUS adapter, and what tasks have to be performed after installing the adapter.
For more information about: See page:
PROFIBUS Adapter Overview 1-1
Startup Procedure 1-2
Chapter Summary and What’s Next 1-4
The POINT I/O 1734-APB adapter resides on the PROFIBUS network and the POINT I/O backplane (PointBus) simultaneously. From this position, the adapter interfaces between the PROFIBUS network and the POINT I/O modules. The illustration below shows the adapter on the PROFIBUS network and the PointBus.
The adapter functions are:
PROFIBUS - adapter serves as a slave that exchanges I/O data
with a PROFIBUS master.
PointBus - the adapter serves as a master that communicates
with up to 63 POINT I/O modules
1 Publication 1734-UM005B-EN-P - June 2001
1-2 What is the PROFIBUS Adapter

Communicating through the Adapter

Output data is sent from the master across the PROFIBUS network to the 1734-APB adapter. The adapter automatically transfers the data across the PointBus backplane to the output modules.
Inputs from the input modules are collected by the PROFIBUS adapter via the backplane and sent across the PROFIBUS network to the master.

I/O Module Removal and Insertion Under Power

I/O modules can be removed under power from their positions in the backplane without interfering with the communication with the other modules. When reinserting the removed module, communication is automatically started up again if the following criteria is fulfilled:
1. The inserted module is the same type as the one removed.

Startup Procedure

2. If more than one module is removed, communication will not be
regained until all modules are inserted in their correct positions again.
Starting the adapter module consists of:
Installing the adapter in the system
setting the adapter node address
configuring the adapter for PROFIBUS communication
configuring the I/O modules for PointBus communication

Set the Adapter Node Address

Set the node address using the 2-position thumbwheel switch. Valid
settings range from 01 to 99. Use a pen to press either the + or – buttons to change the number.
Publication 1734-UM005B-EN-P - June 2001
01
What is the PROFIBUS Adapter 1-3

Configure the Adapter for PROFIBUS Communication

Install the GSD file you received into your configuration tool
add the adapter to your configuration
select the node address and baud rate
add I/O modules to the configuration
For more information, refer to Chapter 3 - Configuring the POINT I/O System.

Configure the I/O Modules for PointBus Communication

You must configure each I/O module to establish its actions on the PointBus. Each module has a set of parameters that can be set (i.e. Idle value, Fault value, etc.).
For more information, refer to Chapter 3 - Configuring the POINT I/O System.
Adapter
Node Address Thumbweel
Profibus Connector
System Power
Field Power
Status
PROFIBUS Status
PointBus Status
1734-APB
01
NC
CHAS GND
Adapter Status
PROFIBUS Status
PointBus Status
System Power Field Power
NC
CHAS GND
NC = No Connection CHAS GND = Chassis Ground C = Common V = Supply
C
V
C
V
Publication 1734-UM005B-EN-P - June 2001
1-4 What is the PROFIBUS Adapter

Diagnostic Indicators

Diagnostic indicators are located on the front panel of the adapter module. They show both normal operation and error conditions in your POINT I/O system. The indicators are:
Adapter status
PROFIBUS status
PointBus status
System power
Field power
Upon power-up, the adapter goes to an initialization state and performs a self-test (memory check, data memory clear, firmware integrity). The indicators also go through a self-test sequence. If a failure occurs, the adapter transitions to a faulted state and waits for reset (cycle power). Otherwise, the adapter begins monitoring the network (run state) for messages. Chapter 6 describes the diagnostic indicators and how to use them for troubleshooting.
Chapter Summary and
What’s Next

Network Connector

Use the 9-pin D-shell connector (shown below) to connect your adapter to the PROFIBUS network.
Connections are provided for connecting the required 24V dc power to the front of the module.
Refer to Chapter 2 or the Installation Instructions (pub. no. 1734-IN014) you received with your adapter to learn how to install and wire the adapter.
This chapter provided a brief overview of the 1734-APB PROFIBUS adapter. Go to chapter 2 to learn how to install and wire your adapter.
Publication 1734-UM005B-EN-P - June 2001

Installing the PROFIBUS Adapter

Chapter
2

General

This chapter describes how to install and wire your adapter.
For information about: See page:
Installing the PROFIBUS Adapter 2-2
Installing a Replacement PROFIBUS Adapter to an Existing System 2-4
Wiring the PROFIBUS Adapter 2-6
Chapter Summary and What’s Next 2-9
When properly installed, POINT I/O is grounded through the DIN rail to chassis ground. Use zinc plated, yellow chromated steel DIN rail to assure proper grounding.
Other DIN rail material (such as aluminum, plastic, etc.) can corrode or oxidize and are poor conductors that may result in improper or intermittent platform grounding.
If you choose not to use zinc plated, yellow chromated steel DIN rail for your POINT I/O, periodically clean the DIN rail to prevent or lessen the effects of oxidation and corrosion.
1 Publication 1734-UM005B-EN-P - June 2001
2-2 Installing the PROFIBUS Adapter

Installing the PROFIBUS Adapter

To install the adapter on the DIN rail prior to installing other base units, proceed as follows.

1. Position the adapter vertically above the DIN rail.

2. Press down firmly to install the adapter on the DIN rail. (The
locking mechanism will lock the adapter to the DIN rail.)
1734-APB communication interface
DIN rail
Orange screw slot
3. Insert the PROFIBUS network plug and tighten the holding
screws.
Publication 1734-UM005B-EN-P - June 2001
Holding screws
Profibus network plug
Installing the PROFIBUS Adapter 2-3
4. Set the node address using the 2-position thumbwheel switch.
Valid settings range from 01 to 99. Press the + or - buttons to change the numbers.
System Power
Field Power
Adapter Status
PROFIBUS Status
PointBus Status
1734-APB
Network Node Address Thumbwheel Press either the + or ­buttons to change the number
01
5. Slide the safety end cap (9) up to remove. This exposes the
backplane and power interconnections.
Safety end cap
ATTENTION
!
Do not discard the safety end cap. Use this end cap to cover the exposed interconnections on the last mounting base on the DIN rail. Failure to do so could result in equipment damage or injury from electric shock.
Publication 1734-UM005B-EN-P - June 2001
2-4 Installing the PROFIBUS Adapter

Installing a Replacement PROFIBUS Adapter to an Existing System

1. Remove the existing adapter from the DIN rail as follows:

A. Pull up on the removable terminal base (RTB) removal
handle (7) to remove the terminal block.
RTB removal handle
B. Loosen the screws holding the PROFIBUS network plug and
pull up to remove.
Loosen holding screws
PROFIBUS network plug

C. Remove the adjacent module from its base.

Remove adjacent
module.
Publication 1734-UM005B-EN-P - June 2001
Installing the PROFIBUS Adapter 2-5
D. Use a small bladed screwdriver to rotate the DIN rail locking
screw (5) to a vertical position. This releases the locking mechanism.

E. Pull straight out to remove.

2. Set the desired node address on the replacement adapter.

3. Slide the safety end cap up and remove it from the replacement
adapter. This exposes the backplane and power connections.
Safety end cap
4. Position the replacement adapter vertically above the DIN rail.
(Make certain the DIN rail lock is in the horizontal position.) Slide the adapter down, allowing the interlocking side pieces to engage the adjacent module.
Align the interlocking side pieces and slide adapter into place on the DIN rail.
Publication 1734-UM005B-EN-P - June 2001
2-6 Installing the PROFIBUS Adapter
5. Press firmly to seat the adapter (1) on the DIN rail. The adapter
locking mechanism will snap into place.
6. Insert the PROFIBUS network plug and tighten the holding
screws.
7. Insert the end opposite the handle into the base unit. This end
has a curved section that engages with the wiring base.
8. Rotate the terminal block into the wiring base until it locks itself
in place.

