POINT I/O Module with 8 Configurable
24V DC Points
Catalog Number 1734-8CFG
TopicPage
Important User Information2
Environment and Enclosure3
Prevent Electrostatic Discharge4
About the Module5
Before You Begin5
Install the Mounting Base7
Install the I/O Module8
Install the Removable Terminal Block10
Remove a Mounting Base11
Wire the Module13
Wiring Diagram14
Configure the Module15
Interpret the Indicators17
Specifications19
2 POINT I/O Module with 8 Configurable 24V DC Points
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical
equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls
(Publication SGI-1.1 available from your local Rockwell Automation sales office or online at
http://literature.rockwellautomation.com
equipment and hard-wired electromechanical devices. Because of this difference, and also because of
the wide variety of uses for solid state equipment, all persons responsible for applying this equipment
must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages
resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the
many variables and requirements associated with any particular installation, Rockwell Automation, Inc.
cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits,
equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING
Identifies information about practices or circumstances that can cause an explosion
in a hazardous environment, which may lead to personal injury or death, property
damage, or economic loss.
) describes some important differences between solid state
IMPORTANT
ATTENTION
SHOCK HAZARD
BURN HAZARD
Publication
Identifies information that is critical for successful application and understanding of
the product.
Identifies information about practices or circumstances that can lead to personal
injury or death, property damage, or economic loss. Attentions help you identify a
hazard, avoid a hazard and recognize the consequences.
Labels may be on or inside the equipment (for example, drive or motor) to alert
people that dangerous voltage may be present.
Labels may be on or inside the equipment (for example, drive or motor) to alert
people that surfaces may reach dangerous temperatures.
1734-IN038A-EN-P - October 2008
POINT I/O Module with 8 Configurable 24V DC Points 3
Environment and Enclosure
ATTENTION
This equipment is intended for use in a Pollution Degree 2 industrial
environment, in overvoltage Category II applications (as defined in IEC
publication 60664-1), at altitudes up to 2000 meters (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according
to IEC/CISPR Publication 11. Without appropriate precautions, there may be
potential difficulties ensuring electromagnetic compatibility in other
environments due to conducted as well as radiated disturbance.
This equipment is supplied as open-type equipment. It must be mounted within
an enclosure that is suitably designed for those specific environmental
conditions that will be present and appropriately designed to prevent personal
injury resulting from accessibility to live parts. The enclosure must have
suitable flame-retardant properties to prevent or minimize the spread of flame,
complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if
non-metallic. The interior of the enclosure must be accessible only by the use
of a tool. Subsequent sections of this publication may contain additional
information regarding specific enclosure type ratings that are required to
comply with certain product safety certifications.
In addition to this publication, see:
• Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley
publication 1770-4.1
• NEMA Standards publication 250 and IEC publication 60529, as
applicable, for explanations of the degrees of protection provided by
different types of enclosure
, for additional installation requirements.
Publication
1734-IN038A-EN-P - October 2008
4 POINT I/O Module with 8 Configurable 24V DC Points
Prevent Electrostatic Discharge
ATTENTION
ATTENTION
ATTENTION
This equipment is sensitive to electrostatic discharge, which can cause
internal damage and affect normal operation. Follow these guidelines when
you handle this equipment.
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in
use.
POINT I/O is grounded through the DIN rail to chassis ground. Use zinc plated,
yellow-chromate steel DIN rail to be sure of proper grounding. The use of other
DIN rail materials, such as aluminum and plastic that can corrode, oxidize, or
are poor conductors, can result in improper or intermittent grounding.
Secure DIN rail to mounting surface approximately every 200 mm (7.87 in.) and
use end-anchors appropriately.
To comply with the CE Low Voltage Directive (LVD), all connected I/O must be
powered from a source compliant with the following:
Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).
