Rockwell Automation 1732E-IR4IM12R User Manual

User Manual
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Isolated Thermocouple and RTD Input Modules
Catalog Numbers
1732E-IT4IM12R, 1732E-IR4IM12R
Important User Information
IMPORTANT
Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/ important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
) describes some
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
Identifies information that is critical for successful application and understanding of the product.
Allen-Bradley, Rockwell Automation, ArmorBlock, RSLogix 500 0, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.

Preface

Read this preface to familiarize yourself with the rest of the manual. It provides information concerning:
who should use this manual
the purpose of this manual
related documentation
conventions used in this manual
Who Should Use this Manual
Purpose of this Manual
Resource Description
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Modules 1732E-WD003
Use this manual if you are responsible for designing, installing, programming, or troubleshooting control systems that 1732E ArmorBlock™ EtherNet/IP Dual Port 4-Point Thermocouple and RTD Modules.
You should have a basic understanding of electrical circuitry and familiarity with relay logic. If you do not, obtain the proper training before using this product.
This manual is a reference guide for the 1732E-IT4IM12R, 1732E-IR4IM12R modules. It describes the procedures you use to install, wire, troubleshoot, and use your module.
Related Documentation
The following documents contain additional information concerning Rockwell Automation products. To obtain a copy, contact your local Rockwell Automation office or distributor.
Information on wiring the ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Modules (1732E-IF4M12R, 1732E-OF4M12R, 1732E-IT4IM12R, 1732E-IR4IM12R).
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules Installation Instructions, publication
1732E-IN005
EtherNet/IP Embedded Switch Technology Application Guide, publication ENET-AP005
EtherNet/IP Modules in Logix5000 Control Systems User Manual, publication ENET-UM001
Getting Results with RSLogix 5000, publication
9399-RLD300GR
Allen-Bradley Industrial Automation Glossary, AG-7.1
Common Techniques Used in this Manual
The following conventions are used throughout this manual:
Bulleted lists such as this one provide information, not procedural steps.
Information on installing the ArmorBlock EtherNet/IP module.
A manual on how to install, configure and maintain linear and Device-level Ring (DLR) networks using Rockwell Automation EtherNet/IP devices with embedded switch technology.
A manual on how to use EtherNet/IP modules with Logix5000 controllers and communicate with various devices on the Ethernet network.
Information on how to install and navigate RSLogix 5000. The guide includes troubleshooting information and tips on how to use RSLogix 5000 effectively.
A glossary of industrial automation terms and abbreviations.
Numbered lists provide sequential steps or hierarchical information.
Italic type is used for emphasis.
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 iii
Notes:
iv Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Table of Contents
Preface
Who Should Use this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iii
Purpose of this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iii
Related Documentation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iii
Common Techniques Used in this Manual. . . . . . . . . . . . . . . . . . . . . . . . . . iii
Chapter 1
Overview of the 1732E ArmorBlock Thermocouple and RTD Input Modules
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Module Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Physical Features of Your Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Types of Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Hardware/Software Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Thermocouple Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
RTD Sensor Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Module Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Digital Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Chapter Summary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Chapter 2
Install Your ArmorBlock Module
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Install the Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Mount the Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Wire the Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Chapter Summary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Cold Junction Compensation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Overrange Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Underrange Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Level Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Set the Network Address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Chapter 3
Configure Your Thermocouple and RTD Input Modules with RSLogix 5000 Software
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 v
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Set Up the Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Create the Example Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Configure Your I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
RSLogix 5000 Configuration Software . . . . . . . . . . . . . . . . . . . . . . . . . 16
Overview of the Configuration Process through RSLogix 5000. . . . . . . 16
Add a New Bridge and Module to Your RSLogix 5000 Project . . . . . . . 16
Add the Local EtherNet/IP Bridge to the I/O Configuration . . . . 17
Add the I/O module as a child of the 1756-EN2T module . . . . . . . 18
Download the Program to Your Controller . . . . . . . . . . . . . . . . . . . . . . . . 20
Table of Contents
Edit Your Module Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
General Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Connection Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Configuration Tab for 1732E-IR4IM12R . . . . . . . . . . . . . . . . . . . . . . 24
Configuration Tab for 1732E-IT4IM12R . . . . . . . . . . . . . . . . . . . . . . 26
Alarm Configuration Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Internet Protocol Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Calibration Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Status and Monitoring Tabs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Chapter Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Chapter 4
Configurable Features for the Thermocouple and RTD Input Modules
Calibrate Your Modules
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Configure Your Input Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Configurable Options and Their Effect on the Channels. . . . . . . . . . . . . 36
Sensor Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Temperature Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Notch Filter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Digital Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Cold Junction Compensation (1732E-IT4IM12R only) . . . . . . . . . 38
Data Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Chapter Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Chapter 5
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Calibrate the Thermocouple Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Calibrate the RTD Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Chapter Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Chapter 6
Troubleshoot the Module
Interpret Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Check for Faults. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Appendix A
Specifications
vi Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Input Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Environmental Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Appendix B
Table of Contents
1732E ArmorBlock Embedded Web Server
Module Tag Definitions
Index
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Typical Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Browser Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Access the Home Page of the Web Server. . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Log On to the Web Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Navigate the 1732E ArmorBlock I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Access Diagnostic Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Access Configuration Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Appendix C
Module Tags for 1732E-IT4IM12R . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Module Tags for 1732E-IR4IM12R . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Access the Module Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 vii
Table of Contents
Notes:
viii Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Chapter
Overview of the 1732E ArmorBlock Thermocouple and RTD Input Modules
1

Overview

Module Features

This chapter provides an introduction to the features and functionalities of the 1732E ArmorBlock Thermocouple and RTD Input Modules. It includes the following sections.
Topic Page
Module Features 1 Physical Features of Your Module 2 Types of Modules 3 Hardware/Software Compatibility 3 Thermocouple Types 3 RTD Sensor Types 4 Digital Filters 6 Module Alarms 5
The 1732E-IT4IM12R and 1732E-IR4IM12R modules let you configure a sensor type for each of four input channels that linearizes analog signal into a temperature value. The RTD module, 1732E-IR4IM12R, linearizes ohms into temperature and the Thermocouple module, 1732E-IT4IM12R, linearizes millivolts into temperature.
The modules have the following features:
Sensor type
Preset temperature selection
Fault mode
Level alarms
overrange and underrange detection
To learn more about module features, see Configurable Features for the
Thermocouple and RTD Input Modules on page 35.
You must use RSLogix 5000 to configure these features. For a detailed how-to­configure instructional guide, see the chapter, Configure Your Thermocouple
and RTD Input Modules with RSLogix 5000 Software on page 13.
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 1
Chapter 1 Overview of the 1732E ArmorBlock Thermocouple and RTD Input Modules
45871
Link 1 status indicator
EtherNet/IP D-code M12 connector
Node address switches
M12 style I/O connectors
Micro-style power in
Micro-style power out
I/O status indicators
EtherNet/IP D-code M12 connector
Link 2 status indicator
Node address switches
Network status indicator
Module status indicator
Auxiliary Power status indicator
Functional Earth Ground
(1)

Physical Features of Your Module

The modules have the following components:
Node address switches
Connectors (two EtherNet/IP D-code M12 connectors, two micro-style
Power in/out connectors, four I/O M12 connectors)
Status indicators (Link, I/O, Module, Network, and Auxiliary power status indicators)
Functional earth ground
Physical Features of 1732E-IT4IM12R and 1732E-IR4IM12R Modules
(1)
Functional Earth grounds the I/O block’s EtherNet/IP communication circuitry which is designed to mitigate the
effect of noise on the network. The device requires a solid earth ground connection, either through a metal screw to a grounded metal panel or through a wire.
2 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Overview of the 1732E ArmorBlock Thermocouple and RTD Input Modules Chapter 1

Types of Modules

Hardware/Software Compatibility

The Thermocouple and RTD modules are as follows.
Catalog Number Description Network
1732E-IT4IM12R 24V DC power, 4-Point Isolated
Thermocouple Input, Dual-Port EtherNet/IP Module
1732E-IR4IM12R 24V DC power, 4-Point Isolated RTD
Input, Dual-Port EtherNet/IP Module
Connector
Dual D-code M12
Power Connector
Dual 4-pin micro
The module and the applications described in this manual are compatible with the following firmware versions and software releases.
Product Firmware Version / Software Release
1732E-IT4IM12R and 1732E-IR4IM12R Firmware rev. 1.1 or later 1756-EN2T, 1756-EN2TR, 1756-EN3TR 3.x version when using RSLogix 5000 v20 or later RSLogix 5000 software 20 or later RSLinx software 2.56 or later

Thermocouple Types

The 1732E-IT4IM12R module supports the following thermocouples.
Supported Thermocouple Types
Type Material Temperature Range
B Pt /30% Rh vs. Pt/5% Rh 40…1820 (104…3308) 0.000…13.820 mV C W/5% Re vs. W/26% Re 0…2320 (32…4208) 0.000…37.107 mV E Ni/Cr vs. Cu/Ni -270…1000 (-454…1832) -9.835…76.373 mV J Fe vs. Cu/Ni -210…1200 (-346…2192) -8.095…69.553 mV K Ni/Cr vs. Ni/Al -270…1372 (-454…2501.6) -6.458…54.886 mV N Ni/14.2%Cr/1.4%Si vs.
Ni/4.4%Si/0.1%Mg R Pt/13%Rh vs. Pt -50…1768 (-58…3214.4) -0.226…21.101 mV S Pt/10%Rh vs. Pt -50…1768 (-58…3214.4) -0.236…18.693 mV T Cu vs. Cu/Ni -270…400 (-454…752) -6.258…20.872 mV
°C (°F)
-270…1300 (-454…2372) -4.345…47.513 mV
Voltage Range
Cold Junction Compensation
When using thermocouples, cold junction compensation is required at the termination of the thermocouple wire. The actual cold junction exists outside of the module at the wiring block internal to the CJC module and is representative of the ambient temperature.
Accomplish a cold junction in the following ways:
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 3
Chapter 1 Overview of the 1732E ArmorBlock Thermocouple and RTD Input Modules
Thermistor resistance used by the module to determine a baseline for the thermocouple
Thermocouple
Hot junction
Cold junction
Face of module connector
871A-TS4CJC-DM or 871A-TR4CJC-DM Terminal Chamber shown
Enter an estimated temperature (Cold Junction Compensation Offset).
Use external cold junction compensators to measure the cold junction
temperature directly.
To compensate for cold junction temperature voltage, the 1732E-IT4IM12R Thermocouple module has to determine actual cold junction temperature. If the module is configured to provide cold junction compensation, then the user must use a CJC Terminal Chamber (such as Allen-Bradley 871A-TS4CJC-DM or
871A-TR4CJC-DM
(1)
as shown in the next diagram).
The module uses this thermistor(s) resistance to deduce the cold junction generated voltage to be applied to accurately measure the hot junction absolute temperature.