9. Replace the adjacent module in its base.

Wiring the PROFIBUS Adapter

Refer to the figure below when wiring the PROFIBUS adapter.
Adapter
Node Address Thumbweel
Profibus Connector
NC = No Connection CHAS GND = Chassis Ground C = Common V = Supply
01
Status
PROFIBUS Status
PointBus Status
1734-APB
System Power
Field Power
NC
CHAS GND
C
V
Adapter Status
PROFIBUS Status
PointBus Status
System Power Field Power
NC
CHAS GND
C
V
Publication 1734-UM005B-EN-P - June 2001
Module Power
The adapter supplies 5V logic power to POINT I/O modules by converting the applied 12/24V dc field power to PointBus 5V power.
You can connect up to 63 I/O modules to each adapter, and you can power up to 14 I/O modules from the adapter (with a maximum of 10A of field power). Add up the current requirements of the modules you want to use, and determine that they do not exceed the amperage limit of the 1734-APB. (Note: Total expansion up to 63 modules - 14 modules (with 75mA current draw) maximum with 1734-APB - add 1734-EP24DC modules for additional 14 modules (or less based on current requirements), up to 63 module maximum)
Installing the PROFIBUS Adapter 2-7
After the 14th (or last) module, you must insert an expansion power supply (cat. no. 1734-EP24DC) to power additional I/O modules.
Refer to the table below for various POINT I/O modules current requirements.
POINT I/O Cat. No. PointBus Current
1734-IB2 1734-IB4 1734-IV2 1734-IV4 1734-OB2E 1734-OB4E 1734-OW2 1734-IE2C 1734-OE2C 1734-IE2V 1734-OE2V 1734-IA2 1734-IM2 1734-OA2 1734-IJ2 1734-IK2 1734-IR2 1734-IT2 1734-VHSC5 1734-VHSC24
Requirements
75mA 75mA 75mA 75mA 75mA 75mA 80mA 75mA 75mA 75mA 75mA 75mA 75mA 75mA 160mA 160mA 220mA 175mA 180mA 180mA
For more information on the Expansion Power Supply, cat. no. 1734-EP24DC, refer to:
POINT I/O Technical Data, publication 1734-TD001A
POINT I/O Expansion Power Supply Installation Instructions,
publication 1734-IN058A
Publication 1734-UM005B-EN-P - June 2001
2-8 Installing the PROFIBUS Adapter
Wiring Connections
12/24V dc
Do not connect 120/240V ac power to this supply.
NC = No Connection CHAS GND = Chassis Ground C = Common V = Supply
V dc
NC
CHAS GND
NC
1
0
CHAS GND
3
2
C
V
C
5
4
V
7
6
This dc supply will be connected to the internal power bus.
Terminal Description Notes
0 No connection Reserved
1 No connection
2 Chassis Ground
3 Chassis Ground
4 Common
5 Common
6 Voltage Input Apply 12/24V dc. Connects to
7 Voltage Input
the internal power bus.
Proceed as follows. Make all connections to the removable terminal block (RTB).
Publication 1734-UM005B-EN-P - June 2001
1. Connect chassis ground to terminal 2.
2. Connect 12/24V supply positive lead to terminal 6.
3. Connect 12/24V negative lead to terminal 4.
External power applied across terminal 6 (+) and 5 (-) connects to the internal power bus. Do not connect anything to terminals 0 and 1. These are reserved terminals.
4. Connect the PROFIBUS connector plug to the D-shell on the
adapter. Tighten the screws to secure.
PROFIBUS Connection Plug Wiring
T
PROFIBUS connection
Pin 6 - +5V
Pin 8 - RX/TX Data -
Pin 3 - RX/TX Data + Pin 4 - Request to send (R Pin 5 - Data Ground
Pin Number Name Description
Housing Shield Connected to Chassis Ground
1 Not connected
2 Not connected
3 RX/TX Data + Positive RX/TX data line
4 RTS Request to send
5 Data Ground Isolated ground
6 +5V BUS Isolated +5V from RS485 side
7 Not connected
8 RX/TX Data - Negative RX/TX data line
9 Not connected
Installing the PROFIBUS Adapter 2-9
Chapter Summary and
What’s Next
In this chapter, you learned how to install and wire your adapter. Move to chapter 3 for information on configuring the POINT I/O system.
Publication 1734-UM005B-EN-P - June 2001
2-10 Installing the PROFIBUS Adapter
Publication 1734-UM005B-EN-P - June 2001

Configuring the POINT I/O System

Chapter
3

In This Chapter

Configuration Overview

This chapter describes how to configure your adapter for PROFIBUS communication and how to configure the POINT I/O modules.
For more information about: See page
Configuration Overview 3-1
Installing the GSD File 3-2
Adding the Master to the Network 3-3
Adding the Adapter to the Network 3-5
Adding I/O Modules to the Adapter 3-6
Configuring I/O Modules 3-8
Download to Master System 3-13
Chapter Summary and What’s Next 3-14
Since the POINT I/O adapter is compatible with any master system, you can use any configuration tool available on the market. Just import the GSD file included on the diskette you received with your shipment of the adapter into your configuration tool. The configuration tool uses the GSD file to help you set up the system. The file is in raw ASCII format and you can view it with any text editor.
Throughout this chapter, we use the Sycon configuration software from HMS Industrial Networks as an example of how to configure the adapter. For information on how to configure your system, refer to the documentation associated with your master and configuration tool.
You must follow these steps during configuration:

1. Install the GSD file

2. Add the adapter to your PROFIBUS network

3. Add I/O modules to the adapter

4. Configure the modules

5. Download to master system

1 Publication 1734-UM005B-EN-P - June 2001
3-2 Configuring the POINT I/O System

Installing the GSD File

1. Open
the file.
Select the GSD file (173404EF.GSD) included on the diskette you received with your shipment of the adapter.
This dialog indicates that the GSD file was successfully imported into the configuration tool.
(Click “Okay” to continue.)
Publication 1734-UM005B-EN-P - June 2001
Adding the Master to the
.
Network
Select the “Master” entry in the “Insert” menu.
Configuring the POINT I/O System 3-3
1. Select “PROFIBUS-DP
Master” in the list called “Available Masters.”

2. Click “Add>>”.

The master appears on the network.
Select station address here
Type a description here.
Publication 1734-UM005B-EN-P - June 2001
3-4 Configuring the POINT I/O System
Select the master icon
Select the “Bus Parameters” entry in the “Settings” menu.
lSelect the required baud rate from the list.
(Click “OK” to continue.)
Publication 1734-UM005B-EN-P - June 2001

Adding the Adapter to the Network

Select the “Slave” entry in the “Insert” menu.
Configuring the POINT I/O System 3-5
1. Select “1734-APB” in
the “Available Slaves” list.

2. Click “Add>>”.

(Click “OK” to continue.)
The slave appears on the network.
Select station address here.
Type a description here.
Publication 1734-UM005B-EN-P - June 2001
3-6 Configuring the POINT I/O System

Adding I/O Modules to the Adapter

After you add the adapter, you must add the POINT I/O modules connected to the adapter in the backplane.
You can select any of 5 different types:

1. Modules with Configuration Data

If you select modules with configuration data (i.e. 1734-IB2), the configuration data would be available for you to manually
modify. Refer to “Configuring I/O Modules” later in this chapter.

2. Modules without Configuration Data

If you select modules without configuration data (i.e.1734-IB2/ No config data), you will not be able to change the configuration data. This data would be set to a default setting. However, you can still disable the diagnostic functionality for the module.

3. Empty Slot Modules

If you have a gap in the backplane, you should use an empty slot module (i.e. 1734-IB2/Empty slot). The empty slot module reserves memory space in your master for addition of a module at a later date.

4. Grouped Modules

In order to use memory more efficiently, modules can be grouped together in a single byte. The modules must be inserted next to each other and be of the same module family. Each module will have the same configuration as the first module in the group. Eight channels (1 byte) is the maximum allowed. Refer to chapters 4 and 5 for “Grouped Mode” information.
When configured for grouped mode, you can save user parameter data and I/O data.

5. Grouped Empty Slot Modules

If you have a gap in the backplane where the missing modules belong to a group, use a grouped empty slot module. Refer to chapter 4 for more information.
NOTE: In the following example, only modules with configuration data are used.
The modules you select are transferred to the adapter with the PROFIBUS Check_Config service. For a detailed description of the Check_Config service, refer to Chapter 4.
Publication 1734-UM005B-EN-P - June 2001
Double click on the slave icon to add modules to your adapter.
Configuring the POINT I/O System 3-7
To add modules, double-click on the slave icon.
1. Double click on the
module you wish to add.
2. The module appears in
the list below.
Publication 1734-UM005B-EN-P - June 2001
3-8 Configuring the POINT I/O System

Configuring I/O Modules

Most I/O modules have configuration data associated with them. This configuration data can be set manually. For a detailed description of the configuration data supported for different modules, refer to Appendix B.
The configuration you select is transferred to the adapter with the PROFIBUS Set_parameter service. (Set_parameter service is described in chapter 4.)
Note: Download of new configuration data is only possible in the offline mode.
Note: If you added modules without configuration data, the only parameter you can edit is Extended diagnostics. All other parameters retain their default settings. (Refer to Appendix B for default settings.)
To configure I/O modules, click on the Parameter Data button in the Slave Configuration window.
Click on the “Parameter Data” button to open the Parameter Data window.
Publication 1734-UM005B-EN-P - June 2001
Parameter Data in hexadecimal.
Select the module you wish to configure.
(Click “OK” to continue.)
Configuring the POINT I/O System 3-9
To configure a module, click
on the “Module” button.
Module Parameters
Select the value you wish to
use, and click “OK.”
From the list, select the parameter you wish to change.
(Click “OK” to continue.)
Example: To change the
“Range” parameter, select “Range” in the list and click “OK.”
Available parameters are module dependant. However, some parameters are common for all module types. These parameters are: Extended Diagnostics, Fault Action and Idle Action.
Publication 1734-UM005B-EN-P - June 2001
3-10 Configuring the POINT I/O System
Module parameters

Enable/Disable Diagnostic Functionality for your Modules

The diagnostic functionality is enabled at default, but may be turned off (disabled) at the module level. When the diagnostic is disabled, the module will not report any diagnostic information to the adapter. Refer to chapter 4 for more information on module diagnostics.
Select the “Extended Diagnostics” parameter.
(Click on “OK” to continue.)
Select “Enable” to enable and “Disable” to disable the diagnostic functionality of an I/O module. (Click on “OK” to continue.)
Module parameters