Publication
1734-IN038A-EN-P - October 2008
POINT I/O Module with 8 Configurable 24V DC Points 5
About the Module
The 1734-8CFG module is a 24V DC I/O module with 8 self-configuring
points. Each of the I/O points can be a DC input or output. The module
supports removal and insertion under power, auto-address, and auto-baud in
compliance with the POINTBus backplane.
Before You Begin
See the figures to familiarize yourself with major parts of the module, noting
that the wiring base assembly is one of the following:
• 1734-TB or 1734-TBS POINT I/O two-piece terminal base, which
includes the 1734-RTB removable terminal block and 1734-MB
mounting base
• 1734-TOP or 1734-TOPS POINT I/O one-piece terminal base
The 1734-8CFG module is not compatible with 1734-TB3, 1734-TB3S,
1734-TOP3, and 1734-TOP3S terminal bases.
Publication
1734-IN038A-EN-P - October 2008
6 POINT I/O Module with 8 Configurable 24V DC Points
Module Locking
Mechanism
Module Wiring
Diagram
DIN Rail Locking
Screw (orange)
Mechanical
Keying (orange)
Interlocking Side
Pieces
Mounting Base
Module
Status
Network
Status
NODE:
4
5
0
6
1
7
2
3
Slide-in Writable
Label
Insertable I/O
Module
RTB Removal
Handle
Removable Terminal
Block (RTB)
44713
Publication
1734-IN038A-EN-P - October 2008
POINT I/O Module with 8 Configurable 24V DC Points 7
Module Locking
Mechanism
Module Wiring
Diagram
DIN Rail Locking
Screw (orange)
Mechanical
Keying (orange)
Interlocking
Side Pieces
44714
Install the Mounting Base
Follow these steps to install the mounting base on the DIN rail.
1. Position the mounting base vertically above the installed units, for
example, adapter, power supply, or existing module.
2. Slide the mounting base down so that the interlocking side pieces
engage the adjacent module or adapter.
Slide-in
Writable Label
Insertable
I/O Module
Handle
1734-TOP or
1734-TOPS
One-piece
Terminal Base
with Screw or
Spring Clamp
3. Press firmly to seat the mounting base on the DIN rail until the
mounting base snaps into place.
4. To remove the mounting base from the DIN rail, remove the module,
and use a small bladed screwdriver to rotate the base locking screw to
a vertical position. This releases the locking mechanism. Then lift
straight up to remove.
Publication
1734-IN038A-EN-P - October 2008
8 POINT I/O Module with 8 Configurable 24V DC Points
Install the I/O Module
The module can be installed before, or after base installation. Make sure the
mounting base is correctly keyed before installing the module into the
mounting base. In addition, make sure the mounting base locking screw is
positioned horizontal referenced to the base.
1734-TB Base
Turn the keyswitch to align
the number with the notch.
Notch position 1 is shown.
Publication
44710
1734-IN038A-EN-P - October 2008
Be sure the DIN-rail
locking screw is in the
horizontal position.
44715
1734-TOP Base
Turn the keyswitch to align
the number with the notch.
Notch position 1 is shown.
44710
POINT I/O Module with 8 Configurable 24V DC Points 9
Be sure the DIN-rail
locking screw is in the
horizontal position.
44228
Follow these steps to install the module.
1. Use a bladed screwdriver to rotate the keyswitch on the mounting
base clockwise until the number required for the type of module being
installed aligns with the notch in the base.
2. Make certain the DIN-rail locking screw is in the horizontal position.
(You cannot insert the module if the locking mechanism is unlocked.)
3. Insert the module straight down into the mounting base and press to
secure. The module will lock into place.
Publication
1734-IN038A-EN-P - October 2008
10 POINT I/O Module with 8 Configurable 24V DC Points
Install the Removable Terminal Block
Read this for information if a removable terminal block (RTB) is supplied
with your wiring base assembly, noting that 1734-TOP and 1734-TOPS bases
do not have an RTB.
To insert the RTB, proceed as follows. Note that if you pull up on the RTB
handle to remove the RTB, you can remove and replace the mounting base as
necessary without removing any of the wiring.