RTD Sensor Types

The compensation voltage to be applied can also be estimated by applying fixed cold junction correction using a fixed offset directly through the RSLogix 5000 software. The module supports thermistor compensation range at 0…70 °C.
The Thermocouple module also supports CJC error detection if a channel CJC module is selected but is not correctly connected to the correct channel. The module detects open circuit condition and triggers the warning status bit and fault LED.
Cold junction compensation is supported on all four channels of the 1732E-IT4IM12R module.
The 1732E-IR4IM12R module supports 100Ω- 200Ωμ = 0.00385/0.003916 Pt RTDs, 100/120Ω Ni RTDs, and a 10Ω Cu α =0.00427 RTD.
(1) The Allen-Bradley 871A-TS4CJC-DM or 871A-TR4CJC-DM terminal chamber has an embedded thermistor,
which facilitates thermocouple-based temperature measurement. The thermistor types supported are Thermometrics MF65F302V/W, or DC95F302V/W.
4 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Overview of the 1732E ArmorBlock Thermocouple and RTD Input Modules Chapter 1
It supports 3-wire and 2-wire RTDs using a jumper in the wiring at the input connector of the module. The following RTD input types are supported.
Supported RTD Types
RTD type Temperature Range °C (°F) Voltage Range
100 Ω Pt 385 0…390.48 Ω -200…850 °C (-328…1562 °F) 0…150 mV 200
Ω
Pt 385 0…781 Ω -200…650 °C (-328…1202 °F) 0…300 mV
100 Ω Pt 3916 0…337.03 Ω -200…630 °C (-328…1166 °F) 0…156.25 mV 200 Ω Pt 3916 0…674.06 Ω -200…630 °C (-328…1166 °F) 0…312.5 mV 10
Ω
Cu 427 0…19.116 Ω -320…500 °C (-544…932 °F) 0…19.47 mV
120 Ω Ni 672 0…445.10 Ω -70…445 °C (-94…833 °F) 0…156.25 mV 100 Ω Ni 618 0…198.88 Ω -60…180 °C (-76…356 °F) 0…75 mV 120
Ω
Ni 618 0…238.65 Ω -90…140 °C (-130…284 °F) 0…75 mV
The module uses a third sensor wire to measure and correct for the cable lead resistance for each RTD type. The compensation circuit depends on an outside module jumper to connect the third wire if the compensating lead wire is not available (that is, if a 2-wire RTD is connected to the I/O connector).

Module Alarms

If the lead resistance is not directly measured with the third lead wire, the user can specify a lead wire resistance offset to be applied to the data for direct compensation via RSLogix 5000.
The ArmorBlock Thermocouple and RTD modules are capable of generating the following alarms.
Overrange
Und erra ng e
Level (low, low-low, high, high-high)
Open-wire detection
Overrange Alarm
The channel overrange alarm is set if the input is greater than the maximum temperature (thermocouple or RTD range dependent), millivolt (+78 mV) or resistance (600 Ω) range value, or above the maximum range of the thermocouple or RTD.
Underrange Alarm
The channel underrange alarm is set if the input is less than the minimum temperature (thermocouple or RTD range dependent), millivolt (-78 mV) or
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 5
Chapter 1 Overview of the 1732E ArmorBlock Thermocouple and RTD Input Modules
resistance (10 Ω) range value, or below the minimum range of the thermocouple or RTD.
Level Alarms
The following level alarms are available.
Low
Low-Low
High
High-High
When the channel input goes below a low alarm or above a high alarm, a bit is set in the data table. All Alarm Status bits can be read individually or by reading the Channel Status Byte (see page 35
You can configure each channel alarm individually.
).

Digital Filters

Chapter Summary

The modules also support a digital filter to smooth input data noise transients on each input channel. This value specifies the time constant for a digital first order lag filter on the input. It is specified in units of milliseconds. A value of 0 disables the filter.
To learn how to configure digital filters, see page 21
In this chapter, you were introduced to the ArmorBlock Thermocouple and RTD input modules.
.
6 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Install Your ArmorBlock Module
Chapter
2

Overview

Install the Module

This chapter shows you how to install and wire the 1732E ArmorBlock EtherNet/IP Dual Port 4-Point Thermocouple and RTD Input modules. The only tools you require are a flat or Phillips head screwdriver and drill. This chapter includes the following topics:
Topics Page
Install the Module 7 Set the Network Address 7 Mount the Module 9 Wire the Module 10
To install the module:
Set the network address
Mount the module
Connect the I/O, Network, and Auxiliary cables to the module.
Set the Network Address
The I/O block ships with the rotary switches set to 999 and DHCP enabled. To change the network address, you can do one of the following:
adjust the node address switches on the front of the module.
use a Dynamic Host Configuration Protocol (DHCP) server, such as
Rockwell Automation BootP/DHCP.
retrieve the IP address from nonvolatile memory.
The I/O block reads the switches first to determine if the switches are set to a valid number. To set the network address:
1. Remove power.
2. Remove the switch dust caps.
3. Rotate the three (3) switches on the front of the module using a small
blade screwdriver.
4. Line up the small notch on the switch with the number setting you wish to use. Valid settings range from 001…254.
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 7
Chapter 2 Install Your ArmorBlock Module
44233
Note: You need to remove the protective switch dust caps before you can adjust the address settings.
Example shows network switches set at 163, which sets the module IP address to 192.168.1.163.
5. Replace switch dust caps. Make sure not to over tighten.
6. Reapply power.
7. Record IP address on product label found on the side of enclosure.
Set Network Address
2
0
2
4
0
6
8
4
8
6
2
0
4
6
8
When the switches are set to a valid number, the I/O block’s IP address is
192.168.1.xxx, where xxx represents the number set on the switches. The I/O block’s subnet mask is 255.255.255.0 and default gateway address is set to
192.168.1.1.
When the I/O block uses the network address set on the switches, the I/O block does not have a host name assigned to it or use any Domain Name Server.
If the switches are set to an invalid number (for example, 000 or a value greater than 254 excluding 888), the I/O block checks to see if DHCP is enabled. If DHCP is enabled, the I/O block asks for an address from a DHCP server. The DHCP server also assigns other Transport Control Protocol (TCP) parameters. (The modules are shipped with the network switches set to 999.)
If DHCP is not enabled, the I/O block uses the IP address (along with other TCP configurable parameters) stored in nonvolatile memory.
Network Address Switch value 001
The module IP address cannot be the same as the gateway address. If the address switches are set to 001, the module IP address becomes 192.168.1.1, which is the same as the default gateway address. In this case, the module gateway address will be set to 0.0.0.0.
Default Factory Configuration
The switch value 888 resets the module to default factory configuration on power up. The module will not operate properly when powered up with this setting. The switches must be set to a different (and valid) value and then power cycled after a reset.
8 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
While in reset state, the module LED flashes red and the network LED goes off.
Install Your ArmorBlock Module Chapter 2
37 (1.46)
16.2 (0.64)
168.6 (6.64)
(1.26)
32
(1.70)
43.3
(0.78)
19.8
166.5 (6.56)
27
(1.06)
6LGH0RXQWLQJ
)URQW0RXQWLQJ
179 (7.05)
18
(0.71)
Millimeters (Inches)
45870
Functional Earth
Grounds the I/O block EtherNet/IP communication circuitry which is designed to mitigate the effect of noise on the network. It requires a solid earth ground connection, either through a metal screw to a grounded metal panel or through a wire.

Mount the Module

To mount the module on a wall or panel, use the screw holes provided in the module. Refer to the drilling dimensions illustration to guide you in mounting the module.
Mounting Dimensions
Install the mounting base as follows:
1. Lay out the required points as shown above in the drilling dimension drawing.
2. Drill the necessary holes for #6 (M3) pan head screws.
3. Mount the module using #6 (M3) screws.
Mount the Module in High Vibration Areas
If you mount the module in an area that is subject to shock or vibration, we recommend you use a flat and a lock washer to mount the module. Mount the flat
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 9
Chapter 2 Install Your ArmorBlock Module
45768
Lock washer
Flat washer
3
4
1
2
5
45868
(View into connector) Pin 1CJC + Pin 2TC + Pin 3CJC ­Pin 4TC ­Pin 5No Connect
3
4
1
2
5
45868
(View into connector) Pin 1No Connect Pin 2A Pin 3B Pin 4C Pin 5No Connect
and the lock washer as shown in the mounting illustration. Torque the mounting screws to 0.68 Nm (6 lb-in.).
High Vibration Area Mounting

Wire the Module

The 1732E-IT4IM12R and 1732E-IR4IM12R modules have 5-pin micro-style M12 I/O connectors. We provide caps to cover the unused connectors on your module. Connect the quick-disconnect cord sets you selected for your module to the appropriate ports.
I/O Connectors
Micro-style M12 5-Pin Input Female Connector – 1732E-IT4IM12R
Micro-style M12 5-Pin Input Female Connector – 1732E-IR4IM12R
(1)
A
B C
10 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
(1) Only 4 of the 5 pins are active. The center pin (5) is internally tied to signal ground to minimize
external noise pickup.
Ethernet Connector
IMPORTANT
IMPORTANT
4
2
3
1
5
(View into connector 1) Pin 1 M12_Tx+ Pin 2 M12_Rx+ Pin 3 M12_Tx­Pin 4 M12_Rx­Pin 5 Connector shell shield GND
44808
D-Code M12 Pin
Wire Color Signal 8-way
Modular RJ45 Pin
1White-
orange
TX+ 1
2 White-green RX+ 3 3 Orange TX- 2 4 Green RX- 6
1
4
3
2
Male Input
Female Output
(View into receptacle) Pin 1 Auxiliary power+ Pin 2 Module power+ Pin 3 Module power­Pin 4 Auxiliary power-
45764
3
4
1
2
45763
D-Code Micro Network Female Connector
Use the 1585D–M4DC–H: Polyamide small body unshielded mating connectors for the D-Code M12 female network connector.
Note that the distance between the center of each Ethernet connector is 16.2 mm (see Mounting Dimensions on page 9 recommends the use of suitable cable based on this measurement. Some of the recommended cables are 1585D-M4TBJM-x and 1585D­M4TBDM-x for daisychains.
Install Your ArmorBlock Module Chapter 2
). Rockwell Automation
Use two twisted pair CAT5E UTP or STP cables.
Power Connectors
Attach the micro-style 4-pin connector to the micro-style 4-pin receptacle as shown below.
Micro-style 4-Pin Input Male Receptacle
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 11
The power required by the module is based on a 4-pin micro-style connector system. Power can be daisy chained through the module either left to right or right to left. The standard configuration is with Module/Auxiliary power entering the module on the left connector.
Chapter 2 Install Your ArmorBlock Module
IMPORTANT
Both modules require two 24V DC (nominal) supplies. These supplies are called the Module Power and the Auxiliary Power. The Module power supplies the microprocessor and Ethernet portions of the module, while Auxiliary power supplies the I/O circuits.
Internally, the Module Power and Auxiliary Power are electrically isolated.
The maximum current that any pin on the power connectors can carry is 4 A.
ATTENTION: To comply with the CE Low Voltage Directive (LVD), this equipment and all connected I/O must be powered from a source compliant with the following: Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).
ATTENTION: To comply with UL restrictions, this equipment must be powered from a source compliant with the following: Limited Voltage/ Limited Current.
ATTENTION: The device meets UL Type 1 Enclosure rating.

