Solid-state equipment has operational characteristics differing from those of electromechanical
equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls
(Publication SGI-1.1
http://www.rockwellautomation.com/literature/
solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also
because of the wide variety of uses for solid-state equipment, all persons responsible for applying this
equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages
resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the
many variables and requirements associated with any particular installation, Rockwell Automation, Inc.
cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits,
equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
available from your local Rockwell Automation sales office or online at
WARNING: Identifies information about practices or circumstances that can cause an
explosion in a hazardous environment, which may lead to personal injury or death,
property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to
personal injury or death, property damage, or economic loss. Attentions help you
identify a hazard, avoid a hazard and recognize the consequences.
) describes some important differences between
SHOCK HAZARD: Labels may be on or inside the equipment (for example, drive or
motor) to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment (for example, drive or
motor) to alert people that surfaces may reach dangerous temperatures.
IMPORTANT Identifies information that is critical for successful application and understanding of the
product.
Publication 1734-IN041B-EN-P - October 2013
Page 3
1734 POINT I/O Dual Port EtherNet/IP Adapter 3
Environment and Enclosure
ATTENTION: This equipment is intended for use in a Pollution Degree 2
industrial environment, in overvoltage Category II applications (as defined in IEC
60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is not intended for use in residential environments and may not
provide adequate protection to radio communication services in such
environments.
This equipment is supplied as open-type equipment. It must be mounted within
an enclosure that is suitably designed for those specific environmental
conditions that will be present and appropriately designed to prevent personal
injury resulting from accessibility to live parts. The enclosure must have suitable
flame-retardant properties to prevent or minimize the spread of flame,
complying with a flame spread rating of 5VA or be approved for the application
if nonmetallic. The interior of the enclosure must be accessible only by the use
of a tool. Subsequent sections of this publication may contain additional
information regarding specific enclosure type ratings that are required to
comply with certain product safety certifications.
In addition to this publication, see the following:
• Industrial Automation Wiring and Grounding Guidelines, publication
1770-IN041
• NEMA Standard 250 and IEC 60529, as applicable, for explanations of the
degrees of protection provided by enclosures.
, for additional installation requirements.
Preventing Electrostatic Discharge
ATTENTION: This equipment is sensitive to electrostatic discharge, which can
cause internal damage and affect normal operation. Follow these guidelines
when you handle this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in use.
Publication 1734-IN041B-EN-P - October 2013
Page 4
4 1734 POINT I/O Dual Port EtherNet/IP Adapter
Additional Resources
Refer to these related publications, as needed.
ResourceDescription
1734 POINT I/O® and 1738
ArmorPOINT I/O
EtherNet/IP Adapter User Manual,
publication 1734-UM017
Industrial Automation Wiring and
Grounding Guidelines, publication
1770-IN041.
® Dual Port
.
If you would like a manual, you can:
• download a free electronic version from the internet:
http://www.rockwellautomation.com/literature/
• purchase a printed manual by contacting your local Allen-Bradley distributor or
Rockwell Automation representative.
A detailed description of module functionality, configuration,
installation procedure and information on how to use the POINT
I/O and ArmorPOINT I/O Dual Port EtherNet/IP adapters
(1734-AENTR, Series B and 1738-AENTR, Series B,
respectively).
More information on proper wiring and grounding techniques.
Publication 1734-IN041B-EN-P - October 2013
Page 5
1734 POINT I/O Dual Port EtherNet/IP Adapter 5
North American Hazardous Location Approval
The following information applies when
operating this equipment in hazardous
locations:
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable
for use in Class I Division 2 Groups A, B, C, D, Hazardous
Locations and nonhazardous locations only. Each product
is supplied with markings on the rat ing nameplate
indicating the hazardous location tempe rature code.
When combining products within a system, the most
adverse temperature code (lowest "T" number) may be
used to help determine the overall temperature code of
the system. Combinations of equipment in you r system
are subject to investigation by the local Authority Having
Jurisdiction at the time of installation.