Configure Fault Action/Value for your Output Modules

When communication between master and adapter is lost, the adapter puts all connected I/O modules in their Fault state.
Select the “Fault Action” parameter.
(Click on “OK” to continue.)
Select the desired state. Possible settings are “Fault Value,” and “Hold Last State (HLS). (Click on “OK” to continue.)
Publication 1734-UM005B-EN-P - June 2001
Module parameters
Configuring the POINT I/O System 3-11
If you select “Hold Last State,” the module outputs are frozen in their current state. If you select “Fault Value,” you need to define the Fault Value parameter. Possible settings are: digital modules - ON/OFF; analog modules - any value within a predefined range.
Select the “Fault Value” parameter.
(Click on “OK” to continue.)
Enter the value you wish to use.
(Click on “OK” to continue.)
Module parameters

Configure Idle Action Value for your Output Modules

When the adapter receives a clear command from the master, the adapter puts all connected I/O modules into their Idle state.
Select the “Idle Value” parameter.
(Click on “OK” to continue.)
Select the desired state. Possible settings are “Idle Value,” and “Hold Last State (HLS). (Click on “OK” to continue.)
Publication 1734-UM005B-EN-P - June 2001
3-12 Configuring the POINT I/O System
Module parameters
If you select “Hold Last State,” the module outputs are frozen in their current state if power to the module is lost. If you select “Idle Value,” you need to define the Idle Value parameter. Possible settings are: digital modules - ON/OFF; analog modules - any value within a predefined range.
Select the “Idle Value” parameter.
(Click on “OK” to continue.)
Enter the value you wish to use.
(Click on “OK” to continue.)
Publication 1734-UM005B-EN-P - June 2001
Configuring the POINT I/O System 3-13

Download to Master System

Select the “Download” entry in the “Online” menu.
Select the “CIF Serial Driver.”
(Click “OK” to continue.)
When you are finished setting parameters, you must download the configuration data into the master
Select port “COM 2.
(Click “OK” to continue.)
If the download is done during bus operation, the communication between master and slave is stopped. Confirm the download by clicking “Yes.”
Downloading...
Publication 1734-UM005B-EN-P - June 2001
3-14 Configuring the POINT I/O System
Chapter Summary and
What’s Next
In this chapter, you learned how to configure the POINT I/O system. Go to chapter 4 for information about communication and I/O table mapping.
Publication 1734-UM005B-EN-P - June 2001
Chapter

Communication and I/O Table Mapping

This chapter describes the communication process and I/O image table mapping as they occur through the 1734-APB adapter.
For more information about: See page:
Image Table Mapping 4-1
How Data Communication Takes Place 4-2
Grouping Modules for Memory Management 4-16
Chapter Summary and What’s Next 4-16
4

Image Table Mapping

The adapter must map the data it receives to its internal memory before passing it to the appropriate module. The image table map for a module is divided into:
Read bytes - input and status bytes
Write bytes - output and configuration bytes
The length of each module’s read bytes and write bytes vary in size depending on module complexity. The following illustration shows how the adapter maps information. Refer to appendix B for the data maps of the different POINT I/O modules.
1 Publication 1734-UM005B-EN-P - June 2001
4-2 Communication and I/O Table Mapping

How Data Communication Takes Place

Publication 1734-UM005B-EN-P - June 2001
Before any data transfer can take place, the adapter has to verify and accept the PROFIBUS services Set_Parameter and Check_Configuration that are sent from the master at startup. If the adapter accepts these services, data transmission is executed automatically in a cyclic manner with the Data_Exchange service. In addition to these 3 services, the adapter may notify the master of its current status by means of the Slave_Diagnostic service.
The master can read the actual configuration with the Get_Configuration service and send control commands to the adapter by means of the Global_Command service.
Communication and I/O Table Mapping 4-3
This section describes how the adapter handles the following services:
Set_Parameter
Check_Configuration
Get_Configuration
Data_Exchange
Global_Command
Slave_Diagnostic

Set_Parameter

The master uses this service to identify itself with the adapter and to specify how the adapter is to operate. Set_parameter data is comprised of a series of octets (maximum of 244). Octet 0-6 is defined in the DIN 19245-3 standard, while octet 7-243 contain specific information for the adapter itself (referred to as User Parameter Data). The module configuration you previously selected is passed on to the adapter and I/O modules via the User Parameter data.
Octet Value Description
0 - Station Status (see DIN 19245-3)
1 1-255 Watchdog Factor 1
2 1-255 Watchdog Factor 2
3 0-255 Minimum Station Delay (TSDR)
4 4 Vendor (High byte)
5 239 Vendor (Low byte)
6 - Group Identification (see DIN 19245-3)
7-243 See below User Parameter Data

User Parameter Data

Octet 7 in the parameter data is reserved for the Profibus-DP ASIC onboard and must equal 00h.
Beginning at octet 8, each configured module allocates a minimum of three bytes of user parameter data as shown in the following table.
The first two bytes define the product code for the installed module, the third byte defines the control byte followed by configuration data (if used).
Publication 1734-UM005B-EN-P - June 2001
4-4 Communication and I/O Table Mapping
Octet Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
7 Reserved
8 Product Code High Byte of First Module
9 Product Code Low Byte of First Module
10 Control Byte for First Module
11 Configuration Data for First Module*
... ...
X Product Code High Byte for last Module
X + 1 Product Code Low Byte for last Module
X + 2 Control Byte for Last Module
X + 3 Configuration Data for Last Module*
* Present only if selected module has configuration data. Refer to “Adding I/O Modules to your Configuration.”
Product Code
The product code is used to determine the identity of the module installed in each slot. The code is defined in the GSD file and is automatically extracted by the configuration tool when you add the modules to your configuration. (Refer to appendix B for module product codes.) If an installed module does not match the product code for that slot, the slot is considered faulty and the adapter will respond to the Set_Parameter service with a negative acknowledgement. This will cause the master to set the Parameter fault bit in the Slave_Diagnostic service.
Note: Data exchange is not possible if the product code and installed module do not match.
Control Byte
The control byte is used to determine how the module should operate. The control byte is included in the GSD file.
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Diagnostic ON/OFF
Module Type
Configuration data size (bytes); or number of bits allocated to the opened byte (in bit-stuffing)
Publication 1734-UM005B-EN-P - June 2001
Bit 7 - This bit is used to enable/disable the diagnostic function for the module.
Bit Value Description
0 Disable diagnostics
1 Enable diagnostics
Communication and I/O Table Mapping 4-5
Bit 6 - This bit is used to enable/disable the module grouping feature for the module.
Bit Value Description
0 Grouped module disabled
1 Grouped module enabled
Bit 0-5 - Without grouped modules - Defines the number of configuration data bytes for the module. With grouped modules - Defines the number of bits the module should allocate in the opened byte.
Configuration Data
Configuration data is passed on to each I/O module using User Parameter Data. The data is module dependant (see Appendix B).
IMPORTANT
Using your PROFIBUS configuration tool, it is possible to select modules with no configuration data. If you use this type of module, the configuration data for that module will be a default value. (See Appendix B.)
The following table is an example of how User Parameter Data might look with a 1734-OB2E in slot 1, 1734-IB4 in slot 2, and 1734-OE2C in slot 3. All modules in this example use Configuration Data.
Octet Value Description
700hReserved
8 00h 1734-OB2E Product Code High Byte
9 85h 1734-OB2E Product Code Low Byte
10 81h 1734-OB2E Control Byte
11 10h 1734-OB2E Configuration Data
12 00h 1734-IB4 Product Code High Byte
13 82h 1734-IB4 Product Code Low Byte
14 81h 1734-IB4 Control Byte
15 00h 1734-IB4 Configuration Data
16 00h 1734-OE2C Product Code High Byte
17 19h 1734-OE2C Product Code Low Byte
18 C9h 1734-OE2C Control Byte
19 03h 1734-OE2C Configuration Data byte 1
20 06h 1734-OE2C Configuration Data byte 2
Publication 1734-UM005B-EN-P - June 2001
4-6 Communication and I/O Table Mapping
Octet Value Description
21 66h 1734-OE2C Configuration Data byte 3
22 1Fh 1734-OE2C Configuration Data byte 4
23 FFh 1734-OE2C Configuration Data byte 5
24 00h 1734-OE2C Configuration Data byte 6
25 00h 1734-OE2C Configuration Data byte 7
26 00h 1734-OE2C Configuration Data byte 8
27 00h 1734-OE2C Configuration Data byte 9
Check_Configuration
After the set_parameter service, the master sends a check_configuration service to the adapter. This service causes the adapter to check its default configuration (determined at powerup), against the actual configuration specified in the master configuration. If the actual configuration does not match the default configuration, the master will respond to the Check_configuration service with a negative acknowledgement, which causes the master to set the Configuration fault bit in the Slave_diagnostic service.
Note: Data exchange is not possible as long as the actual configuration does not match the default configuration.
The POINT I/O PROFIBUS adapter is a modular slave, which means that the size of the I/O block is flexible and not tied to a specific block length. Each I/O module is represented by an identifier byte. This byte defines the input- and/or output data length as well as the data consistency of the I/O data.
The identifier bytes for all POINT I/O modules are contained in the GSD file and are automatically extracted by the configuration tool when you add the modules to your configuration.
The identifier byte is described below. More information is contained in the PROFIBUS-DP standard (DIN 19245-3).
Bit 7
0 = Consistency of byte/word 1 = Consistency of entire length
0 = Byte 1 = Word
Bit 0
Length of Data 0 = 1 byte/word 15 = 16 bytes/words
Input/Output 00 = Special Format 01 = Input 10 = Output 11 = Input and Output
Publication 1734-UM005B-EN-P - June 2001
Communication and I/O Table Mapping 4-7