Chapter Summary

In this chapter, you learned how to install and wire your module.
12 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Chapter
3
Configure Your Thermocouple and RTD Input Modules with RSLogix 5000 Software

Introduction

This chapter guides you through the steps required to configure your modules using the RSLogix 5000 software. Note that the modules presented in this chapter can be configured using RSLogix 5000 software, version 20, or later.
Topic Page
Set Up the Hardware 14 Create the Example Application 15 Configure Your I/O Module 16 Overview of the Configuration Process through RSLogix 5000 16 Add a New Bridge and Module to Your RSLogix 5000 Project 16 Download the Program to Your Controller 20 Edit Your Module Configuration 21 Chapter Summary 33
Configuring the two modules through RSLogix 5000 involve the same general procedure. Note, however, that the two modules do not have exactly similar Module Definition properties. These are distinctly covered in this chapter.
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 13
Chapter 3 Configure Your Thermocouple and RTD Input Modules with RSLogix 5000 Software
Local
Chassis
1732E ArmorBlock
Logix5565 Controller (slot 1)
1756-EN2T
192.168.1.20 (slot 3)
Data
Switch
192.168.1.100
Programming Terminal
0
1732E ArmorBlock
Ethernet Module
192.168.1.3
44971
32Slot 1
Embedded Technology

Set Up the Hardware

In this example, a ControlLogix chassis contains the Logix5565 processor in slot 1 and a 1756-EN2T bridge module in slot 3. The 1732E ArmorBlock module is mounted remotely.
Logix5565
EtherNet/IP
Logix5565
1756-EN2T
To work along with this example set up your system as shown.
Note that in the example application, the Logix5565 controller and 1756-EN2TR module (firmware version 2.3 or higher) are assumed to be in the slots shown.
Verify the IP addresses for your programming terminal, 1756-EN2TR module and 1732E ArmorBlock Ethernet module.
Verify that you connected all wiring and cabling properly.
Be sure you configured your communication driver (for example,
AB_ETH-1 or AB-ETHIP-1) in RSLinx software.
14 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Configure Your Thermocouple and RTD Input Modules with RSLogix 5000 Software Chapter 3

Create the Example Application

Perform the following steps to create the example application:
1. From the File menu, select New.
The New Controller dialog opens.
2. Enter an appropriate name for the Controller, for example, ArmorBlock_IO_Controller.
3. Select the correct version, chassis type, and slot number of the controller, and the folder where you want to save the RSLogix 5000 software file (Create In). The Description is optional.
To use redundancy in your system, select the Redundancy Enabled checkbox.
4. Click OK.
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 15
Chapter 3 Configure Your Thermocouple and RTD Input Modules with RSLogix 5000 Software
IMPORTANT

Configure Your I/O Module

Overview of the Configuration Process through RSLogix 5000

You must configure your module upon installation. The module will not work until it has been configured with at least the default configuration.
RSLogix 5000 Configuration Software
You must use RSLogix 5000, version 20 or later, to configure your module. You have the option of accepting default configuration for your module or writing point-level configuration specific to your application.
Both options are explained in detail, including views of software screens, in this chapter.
When you use the RSLogix 5000 software to configure a module, you must perform the following steps:
1. Add the Local EtherNet/IP Bridge (1756-EN2T, 1756-EN2TR, or 1756-EN3TR) to your project’s I/O Configuration.
2. Add the 1732E-IT4IM12R or 1732E-IR4IM12R module as a child of the 1756-EN2T module.

Add a New Bridge and Module to Your RSLogix 5000 Project

3. Accept the default configuration or change it to specific configuration for the module.
4. Edit configuration for a module when changes are needed.
After you have started RSLogix 5000 software and created a controller, you must add a new bridge and a new module to your project. The bridge allows your module to communicate with the controller.
The wizard allows you to create a new module and write configuration. You can use default configuration or write specific configuration for your application.
Click Help on the configuration dialogs shown in this section if you need assistance in selecting and setting the parameters.
16 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Configure Your Thermocouple and RTD Input Modules with RSLogix 5000 Software Chapter 3
If you are not offline, use this pull-down menu to go offline.
A. Right-click 1756 Backplane.
B. Select New Module.
A. Select the 1756-EN2T
EtherNet/IP Bridge.
B. Click OK.
Add the Local EtherNet/IP Bridge to the I/O Configuration
1. If necessary, go offline.
2. Add the EtherNet/IP Bridge to your RSLogix 5000 project.
3. Expand Communications and select the new module in the Select Module
dialog that appears. Select the 1756-EN2T EtherNet/IP Bridge.
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 17
Chapter 3 Configure Your Thermocouple and RTD Input Modules with RSLogix 5000 Software
A. Name the bridge.
B. Enter the IP address.
C. Select slot 3 for the EtherNet/IP bridge.
D. Make sure the Minor Revision number
matches your module revision number.
E. Choose an Electronic Keying method.
For more information, see page 22
.
F. Click OK.
4. The New Module dialog opens. Configure the bridge module as illustrated below.
Note that we have entered the following properties in this example:
Name TEST_1756EN2T IP address 192.168.1.20 Slot 3 Revision 3.1 Electronic Keying Compatible Module
The local 1756-EN2T communication module will communicate with the 1732E ArmorBlock module on Ethernet. Before you can communicate with your module, you need to add it as a child of the 1756-EN2T communication module. For more information about using 1756 controller and EtherNet/IP products, see publication ENET-UM001
.
Add the I/O module as a child of the 1756-EN2T module
1. Right-click the Ethernet folder that appears below the 1756-EN2T bridge you added to the I/O Configuration tree and select New Module.
18 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Configure Your Thermocouple and RTD Input Modules with RSLogix 5000 Software Chapter 3
TIP
2. On the Select Module Type dialog that appears, select the 1732E-IT4IM12R module. Click Create. To look for the 1732E-IT4IM12R module in the list, you can type the catalog number in the search box or use the filters. To do so, click Clear Filters and check Analog in the Module Type Category Filters.
If the 1732E-IT4IM12R, 1732E-IR4IM12R modules are not listed under the analog category of the Select Module Type dialog you may need to download the Add-On Profile (AOP) for the 1732E ArmorBlock 2-Port and install it as an add-on to RSLogix 5000. The AOP file can be downloaded from:
support.rockwellautomation.com/controlflash/LogixProfiler.asp
3. The New Module dialog appears. Fill in the Module Properties information as shown, and then click OK.
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 19
Chapter 3 Configure Your Thermocouple and RTD Input Modules with RSLogix 5000 Software
A. Click here to see the
pull-down menu.
B. Click download.
Note that we have used the following properties in this example:
Field Name Value
Name TEST_1732EIT4IM12R IP address 192.168.1.3 Electronic keying Compatible Module Revision 1.1 Connection Input Only
To add the 1732E-IR4IM12R RTD module, follow the same steps. After adding the modules to your project, the I/O Configuration tree should appear as follows:

Download the Program to Your Controller

This example uses default Module Definition and configuration properties. To edit your configuration, see Edit Your Module
Configuration on page 21.
After you write configuration for your module, the module does not use this configuration until you download it to the owner-controller. The download transfers the entire program to the controller, overwriting any existing program.
Download module configuration as shown below:
Depending on your application, a variety of RSLogix 5000 software screens may appear to choose a path to your ControlLogix controller and to verify the download. Navigate those screens as best fits your application.
This completes the download process.
20 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Configure Your Thermocouple and RTD Input Modules with RSLogix 5000 Software Chapter 3
IMPORTANT
TIP