EXPLOSION HAZARD
• Do not disconnect equipment unless
power has been removed or the area i s
known to be nonhazardous.
• Do not disconnect connections to this
equipment unless power has been
removed or the area is known to be
nonhazardous. Secure any external
connections that mate to this equipment
by using screws, sliding latches,
threaded connectors, or other means
provided with this product.
• Substitution of components may impair
suitability for Class I, Division 2.
• If this product contains batteries, they
must only be changed in an area known
to be nonhazardous.
Informations sur l’utilisation de cet équipement
en environnements dangereux:
Les produits marqués "CL I, DIV 2, GP A, B, C, D" n e conviennent
qu'à une utilisation en environnements de Classe I Division 2
Groupes A, B, C, D dangereux et non dangere ux. Chaque produit
est livré avec des marquages sur sa plaque d 'identification qui
indiquent le code de température pour les environnements
dangereux. Lorsque plusieurs produits sont combin és dans un
système, le code de température le plus défavorable (code de
température le plus faible) peut être utilisé pour déterminer le
code de température global du système . Les combinaisons
d'équipements dans le système sont sujettes à inspection par
les autorités locales qualifiées au moment de l'installation.
RISQUE D’EXPLOSION
• Couper le courant ou s'assurer que
l'environnement est classé non dangereux
avant de débrancher l'équipement.
• Couper le courant ou s'assurer que
l'environnement est classé non dangereux
avant de débrancher les connecteurs. Fixer
tous les connecteurs externes reliés à cet
équipement à l'aide de vis, loquets
coulissants, connecteurs filetés ou autres
moyens fournis avec ce produit.
• La substitution de composants peut rendre cet
équipement inadapté à une utilisation en
environnement de Classe I, Division 2.
• S'assurer que l'environnement est classé non
dangereux avant de changer les piles.
Publication 1734-IN041B-EN-P - October 2013
Page 6
6 1734 POINT I/O Dual Port EtherNet/IP Adapter
European Hazardous Location Approval
The following applies when the product bears the Ex Marking
This equipment is intended for use in potentially explosive atmospheres as defined by
European Union Directive 94/9/EC and has been found to comply with the Essential
Health and Safety Requirements relating to the design and construction of Category 3
equipment intended for use in Zone 2 potentially explosive atmospheres, given in Annex II
to this Directive.
Compliance with the Essential Health and Safety Requirements has been assured by
compliance with EN 60079-15 and EN 60079-0.
ATTENTION: This equipment is not resistant to sunlight or other sources of
UV radiation.
WARNING: This equipment shall be mounted in an ATEX certified enclosure
with a minimum ingress protection rating of at least IP54 (as defined in
IEC60529) and used in an environment of not more than Pollution Degree 2
(as defined in IEC 60664-1) when applied in Zone 2 environments. The
enclosure must utilize a tool removable cover or door.
WARNING: Provision shall be made to prevent the rated voltage from being
exceeded by transient disturbances of more than 140% of the rated voltage
when applied in Zone 2 environments.
WARNING: Secure any external connections that mate to this equipment by
using screws, sliding latches, threaded connectors, or other means provided
with this product.
WARNING: Do not disconnect equipment unless power has been removed
or the area is known to be nonhazardous.
WARNING: Enclosure must be marked with the following: "Warning - Do
not open when energized." After installation of equipment into the enclosure,
access to termination compartments shall be dimensioned so that
conductors can be readily connected.
WARNING: Earthing is accomplished through mounting of modules on rail.
Publication 1734-IN041B-EN-P - October 2013
Page 7
1734 POINT I/O Dual Port EtherNet/IP Adapter 7
1
2
4
5
6
3
44849
About The Adapter
Read this publication for information about the Series B, POINT I/O Dual Port
EtherNet/IP adapter, a communications adapter for POINT I/O modules.
This adapter is for the POINT I/O backplane that provides connectivity to an
EtherNet/IP network with two RJ-45 connectors for 2 port pass-through to support
daisy-chain or ring, and the existing star and tree network topologies.