Without Grouped Modules

The table below shows an example of how the identifier bytes would look for a configuration with a 1734-OB2E in slot 1; a 1734-IE2C in slot 2; a 1734-OE2C in slot 3; and a 1734-IA2 in slot 4.
Identifier Byte Value Description
0 20h 1734-OB2E; 1 byte out, consistency over byte
1 51h 1734-IB4; 1 byte in, consistency over byte
2 61h 1734-OE2C; 2 words out, consistency over word
3 10h 1734-IA2, 2 byte in, consistency over byte

With Grouped Modules

If using grouped modules, the following table shows an example of how the identifier bytes would look for a configuration with four 1734-OB2E modules.
Slot Number
1 1734-OB2E Byte 1 = 0x20; 1
2 1734-OB2E/grouped Byte 2 = 0x00; 0
3 1734-OB2E/grouped Byte 3 = 0x00; 0
4 1734-OB2E/grouped Byte 4 = 0x00; 0
Description Identifier Byte
Buffer
byte output
bytes of I/O data
bytes of I/O data
bytes of I/O data
User Parameter Data Buffer
Byte 1 = 0x00; product code (high byte) Byte 2 = 0x85; product code (low byte) Byte 3 = 0x81; control byte (diagnostics enabled, no bit stuffing, 1 byte of configuration data follows) Byte 4 = 0x10; configuration data
Byte 5 = 0x00; product code (high byte) Byte 6 = 0x85; product code (low byte) Byte 7 = 0xC2; control byte (diagnostics enabled, bit stuffing module, 2 bits (channels) to store in the opened byte.
Byte 8 = 0x00; product code (high byte) Byte 9 = 0x85; product code (low byte) Byte 10 = 0xC2; control byte (diagnostics enabled, bit stuffing module, 2 bits (channels) to store in the opened byte.
Byte 11 = 0x00; product code (high byte) Byte 12 = 0x85; product code (low byte) Byte 13 = 0xC2; control byte (diagnostics enabled, bit stuffing module, 2 bits (channels) to store in the opened byte.
Publication 1734-UM005B-EN-P - June 2001
4-8 Communication and I/O Table Mapping
Get_Configuration
This service permits the master to read out the Identifier bytes for the actual adapter configuration. (Refer to the previous section for the format of the identifier byte.)
The table below shows an example of how the identifier bytes from a Get_configuration response would look like when you have the following modules in the backplane: slot 1 = 1734-OB4E; slot 2 = 1734-IE2C; slot 3 = 1734-OE2C; and slot 4 = 1734-IA2.
Identifier Byte Value Description
0 20h 1734-OB4E; 1 byte out, consistency over byte
1 51h 1734-IE2C; 2 words in, consistency over word
2 61h 1734-OE2C; 2 words out, consistency over word
3 10h 1734-IA2; 1 byte in, consistency over byte
Global_Command
Sync/Freeze
In addition to the cyclic data exchange, which is executed automatically by the master, the master can send control commands to a single slave, a group of slaves or all slaves simultaneously. These control commands are transmitted as multicast commands and permit use of sync and freeze modes for event-controlled synchronization of the slaves.
The POINT I/O adapter begins sync mode when it receives a sync command from the assigned master. The output channels of all I/O modules are then frozen in their current state. During subsequent user data transmissions, the output data are stored at the adapter, but the output states remain unchanged. The stored output data is not sent to the outputs until the sync command is receivied. Sync mode is concluded with the unsync command.
Similarly, a freeze control command causes the adapter to assume freeze mode. In this operating mode, the states of the input channels of all I/O modules are frozen at the current value. Input data is not updated again until the master sends the next freeze command. Freeze is concluded with the unfreeze command.
Publication 1734-UM005B-EN-P - June 2001
Communication and I/O Table Mapping 4-9
Operating States
The general system behavior is determined by the operating status of the master. The 3 main states are:
Stop - No data transmission occurs between the master and the
slaves.
Operate - The master is in the data transfer phase. In cyclic data
communication , inputs of the slaves are read, and output information is written to the slaves.
Clear - The master reads the information of the slaves and sets
the outputs to an idle state. (Refer to “Configure Idle Action Value for Your Output Modules,” page 3-11.)
Data_Exchange
After correct set_parameter and check_configuration services, the master automatically starts exchanging data with the adapter by means of the data_exchange service.
Slave_Diag
The adapter may notify the master of its current state by means of the slave_diag service. The information received from this service request can be divided into 3 parts:
Standard diagnostic information according to the PROFIBUS
standard DIN 19245-3
Module related diagnostics indicates which I/O module has
diagnostic events pending.
Channel related diagnostics, give more detailed information of
the actual cause of the event (wire-break, overcurrent, etc.).
Publication 1734-UM005B-EN-P - June 2001
4-10 Communication and I/O Table Mapping
Structure of Slave_Diagnosis
Octet Description
0 Station Status 1
1 Station Status 2
2 Station Status 3
3 Master PROFIBUS address
4 Identifier number (high byte)
5 Identifier number (low byte)
6 Module-related header byte
7-14 Module-related diagnostic block
15-17 1st channel-related diagnostic message
18-20 2nd channel-related diagnostic message
..
..
42-44 10th channel-related diagnostic message
IMPORTANT
The length of the diagnostic frame varies between 15 and 45 bytes since the length of the channel-related part is dynamic in its structure.
Publication 1734-UM005B-EN-P - June 2001
Communication and I/O Table Mapping 4-11
Station Status 1, 2 and 3
Station status 1, 2 and 3 provide an overview of the status of the slave.
Station Status 1
Bit Description Cause
0 - Station nonexistent The master cannot be
addressed by the master
Correct node address set on the
Bus connector connected?
Bus cable pin configuration
Power to the slave switched on?
Is the RS485 repeater set
adapter?
correct (Pin 3 to 3 and pin 8 to 8)?
correctly?
1 - Station not ready Adapter not yet ready for
data exchange
2 - Configuration fault Configuration data sent by
the master to the adapter does not match the backplane configuration.
3 - Extended diagnostic Diagnostics available for the
master
4 - Function not supported The requested function is
not supported by the module
5 - Invalid slave response The master has received an
invalid response
6 - Parameter fault Parameters sent by the
master are containing wrong or insufficient data.
7 - Master lock The adapter has already
been parameterized by another master and is locked in its access.
Wait for the adapter to start up.
Do the modules installed in the backplane match the modules entered in the master configuration?
Evaluate the module-related and/or channel-related diagnostics. This bit is cleared (0) when there are no diagnostic messages available.
Trying to set PROFIBUS address over the network?
Check the bus setup.
Do the modules installed in the backplane match the modules entered in the master configuration?
Check if another master is present on the network, and delete its assignments to the adapter or remove the other assigned master from the network to get the communication with the adapter run.
Publication 1734-UM005B-EN-P - June 2001
4-12 Communication and I/O Table Mapping
Bit Description Cause
Station Status 2
0 - Parameterization requested
1 - Static diagnostic The adapter cannot provide
2 - Not used Always set to 1.
3 - Watchdog on Watchdog control is the
4 - Freeze mode The adapter has received a
5 - Sync mode The adapter has received a
6 - Reserved Always set to 0.
7 - Slave deactivated The adapter has been
The slave has forced the master system to do a new parameterization.
valid I/O data.
adapter is active to supervise its corresponding master connection.
freeze command.
sync command.
marked inactive in its parameter set and has been removed from cyclic I/O processing.
This bit is set as long as new parameterization must be performed.
The backplane bus communication is terminated. This bit will not be cleared (0) until the power to the adapter is cycled.
Check bus settings in the configuration tool.
Station Status 3
Bit Description Cause
0 to 6 - Not used These bits are always 0.
7 - Diagnostic overflow There are more diagnostic
messages than the adapter can store.
More than 10 channel-related messages present at the same time. Note: New messages are queued in the adapter and are passed on to the master as soon as ther is space in the diagnostic buffer.
Publication 1734-UM005B-EN-P - June 2001
Communication and I/O Table Mapping 4-13
Master PROFIBUS Address
In this octet (byte 3), the address of the master that has done the parameterization of the adapter is entered. If the adapter is not parameterized from any master, the adapter writes the address 255 (decimal) here.
Identity Number
The identity number (byte 4-5) is a unique code that describes the type of DP-slave. The identity number for the 1734-APB adapter is 04EF (hexidecimal).
Module-related Diagnostics
The module-related diagnostics indicates if any of the connected I/O modules reports errors. More detailed information of the error can be found by further evaluation of the channel-related diagnostic message.
Bit Value Module Status
0 Module is OK
1 Module reports error
Octet Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
601001001
...
7 Module 8 Module 7 Module 6 Module 5 Module 4 Module 3 Module 2 Module 1
8 Module 16 Module 15 Module 14 Module 13 Module 12 Module 11 Module 10 Module 9
9 Module 24 Module 23 Module 22 Module 21 Module 20 Module 19 Module 18 Module 17
10 Module 32 Module 31 Module 30 Module 29 Module 28 Module 27 Module 26 Module 25
11 Module 40 Module 39 Module 38 Module 37 Module 36 Module 35 Module34 Module 33
12 Module 48 Module 47 Module 46 Module 46 Module 44 Module 43 Module 42 Module 41
13 Module 56 Module 55 Module 54 Module 53 Module 52 Module 51 Module 50 Module 49
14 Not used Module 63 Module 62 Module 61 Module 60 Module 59 Module 58 Module 57
Channel Related Diagnostics
These diagnostics give information on channel errors of the I/O modules and expand on the module related diagnostics. The message entry length is 3 bytes.
Publication 1734-UM005B-EN-P - June 2001
4-14 Communication and I/O Table Mapping
Byte 15 1 0 Slot number of the module that reports diagnostics (1-63)
A maximum of 10 channel related diagnostic messages are possible. If you exceed the limit, the diagnostic overflow bit in station status 3 will be set.
Note: If the diagnostic buffer is full and the adapter receives an additional error message, this new message will be queued in the adapter internally and passed on to the master as soon as space is available in the diagnostic buffer (i.e. when older messages are deleted).
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Channel Direction
Byte 16
Byte 17 Channel Type:
Byte 18-20 2nd channel specific message (same assignments as bytes 15-17)
Byte 42-44 10th channel specific message (same assignments as bytes 15-17)
01 - Input 10 - Output 11 - Input/Output
001 = Bit 010 - 2 bits 011 - 4 bits 100 - Byte 101 - Word 110 - Double word
Type of channel that reports diagnostics
Error codes (see Appendix B)
Publication 1734-UM005B-EN-P - June 2001
Select the “Start Debug Mode” entry in the “Online” menu.
Double click on the slave icon.
Communication and I/O Table Mapping 4-15
Viewing Diagnostic Data within the Configuration Tool
Station status 1 - 3
Interpreted view of diagnostic messages
Error details
Complete diagnostic message in hexadecimal.
Station status 1 - 3
1. Select error message
2. A detailed description
appears
(Click on “OK” to exit.)
Publication 1734-UM005B-EN-P - June 2001
4-16 Communication and I/O Table Mapping