Edit Your Module Configuration

RSLogix 5000 programming software automatically creates module-defined data types and tags when a module is created. This section describes how to modify the default configuration for input modules.
Data types symbolically name module configuration, input and output data. Tags let you provide each a unique name, such as where the user-defined data type and slot reside on the controller. This information is used to communicate data between the controller and module.
After you have set configuration for a module, you can review and change your choices. You can change configuration data and download it to the controller while online. This is called dynamic reconfiguration.
Your freedom to change some configurable features, though, depends on whether the controller is in Remote Run Mode or Program Mode.
Although you can change configuration while online, you must go offline to add or delete modules from the project.
The editing process begins on the main page of RSLogix 5000 software.
1. On the I/O Configuration tree for your project in RSLogix 5000, right-click the name of your module.
2. Select Properties. The Module Properties dialog appears and has the following tabs available for configuration.
3. Click any of the tabs to edit the parameters for your module. The next sections show you how to edit the different tabs in the Module Properties dialog.
Tabs can be selected in any order. The following examples are for instructional purposes.
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 21
Chapter 3 Configure Your Thermocouple and RTD Input Modules with RSLogix 5000 Software
General Tab
The General tab allows you to edit general properties such as Name, IP Address, and Description for your module.
You also can edit Module Definition properties such as revision, electronic keying, and data. To do so, click Change.
Module Definition Fields
Field Name Description
Series Specifies the module series. Revision Specifies the module’s major and minor revision. Electronic Keying The electronic keying feature automatically compares the expected
module, as shown in the RSLogix 5000 I/O Configuration tree, to the physical module before I/O communication begins. You can use electronic keying to help prevent communication to a module that does not match the type and revision expected.
For each module in the I/O Configuration tree, the user-selected keying option determines if, and how, an electronic keying check is performed.
Typically, three keying options are available:
Exact Match
Compatible Module (default value)
Disable Keying Exact Match is an electronic keying protection mode that requires the
physical module and the module configured in the software to match according to vendor, catalog number, major revision and minor revision.
Compatible Module indicates that the module determines whether to accept or reject communication. Compatible Keying is the default setting. It allows the physical module to accept the key of the module configured in the software, provided that the configured module is one the physical module is capable of emulating. The exact level of emulation required is product and revision specific.
Disable Keying indicates the keying attributes are not considered when attempting to communicate with a module. Other attributes, such as data size and format, are considered and must be acceptable before I/O communication is established. With Disabled Keying, I/O communication may occur with a module other than the type specified in the I/O configuration tree with unpredictable results. We generally do not recommend using Disabled Keying.
22 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Configure Your Thermocouple and RTD Input Modules with RSLogix 5000 Software Chapter 3
Module Definition Fields
Field Name Description
Connection Available options are Data, Input Only, Exclusive Owner, and Listen Only.
Calibration and Configuration options are not available for Listen Only option.
Input Only specifies an independent connection where a device receives inputs from the target device and sends configuration data to the target device. An Input Only connection does not send outputs; it only receives inputs. You can specify multiple Input Only connections to the target device from different originators.
Exclusive Owner specifies an independent connection where a single device controls the output states in the target device. If you have an existing Exclusive Owner connection to a target device, you cannot specify another Exclusive Owner or Redundant connection to that same target device.
Listen Only specifies a dependent connection where a device receives inputs from the target device, but does not send configuration data with the target device. A Listen Only connection only functions properly when another non-Listen Only connection exists to the same target device. A Listen Only connection does not send outputs; it only receives inputs. You can specify multiple Listen Only connections to the target device from different originators.
Connection Tab
The Connection tab on the Module Properties dialog box lets you enter a requested packet interval (RPI), inhibit a module, and set a connection fault when the controller is in Run mode. The RPI provides a defined, maximum period of time when data is transferred to the owner-controller.
1. Choose from the options on the Connection tab.
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 23
Chapter 3 Configure Your Thermocouple and RTD Input Modules with RSLogix 5000 Software
Connection Tab Fields
Field Description
Requested Packet Interval (RPI) (ms)
Inhibit Module Check the box to prevent communication between the ownercontroller
Major fault On Controller If Connection Fails While in Run Mode
Use Unicast Connection over EtherNet/IP
Module Fault The fault box is empty if you are offline. The type of connection fault
A user-defined rate at which the module updates the information sent to its owner-controller.
This interval defines the slowest rate at which a module sends its data to the owner-controller. The time ranges from 2.0…750 ms and is sent to the module with all other configuration parameters.
and the module. This option allows for maintenance of the module without faults being reported to the controller.
Check the box to create a major fault if there is a connection failure with the controller while in Run mode.
This option is enabled by default. Unicast connections are point to point transmissions between a
source node and destination node on the network. A Frame is sent to a single destination.
appears in the text box if a fault occurs when the module is online.
2. Do one of the following:
Click Apply to store a change but stay on the dialog box to choose another tab.
Click OK if you are finished making changes.
Configuration Tab for 1732E-IR4IM12R
The Configuration tab on the Module Properties dialog box lets you program information on each of the four channels on the 1732E-IR4IM12R module.
24 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Configure Your Thermocouple and RTD Input Modules with RSLogix 5000 Software Chapter 3
Default value: 60 Hz
1. Choose from the options on the Configuration tab.
Configuration tab
Field Description
Channel Indicates the four input channels 0…3. Sensor Type Specifies the sensor type for each channel.
To learn more about sensor types, see Sensor Type
Units Refers to the temperature unit that will be used.
Digital Filter Choose a value in milliseconds that specifies the time constant for a
Notch Filter
High Engineering Low Engineering
Available in °C and °F. When the RTD sensor type is set to Ohms, the temperature unit field
is not available.
digital first order lag filter on the input. A value of 0 disables the filter. Valid filter range is 1…10000.
An analog-to-digital converter (ADC) filter removes line noise in your application for each channel. Choose a notch filter that most closely matches the anticipated noise
frequency in your application. Remember that each filter time affects the response time of your module. Also, the highest frequency notch filter settings also limit the effective resolution of the channel.
High Engineering and Low Engineering values are determined by the Sensor Type selected for each channel. The corresponding values for each sensor type are listed in the table, High Engineering and Low
Engineering Values for 1732E-IR4IM12R on page 25.
on page 36.
2. Do one of the following:
Click Apply to store a change but stay on the dialog box to choose another tab.
Click OK if you are finished making changes.
High Engineering and Low Engineering Values for 1732E-IR4IM12R
RTD Sensor Type Units Low
Engineering
Ohms N/A 0 5000 100 Ω Pt 385 °C -2000 8500
°F -3280 15620
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 25
High Engineering
Chapter 3 Configure Your Thermocouple and RTD Input Modules with RSLogix 5000 Software
High Engineering and Low Engineering Values for 1732E-IR4IM12R
RTD Sensor Type Units Low
Engineering
200 Ω Pt 385 °C -2000 6300
°F -3280 11660
100 Ω Pt 3916 °C -2000 6500
°F -3280 12020
200 Ω Pt 3916 °C -2000 6500
°F -3280 12020
10 Ω Cu 427 °C -1000 2600
°F -1480 5000
120 Ω Ni 672 °C -800 2600
°F -1120 5000
100 Ω Ni 618 °C -600 1800
°F -760 3560
120 Ω Ni 618 °C -900 1400
°F -1300 2840
Configuration Tab for 1732E-IT4IM12R
High Engineering
26 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Configure Your Thermocouple and RTD Input Modules with RSLogix 5000 Software Chapter 3
Default value: 60 Hz
1. Choose from the options on the Configuration tab.
Configuration tab
Field Description
Channel Indicates the four input channels 0…3. Sensor Type Specifies the sensor type for each channel.
To learn more about sensor types, see Sensor Type
Units Refers to the temperature unit that will be used.
Digital Filter Choose a value in milliseconds that specifies the time constant for a
Notch Filter
High Engineering Low Engineering
Enable Cold Junction Compensation
Available in °C and °F. When the Thermocouple sensor type is set to mV, the temperature
unit field is not available.
digital first order lag filter on the input. A value of 0 disables the filter. Valid filter range is 1…10000.
Use the default (60 Hz) or choose a frequency that attenuates the input signal at this specified frequency.
See Notch Filter on page 37 for more information. High Engineering and Low Engineering values are determined by the
Sensor Type selected for each channel. This parameter enables or disables the use of the external cold
junction compensation for the channel. If enabled, the proper cold junction compensation value is applied to the selected thermocouple as determined by the external thermistor. If disabled, the data (cold junction temperature) is still available but not applied to the input. A cold junction value can be added using the Cold Junction Offset parameter.
Cold Junction Compensation is supported on all four channels of the thermocouple module.
For more information, see Cold Junction Compensation (1732E-
IT4IM12R only) on page 38.
on page 36.
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 27
Chapter 3 Configure Your Thermocouple and RTD Input Modules with RSLogix 5000 Software
Click Channel button to set limits and alarm configuration for each of the 4 channels.
Use the sliders to set limits. HH slider sets High High limits; HI sets High limits; LL for Low Low; and LO for Low.
Configuration tab
Field Description
Cold Junction Compensation Offset
Cold Junction Compensation Mode
Select Channels for Averaging
Cold Junction Compensation Offset lets you manually enter a cold junction temperature. This can only be done if the external cold junction compensation is disabled.
If there is no thermistor available, and the ambient temperature is known to be, for example, 28.00 °C (82.40 °F), you can type the value into the box to provide the cold junction compensation.
For more information, see Cold Junction Compensation (1732E-
IT4IM12R only) on page 38.
When the cold junction is enabled, the mode determines where the temperature measurement source (the thermistor) is located. Valid values are Channel Independent, or Average Selected.
See Cold Junction Compensation (CJC) Mode on page 39 to learn more about the CJC modes.
This option is only available if the Cold Junction Compensation Mode is Average Selected. It allows you to select all the channels that have a thermistor attached.
When a single channel is selected, the thermistor attached to that channel provides the compensation temperature for all channels. When more than one channel is selected, the temperature used by the selected channels is averaged across all selected channels that have a valid thermistor detected.
Alarm Configuration Tab
The Alarm Configuration tab on the Module Properties dialog box lets you program high and low limits, and disable and latch alarms per channel.
28 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Configure Your Thermocouple and RTD Input Modules with RSLogix 5000 Software Chapter 3
1. Choose from the options on the Alarm Configuration tab.
Alarm Configuration tab
Field What to do Description
Channel Select a push button
to correspond to a channel (0…3)
Process Alarms Type a value for each of the four alarm trigger
High-High Set from
-32,768...32,767
High Set from
-32,768...32,767
Low Set from
-32,768...32,767
Low-Low Set from
-32,768...32,767
Disable All Alarms Click to check the
checkbox
Latch Process Alarms Click to check the
checkbox
Click the channel that is being configured.
points that alert you when the module has exceeded these limitations.
You also can use the respective slider icon to set a trigger value.
The Unlatch buttons are enabled only when the module is online.
Select a value so that any value out of range in this field causes a profile validation error. This value also appears in the HH slider on
this dialog. Select a value so that any value out of range in this
field causes a profile validation error. This value also appears in the HI slider on this dialog.
Select a value so that any value out of range in this field causes a profile validation error. This value also appears in the LO slider on this dialog.
Select a value so that any value out of range in this field causes a profile validation error. This value also appears in the LL slider on this dialog.
Check the box to disable all alarms. Important: When you disable all alarms, you
disable process, and channel diagnostic alarms (for example, underrange and overrange). We recommend that you disable only unused channels so extraneous alarm bits are not set.
Check the box to latch an alarm in the set position even if the condition that causes the alarm disappears.
Click to unlatch all alarms together. This feature is disabled when offline
2. After the channels are configured, do one of the following:
Click Apply to store a change but stay on the dialog box to choose another tab.
Click OK to apply the change and close the dialog box.
Click Cancel to close the dialog box without applying changes.
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 29
Chapter 3 Configure Your Thermocouple and RTD Input Modules with RSLogix 5000 Software
Internet Protocol Tab
1. To configure your IP settings, click the Internet Protocol tab. This tab is only available for editing when the device is online. To manually configure your IP settings, specify the IP address in the Physical Module IP Address field.
2. On the other fields (Domain Name, Host Name, Primary DNS Server Address, Secondary DNS Server Address), specify the corresponding parameter. Click Set and then click OK.
Port Configuration Tab
30 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Configure Your Thermocouple and RTD Input Modules with RSLogix 5000 Software Chapter 3
IMPORTANT
To configure the Ethernet ports, click the Port Configuration tab. This tab is only available for editing when the device is online.
To configure the ports:
To Then
Use the default port speed and duplex settings Leave Auto-negotiate port speed and duplex
Manually configure your port’s speed and duplex settings
Consider the following when you configure the module’s port settings:
If the module is connected to an unmanaged switch, leave Auto-negotiate port
speed and duplex checked or the module will fail.
If you are forcing the port speed and duplex with a managed switch, the
corresponding port of the managed switch must be forced to the same settings or the module will fail.
checked. This setting determines the actual speed and duplex setting.
Follow these steps.
1. Clear the Auto-negotiate port speed and duplex checkbox.
2. From the Current Port Speed pull-down menu, choose a port speed.
3. From the Current Duplex pull-down menu, choose the appropriate Duplex value, that is, Half Duplex or Full Duplex.
Calibration Tab
The Calibration tab on the Module Properties dialog box lets you recalibrate the module, if necessary. Calibration corrects any hardware inaccuracies on a particular channel.
Calibration is available on a per-channel basis for both Thermocouple and RTD modules. Calibration points for the Thermocouple module is 0 and 78.125 mV for each channel. For the RTD module, calibration endpoints are dependent on the sensor type configured for each channel.
For a step-by-step guide on how to calibrate your modules, see Calibrate Your
Modules on page 45.
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 31
Chapter 3 Configure Your Thermocouple and RTD Input Modules with RSLogix 5000 Software
Status and Monitoring Tabs
Although each dialog box maintains importance during online monitoring, some of the tabs, such as the Module Info and Network, are blank during the initial module configuration. You can refer to these tabs
32 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Configure Your Thermocouple and RTD Input Modules with RSLogix 5000 Software Chapter 3
Check the status of your module using these tabs.

Chapter Summary

This chapter provided instructions on how to configure the 1732E ArmorBlock Thermocouple and RTD modules through the RSLogix 5000 software.
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 33
Chapter 3 Configure Your Thermocouple and RTD Input Modules with RSLogix 5000 Software
Notes:
34 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Chapter
4
Configurable Features for the Thermocouple and RTD Input Modules

Overview

Configure Your Input Modules

This chapter describes how the different configuration parameters affect the Thermocouple and RTD input channels. It also includes the data structure for both modules.
Topic Page
Configure Your Input Modules 36 Configurable Options and Their Effect on the Channels 36 Data Tables 39 Chapter Summary 44
The parameters discussed in this chapter can be set through the RSLogix 5000 software. See the previous chapter, Configure Your Thermocouple and RTD Input Modules with RSLogix 5000 Software, to learn more about the step-by­step I/O configuration and setup process.
The modules are configured using a group of data table words mapped by the processor that is used when the connection to the module is established.
The software configurable features available are:
sensor type
temperature units reported in °C, °F
cold junction compensation enable, mode, and offset
(for 1732E-IT4IM12R)
digital filters
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 35
Chapter 4 Configurable Features for the Thermocouple and RTD Input Modules
Sensor Type
Temperature Units
Digital Filter
Notch Filter
(1)
CJC Enable
(2)
CJC Offset
(2)
CJC Mode
(2)
(1) Notch Filter can be set per channel on the Thermocouple module, and module-wide on the RTD module.
(2) Available on the 1732E-IT4IM12R Thermocouple module only.