To effectively use your adapter, note the following considerations.
Determine Compatibility
RSLogix 5000™ software version 17, or greater, must be used for the 1734-AENTR
Add-on Profile. The 1734-AENTR adapters will accept I/O connections with electronic
keying for the 1734-AENT. This allows the 1734-AENTR adapter to be used in a
daisy-chain topology with the 1734-AENT profile used for the 1734-AENTR.
If using the adapter with a 1756-ENBT module, 1768-ENBT module or an L3xE
processor, use the following required firmware versions for these bridge modules:
• 1756-ENBT firmware version 4.5 or greater
• 1768-ENBT firmware version 2.1 or greater
• L3xE processor firmware version 17 or greater
If you use the BootP/DHCP utility to assign IP addresses to the adapter, use version 2.3.2
or greater.
Understand Messaging
Class 3 (Explicit Message) requests through the 1734-AENTR adapter to a specific
POINT I/O module do not always receive a response from the I/O modules. In the case
where the I/O module does not reply to the request, the adapter responds with an error
code indicating a time-out.
Configure Autobaud
The adapter cannot reconfigure an I/O module that you previously configured to operate
at a fixed baud rate. When you reuse a POINT I/O module from another POINT I/O
system, configure the module to autobaud before using it with the adapter.
Publication 1734-IN041B-EN-P - October 2013
Page 9
1734 POINT I/O Dual Port EtherNet/IP Adapter 9
1734-AENTR Series B
Module
Status
Network
Activity
Network
Status
Point Bus
Status
System
Power
Field
Po
w
e
r
POINT I O
75.30
(2.96)
74.00
(2.91)
132.72
(5.23)
52.23
(2.06)
35.55
(1.40)
A
B
45174
A = DIN rail
B = Secure DIN rail approximately every 200 mm (7.8 in.)
Install the Adapter
Follow this procedure to install the adapter on the DIN rail.
ATTENTION: You must only use Series C POINT I/O modules with
1734-AENTR EtherNet/IP Adapters. Series A or Series B POINT I/O modules
will not work with 1734-AENTR EtherNet/IP Adapters (does not apply to
POINTGuard modules).
Mount the POINT I/O Dual Port EtherNet/IP Adapter on a DIN Rail
Position the I/O adapter vertically above the DIN rail. Make sure that the DIN rail lock is
in horizontal position.
1. Position the adapter module on an IEC standard (35 x 7.5 x 1 mm) top-hat DIN
rail at a slight angle (DIN rail: Allen-Bradley part number 199-DR1; 46277-3; EN50022).
Publication 1734-IN041B-EN-P - October 2013
Page 10
10 1734 POINT I/O Dual Port EtherNet/IP Adapter
2. Press down firmly to install the adapter on a DIN rail, noting that the locking
mechanism locks the adapter to the DIN rail.
3. Set the network address thumbwheel switches to the desired value. See Set the
Network Address for more information on setting the IP address.
4. Slide the safety end cap up to remove it, exposing the backplane and power
interconnections.
ATTENTION: Do not discard the end cap. Use this end cap to cover the
exposed interconnections on the last mounting base on the DIN rail. Failure to
do so could result in equipment damage or injury from electric shock.
ATTENTION: This product is grounded through the DIN rail to chassis ground.
Use zinc plated yellow-chromate steel DIN rail to assure proper grounding. The
use of other DIN rail materials (for example, aluminum or plastic) that can
corrode, oxidize, or are poor conductors, can result in improper or intermittent
grounding. Secure DIN rail to mounting surface approximately every 200 mm
(7.8 in.) and use end-anchors appropriately.
ATTENTION: Allow 25.4 mm (1 in.) of space between adjacent equipment for
adequate ventilation.
WARNING: If you connect or disconnect the communications cable with
power applied to this module or any device on the network, an electrical arc
can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
ATTENTION: Do not remove or replace an Adapter Module while power is
applied. Interruption of the backplane can result in unintentional operation or
machine motion.