Grouping Modules for Memory Management

You can install up to 8 of the same type of module (identical product code) next to each other and use only one word of input or output memory. The module requirements are:
the modules must be next to each other
the modules must be members of the same module family
must total 8 channels or less
the modules will share the same configuration data.
You select the option 4, bit stuffing module, in the hardware catalog in the configuration tool.

1. Select the 1734-OB2E (hardware type 1) from the hardware catalog.

The adapter will open a byte and store the first 1734-OB2E module there.
2. Select the 1734-OB2E (hardware type 4 - grouped) from the hardware catalog.
The adapter will store the second 1734-OB2E in the opened byte.
Chapter Summary and
What’s Next
3. Select the 1734-OB2E (hardware type 4 - grouped) from the hardware catalog.
The adapter will store the third 1734-OB2E in the opened byte.
4. Select the 1734-OB2E (hardware type 4 - grouped) from the hardware catalog.
The adapter will store the fourth 1734-OB2E in the opened byte.
Note that the grouped modules will share the same configuration data as the first module in the group. If the first module has no configuration data, the other three modules will have no configuration data.
In this chapter, you learned about communication and I/O table mapping. Move to chapter 5 for troubleshooting.
Publication 1734-UM005B-EN-P - June 2001

Grouped Mode

Chapter
5

In This Chapter

General

In this chapter, you will learn about:
For more information about: See page:

General 5-1

How to Configure the Adapter for Grouped Mode 5-2

Configuration Example 5-3

Chapter Summary and What’s Next 5-4

In order to use master memory most effectively, and reduce data transfer between the POINT I/O adapter and the master, you can group several modules in a single byte.
To configure the adapter for grouped mode you must:

1. insert modules adjacent to each other

2. Modules must be in the same module family

Groups may exist as follows:
1734-IB2, 1734-IV2, 1734-IM2 and 1734-IA2 can be grouped
together
1734-IB4 and 1734-IV4 can be grouped together
1734-OW2, 1734-OA2 and 1734-OX2 can be grouped together
The following modules cannot be grouped with any other module type:
1734-OB2E can only be grouped with 1734-OB2E modules
1734-OB4E can only be grouped with 1734-OB4E modules

3. A maximum of 8 channels (1 byte) per group

4. Modules in a single byte will have the configuration of the first
module in the group. (Exception: Extended diagnostics can be enabled/disabled on a per module basis.)
1 Publication 1734-UM005B-EN-P - June 2001
5-2 Grouped Mode

How to Configure the Adapter for Grouped Mode

You can select the following modules in the configuration tool:

1. Module without configuration data (e.g. 1734-OB2E/no config)

2. Module with configuration data (e.g. 1734-OB2E/with config)

3. Empty slot module (e.g. 1734-OB2E/empty slot)

4. Grouped module (e.g. 1734-OB2E/grouped)

5. Grouped empty slot module (e.g. 1734-OB2E/grouped empty
slot)
By combining these modules, groups can be created in 3 different ways:

1. A group of modules with configuration data

2. A group of modules without configuration data (default
configuration will be used for all modules in the group)

3. A group of empty slot modules

The following example illustrates how to group modules in a single byte.
1. Select the 1734-OB2E (hardware type 1) from the hardware catalog.
The adapter will open a byte and store the first 1734-OB2E module there.
Bit
Output Byte
2. Select the 1734-OB2E (hardware type 4 - grouped) from the hardware catalog.
The adapter will store the second 1734-OB2E in the opened byte.
Bit
Output Byte
3. Select the 1734-OB2E (hardware type 4 - grouped) from the hardware catalog.
The adapter will store the third 1734-OB2E in the opened byte.
Bit
Output Byte
4. Select the 1734-OB2E (hardware type 4 - grouped) from the hardware catalog.
The adapter will store the fourth 1734-OB2E in the opened byte.
Bit
Output Byte
5
5
5
5
0123467
0123467
0123467
0123467
Publication 1734-UM005B-EN-P - June 2001
If more modules are to be grouped, a new byte has to be opened (repeat steps 1 through 4).
Grouped Mode 5-3
Note that the grouped modules will share the same configuration data as the first module in the group. If the first module has no configuration data, the other modules in the group will have no configuration data.
The configuration for the above example will look like the following in the configuration tool.
Slot

Configuration Example

The following example shows how modules can be grouped together, and how the I/O data is mapped in the PROFIBUS adapter.
12 3 4 5 6 7 8 91011121314
PROFIBUS Adapter
1734-OB2E Output Module
1734-OB2E Output Module/Grouped
1734-OB2E Output Module/Grouped
1734-OB2E Output Module/Grouped
1734-IB2 Input Module/Grouped
1734-OB4E/Empty slot
1734-OB4E/Grouped Empty slot
1734-IB2 Input Module
1734-IV2 Input Module/Grouped
1734-IE2C Input Module
1734-OE2C Output Module
1734-IB4 Input Module/No config
1734-IB4 Input Module/Grouped
1734-IB4 Input Module
Publication 1734-UM005B-EN-P - June 2001
5-4 Grouped Mode
Configuration table and memory map
Note the following module groups:
slots 1, 2, 3 and 4 - A group of modules with configuration data
Slots 7, 8 and 9 - A group of modules with configuration data
Slots 5 and 6 - A group of empty slots
Slots 12 and 13 - A group of modules without configuration data
(default configuration data)
In this example, the input/output addresses start at byte 0.
Slot Module

1 1734-OB2E 0.0 to 0.1

2 1734-OB2E/grouped 0.2 to 0.3 Same configuration data as first

3 1734-OB2E/grouped 0.4 to 0.5

4 1734-OB2E/grouped 0.6 to 0.7

5 1734-OB4E/empty slot 1.0 to 1.3

6 1734-OB4E/grouped empty slot 1.4 to 1.7

7 1734-IB2E 0.0 to 0.1

8 1734-IB2E/grouped 0.2 to 0.3 Same configuration data as first

9 1734-IV2E/grouped 0.4 to 0.5

10 1734-OE2C 2 to 5

11 1734-IE2C 1 to 4

12 1734-IB4/no configuration 5.0 to 5.3 Default configuration data

13 1734-IB4/grouped 5.4 to 5.7

14 1734-IB4 6.0 to 6.3

I/O Address
Notes
Input Output
module in group (slot 1).
module in group (slot 7).
Chapter Summary and
What’s Next
Publication 1734-UM005B-EN-P - June 2001
In this chapter, you learned how to group modules for reduced memory space. Move to chapter 6 for information on troubleshooting your adapter.
Chapter