Configurable Options and Their Effect on the Channels

The following features affect the four input channels for the Thermocouple and RTD Input modules.
Unless otherwise specified, the following features apply to both 1732E-IT4IM12R and 1732E-IR4IM12R modules.
Sensor Type
This set of bits allows you to select one of nine types for the thermocouple module or one of ten RTD types.
The following sensor type options are available for the Thermocouple and RTD modules.
Supported Sensor Types – 1732E-IT4IM12R
Type Material Temperature
Range °C (°F)
B Pt /30% Rh vs. Pt/5% Rh 40…1820 °C (104…3308 °F) 0…13.820 C W/5% Re vs. W/26% Re 0…2320 °C (32…4208 °F) 0…37.107 E Ni/Cr vs. Cu/Ni -270…1000 °C (-454…1832 °F) -9.835…76.373 J Ni/Cr vs. Cu/Ni -210…1200 °C (-346…2192 °F) -8.095…69.553 K Ni/Cr vs. Ni/Al -270…1372 °C (-454…2501.6 °F) -6.458…54.886
Voltage Range (mV)
36 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Configurable Features for the Thermocouple and RTD Input Modules Chapter 4
Supported Sensor Types – 1732E-IT4IM12R
Type Material Temperature
N Ni/14.2%Cr/1.4%Si vs.
R Pt/13%Rh vs. Pt -50…1768 °C (-58…3214.4 °F) -0.226…21.101 S Pt/10%Rh vs. Pt -50…1768 °C (-58…3214.4 °F) -0.236…18.693 T Cu vs. Cu/Ni -270…400 °C (-454…752 °F) -6.258…20.872
Supported Sensor Types – 1732E-IR4IM12R
RTD Type
100 200 Ω Pt 385 0…781Ω -200…850 °C (-328…1562 °F) 0…312.5 mV 100 Ω Pt 3916 0…337.03Ω -200…630 °C (-328…1166 °F) 0…156.25 mV 200 10 Ω Cu 427 0…19.116Ω -320…500 °C (392…932 °F) 0…19.53 mV 120 Ω Ni 672 0…445.10Ω -70…445 °C (-94…833 °F) 0…156.25 mV 100 120 Ω Ni 618 0…238.65Ω -90…140 °C (-130…284 °F) 0…78.125mV
Ni/4.4%Si/0.1%Mg
Ω
Pt 385 0…390.48Ω -200…850 °C (392…1562 °F) 0…156.25 mV
Ω
Pt 3916 0…674.06Ω -200…630 °C (-328…1166 °F) 0…312.5 mV
Ω
Ni 618 0…198.88Ω -60…180 °C (-76…356 °F) 0…78.125 mV
Range °C (°F)
-270…1300 °C (-454…2372 °F) -4.345…47.513
Temperature Range °C (°F) Voltage range
Voltage Range (mV)
Temperature Units
This set of bits allows you to select one of these two formats:
Degree C (default)
Degree F
When the Thermocouple sensor type is set to mV or the RTD sensor type is set to Ohms, the temperature unit field is not available.
Notch Filter
An analog-to-digital converter (ADC) filter that removes line noise in your application for each channel.
Choose a notch filter that most closely matches the anticipated noise frequency in your application. Remember that each filter time affects the response time of your module. Also, the highest frequency notch filter settings also limit the effective resolution of the channel.
The following notch filter values can be set per channel on the 1732E-IT4IM12R Thermocouple module and module-wide on the 1732E-IR4IM12R RTD module:
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 37
Chapter 4 Configurable Features for the Thermocouple and RTD Input Modules
TIP
50 Hz
60 Hz (default)
250 Hz
500 Hz
Digital Filter
A digital filter can be configured for each of the four channels for both Thermocouple and RTD modules based on a configurable time constant set by the user. The time constant value can be configured up to 10,000 ms. A value of 0 disables the filter and is the default value. The minimum digital filter value is dependent on the selected Notch Filter as shown in the table below.
Minimum and Maximum Digital Filter Values
Notch Filter Minimum Digital
50 Hz 60 Hz
250 Hz 2 10,000 500 Hz 1 10,000
(1) Setting the value as 0 disables the filter. It is the default value.
Filter Value (ms)
20 10,000
(1)
Maximum Digital Filter Value (ms)
Cold Junction Compensation (1732E-IT4IM12R only)
Cold junction compensation (CJC) is the temperature at the cold, or reference, point. This value helps determine the temperature at the hot, or measured, point. Two me cha ni sm s ca n h el p d erive CJC :
From a user-entered value
From one or more thermistors attached to the module
In RSLogix 5000, the following parameters configure CJC behavior:
Cold Junction Compensation Enable (available for each of the 4 channels)
Cold Junction Compensation Mode (module-wide setting)
Cold Junction Compensation Offset (available for each of the 4 channels)
Cold Junction Compensation feature is only available for a channel when it is configured as a Thermocouple type. If a channel is set as mV (no linearization), CJC Enable and CJC Offset are not available.
Cold Junction Compensation Enable
The Cold Junction Compensation Enable box on the Module Properties Configuration tab enables cold junction compensation on each of the four
38 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Configurable Features for the Thermocouple and RTD Input Modules Chapter 4
IMPORTANT
channels. Typically, this option should always be enabled except for systems that have no thermoelectric effect, such as test equipment in a controlled lab.
When this parameter is set for a channel, compensation is derived from one or more thermistors attached to the module. If not set (disabled), compensation will come from a user-entered value (CJC Offset).
In most applications, we recommend that you use the cold junction compensation enable option with the recommended thermistor based terminal blocks attached to the module..
Cold Junction Compensation (CJC) Mode
When CJC is enabled, CJC Mode determines where the temperature measurement source (thermistor) is located. The following options are available for the user:
Average Selected
Channel Independent
When CJC Mode is Average Selected, all sensor channels will use an average of the compensation determined by thermistor(s) attached to the user-selected channel(s).
When CJC Mode is Channel Independent, each sensor channel uses the compensation derived from a thermistor attached to the channel.
The produced cold junction compensation data is the temperature value read by the thermistor(s), in °C, which is being applied to the reading on any channel configured for thermistor compensation.
If a thermistor is not detected from the specified channel(s), the produced cold junction data indicates an error (0x8000) and no compensation is applied.
Cold Junction Compensation Offset
When no thermistor is attached to the module or channel, the user can specify the CJC Offset value to be added to the CJC input during temperature calculation. CJC Offset compensates for any inaccuracies of the CJC sensor. Valid values range from 0…70 °C, with 0 °C as default value.
CJC Offset parameter is enabled for configuration when the CJC Enable parameter is not checked for that channel.

Data Tables

The data structure of each Assembly instance used by the Thermocouple and RTD Input modules is defined in the tables below.
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 39
Chapter 4 Configurable Features for the Thermocouple and RTD Input Modules
1732E-IT4IM12R – Configuration Data Structure for Thermocouple Input
Configuration Byte
4 Cold Junction Mode 5…7 Reserved (Ignore) 8…9 Channel 0 Low Engineering 10…11 Channel 0 High Engineering 12 Channel 0 Disable Alarms 13 Channel 0 Enable Alarm Latch 14 Channel 0 Notch Filter 15 Channel 0 Thermocouple Type 16…17 Channel 0 Digital Filter 18…19 Channel 0 Low Alarm 20…21 Channel 0 High Alarm 22…23 Channel 0 Low Low Alarm 24…25 Channel 0 High High Alarm 26 Channel 0 Temperature Units 27 Channel 0 Cold Junction Compensation Enable 28…29 Channel 0 Cold Junction Compensation Offset 30…31 Reserved (Ignore) 32…33 Channel 1 Low Engineering 34…35 Channel 1 High Engineering 36 Channel 1 Disable Alarms 37 Channel 1 Enable Alarm Latch 38 Channel 1 Notch Filter 39 Channel 1 Thermocouple Type 40…41 Channel 1 Digital Filter 42…43 Channel 1 Low Alarm 44…45 Channel 1 High Alarm 46…47 Channel 1 Low Low Alarm 48…49 Channel 1 High High Alarm 50 Channel 1 Temperature Units 51 Channel 1 Cold Junction Compensation Enable 52…53 Channel 1 Cold Junction Compensation Offset 54…55 Reserved (Ignore) 56…57 Channel 2 Low Engineering 58…59 Channel 2 High Engineering 60 Channel 2 Disable Alarms 61 Channel 2 Enable Alarm Latch
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
(1)
40 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Configurable Features for the Thermocouple and RTD Input Modules Chapter 4
1732E-IT4IM12R – Configuration Data Structure for Thermocouple Input
Configuration Byte
62 Channel 2 Notch Filter 63 Channel 2 Thermocouple Type 64…65 Channel 2 Digital Filter 66…67 Channel 2 Low Alarm 68…69 Channel 2 High Alarm 70…71 Channel 2 Low Low Alarm 72…73 Channel 2 High High Alarm 74 Channel 2 Temperature Units 75 Channel 2 Cold Junction Enable 76…77 Channel 2 Cold Junction Offset 78…79 Reserved (Ignore) 80…81 Channel 3 Low Engineering 82…83 Channel 3 High Engineering 84 Channel 3 Disable Alarms 85 Channel 3 Enable Alarm Latch 86 Channel 3 Notch Filter 87 Channel 3 Thermocouple Type 88…89 Channel 3 Digital Filter 90…91 Channel 3 Low Alarm 92…93 Channel 3 High Alarm 94…95 Channel 3 Low Low Alarm 96…97 Channel 3 High High Alarm 98 Channel 3 Temperature Units 99 Channel 3 Cold Junction Enable 100…101 Channel 3 Cold Junction Offset
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
(1) Cold Junction Compensation Mode values are:
0 = None, 1 = Channel 1, 2 = Channel 2, 3 = Channel 3, 4 = Channel 4, 5 = Average of all channels with thermistor attached.
1732E-IR4IM12R – Configuration Data Structure for RTD Input
Configuration Byte
4…5 Channel 0 Low Engineering 6…7 Channel 0 High Engineering 8…9 Channel 0 Digital Filter 10…11 Channel 0 Low Alarm 12…13 Channel 0 High Alarm 14…15 Channel 0 Low Low Alarm
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 41
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Chapter 4 Configurable Features for the Thermocouple and RTD Input Modules
1732E-IR4IM12R – Configuration Data Structure for RTD Input
Configuration Byte
16…17 Channel 0 High High Alarm 18 Channel 0 Enable Alarm Latch 19 Channel 0 Disable Alarms 20 Channel 0 RTD Type 21 Channel 0 Temperature Scale 22…23 Reserved (Ignore) 24…25 Channel 1 Low Engineering 26…27 Channel 1 High Engineering 28…29 Channel 1 Digital Filter 30…31 Channel 1 Low Alarm 32…33 Channel 1 High Alarm 34…35 Channel 1 Low Low Alarm 36…37 Channel 1 High High Alarm 38 Channel 1 Enable Alarm Latch 39 Channel 1 Disable Alarms 40 Channel 1 RTD Type 41 Channel 1 Temperature Scale 42…43 Reserved (Ignore) 44…45 Channel 2 Low Engineering 46…47 Channel 2 High Engineering 48…49 Channel 2 Digital Filter 50…51 Channel 2 Low Alarm 52…53 Channel 2 High Alarm 54…55 Channel 2 Low Low Alarm 56…57 Channel 2 High High Alarm 58 Channel 2 Enable Alarm Latch 59 Channel 2 Disable Alarms 60 Channel 2 RTD Type 61 Channel 2 Temperature Scale 62…63 Reserved (Ignore) 64…65 Channel 3 Low Engineering 66…67 Channel 3 High Engineering 68…69 Channel 3 Digital Filter 70…71 Channel 3 Low Alarm 72…73 Channel 3 High Alarm 74…75 Channel 3 Low Low Alarm 76…77 Channel 3 High High Alarm
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
42 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Configurable Features for the Thermocouple and RTD Input Modules Chapter 4
1732E-IR4IM12R – Configuration Data Structure for RTD Input
Configuration
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Byte
78 Channel 3 Enable Alarm Latch 79 Channel 3 Disable Alarms 80 Channel 3 RTD Type 81 Channel 3 Temperature Scale 82…83 Reserved (Ignore) 84 Notch Filter 85 Reserved (Ignore)
1732E-IT4IM12R – Produced Data Structure for Thermocouple Input
Configuration Byte
0…3 Reserved (must be zero) 4…5 Channel 0 Data 6…7 Channel 1 Data 8…9 Channel 2 Data 10…11 Channel 3 Data 12 Channel 0 Status 13 Channel 1 Status 14 Channel 2 Status 15 Channel 3 Status 16 Cold Junction Temperature Channel 0 (low byte) 17 Cold Junction Status
18 Cold Junction Temperature Channel 1 (low byte) 19 Cold Junction Status
20 Cold Junction Temperature Channel 2 (low byte) 21 Cold Junction Status
22 Cold Junction Temperature Channel 3 (low byte) 23 Cold Junction Status
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
(1)
(1)
(1)
(1)
Channel 0
Channel 1
Channel 2
Channel 3
(2)
(2)
(2)
(2)
Cold Junction Temperature Channel 0 (high byte, low 6 bits)
Cold Junction Temperature Channel 2 (high byte, low 6 bits)
Cold Junction Temperature Channel 2 (high byte, low 6 bits)
Cold Junction Temperature Channel 3 (high byte, low 6 bits)
(1) This parameter is in Byte and has the following structure:
Bit 0 = Fault; Bit 1 = Calibration; Bit 2 = Low Alarm; Bit 3 = High Alarm; Bit 4 = Low Low Alarm; Bit 5 = High High Alarm; Bit 6 = Underrange; Bit 7 = Overrange
(2) Cold junction status is defined below. When a fault is detected, the Cold Junction Temperature is set to zero (thus,
a word value of 0xC000 indicates that the cold junction is enabled, but no thermistor data is available). 00 = No fault; 01 = Underrange; 02 = Overrange; 03 = No thermistor detected
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 43
Chapter 4 Configurable Features for the Thermocouple and RTD Input Modules
1732E-IR4IM12R – Produced Data Structure for RTD Input