Publication 1734-IN041B-EN-P - October 2013
Page 11
1734 POINT I/O Dual Port EtherNet/IP Adapter 11
02
0
1734-AENTR Series B
Module
Status
Network
Activity
Network
Status
Point Bus
Status
System
Power
Field
Power
POINT I O
Link 1
Activity/
Status
IP ADDRESS
44848
Press either the + or - buttons to
change the number and assign the
adapter IP address
Set the Network Address
The thumbwheel switches are set to 999 and DHCP enabled, by default. You can set the
network Internet Protocol (IP) address in the following ways:
• Use the thumbwheel switches on the adapter.
• Use a Dynamic Host Configuration Protocol (DHCP) server, such as
Rockwell Automation BootP/DHCP.
• Retrieve the IP address from nonvolatile memory.
The adapter reads the thumbwheel switches first to determine if the switches are set to a
valid number. You set the node address by using the 3-position thumbwheel switch. Press
the + or - buttons to change the number. Valid settings range from 001…254.
When you use the thumbwheel to assign an address and set it to 001, the adapter gateway
address is set to 0.0.0.0. and the subnet mask is 255.255.255.0 . When you use the
thumbwheel to assign an address and set it between 002...254, the adapter gateway address
is set to 192.168.1.1.
The adapter does not have a host name assigned, or use any Domain Name System when
using the thumbwheel settings.
Network Address Thumbwheel
Refer to publication POINT I/O and ArmorPOINT I/O Dual Port EtherNet/IP
Adapter User Manual, 1734-UM017
for more information.
Publication 1734-IN041B-EN-P - October 2013
Page 12
12 1734 POINT I/O Dual Port EtherNet/IP Adapter
If you set the switches to an invalid number (for example, 000 or a value greater than 254
excluding 888), the adapter checks to see if you enabled DHCP.
DHCP Enabled and Not Enabled
DHCP StateAdapter Action
EnabledAsks for an address from a DHCP server. The DHCP server also assigns other
Not enabledUses the IP address (along with other TCP configurable parameters) stored in
Transport Control Protocol (TCP) parameters.
nonvolatile memory.
WARNING: When you change switch settings while power is on, an electrical
arc can occur. This could cause an explosion in hazardous location
installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
Replace The Adapter
Use these procedures to install a replacement adapter to an existing system.
1. Disconnect the Ethernet connector(s) from the adapter.
2. Pull up on the Removable Terminal Block (RTB) handle to remove the terminal
block.
WARNING: When you insert or remove the module while backplane power is
on, an electrical arc can occur. This could cause an explosion in hazardous
location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
Repeated electrical arcing causes excessive wear to contacts on both the
module and its mating connector. Worn contacts may create electrical
resistance that can affect module operation.
WARNING: When you connect or disconnect the Removable Terminal Block
(RTB) with field side power applied, an electrical arc can occur. This could
cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
Publication 1734-IN041B-EN-P - October 2013
Page 13
1734 POINT I/O Dual Port EtherNet/IP Adapter 13
WARNING: If you connect or disconnect the communications cable with
power applied to this module or any device on the network, an electrical arc
can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
3. Remove the adjacent module from its base.
4. Use a small bladed screwdriver to rotate the DIN rail locking screw to a vertical
position. This releases the locking mechanism.
5. Lift straight up to remove.
6. Slide the safety end cap up to remove it, which exposes the backplane and power
connections.
7. Position the replacement adapter vertically above the DIN rail, making certain
the DIN rail lock is in the horizontal position.
8. Slide the adapter down, allowing the interlocking side pieces to engage the
adjacent module.
9. Press firmly to seat the adapter on the DIN rail, noting that the adapter locking
mechanism will snap into place.
10. Set the node address on the node address thumbwheel.
11. Insert the end of the terminal block opposite the handle into the base unit, noting
that this end has a curved section that engages with the wiring base.