1. Insert the end opposite the handle into the base unit, noting that this
end has a curved section that engages with the wiring base.
2. Rotate the terminal block into the wiring base until it locks itself into
place.
3. If an I/O module is installed, snap the RTB handle into place on the
module.
Publication
1734-IN038A-EN-P - October 2008
POINT I/O Module with 8 Configurable 24V DC Points 11
Remove a Mounting Base
To remove a mounting base, you must first remove any installed module and
the module installed in the base to the right.
1. For a module with a two-piece terminal base, use these steps;
otherwise, use step 2
a. Remove the removable terminal block (RTB), if wired.
b. Unlatch the RTB handle on the I/O module.
c. Pull on the RTB handle to remove the RTB.
2. Press on the module lock on the top of the module.
3. Pull on the I/O module to remove from the base.
4. Repeat steps 1, 2, 3, and 4 for the module to the right.
5. Lift straight up to remove.
.
Publication
1734-IN038A-EN-P - October 2008
12 POINT I/O Module with 8 Configurable 24V DC Points
Install a 1734-TOPS Base
1. Position the base vertically above the installed units, such as an
adapter, power supply, or existing module.
2. Slide the base down, allowing the interlocking side pieces to engage
the adjacent installed unit.
3. Press firmly to seat the base on the DIN rail until the base snaps into
place.
4. Verify that the DIN-rail locking screw is in a horizontal, locked
position before inserting an I/O module.
Remove a 1734-TOPS Base
To remove a wiring base from the DIN rail, you must remove the module
installed to the right of the base.
1. Squeeze the module locking mechanism of the module to the right of
the base, pulling up to remove the module.
2. Turn the orange locking screw to a vertical position to unlock the base
from the DIN rail.
3. Slide the base up to release it from its mating units.
Publication
1734-IN038A-EN-P - October 2008
POINT I/O Module with 8 Configurable 24V DC Points 13
Wire the Module
See the figures and tables for information about how to wire the module.
1734-8CFG
I/O 0
Module
Status
Network
Status
NODE:
NODE:
24Vdc
SINK IN
SOURCE OUT
0
0
1
1
2
2
3
3
1734-8CFG
4
Status of I/O 4
5
Status of I/O 5
6
Status of I/O 6
7
7
Status of I/O 7
I/O 1
Module Status
Network Status
Status of I/O 0
Status of I/O 1
Status of I/O 2
Status of I/O 3
I/O 2I/O 3
I/O 4I/O 5
I/O 6I/O 7
44543
Note that voltage and current to the module is applied through the adapter,
the 1734-FPD module, or the 1734-EP24DC module. V = 10…28.8 V DC.
Publication
1734-IN038A-EN-P - October 2008
14 POINT I/O Module with 8 Configurable 24V DC Points
Wiring Diagram
Prox
Prox
Prox
Prox
I/O 0
I/O 2
I/O 4
I/O 6
I/O 1
I/O 3
I/O 5
I/O 7
Load
Load
Load
Load
VCC
If a connection to Common or the Supply Voltage is required for two- or three-wire
devices, then a 1734-CTM or 1734-VTM can be used.
Each I/O point is either Input or Output.
ChannelTerminal Number
I/OCommonVoltage
00
External
(1)
External
11
22
33
44
55
66
77
10/28.8 V DC is supplied through the internal power bus.
(1)
Common connections require an external connection, such as a 1734-CTM module.
(2)
Supply Voltage Connections require an external connection such as a 1734-VTM module.
44687
(2)
Publication
1734-IN038A-EN-P - October 2008
POINT I/O Module with 8 Configurable 24V DC Points 15
Configure the Module
Read this section for information about how to communicate with your
module.
I/O messages are sent to (consumed) and received from (produced) the
POINT I/O modules. These messages are mapped into the processor’s or
scanner’s memory. Each module produces 1 byte of input data and consumes
1 byte of I/O data (scanner Tx).