Troubleshooting the PROFIBUS Adapter

6

In This Chapter

Using the Status Indicators

In this chapter, you will learn about:
For more information about: See page:
Using the Status Indicators 6-1
Using PROFIBUS Diagnostics 6-3
Chapter Summary and What’s Next 6-3
You can use the status indicators to troubleshoot your adapter. These indicators consist of:
Adapter
System Power
Field Power
Status
PROFIBUS Status
PointBus Status
1734-APB
Adapter Status
PROFIBUS Status
PointBus Status
System Power
Field Power
1734apbfrt
Use the following table to troubleshoot your adapter.
1 Publication 1734-UM005B-EN-P - June 2001
6-2 Troubleshooting the PROFIBUS Adapter

Indicator Indication Probable Cause

System Power Off Not active.
Field power is off; or dc-dc converter problem.
Green System power on.
Dc-dc converter active (5V).
Field Power Off Not active.
Field power not applied.
Green Power on, 24V present.
Adapter Status Off No power supplied.
Hardware check in progress. Initialization in progress.
Green Adapter operating normally
Red Hardware check fault.
PROFIBUS Status Off No power supplied.
Adapter is off-line (no data exchange with the PROFIBUS master).
Green Adapter is online (data exchange with the PROFIBUS
master).
Flashing Green Adapter is in CLEAR mode and has set the connected
I/O modules into an idle state.
Red No POINT I/O modules installed in the backplane.
Flashing Red Set_Parameter telegram rejected.
Maximum number of user parameter bytes overridden.
PointBus Status Off No power applied to adapter
PointBus initialization in progress.
Green Normal operation.
Flashing Red Incorrect POINT I/O module installed or
POINT I/O module removed from backplane.
Red Critical link failure. Adapter detected error that
prevents its communication on the PointBus.
Publication 1734-UM005B-EN-P - June 2001
Troubleshooting the PROFIBUS Adapter 6-3

Using PROFIBUS Diagnostics

PROFIBUS diagnostics provides detailed information about the adapter and the I/O modules. (Refer to Slave_Diag in chapter 4 for detailed information about diagnostic capabilities of the adapter.)
Pay special attention to the following indications in the diagnostic response.
Station Bit Response Reason
Station Status 1 0 Station nonexistent Wrong node address.
Bus cable problem. Incorrect pin configuration.
2 Configuration fault Wrong module installed.
Identifier bytes for one or more modules does not match master configuration identifier bytes.
3 Extended diagnostic One or more modules report errors.
(To find out reasons for the error indication, evaluate the module and channel related diagnostic.)
6 Parameter fault Wrong module installed.
Product code for one or more modules does not match master configuration product code.
Chapter Summary and
What’s Next
Station Status 2 1 Static diagnostic PointBus communication
terminated. Adapter cannot provide valid data.
Station Status 3 7 Diagnostic overflow More than 10 channel related
messages present at the same time.
In this chapter, you learned how to troubleshoot your adapter. Move to Appendix A for adapter specifications.
Publication 1734-UM005B-EN-P - June 2001
6-4 Troubleshooting the PROFIBUS Adapter
Publication 1734-UM005B-EN-P - June 2001
Appendix

Specifications

Specifications - 1734-APB PROFIBUS Adapter Module Communication Interface Specifications
Expansion I/O Capacity Up to 13 modules (13 times 75mA = 0.975, just under the limit
of 1.0A). The actual number of modules can vary. Add up the current requirements of the modules you want to use to make sure they do not exceed the amperage limit of the 1734-ADN. (Note: Total expansion up to 63 modules - 13 modules maximum with 1734-APB - add 1734-EP24DC modules for an additional 17 modules (or less based on current requirements), up to 63 module maximum)
Cat. No. PointBus Current Requirements
1734-IB2 75mA 1734-IB4 75mA 1734-IV2 75mA 1734-IV4 75mA 1734-OB2E 75mA 1734-OB4E 75mA 1734-OW2 80mA 1734-IE2C 75mA 1734-OE2C 75mA 1734-IE2V 75mA 1734-OE2V 75mA 1734-IA2 75mA 1734-IM2 75mA 1734-OA2 75mA 1734-IJ2 160mA 1734-IK2 160mA 1734-IR2 220mA 1734-IT2 175mA 1734-VHSC5 180mA 1734-VHSC24 180mA
Module Location Starter module - left side of 1734 system
Power Supply Specifications
Power Supply Note: In order to comply with CE Low Voltage Directives (LVD),
you must use either a NEC Class 2, a Safety Extra Low Voltage (SELV) or a Protected Extra Low Voltage (PELV) power supply to power this adapter.A SELV supply cannot exceed 30V rms, 42.4V peak or 60V dc under normal conditions and under single fault conditions. A PELV supply has the same rating and is connected to protected earth.
A
Input Voltage Rating 24V dc nominal
Field Side Power Requirements 24V dc (+20% = 28.8V dc maximum) @ 400mA maximum Inrush Current 6A maximum for 10ms PointBus Output Current 1A maximum @ 5V dc ±5% (4.75 - 5.25)
Input Overvoltage Protection Reverse polarity protected Interruption Output voltage will stay within specifications when input drops
Specifications continued on next page.
1 Publication 1734-UM005B-EN-P - June 2001
10-28.8V dc range
out for 10ms at 10V with maximum load.
A-2 Specifications

General Specifications

Indicators 3 red/green status indicators
Adapter status PROFIBUS status PointBus status 2 green power supply status indicators: System Power (PointBus 5V power)
Field Power (24V from field supply) Power Consumption 8.1W maximum @ 28.8V dc Power Dissipation 2.8W maximum @ 28.8V Thermal Dissipation 9.5 BTU/hr maximum @ 28.8V dc Isolation Voltage 1250V rms/V ac Field Power Bus
Nominal Voltage Supply Voltage Range Supply Current
Dimensions Inches
(Millimeters)
Environmental Conditions
Operational Temperature Storage Temperature Relative Humidity Shock Operating
Non-operating
Vibration
Conductors Wire Size
24V dc
10-28.8V dc range,
10A maximum
3.0H x 2.16W x 5.25L
(76.2H x 54.9W x 133.4L)
o
-10 to 55
-40 to 85
C (14 to 131°F)
o
C (-40 to 185°F) 5 to 95% noncondensing 30g peak acceleration, 11(±1)ms pulse width 50g peak acceleration, 11(±1)ms pulse width Tested 5g @ 10-500Hz per IEC 68-2-6
2
14 AWG (2.5mm
) - 22 AWG (0.25mm2) solid or stranded copper
wire rated @ 75°C or higher
Category
3/64 inch (1.2mm) insulation maximum
1
2
Terminal Base Screw Torque 7 pound-inches (0.6Nm) Field Wiring Terminations
PROFIBUS 1 - Not connected 6 - +5V Bus
2 - Not connected 7 - Not connected 3 - +RTX/TX data line 8 - Negative RTX/TX 4 - Request to send 9 - Not connected 5 - Ground Bus Housing - Earth ground
Power Supply 0 - No Connection 1 - No Connection
2 - Chassis Ground 3 - Chassis Ground 4 - Common 5 - Common 6 - Supply 7 - Supply
Mass 9.0 oz/255 grams Agency Certification (when
product is marked) 1
Use this conductor category information for planning conductor routing as described in publication 1770-4.1, “Industrial Automation Wiring and Grounding Guidelines.”
CE marked for all applicable directives C-Tick marked for all applicable acts
Publication 1734-UM005B-EN-P - June 2001
Appendix
B

Default Data Maps

I/O messages are sent to (consumed) and received from (produced) the POINT I/O modules. These messages are mapped into the
processor’s memory. This appendix lists the default maps for 1734 POINT I/O modules.
For more information: See page:
1734-IB2 Sink Input Module B-2
1734-IB4 Sink Input Module B-3
1734-IV2 Source Input Module B-4
1734-IV4 Source Input Module B-5
1734-OB2E Electronically Protected Output Module B-6
1734-OB4E Electronically Protected Output Module B-7
1734-OW2 Relay Sink/Source Output Module B-8
1734-IE2C Analog Current Input Module B-9
1734-OE2C Analog Current Output Module B-11
1734-IE2V Analog Voltage Input Module B-12
1734-OE2V Analog Voltage Output Module B-14
1734-IA2 120V ac Input Module B-15
1734-IM2 220V ac Input Module B-16
1734-OA2 120/220V ac Output Module B-17
1 Publication 1734-UM005B-EN-P - June 2001
B-2 Default Data Maps

1734-IB2 Sink Input Module

Product Code: 0081h

Data Map:

Output size: 0 bytes; Input size: 1 byte
Produces (Rx) Not used CH1
Consumes (Tx) No consumed data
7654321 0
state
Where: CH0 = input channel 0, CH1 = input channel 1; 0 = OFF, 1 = ON

Configuration Data:

7654321 0
Reserved Filter
Meaning of bits described below
CH0
state
Filter Values
Value Definition
00 1ms
01 0.33ms
10 3ms
11 10ms
Default: H00 (1ms)