Chapter Summary

Configuration Byte
0…3 Reserved (must be zero) 4…5 Channel 0 Data 6…7 Channel 1 Data 8…9 Channel 2 Data 10…11 Channel 3 Data 12 Channel 0 Status 13 Channel 1 Status 14 Channel 2 Status 15 Channel 3 Status
(1) This parameter is in Byte and has the following structure:
Bit 0 = Fault; Bit 1 = Calibration; Bit 2 = Low Alarm; Bit 3 = High Alarm; Bit 4 = Low Low Alarm; Bit 5 = High High Alarm; Bit 6 = Underrange; Bit 7 = Overrange
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
(1)
(1)
(1)
(1)
This chapter discussed the different configurable features and their effect on all input channels for both Thermocouple and RTD modules.
44 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Calibrate Your Modules
IMPORTANT
Chapter
5

Overview

The Thermocouple and RTD modules are shipped to you calibrated but calibration is also made available through the RSLogix 5000 software should you choose to recalibrate your module to increase accuracy for your specific application.
This chapter shows you how to calibrate your modules through the RSLogix 5000 software. It includes the following topics.
Topic Page
Calibrate the Thermocouple Module 46 Calibrate the RTD Module 49
Analog I/O modules can be calibrated on a channel-by-channel basis or with the channels grouped together. Regardless of which option you choose, we recommend you calibrate all channels on your module each time you calibrate. This will help you maintain consistent calibration readings and improve module accuracy.
Calibration is meant to correct any hardware inaccuracies that may be present on a particular channel. The calibration procedure compares a known standard, either input signal or recorded output, with the channel’s performance and then calculating a linear correction factor between the measured and the ideal.
The linear calibration correction factor is applied on every input or output same to obtain maximum accuracy.
To maintain your module’s accuracy specifications, we recommend you use calibration instruments with specific ranges. The table lists the recommended instruments for the two modules.
Module Recommended Instrument Range
1732E-IT4IM12R 0 mV…78.125 mV source ±0.3 μV 1732E-IR4IM12R 0…1000 Ω resistors
(1) We suggest you use these precision resistors.
KRL Electronics - 534A1-1R0T 1.0 Ohm 0.01% / 534A1-487R0T 487 Ohm 0.01% A precision decade resistor box also can be used that meets or exceeds the required accuracy specifications. You are responsible for assuring that the decade box maintains accuracy by periodic calibration.
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 45
(1)
±0.01%
Chapter 5 Calibrate Your Modules
IMPORTANT
TIP

Calibrate the Thermocouple Module

The 1732E-IT4IM12R module only calibrates in millivolts. You can calibrate the module to a 0…78.125 mV range.
Perform the calibration process through the RSLogix 5000 software.
While you are online, you must access the Calibration tab on the Module Properties dialog box.
Apply power to the power supply and module for at least 10 minutes before calibrating the module.
1. Click Calibration Tab on the Module Properties dialog box.
2. Check the Calibrate checkbox to specify which channel to calibrate.
In this example, check all channels. Calibration points are automatically set to 0 and 78.125 mV.
3. Under Calibrate Channels select One at a time.
4. Under Type of Calibration, select Input.
5. Click Start Calibration, which is active when:
the system is online, and
you selected at least one of the channels.
Note that you can press the F1 button on your keyboard or click Help from the wizard and warning message that appear to get detailed information about the procedures for calibration.
46 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Calibrate Your Modules Chapter 5
TIP
TIP
6. After clicking Start Calibration, a warning dialog appears notifying you of the risk involved in calibrating an active system and gives you the option to quit.
If at least one channel has been selected and there is a mismatch between the device in the RSLogix 5000 I/O Configuration and the actual physical device, another warning dialog comes up. It informs you that this is dangerous with an active system and there is a mismatch. This message box gives you an option to quit. Help is provided to you more information.
From the Danger dialog, for a module not currently used for control, click OK to continue.
7. The Input Calibration - Low Value dialog appears. Set the calibrator for the low reference and apply it to the module.
Click Next to start low reference calibration.
If several channels have been selected for calibration with One At a Time option enabled, only one channel will appear in the list at the first round (low reference and high reference) of calibration.
If calibration is configured to be done In Groups, the Low Value dialog box shows all the channels enabled for calibration.
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 47
Chapter 5 Calibrate Your Modules
TIP
TIP
TIP
8. Set the calibrator for the high reference voltage and apply it to the module The Input Calibration - High Value dialog appears.
If several channels have been selected for calibration with One At a Time option enabled, only one channel will appear in the list at the first round (low reference and high reference) of calibration.
If calibration is configured to be done In Groups, the High Value dialog box shows all the channels enabled for calibration.
9. From the High Value dialog, click Next to start calibration. The Input Calibration - Results dialog appears. It shows you the results of calibration.
For failed calibration, go to step 10
For successful calibration, go to step 11
.
.
10. If the calibration failed, click Retry to recalibrate the same channel. This takes you back to steps 6
9 until you get successful calibration on the
channel.
11. If the calibration is successful, click Next to start calibration on the next channel (in this example, channel 1). This takes you back to steps 6
9.
12. After successful calibration on the channel(s), click Finish to close the Calibration Wizard.
Cold junction compensation calibration follows the same steps, with resistance used on the thermistor connections.
48 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Calibrate Your Modules Chapter 5
Choose whether to calibrate each
channel one at a time or in groups all
at once

Calibrate the RTD Module

The 1732E-IR4IM12R does not calibrate for voltage or current. It uses two precision resistors to calibrate the channels in ohms. The module has a preset calibration points for the sensor type configured for each input channel,
Calibration Points for the RTD Module
RTD Sensor Type Calibration Points
Ohms 0 and 500 Ohms 100 Ω Pt 385 0 and 500 Ohms 200 Ω Pt 385 0 and 1000 Ohms 100 Ω Pt 3916 0 and 500 Ohms 200 Ω Pt 3916 0 and 1000 Ohms 10 Ω Cu 427 0 and 64.9 Ohms 120 Ω Ni 672 0 and 500 Ohms 100 Ω Ni 618 0 and 250 Ohms 120 Ω Ni 618 0 and 250 Ohms
Perform the calibration process through the RSLogix 5000 software.
While you are online, you must access the Calibration tab on the Module Properties dialog box. See Edit Your Module Configuration
on page 21.
1. Click Calibration Tab on the Module Properties dialog box.
2. Check the Calibrate checkbox to specify which channel to calibrate.
In this example, check Channels 0…3.
3. Under Calibrate Channels select One At a Time.
4. Click Start Calibration, which is active when:
the system is online, and
you selected at least one of the channels.
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 49
Chapter 5 Calibrate Your Modules
TIP
TIP
Note that you can press the F1 button on your keyboard or click Help from the wizard and warning message that appear to get detailed information about the procedures for calibration.
5. After clicking Start Calibration, a warning dialog appears notifying you of the risk involved in calibrating an active system and gives you the option to quit.
If at least one channel has been selected and there is a mismatch between the device in the RSLogix 5000 I/O Configuration and the actual physical device, another warning dialog comes up. It informs you that this is dangerous with an active system and there is a mismatch. This message box gives you an option to quit. Help is provided to you more information.
From the Danger dialog, for a module not currently used for control, click OK to continue.
6. The Low Value dialog appears. Set the calibrator for the low reference and apply it to the module.
Click Next to start low reference calibration.
If several channels have been selected for calibration with One At a Time option enabled, only one channel will appear in the list at the first round (low reference and high reference) of calibration.
If calibration is configured to be done In Groups, the Low Value dialog box shows all the channels enabled for calibration.
50 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Calibrate Your Modules Chapter 5
TIP
TIP
7. Set the calibrator for the high reference voltage and apply it to the module The High Value dialog appears.
If several channels have been selected for calibration with One At a Time option enabled, only one channel will appear in the list at the first round (low reference and high reference) of calibration.
If calibration is configured to be done In Groups, the High Value dialog box shows all the channels enabled for calibration.
8. From the High Value dialog, click Next to start calibration. The Input Calibration - Results dialog appears. It shows you the results of calibration.
For failed calibration, go to step 9
For successful calibration, go to step 11
.
.
9. If the calibration failed, click Retry to recalibrate the same channel. This takes you back to steps 6
8 until you get successful calibration on the
channel.
10. If the calibration is successful, click Next to start calibration on the next channel (in this example, channel 1). This takes you back to steps 6
8. You will have to go through the same
cycle of steps for each of the next channels lined up for calibration.
11. After successful calibration on the channel(s), click Finish to close the Calibration Wizard.

Chapter Summary

This chapter provided instructions on how to calibrate the ArmorBlock Thermocouple and RTD modules.
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 51
Chapter 5 Calibrate Your Modules
Notes:
52 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Chapter
Link 2 status indicator
Network status indicator
Module status indicator
I/O status indicators
Auxiliary power status indicator
Link 1 status indicator
45871
6
Troubleshoot the Module
This chapter describes the different status indicators available in the 1732E-IT4IM12R and 1732E-IR4IM12R modules and how to interpret these indicators to help troubleshoot the modules. It also includes a section on how to check your module for faults through the RSLogix 5000 software.

Interpret Status Indicators

The 1732E-IT4IM12R and 1732E-IR4IM12R modules have the following status indicators:
Network, Module, and Link status indicators for EtherNet/IP
Auxiliary power status indicator
Individual I/O status indicators for inputs
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 53
Chapter 6 Troubleshoot the Module
Indicator Status for the Modules
Indicator Status Description
Module status
Network status
Network link status (Link 1/Link 2)
Auxiliary Power status
I/O status Off The input channel is inactive, can be calibrated.
Off No power applied to the device. Flashing red/
green Green Device operating normally. Flashing red Module has experienced a recoverable fault. Possible minor
Red Unrecoverable fault – may require device replacement. Off The device is not initialized or the module does not have an IP
Flashing green The device has no CIP connections. The device has an IP address,
Green Device is online, has an IP address. CIP connections are
Flashing red One or more connections have timed out. Red The module has detected that its IP address is
Flashing red/ green
Off No link established. Green Link established on indicated port at 100 Mbps. Flashing green Link activity present on indicated port at 100 Mbps. Yellow Link established on indicated port at 10 Mbps. Flashing yellow Link activity present on indicated port at 10 Mbps. Off Auxiliary power off or not connected. Green Auxiliary Power applied to device.
Flashing Green Channel is calibrating. Green Normal operation, inputs being scanned. Flashing Yellow Thermistor fault. Flashing Red Fault. Overrange, underrange, or process alarm is present. Red No power is detected.
The module is performing POST (Power-On Self Test), which completes within 30 s.
faults include the following:
IP Address switches do not match configuration in use.
The device has completed a reset to factory default request
due to the switches being set to 888 at power up, and a power cycle is required.
The device is performing a firmware flash update.
Channel fault
No auxiliary power
address.
but no CIP connections are established.
established.
already in use. The module is performing a power-on self test (POST).