12. Rotate the terminal block into the wiring base until it locks itself into place.
13. Replace the adjacent module in its base.
14. Reconnect the Ethernet cable(s) to the adapter.
15. Set the IP Address for this module.
16. Configure the adapter’s chassis size.
WARNING: When used in a Class I, Division 2, hazardous location, this
equipment must be mounted in a suitable enclosure with proper wiring method
that complies with the governing electrical codes.
Publication 1734-IN041B-EN-P - October 2013
Page 14
14 1734 POINT I/O Dual Port EtherNet/IP Adapter
Chas Gnd
C
V
NC
Ethernet
RJ-45
connectors
NCVNC
Chas
Gnd
V
0
4
2
6
Chas
Gnd
1
5
3
7
V DC
C
C
NC = No Connection
Chas GND = Chassis Ground
C = Common
V = Supply
44848
Wire The Adapter
02
0
Link 1
Activity/
Status
IP ADDRESS
Link 2
Activity/
Status
1734-AENTR Series B
POINT I O
Module
Status
Network
Activity
Network
Status
Point Bus
Status
System
Power
Field
Power
IMPORTANT
Publication 1734-IN041B-EN-P - October 2013
Do not connect 120/240V AC power to this supply. This DC supply will be
connected to the internal power bus.
Page 15
1734 POINT I/O Dual Port EtherNet/IP Adapter 15
WARNING: Do not wire more than two conductors on any single terminal.
WARNING: To comply with the CE Low Voltage Directive (LVD), this
equipment must be powered from a Safety Extra Low Voltage (SELV) or
Protected Extra Low Voltage (PELV) compliant source.
WARNING: If you connect or disconnect wiring while the field-side power is
on, an electrical arc can occur. This could cause an explosion in hazardous
location installations. Be sure that power is removed or the area is
nonhazardous before proceeding.
Publication 1734-IN041B-EN-P - October 2013
Page 16
16 1734 POINT I/O Dual Port EtherNet/IP Adapter
43264
Network status
POINTBus status
System power
Field power
NC
Chas Gnd
C
V
Module status
Network activity
Network address
thumbwheels
Ethernet
RJ-45
connectors
Interpret Status Indicators
Refer to the following diagram and table for information on how to interpret the
status indicators.
POINT I/O Dual Port EtherNet/IP Adapter, Series B
0
Indicator Status for Modules
Indicator StatusDescription
Module
status
OffNo power applied to device
Flashing greenDevice needs commissioning due to missing, incomplete, or
Solid redUnrecoverable fault, may require device replacement
Flashing
red/green
Module self-test
02
Link 1
Activity/
Status
IP ADDRESS
Link 2
Activity/
Status
1734-AENTR Series B
POINT I O
Module
Status
Network
Activity
Network
Status
Point Bus
Status
System
Power
Field
Power
Publication 1734-IN041B-EN-P - October 2013
Page 17
1734 POINT I/O Dual Port EtherNet/IP Adapter 17
Indicator Status for Modules
Network
status
Network
Activity
Link 1 or
Link 2
Activity /
Status
POINTBus
status
System
power
Field power OffNot active. Adapter power is off.
OffDevice is not on-line
Flashing greenDevice is on-line but has no CIP connections in the
Solid greenDevice on-line and has CIP connections in the established state.
Flashing redOne or more CIP connections in timed-out state. Check for I/O module
Solid redDuplicate IP address detected.
Flashing red/green Module self-test
OffNo link established with Port 1 or Port 2.
Flashing greenTransmit or receive activity present on Port 1 and/or Port 2 @ 100 Mb.
Solid greenLink established with Port 1 and/or Port 2 @ 100 Mb.
Solid yellowLink established with Port 1 and/or Port 2 @ 10 Mb.
Flashing yellowTransmit or receive activity present on Port 1 and/or Port 2 @ 10 Mb.
OffNo link established.
Solid greenLink established @ 100 Mbps.
Flashing greenTransmit or receive activity present on indicated port @ 100 Mbps.
Solid yellowLink established @ 10 Mbps.