Diagnostic Data

Possible Error Codes:
Error Code Error Type
16 Module incorrect or missing. Reported on channel 0 and applies to
whole module.
Publication 1734-UM005B-EN-P - June 2001
Default Data Maps B-3

1734-IB4 Sink Input Module

Product Code: 0082h

Data Map:

Output size: 0 bytes; Input size: 1 byte
Produces (Rx) Not used CH3
Consumes (Tx) No consumed data
7654321 0
CH2
state
Where: CH0 = input channel 0, CH1 = input channel 1; 0 = OFF, 1 = ON
state
CH1
state

Configuration Data:

7654321 0
Reserved Filter
Meaning of bits described below
CH0
state
Filter Values
Value Definition
00 1ms
01 0.33ms
10 3ms
11 10ms
Default: H00 (1ms)

Diagnostic Data

Possible Error Codes:
Error Code Error Type
16 Module incorrect or missing. Reported on channel 0 and applies to
whole module.
Publication 1734-UM005B-EN-P - June 2001
B-4 Default Data Maps

1734-IV2 Source Input Module

Product Code: 0083h

Data Map:

Output size: 0 bytes; Input size: 1 byte
Produces (Rx) Not used CH1
Consumes (Tx) No consumed data
7654321 0
state
Where: CH0 = input channel 0, CH1 = input channel 1; 0 = OFF, 1 = ON

Configuration Data:

7654321 0
Reserved Filter
Meaning of bits described below
CH0
state
Filter Values
Value Definition
00 1ms
01 0.33ms
10 3ms
11 10ms
Default: H00 (1ms)

Diagnostic Data

Possible Error Codes:
Error Code Error Type
16 Module incorrect or missing. Reported on channel 0 and applies to
whole module.
Publication 1734-UM005B-EN-P - June 2001
Default Data Maps B-5

1734-IV4 Source Input Module

Product Code: 0084h

Data Map:

Output size: 0 bytes; Input size: 1 byte
Produces (Rx) Not used CH3
Consumes (Tx) No consumed data
7654321 0
CH2
state
Where: CH0, CH1, CH2, CH3 = input channel 1; 0 = OFF, 1 = ON
state
CH1
state

Configuration Data:

7654321 0
Reserved Filter
Meaning of bits described below
CH0
state
Filter Values
Value Definition
00 1ms
01 0.33ms
10 3ms
11 10ms
Default: H00 (1ms)

Diagnostic Data

Possible Error Codes:
Error Code Error Type
16 Module incorrect or missing. Reported on channel 0 and applies to
whole module.
Publication 1734-UM005B-EN-P - June 2001
B-6 Default Data Maps

1734-OB2E Electronically Protected Output Module

Product Code: 0085h

Data Map:

Output size: 1 bytes; Input size: 0 byte
)Produces (Rx) No produced data
Consumes (Tx) Not used CH1
7654321 0
state
Where: CH0 = output channel 0, CH1 = output channel 1; 0 = OFF, 1 = ON

Configuration Data:

7654321 0
Reserved RM NL IV IA FV FA
Meaning of bits described below
FA = Fault Action FV = Fault Value
Value Definition Value Definition
CH0
state
0 Fault Value 0 OFF
1 Hold Last State 1 ON
IA = Idle Action IV = Idle Value
Value Definition Value Definition
0 Idle Value 0 OFF
1 Hold Last State 1 ON
NL = No Load Enble RM = Reset Mode
Value Definition Value Definition
0 Disable 0 Latch
1 Enable 1 Auto Retry
Default: H10 (Default: Fault/Idle value = OFF, No load, Latch)

Diagnostic Data

Possible Error Codes:
Code Error Type
Publication 1734-UM005B-EN-P - June 2001
4 Overload
6 Wire Break
16 Module incorrect or missing. Reported on channel 0, applies to whole module.
Default Data Maps B-7

1734-OB4E Electronically Protected Output Module

Product Code: 0086h

Data Map:

Output size: 1 bytes; Input size: 0 byte
)Produces (Rx) No produced data
Consumes (Tx) Not used CH3
7654321 0
state
Where: CH0, CH1, CH2, CH3; 0 = OFF, 1 = ON
CH2 state
CH1
state

Configuration Data:

7654321 0
Reserved RM NL IV IA FV FA
Meaning of bits described below
FA = Fault Action FV = Fault Value
Value Definition Value Definition
CH0
state
0 Fault Value 0 OFF
1 Hold Last State 1 ON
IA = Idle Action IV = Idle Value
Value Definition Value Definition
0 Idle Value 0 OFF
1 Hold Last State 1 ON
NL = No Load Enble RM = Reset Mode
Value Definition Value Definition
0 Disable 0 Latch
1 Enable 1 Auto Retry
Default: H10 (Default: Fault/Idle value = OFF, No load, Latch)

Diagnostic Data

Possible Error Codes:
Code Error Type
4 Overload
6 Wire Break
16 Module incorrect or missing. Reported on channel 0, applies to whole module.
Publication 1734-UM005B-EN-P - June 2001
B-8 Default Data Maps

1734-OW2 Relay Sink/Source Output Module

Product Code: 0087h

Data Map:

Output size: 1 bytes; Input size: 0 byte
)Produces (Rx) No produced data
Consumes (Tx) Not used CH1
7654321 0
state
Where: CH0 = output channel 0, CH1 = output channel 1; 0 = OFF, 1 = ON

Configuration Data:

7654321 0
Reserved IV IA FV FA
Meaning of bits described below
FA = Fault Action FV = Fault Value
Value Definition Value Definition
CH0
state
0 Fault Value 0 OFF
1 Hold Last State 1 ON
IA = Idle Action IV = Idle Value
Value Definition Value Definition
0 Idle Value 0 OFF
1 Hold Last State 1 ON
Default: H00 (Default: Fault/Idle value = OFF)

Diagnostic Data

Possible Error Codes:
Code Error Type
16 Module incorrect or missing. Reported on channel 0, applies to whole module.
Publication 1734-UM005B-EN-P - June 2001
Default Data Maps B-9

1734-IE2C Analog Current Input Module

Product Code: 0018h

Data Map:

Output size: 0 Words; Input size: 2 Words
Produces (Rx) Input Channel 0
Consumes (Tx) No consumed data
7654321 0
Input Channel 1

Configuration Data:

7 654321 0
Reserved DF AD R Notch Filter NF
Engineering Units Low (high byte) Default value = 06h
Engineering Units Low (low byte) Default value = 66h
Engineering Units High (high byte) Default value = 3Fh
Engineering Units High (low byte) Default value = FFh
Low Alarm Threshold (high byte) Default value = 0Ch
Low Alarm Threshold (low byte) Default value = 29h
High Alarm Threshold (high byte) Default value =40h
High Alarm Threshold (low byte) Default value = A3h
Meaning of bits described below
NF = Notch Filter Values
Value Definition
00 50Hz
01 60Hz (default)
10 250Hz
11 500Hz
AD = Alarm Disable R = Range
Value Definition Value Definition
0 Enable (default) 0 4 to 20mA (default)
1 Disable 1 0 to 20mA
Publication 1734-UM005B-EN-P - June 2001
B-10 Default Data Maps
DF = Definition
Value Definition
000 No filtering (default
001 5ms
010 10ms
011 50ms
100 100ms
101 250ms
110 500ms
111 1s

Diagnostic Data

Possible Error Codes:
Code Error Type
2 Undercurrent
3 Overcurrent
6 Wire Break
7 High Alarm Exceed
8 Low Alarm Exceed
16 Module incorrect or missing. Reported on channel 0, applies to whole module.
Publication 1734-UM005B-EN-P - June 2001
Default Data Maps B-11

1734-OE2C Analog Current Output Module

Product Code: 0019h

Data Map:

Output size: 2 Word; Input size: 0 Word
Produces (Rx) Output Channel 0
Consumes (Tx) No consumed data
7654321 0
Output Channel 1

Configuration Data:

7 654321 0
Reserved AD R IA FA
Engineering Units Low (high byte) Default value = 06h
Engineering Units Low (low byte) Default value = 66h
Engineering Units High (high byte) Default value = 1Fh
Engineering Units High (low byte) Default value = FFh
Fault Value (high byte) Default value = 00
Fault Value (low byte) Default value = 00
Idle Value (high byte) Default value = 00
Idle Value (low byte) Default value = 00
Meaning of bits described below
FA = Fault Action IA = Idle Value
Value Definition Value Definition
0 Hold Last State 0 Hold Last State
1 Fault Value (default) 1 Idle Value (default)
R = Range AD = Alarm Disable
Value Definition Value Definition
0 4 to 20mA (default) 0 Enable (default)
1 0 to 20mA 1 Disable

Diagnostic Data

Possible Error Codes:
Code Error Type
6 Wire Break
16 Module incorrect or missing. Reported on channel 0, applies to whole module.
Publication 1734-UM005B-EN-P - June 2001
B-12 Default Data Maps

1734-IE2V Analog Voltage Input Module

Product Code: 0018h

Data Map:

Output size: 0 Words; Input size: 2 Words
Produces (Rx) Input Channel 0
Consumes (Tx) No consumed data
7654321 0
Input Channel 1

Configuration Data:

7 654321 0
Reserved DF AD R Notch Filter NF
Engineering Units Low (high byte) Default value = 06h
Engineering Units Low (low byte) Default value = 66h
Engineering Units High (high byte) Default value = 3Fh
Engineering Units High (low byte) Default value = FFh
Low Alarm Threshold (high byte) Default value = 0Ch
Low Alarm Threshold (low byte) Default value = 29h
High Alarm Threshold (high byte) Default value =40h
High Alarm Threshold (low byte) Default value = A3h
Meaning of bits described below
NF = Notch Filter Values
Value Definition
00 50Hz
01 60Hz (default)
10 250Hz
11 500Hz
AD = Alarm Disable R = Range
Value Definition Value Definition
0 Enable (default) 0 -10 to +10V (default)
Publication 1734-UM005B-EN-P - June 2001
1 Disable 1 0 to +10V
DF = Definition
Value Definition
000 No filtering (default
001 5ms
010 10ms
011 50ms
100 100ms
101 250ms
110 500ms
111 1s

Diagnostic Data

Default Data Maps B-13
Possible Error Codes:
Code Error Type
2 Undercurrent
3 Overcurrent
6 Wire Break
7 High Alarm Exceed
8 Low Alarm Exceed
16 Module incorrect or missing. Reported on channel 0, applies to whole module.
Publication 1734-UM005B-EN-P - June 2001
B-14 Default Data Maps

1734-OE2V Analog Voltage Output Module

Product Code: 0019h

Data Map:

Output size: 2 Word; Input size: 0 Word
Produces (Rx) Output Channel 0
Consumes (Tx) No consumed data
7654321 0
Output Channel 1

Configuration Data:

7 654321 0
Reserved AD R IA FA
Engineering Units Low (high byte) Default value = 06h
Engineering Units Low (low byte) Default value = 66h
Engineering Units High (high byte) Default value = 1Fh
Engineering Units High (low byte) Default value = FFh
Fault Value (high byte) Default value = 00
Fault Value (low byte) Default value = 00
Idle Value (high byte) Default value = 00
Idle Value (low byte) Default value = 00
Meaning of bits described below
FA = Fault Action IA = Idle Value
Value Definition Value Definition
0 Hold Last State 0 Hold Last State
1 Fault Value (default) 1 Idle Value (default)
R = Range AD = Alarm Disable
Value Definition Value Definition
0 -10 to +10V (default) 0 Enable (default)
1 0 to +10V 1 Disable

Diagnostic Data

Possible Error Codes:
Code Error Type
Publication 1734-UM005B-EN-P - June 2001
6 Wire Break
16 Module incorrect or missing. Reported on channel 0, applies to whole module.
Default Data Maps B-15

1734-IA2 120V ac Input Module

Product Code: 1111h

Data Map:

Output size: 0 bytes; Input size: 1 byte
Produces (Rx) Not used CH1
Consumes (Tx) No consumed data
7654321 0
state
Where: CH0 = input channel 0, CH1 = input channel 1; 0 = OFF, 1 = ON

Configuration Data:

7654321 0
Reserved Filter
Meaning of bits described below
CH0
state
Filter Values
Value Definition
00 1ms
01 0.33ms
10 3ms
11 10ms
Default: H00 (1ms)

Diagnostic Data

Possible Error Codes:
Code Error Type
16 Module incorrect or missing. Reported on channel 0, applies to whole module.
Publication 1734-UM005B-EN-P - June 2001
B-16 Default Data Maps

1734-IM2 220V ac Input Module

Product Code: 1112h

Data Map:

Output size: 0 bytes; Input size: 1 byte
Produces (Rx) Not used CH1
Consumes (Tx) No consumed data
7654321 0
state
Where: CH0 = input channel 0, CH1 = input channel 1; 0 = OFF, 1 = ON

Configuration Data:

7654321 0
Reserved Filter
Meaning of bits described below
CH0
state
Filter Values
Value Definition
00 1ms
01 0.33ms
10 3ms
11 10ms
Default: H00 (1ms)

Diagnostic Data

Possible Error Codes:
Code Error Type
16 Module incorrect or missing. Reported on channel 0, applies to whole module.
Publication 1734-UM005B-EN-P - June 2001
Default Data Maps B-17

1734-OA2 120/220V ac Output Module

Product Code: 1113h

Data Map:

Output size: 1 bytes; Input size: 0 byte
)Produces (Rx) No produced data
Consumes (Tx) Not used CH1
7654321 0
state
Where: CH0 = output channel 0, CH1 = output channel 1; 0 = OFF, 1 = ON

Configuration Data:

7654321 0
Reserved IV IA FV FA
Meaning of bits described below
FA = Fault Action FV = Fault Value
Value Definition Value Definition
CH0
state
0 Fault Value 0 OFF
1 Hold Last State 1 ON
IA = Idle Action IV = Idle Value
Value Definition Value Definition
0 Idle Value 0 OFF
1 Hold Last State 1 ON
Default: H00 (Default: Fault/Idle value = OFF)

Diagnostic Data

Possible Error Codes:
Code Error Type
16 Module incorrect or missing. Reported on channel 0, applies to whole module.
Publication 1734-UM005B-EN-P - June 2001
B-18 Default Data Maps
Publication 1734-UM005B-EN-P - June 2001

Numerics

1734-IA2 data map B-15 1734-IB2 data map B-2 1734-IB4 data map B-3 1734-IE2C data map B-9 1734-IE2V data map B-12 1734-IM2 data map B-16 1734-IV2 data map B-4 1734-IV4 data map B-5 1734-OA2 data map B-17 1734-OB2E data map B-6 1734-OB4E data map B-7 1734-OE2C data map B-11 1734-OE2V data map B-14 1734-OW2 data map B-8
data map, 1734-OE2C B-11 data map, 1734-OE2V B-14 data map, 1734-OW2 B-8 diagnostic indicators 1-4 DIN rail mounting 2-2 directives, European Union P-3
G
grouped module, control word bit 6 4-5 grouping 5-1, 5-2 grouping example 5-3
H
how to in a single byte 5-2
A
address switch 1-2
B
bit-stuffing, an example using 1734-OB2E modules
4-16
bit-stuffing, example of 4-7 bit-stuffing, memory management 4-16
C
CE directives P-3 channel related diagnostics 4-13 check_configuration telegram 4-6 configure the adapter 1-3 configure the I/O modules 1-3 connecting wiring 2-6 connection plug wiring 2-9 connector, network 1-4 control byte 4-4
D
data map, 1734-IA2 B-15 data map, 1734-IB2 B-2 data map, 1734-IB4 B-3 data map, 1734-IE2C B-9 data map, 1734-IE2V B-12 data map, 1734-IM2 B-16 data map, 1734-IV2 B-4 data map, 1734-IV4 B-5 data map, 1734-OA2 B-17 data map, 1734-OB2E B-6 data map, 1734-OB4E B-7
I
indicators, diagnostic 1-4
M
memory management, using bit-stuffing 4-16 modules in the configuration tool 5-2
N
network connector 1-4 node address 1-2
P
product code 4-4 PROFIBUS module description 1-1
R
replacing an adapter module 2-4
S
set_parameter data 4-3 specifications A-1 starting the adapter 1-2
T
types of 5-1
W
wiring connections 2-8 wiring, connection plug 2-9
Publication 1734-UM005B-EN-P - June 2001
2
Publication 1734-UM005B-EN-P - June 2001
Allen-Bradley Publication Problem Report
If you find a problem with our documentation, please complete and return this form.
Pub. Title/Type POINT I/O PROFIBUS Adapter Module User Manual
Cat. No.
Check Problem(s) Type: Describe Problem(s)
Technical Accuracy t e x t illustration
Completeness procedure/step illustration definition info in manual
What information is missing?
Clarity
What is unclear?
1734-APB Pub. No. 1734-UM005B-EN-P Pub. Date June 2001 Part No.
Internal Use Only
example guideline feature (accessibility)
explanation other info not in manual
Sequence
What is not in the right order?
Other Comments
Use back for more comments.
Your Name Location/Phone
Return to: Marketing Communications, Allen-Bradley., 1 Allen-Bradley Drive, Mayfield Hts., OH 44124-6118Phone:(440) 646-3176 FAX:(440) 646-4320
Publication ICCG-5.21- August 1995 PN 955107-82
Other Comments
PLEASE FASTEN HERE (DO NOT STAPLE)
PLEASE FOLD HERE
BUSINESS REPLY MAIL
FIRST-CLASS MAIL PERMIT NO. 18235 CLEVELAND OH
POSTAGE WILL BE PAID BY THE ADDRESSEE
NO POSTAGE
NECESSARY
IF MAILED
IN THE
UNITED STATES
PLEASE REMOVE
1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705

Back Cover

Publication 1734-UM005B-EN-P - June 2001 7 PN 957564-10
Supersedes 1734-UM005A- EN-P - January 2001 © 2001 Rockwell International Corporat ion. Printed in the U.S.A.
Loading...