Check for Faults

In addition to the status indicators on the module, RSLogix 5000 software alerts you to fault and other conditions in one of three ways:
54 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Troubleshoot the Module Chapter 6
Warning icon appears when a communications fault occurs or if the module is inhibited
Warning signal – The module has a communications fault
Status line provides information on the module fault and on the connection to the module
RSLogix 5000 software generates 1 s in response to a module communication fault. In this example, a communication fault occurred between the controller and the module, so the controller automatically writes 1 s for all bits in the word.
Warning signal on the main screen next to the module – This occurs when the connection to the module is broken.
Message in a screen’s status line.
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 55
Notification in the Tag Monitor – General module faults are also reported in the Tag Monitor. Communication faults are reported in the input tags.
Chapter 6 Troubleshoot the Module
Notes:
56 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Specifications
Appendix
A

General Specifications

The 1732E ArmorBlock Thermocouple and RTD Input Modules have the following general specifications.
General Specifications
Attributes Value
Voltage, power, max 30V DC Voltage, power, min 12V DC Module power 12…30V DC @ 300 mA Power consumption 3 W @ 24V DC, typical
Isolation voltage 50V (continuous), Basic Insulation Type
Communication rate EtherNet/IP
Status indicators Module status – red/green
Dimensions, approx., HxWxD 179 x 37 x 27 mm (7.05 x 1.46 x 1.06 in.) Weight, approx. 0.34 kg (0.75 lb) Wiring category
(1)
3.5 W, max (module unloaded)
Type tested @ 707V DC for 60 s
10/100 Mbps Full or half-duplex 100 meter per segment
Network status – red/green Link status – green/yellow Auxiliary power status – green I/O LED – red/green
1 – on signal ports 1 – on power ports 1 – on communication ports
(1) Use this Conductor Category information for planning conductor routing. Refer to publication
1770-4.1
, Industrial Automation Wiring and Grounding Guidelines.

Input Specifications

The 1732E-IT4IM12R Thermocouple input module has the following input specifications.
Input Specifications – 1732E-IT4IM12R
Attributes Value
Number of inputs 4, isolated Resolution, min 16 bits Data format Signed integer
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 57
Appendix A Specifications
Input Specifications – 1732E-IT4IM12R
Attributes Value
Thermocouple types Type Material Temperature
B Pt /30% Rh vs. Pt/
5% Rh
C W/5% Re vs. W/
26% Re
E Ni/Cr vs. Cu/Ni -270…1000
J Ni/Cr vs. Cu/Ni -210…1200
K Ni/Cr vs. Ni/Al -270…1372
N Ni/14.2%Cr/1.4%Si
vs. Ni/4.4%Si/
0.1%Mg
R Pt/13%Rh vs. Pt -50…1768
S Pt/10%Rh vs. Pt -50…1768
T Cu vs. Cu/Ni -270…400
Cold junction compensation Rockwell Automation 871A-TS4CJC-DM, 871A-TR4CJC-DM Cold junction compensation
range Thermistor types supported Thermometrics MF65F302V/W or DC95F302V/W Input voltage range ±78 mV, 1 mW Accuracy 0.1% Full Scale @ 25 °C (77 °F) Accuracy drift with
temperature Calibration Factory calibrated. Calibration is also supported through
Common mode rejection rate 120 dB @ 50/60 Hz Normal mode rejection rate 100 dB @ 50/60 Hz Sample Rate Filters
(1)
0…70 °C (32…158 °F) for 302 type thermistors
30 ppm % Full Scale /°C @ 25 °C (77 °F)
RSLogix 5000.
50 Hz 60 Hz 250 Hz 500 Hz
Range °C (°F) 40…1820
(104…3308) 0…2320
(32…4208)
(-454…1832)
(-346…2192)
(-454…2501.6)
-270…1300 (-454…2372)
(-58…3214.4)
(-58…3214.4)
(-454…752)
Voltage Range (mV)
0…13.820
0…37.107
-9.835…76.373
-8.095…69.553
-6.458…54.886
-4.345…47.513
-0.226…21.101
-0.236…18.693
-6.258…20.872
(1) Sample Rate/Notch Filter Frequency, selectable per channel.
The 1732E-IR4IM12R RTD input module has the following input specifications.
Input Specifications – 1732E-IR4IM12R
Attributes Value
Number of inputs 4, isolated Resolution, min 16 bits
58 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Specifications Appendix A
Input Specifications – 1732E-IR4IM12R
Attributes Value
Data format 16-bit sign magnitude Sensors supported 100…200 Ω α=0.00385/0.003916 Pt RTD
Sensor Types 100 Ω Pt 385
Input range RTD type Temperature
Input resistance 0…1000 Ω 300 mV, 5 mW Accuracy 0.1% Full Scale @ 25 °C (77 °F) Accuracy drift with
temperature Calibration Factory calibrated. Calibration is also supported through
Sample Rate Filters
(1)
Common Mode Rejection Ratio
Normal Mode Rejection Ratio
100/120 Ω Ni RTD 10 Ω Cu α =0.00427 RTD
200 Ω Pt 385 100 Ω Pt 3916 200 Ω Pt 3916 10 Ω Cu 427 120 Ω Ni 672 100 Ω Ni 618 120 Ω Ni 618
Range (°C)
100 Ω Pt 385 0…390.48 Ω -200…850 °C 0…156.25 mV 200
Ω
Pt 385 0…781 Ω -200…850 °C 0…312.5 mV
100 Ω Pt 3916 0…337.03 Ω -200…630 °C 0…156.25 mV 200 Ω Pt 3916 0…674.06 Ω -200…630 °C 0…312.5 mV 10
Ω
Cu 427 0…19.116 Ω -320…500 °C 0…19.53 mV
120 Ω Ni 672 0…445.10 Ω -70…445 °C 0…156.25 mV 100 Ω Ni 618 0…198.88 Ω -60…180 °C 0…78.125 mV 120
Ω
Ni 618 0…238.65 Ω -90…140 °C 0…78.125mV
30 ppm % Full Scale /°C @ 25 °C (77 °F)
RSLogix 5000. 50 Hz
60 Hz 250 Hz 500 Hz
120 dB @ 50/60 Hz
100 dB @ 50/60 Hz
Voltage Range
(1) Sample rate filter selectable on a module basis only.
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 59
Appendix A Specifications

Environmental Specifications

The 1732E ArmorBlock Thermocouple and RTD Input Modules have the following environmental specifications.
Environmental Specifications
Attribute Value
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…60 °C (-4…140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40…85 °C (-40…185 °F) Temperature, ambient, max 60 °C (140 °F) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing
Vibration IEC60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz
Shock, operating IEC60068-2-27 (Test Ea, Unpackaged Shock):
30 g
Shock, nonoperating IEC60068-2-27 (Test Ea, Unpackaged Shock):
50 g
Emissions CISPR 11:
Group 1, Class A
ESD immunity IEC 61000-4-2:
6 kV contact discharges 8 kV air discharges
Radiated RF immunity IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 10V/m with1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4:
±3 kV @ 5 kHz on power ports ±3 kV @ 5 kHz on signal ports ±3 kV @ 5 kHz on communication ports
Surge transient immunity IEC 61000-4-5:
±2 kV line-line (DM) and ±2 kV line-earth (CM) on power ports ±500V line-line (DM) and ±1 kV line-earth (CM) on signal ports ±2 kV line-earth (CM) on communication ports
Conducted RF immunity IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from150 kHz…80 MHz
Enclosure type rating Meets IP65/66/67/69K (when marked)

Certifications

The 1732E ArmorBlock Thermocouple and RTD Input Modules have the following certifications.
60 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Certifications
Specifications Appendix A
Certification (when product is marked)
(1)
Value
c-UR-us UL Recognized Component Industrial Control Equipment, certified for
US and Canada. See UL File E322657.
CE European Union 2004/108/EC EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
KC Korean Registration of Broadcasting and Communications
Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3
EtherNet/IP ODVA conformance tested to EtherNet/IP specifications.
(1) See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other
certification details.
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 61
Appendix A Specifications
Notes:
62 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Appendix
1732E ArmorBlock Embedded Web Server
B

Introduction

Typical Applications

Browser Requirements

Rockwell Automation offers enhanced 1732E ArmorBlock for your EtherNet/IP control systems so you can monitor data remotely via web pages.
This chapter shows how you can use the module’s web server.
Topic Page
Typical Applications 63 Browser Requirements 63 Access the Home Page of the Web Server 64 Log On to the Web Server 64 Navigate the 1732E ArmorBlock I/O 65
The module provides access to internal and network diagnostics. This access opens up different, remote access applications to control systems. Use the ArmorBlock I/O web browser to remotely access module data. Use a web browser to monitor live module data and access diagnostic information.
You can access the 1732E ArmorBlock I/O web pages only with Internet Explorer 6.0 or higher. To access data view pages, the browser requires Javascript support.
The supported display size is 640 x 480 or greater. Smaller display sizes work but might require extensive scrolling to view the information.
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 63
Appendix B 1732E ArmorBlock Embedded Web Server
Specify the IP address of the module in the Address field.
Module home page
Default Access
User Name: administrator Password: <blank>

Access the Home Page of the Web Server

From your web browser, enter the IP address of the 1732E ArmorBlock module. The module displays its home page.

Log On to the Web Server

Many of the features of the 1732E ArmorBlock I/O require you to log on with appropriate access. If you select a feature, such as Configuration, the 1732E ArmorBlock I/O prompts you to enter your user name and password. The user name is Administrator. The default password is blank. Both are case sensitive.
64 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
1732E ArmorBlock Embedded Web Server Appendix B
Click folders to open
and close additional
levels of information.
Click a document to display
a web page showing
specific information.
Tabs across the top match
the documents within a
folder, as shown in the left
navigation panel.

Navigate the 1732E ArmorBlock I/O

You navigate the web server pages by using the navigation panel on the left of the screen. There are also tabs across the top you can use to navigate the sections within folders.
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 65
Appendix B 1732E ArmorBlock Embedded Web Server
Click the Diagnostics
folder to expand the
navigation, then click
the Diagnostic
Overview page.
View diagnostic information such as Ring Status, System Resource
Utilization, and CIP
Connection Statistics.
Click the Configuration
folder to expand the
navigation.
You can view and edit
Device Identity,
Network Configuration
and Device Services
information.

Access Diagnostic Information

You can view specific diagnostic information by clicking Diagnostic Overview on the navigational panel on the left.