Flashing yellowTransmit or receive activity present on indicated port @ 10 Mbps.
OffDevice is not online.
Flashing greenDevice is online but has no connections in the established state.
Solid greenAdapter online with connections established.
Flashing redRecoverable fault occurred:
Solid redUnrecoverable fault occurred - the adapter is bus off.
Flashing red/green LED powerup test is in progress.
OffNot active. Adapter power is off or there is a DC-DC converter problem.
Solid greenSystem power is on. DC-DC converter output is active (5V).
Solid greenPower is on. 24V input is present.
- Device has not completed dup_MAC_id test.
- Device not powered - check module status indicator
established state.
failure and controller operation.
Note: This does not apply to POINTGuard I/O connection timeout.
Verify IP address setting and correct, as needed.
Transmit or receive activity present on Port 1 and/or Port 2.
One port @ 100 Mb and the other port @ 10 Mb.
Link established with Port 1 and Port 2.
One port @ 100 Mb and the other port @ 10 Mb.
Device has not completed Dup_MAC_ID test.
Device not powered - check module status indicator.
Firmware (NVS) update in progress.
•At cycle power, the number of expected modules does not equal the
number of modules present.
•A module is missing.
•Node fault (I/O connection timeout) occurred.
Publication 1734-IN041B-EN-P - October 2013
Page 18
18 1734 POINT I/O Dual Port EtherNet/IP Adapter
Specifications
POINT I/O EtherNet/IP Adapter — 1734-AENTR, Series B
AttributeValue
Expansion I/O capacity, max•63 modules
POINTBus current requirements, max• 50 mA (Catalog number 1734-IB4D)
Module locationStarter module - left side of the 1734 system
(1)
Maximum 31 direct connections for standard I/O or maximum 20 direct connections if any safety I/O module resides in
the backplane.
•5 rack optimized connections (for digital modules only)
•31 direct connections
•1734-AENTR backplane current output = 0.8 A.
•Actual number of modules can vary.
•Add up current requirements of modules you want to use to
make sure they do not exceed the amperage limit of 0.8 A for
the 1734-AENTR adapter.
•Backplane current can be extended beyond 0.8 A by
1734-EP24DC or 1734-EPAC backplane extension power
supplies.
•Add multiple 1734-EP24DC or 1734-EPAC modules to reach
the 63 module max.
Input voltage rating24V DC @ 10A
Input voltage, range10...28.8V DC
Field side power, max24V DC @ 400 mA
Inrush current, max6 A for 10 ms
Publication 1734-IN041B-EN-P - October 2013
Page 19
1734 POINT I/O Dual Port EtherNet/IP Adapter 19
Power Supply
AttributeValue
Input overvoltage protectionReverse polarity protected
POINTBus output current, max5V DC @ 0.8A
InterruptionOutput voltage stays within specifications when input drops out
for 10 ms @ 10V with max load
Ethernet Communication
AttributeValue
Ethernet communication rate10/100 Mbits/s, half or full-duplex
Ethernet ports2, configured as Embedded Switch
Ethernet network topologies supported Star, Tree, Daisy-chain/Linear, and Ring
Ethernet connectorsRJ-45, Category 5
Ethernet cableCategory 5:
Ethernet wire connections, maxSee Wire Size
shielded or unshielded
on page 20
General Specifications
AttributeValue
Indicators3 red/green status indicators on CPU:
Power consumption, max10.4 W @ 28.8V DC
Power dissipation, max6.3 W @ 28.8V DC
Input overvoltage protectionReverse polarity protected
Thermal dissipation, max21.5 BTU/hr @ 28.8V DC
– Module status
– Network status (Ports 1 and 2 combined)
– POINTBus status
1 green/yellow status indicator on CPU:
– Network activity (Ports 1 and 2 combined)
2 green/yellow status indicators on base:
– Link 1 activity/status
– Link 2 activity/status
2 green power supply status indicators on DC-DC Converter:
– System power (5V DC to POINTBus Out)
– Field power (24V DC from Field In)
Publication 1734-IN041B-EN-P - October 2013
Page 20
20 1734 POINT I/O Dual Port EtherNet/IP Adapter
General Specifications
AttributeValue
Isolation voltage50V (continuous), Reinforced Insulation Type, between
Field power supply10...28.8V DC @ 10A
Field power output10...28.8V DC @ 9A
Module input10...28V DC @ 1000 mA
POINTBus output, max5V DC @ 0.8A
Dimensions (HxWxD), approx. 76.2 x 73.0 x 133.4 mm (3.0 x 2.87 x 5.25 in.)