Default Data Map - Produced Assembly Instance 4
Message Size: 1 Byte
76543210
DataPt 07Pt 06Pt 05Pt 04Pt 03Pt 02Pt 01Pt 00
Where: Pt = state of the input point
In RSLogix5000, the default tag will be AdapterName:SlotNumber:I.Data.
The data type is a SINT.
Default Data Map - Consumed Assembly Instance 34
Message Size: 1 Byte
76543210
DataPt 07Pt 06Pt 05Pt 04Pt 03Pt 02Pt 01Pt 00
Where: Pt = state of the output point
In RSLogix5000, the default tag will be AdapterName:SlotNumber:O.Data.
The data type is a SINT.
Publication
1734-IN038A-EN-P - October 2008
16 POINT I/O Module with 8 Configurable 24V DC Points
Default Data Map - Configuration Assembly Instance 103
Message Size: 8 Bytes
76543210
Data [0]Group Off2On Input filter
Data [1]
Data [2]Group On2Off Input filter
Data [3]
Data [4]FltM 7FltM 6FltM 5FltM 4FltM 3FltM 2FltM 1FltM 0
Data [5]FltV 7FltV 6FltV 5FltV 4FltV 3FltV 2FltV 1FltV 0
Data [6]IdlM 7IdlM 6IdlM 5IdlM 4IdlM 3IdlM 2IdlM 1IdlM 0
Data [7]IdlV 7IdlV 6IdlV 5IdlV 4IdlV 3IdlV 2IdlV 1IdlV 0
Where:
Filter = 0 to 65000 ms (0 = default)
Filter = 0 to 65535 ms (1000 = default)
FltM = Fault Mode (0 = Fault Value (default), 1 = Hold Last State)
FltV = Fault Value (0 = OFF (default), 1 = ON)
IdlM = Idle Mode (0 = Idle Value (default), 1 = Hold Last State)
IdlV = Idle Value (0 = OFF (default), 1 = ON)
POINT I/O Module with 8 Configurable 24V DC Points 17
Interpret the Indicators
See the figure and table that show how to interpret indicators.
Module
Module Status
Status
Network
Network Status
Status
NODE:
NODE:
24Vdc
SINK IN
SOURCE OUT
Status of I/O 0
Status of I/O 1
Status of I/O 2
Status of I/O 3
Indicator StateDescription
Module
status
OffNo power applied to device.
GreenDevice operating normally.
Flashing greenDevice needs commissioning due to configuration
missing, incomplete or incorrect.
Flashing redRecoverable fault.
RedUnrecoverable fault may require device replacement.
Flashing red/greenDevice is in self-test.
0
0
1
1
2
2
3
3
1734-8CFG
Status of I/O 4
4
Status of I/O 5
5
Status of I/O 6
6
Status of I/O 7
7
44688
Publication
1734-IN038A-EN-P - October 2008
18 POINT I/O Module with 8 Configurable 24V DC Points
Indicator StateDescription
Network
status
I/O statusOffInput is in the OFF state.
OffDevice is not online.
- Device has not completed dup_MAC_id test.
- Device not powered - check module status indicator.
Flashing greenDevice is online but has no connections in the
established state.
GreenDevice is online and has connections in the
established state.
Flashing redOne or more I/O connections in timed-out state.
RedCritical link failure - failed communication device.
Device detected error that prevents it communicating
on the network.
Flashing red/greenCommunication faulted device - the device has
detected a network access error and is in
communication faulted state.
Device has received and accepted an Identify
Communication Faulted Request - long protocol
message.
Output is in the OFF state.
Yel lowInput is in the ON state.
Output is in the ON state.