Enclosure type ratingNone (open-style)
Terminal base screw torque0.8 Nm (7 lb-in)
Weight, approx.0.28 Kg (0.62 lb)
(1)
Wiring category
Wire SizePower connections:
North American temp codeT4
IEC Temp CodeT4
(1)
Use this Conductor Category information for p lanning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication 17 70-IN041.
1 – on power ports
all circuits
Type tested @ 500V AC for 60 s
1 – on communications ports
0.34... 2.1 mm
@ 75 °C (167 °F ) or greater, 1.2 mm (3/64 in.) insulation max or
90
Ethernet wiring:
RJ45 connector according to IEC 60603-7, 2 or 4 pair Category 5e
min cable according to TIA 568-B.1 or Category 5 cable according
to ISO/IEC 24702.
10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
10V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
±4 kV @ 5 kHz on power ports
±3 kV @ 5 kHz on communications ports
±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
±2 kV line-earth (CM) on communications ports
10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
Publication 1734-IN041B-EN-P - October 2013
Page 22
22 1734 POINT I/O Dual Port EtherNet/IP Adapter
Certifications
Certification (when
product is marked)
c-UL-usUL Listed Industrial Control Equipment, certified for US and
CEEuropean Union 2004/108/EC EMC Directive, compliant with:
ExEuropean Union 94/9/EC ATEX Directive, compliant with:
KCKorean Registration of Broadcasting and Communications
EtherNet/IPODVA conformance tested to EtherNet/IP specifications
(1)
See the Product Certification lin k at http://www.rockwellautomation.com/products/certification/ for Declaration of
Conformity, Certificates, and other certification details.
(1)
Valu e
Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous
Locations, certified for U.S. and Canada. See UL File E194810.
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
AS/NZS CISPR11; Industrial Emissions
EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
EN 60079-0; General Requirements
II 3 G Ex nA IIC T4 Gc
DEMKO 04 ATEX 0330347X
Equipment, compliant with:
Article 58-2 of Radio Waves Act, Clause 3
Publication 1734-IN041B-EN-P - October 2013
Page 23
Notes:
1734 POINT I/O Dual Port EtherNet/IP Adapter 23
Publication 1734-IN041B-EN-P - October 2013
Page 24
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At
http://www.rockwellautomation.com/support/
technical and application notes, sample code and links to software service packs, and a MySupport feature
that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration and troubleshooting, we
offer TechConnect support programs. For more information, contact your local distributor or Rockwell
Automation representative, or visit http://www.rockwellautomation.com/support/
, you can find technical manuals, a knowledge base of FAQs,
.
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the information that's
contained in this manual. You can also contact a special Customer Support number for initial help in getting
your product up and running.
United States or Canada 1.440.646.3434
Outside United States or
contact your local Rockwell Automation representative.
, or
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from
the manufacturing facility. However, if your product is not functioning and needs to be returned, follow
these procedures.
United StatesContact your distributor. You must provide a Customer Support case number
Outside United StatesPlease contact your local Rockwell Automation representative for the return
(call the phone number above to obtain one) to your distributor to complete
the return process.
procedure.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to
improve this document, complete this form, publication RA-DU002
http://www.rockwellautomation.com/literature/
.
, available at
Allen-Bradley, Rockwell Automation, POINT I/O, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 1734-IN041B-EN-P - October 2013PN-226424