Publication
1734-IN038A-EN-P - October 2008
POINT I/O Module with 8 Configurable 24V DC Points 19
Specifications
Specifications for POINT I/O Module 1734-8CFG DC Input
AttributeValue
On-state voltage, min11V DC
On-state current, min2.0 mA
On-state current, max5.0 mA
Off-state voltage, max 5V DC
Off-state current, min1.5 mA
Input filterEach input independently settable in 1 ms intervals
Off to On filter, min0 ms
Off to On filter, max65535 ms
On to Off filter, min0 ms
On to Off filter, max65535 ms
Specifications for POINT I/O Module 1734-8CFG DC Output
AttributeValue
On-state voltage range, min10V DC
On-state voltage range, max28.8V DC
On-state voltage range, nom24V DC
On-state voltage drop, max0.4V DC
On-state current, max0.5 A
Off-state leakage, max0.5 mA
Module current (all outputs),
max
Surge current - for 100 ms,
repeatable every 2 s, max
(truncated to 1 ms resolution). Default value is 1000 ms.
3.0 A
1.0 A
Publication
1734-IN038A-EN-P - October 2008
20 POINT I/O Module with 8 Configurable 24V DC Points
General Specifications
AttributeValue
Module location1734-TB, 1734-TBS, 1734-TOP, and 1734-TOPS bases
POINTBus current, max100 mA @ 5V DC
Power dissipation, max2.6 W @ 28.8V DC
Thermal dissipation, max8.9 BTU/hr @ 28.8V DC
Isolation voltage 50V (continuous), Reinforced Insulation Type
Type tested at 2121V DC for 60 s, field-side to system
No isolation between individual channels
Field power bus
Supply voltage, nom
Voltage range
Dimensions HxWxL, approx.56 x 12 x 75.5 mm
Terminal block screw torqueDetermined by installed terminal block
Keyswitch position1
Reverse polarity protectionYes
Enclosure type ratingNone (open-style)
Wire sizeDetermined by installed terminal block.
Wire category
Pilot duty ratingNot rated
(1)
Use this Conductor Category information for planning conductor routing. Refer to
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
24V DC
10…28.8V DC
2.2 x 0.47 x 2.97 in.
1 - on signal ports
(1)
.
Publication
1734-IN038A-EN-P - October 2008
POINT I/O Module with 8 Configurable 24V DC Points 21
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
Publication
1734-IN038A-EN-P - October 2008
22 POINT I/O Module with 8 Configurable 24V DC Points
Environmental Specifications (Continued)
AttributeValue
EFT/B immunityIEC 61000-4-4:
±3 kV at 5 kHz on signal ports
Surge transient
immunity
Conducted RF immunityIEC 61000-4-6:
IEC 61000-4-5:
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Publication
1734-IN038A-EN-P - October 2008
Certifications
POINT I/O Module with 8 Configurable 24V DC Points 23
Certification (when
product is marked)
Value
(1)
CEEuropean Union 2004/108/EC EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates,
and other certification details.
Publication
1734-IN038A-EN-P - October 2008
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using
its products. At http://support.rockwellautomation.com
, you can find technical
manuals, a knowledge base of FAQs, technical and application notes, sample code and
links to software service packs, and a MySupport feature that you can customize to
make the best use of these tools.
For an additional level of technical phone support for installation, configuration, and
troubleshooting, we offer TechConnect support programs. For more information,
contact your local distributor or Rockwell Automation representative, or visit
http://support.rockwellautomation.com
.
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the
information that's contained in this manual. You can also contact a special Customer
Support number for initial help in getting your product up and running.
United States1.440.646.3434
Outside United StatesPlease contact your local Rockwell Automation representative for any
Monday – Friday, 8 a.m. – 5 p.m. EST
technical support issues.
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational
when shipped from the manufacturing facility. However, if your product is not
functioning and needs to be returned, follow these procedures.
United StatesContact your distributor. You must provide a Customer Support case number
Outside United StatesPlease contact your local Rockwell Automation representative for the return
Allen-Bradley, POINT I/O, POINTBus, Rockwell Automation, and TechConnect are trademarks of Rockwell
Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
(see phone number above to obtain one) to your distributor in order to
complete the return process.
procedure.
Publication 1734-IN038A-EN-P - October 2008PN 30356