Access Configuration Information

66 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
You can also view configuration information through the Web Server pages. Click Configuration folder.
Appendix
C
Module Tag Definitions
The 1732E-IT4IM12R and 1732E-IR4IM12R modules have two sets of tags:
Configuration
Input

Module Tags for 1732E-IT4IM12R

Input Tags (1732E-IT4IM12R)
Tag Name Data Type Definition
I.Fault DINT Collection of all module level fault bits I.Ch0Data
I.Ch1Data I.Ch2Data I.Ch3Data
I.Ch0Fault I.Ch1Fault I.Ch2Fault I.Ch3Fault
I.Ch0Calibration I.Ch1Calibration I.Ch2Calibration I.Ch3Calibration
I.Ch0Lalarm I.Ch1Lalarm I.Ch2Lalarm I.Ch3Lalarm
I.Ch0HAlarm I.Ch1HAlarm I.Ch2HAlarm I.Ch3HAlarm
I.Ch0LLAlarm I.Ch1LLAlarm I.Ch2LLAlarm I.Ch3LLAlarm
I.Ch0HHAlarm I.Ch0HHAlarm I.Ch0HHAlarm I.Ch0HHAlarm
I.Ch0Underrange I.Ch1Underrange I.Ch1Underrange I.Ch1Underrange
I.Ch0Overrange I.Ch1Overrange I.Ch2Overrange I.Ch3Overrange
INT The channel input signal represented in counts where -32,768 counts is the minimum detectable input signal and
32,767 counts is the maximum detectable.
BOOL Individual channel fault status bit. Indicates a ‘hard’ fault has occurred on the channel that means: calibration is
ongoing; or if an input, an overrange or underrange condition is present. These bits also are set by the controller if communication is lost with the I/O module.
BOOL Indicates if calibration is currently in progress on a channel.
BOOL Low alarm bits that set when the input signal moves beneath the configured low alarm trigger point,
Ch<0...3>LAlarmLimit. Remains set until the input signal moves above the trigger point, unless latched via Ch<0…3>LimitAlarmLatch.
BOOL High alarm bit that sets when the input signal moves above the configured high alarm trigger point,HAlarmLimit.
emains set until the input signal moves below the trigger point, unless latched via Ch0LimitAlarmLatch of the high alarm trigger point.
BOOL Low low alarm bit that sets when the input signal moves beneath the configured low low alarm trigger point,
Ch<0…3>LLAlarmLimit. Remains set until the input signal moves above the trigger point, unless latched via Ch<0…3>LimitAlarmLatch.
BOOL High high alarm bit that sets when the input signal moves above the configured high high alarm trigger point,
Ch<0…3>HAlarmLimit. Remains set until the input signal moves below the trigger point.
BOOL Alarm bits indicating the channel’s input is less than the minimum detectable input signal.
BOOL Alarms bit indicating the channel’s input is greater than the maximum detectable input signal.
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 67
Appendix C Module Tag Definitions
Data =
(Signal-LowSignal)(HighEngineering-LowEngineering)
High Signal - Low Signal
+ Low Engineering
Data =
(Signal-LowSignal)(HighEngineering-LowEngineering)
High Signal - Low Signal
+ Low Engineering
Input Tags (1732E-IT4IM12R)
Tag Name Data Type Definition
I.CJData INT The cold junction sensor temperature in counts where -32,768 counts is 0 °C (32 °F) and 32,767 counts is 86 °C (186
°F).
Configuration Tags (1732E-IT4IM12R)
Tag Name Data Type Definition
C.Ch0CJCMode C.Ch1CJCMode C.Ch2CJCMode C.Ch3CJCMode
C.CJCModeIndependent SINT See Cold Junction Compensation (CJC) Mode on page 39. C.Ch0LEngineering
C.Ch1LEngineering C.Ch2LEngineering C.Ch3LEngineering
SINT See Cold Junction Compensation (CJC) Mode on page 39
INT One of four points used in scaling. The low engineering helps determine the engineering units the
signal values scale into. The low engineering term corresponds to the low signal value. The scaling equation used is as follows:
.
C.Ch0HEngineering C.Ch1HEngineering C.Ch2HEngineering C.Ch3HEngineering
C.Ch0AlarmDisable C.Ch1AlarmDisable C.Ch2AlarmDisable C.Ch3AlarmDisable
C.Ch0LimitAlarmLatch C.Ch1LimitAlarmLatch C.Ch2LimitAlarmLatch C.Ch3LimitAlarmLatch
C.Ch0NotchFilter C.Ch1NotchFilter C.Ch2NotchFilter C.Ch3NotchFilter
C.Ch0SensorType C.Ch1SensorType C.Ch2SensorType C.Ch3SensorType
C.Ch0DigitalFilter C.Ch1DigitalFilter C.Ch2DigitalFilter C.Ch3DigitalFilter
C.Ch0LAlarmLimit C.Ch1LAlarmLimit C.Ch2LAlarmLimit C.Ch3LAlarmLimit
INT One of four points used in scaling. The high engineering helps determine the engineering units the
SINT Disables all alarms for the channel:
SINT Enables latching for all four process alarms: low, low low, high and high high. Latching causes the
SINT Configures the channel’s notch filter settings.
SINT Configures the channel’s sensor type settings.
INT A non-zero value enables the filter. The value serves as a time constant in milliseconds that can be
INT The low alarm trigger point. This value causes the Ch<0...3>LAlarm bit to trigger when the input signal
signal values scale into. The high engineering term corresponds to the high signal value. The scaling equation used is as follows:
0 - Alarms are not disabled 1 - Alarms are disabled
process alarm to remain set until an unlatch service is explicitly sent to the channel or alarm.
See Notch Filter on page 37
See Sensor Type on page 36
used in a first order lag filter to smooth the input signal.
moves beneath the configured trigger point, in engineering units.
for list of valid input values.
for list of valid sensor types.
68 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Configuration Tags (1732E-IT4IM12R)
Tag Name Data Type Definition
C.Ch0HAlarmLimit C.Ch1HAlarmLimit C.Ch2HAlarmLimit C.Ch3HAlarmLimit
C.Ch0LLAlarmLimit C.Ch1LLAlarmLimit C.Ch2LLAlarmLimit C.Ch3LLAlarmLimit
C.Ch0HHAlarmLimit C.Ch0HHAlarmLimit C.Ch0HHAlarmLimit C.Ch0HHAlarmLimit
Ch0TempMode Ch1TempMode Ch2TempMode Ch3TempMode
Ch0CJEn Ch0CJEn Ch0CJEn Ch0CJEn
Ch0CJOffset Ch1CJOffset Ch2CJOffset Ch3CJOffset
INT The high alarm trigger point. This value causes the Ch<0...3>HAlarm bit to trigger when the input signal
moves above the configured trigger point, in engineering units.
INT The low low alarm trigger point. This value causes the Ch<0...3>LLAlarm bit to trigger when the input
signal moves beneath the configured trigger point, in engineering units.
INT The high high alarm trigger point. This value causes the Ch<0...3>HHAlarm bit to trigger when the input
signal moves above the configured trigger point, in engineering units.
SINT Controls the temperature scale to use on the module.
0 = Celsius 1 = Fahrenheit
SINT Enables the cold junction sensor that turns on cold junction compensation to linearize thermocouple
inputs.
INT Provides a user-defined offset to add into the read cold-junction sensor value. Allows a sensor with a
built-in bias to be compensated for.
Module Tag Definitions Appendix C

Module Tags for 1732E-IR4IM12R

Input Tags (1732E-IR4IM12R)
Tag Name Data Type Definition
I.Fault DINT Collection of all module level fault bits I.Ch0Data
I.Ch1Data I.Ch2Data I.Ch3Data
I.Ch0Fault I.Ch1Fault I.Ch2Fault I.Ch3Fault
I.Ch0Calibration I.Ch1Calibration I.Ch2Calibration I.Ch3Calibration
I.Ch0LAlarm I.Ch1LAlarm I.Ch2LAlarm I.Ch3LAlarm
I.Ch0HAlarm I.Ch1HAlarm I.Ch2HAlarm I.Ch3HAlarm
I.Ch0LLAlarm I.Ch1LLAlarm I.Ch2LLAlarm I.Ch3LLAlarm
INT The channel input signal represented in counts where -32,768 counts is the minimum detectable input
signal and 32,767 counts is the maximum detectable.
BOOL Individual channel fault status bit. Indicates a ‘hard’ fault has occurred on the channel that means:
calibration is ongoing; or if an input, an overrange or underrange condition is present. These bits also are set by the controller if communication is lost with the I/O module.
BOOL Indicates if calibration is currently in progress on a channel.
BOOL Low alarm bits that set when the input signal moves beneath the configured low alarm trigger point,
Ch<0...3>LAlarmLimit. Remains set until the input signal moves above the trigger point, unless latched via Ch<0...3>LimitAlarmLatch, of the low alarm trigger point.
BOOL High alarm bit that sets when the input signal moves above the configured high alarm trigger point,
Ch<0...3>HAlarmLimit. Remains set until the input signal moves below the trigger point, unless latched via Ch<0...3>LimitAlarmLatch.
BOOL Low low alarm bit that sets when the input signal moves beneath the configured low low alarm trigger
point, Ch<0...3>LLAlarmLimit. Remains set until the input signal moves above the trigger point, unless latched via Ch<0...3>LimitAlarmLatch.
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 69
Appendix C Module Tag Definitions
Data =
(Signal-LowSignal)(HighEngineering-LowEngineering)
High Signal - Low Signal
+ Low Engineering
Data =
(Signal-LowSignal)(HighEngineering-LowEngineering)
High Signal - Low Signal
+ Low Engineering
Input Tags (1732E-IR4IM12R)
Tag Name Data Type Definition
I.Ch0HHAlarm I.Ch0HHAlarm
BOOL High high alarm bit that sets when the input signal moves above the configured high high alarm trigger
point, Ch0HHAlarmLimit. Remains set until the input signal moves below the trigger point. I.Ch0HHAlarm I.Ch0HHAlarm
I.Ch0Underrange
BOOL Alarm bits indicating the channel’s input is less than the minimum detectable input signal. I.Ch1Underrange I.Ch1Underrange I.Ch1Underrange
I.Ch0Overrange
BOOL Alarms bit indicating the channel’s input is greater than the maximum detectable input signal. I.Ch1Overrange I.Ch2Overrange I.Ch3Overrange
Configuration Tags (1732E-IR4IM12R)
Tag Name Data Type Definition
C.Ch0LEngineering C.Ch1LEngineering C.Ch2LEngineering C.Ch3LEngineering
INT One of four points used in scaling. The low engineering helps determine the engineering units the
signal values scale into. The low engineering term corresponds to the low signal value. The scaling equation used is as follows:
C.Ch0HEngineering C.Ch1HEngineering C.Ch2HEngineering C.Ch3HEngineering
C.Ch0DigitalFilter C.Ch1DigitalFilter C.Ch2DigitalFilter C.Ch3DigitalFilter
C.Ch0LAlarmLimit C.Ch1LAlarmLimit C.Ch2LAlarmLimit C.Ch3LAlarmLimit
C.Ch0HAlarmLimit C.Ch1HAlarmLimit C.Ch2HAlarmLimit C.Ch3HAlarmLimit
C.Ch0LLAlarmLimit C.Ch1LLAlarmLimit C.Ch2LLAlarmLimit C.Ch3LLAlarmLimit
C.Ch0HHAlarmLimit C.Ch1HHAlarmLimit C.Ch2HHAlarmLimit C.Ch3HHAlarmLimit
C.Ch0LimitAlarmLatch C.Ch1LimitAlarmLatch C.Ch2LimitAlarmLatch C.Ch3LimitAlarmLatch
INT One of four points used in scaling. The high engineering helps determine the engineering units the
signal values scale into. The high engineering term corresponds to the high signal value. The scaling equation used is as follows:
INT A non-zero value enables the filter. The value serves as a time constant in milliseconds that can be
used in a first order lag filter to smooth the input signal.
INT The low alarm trigger point. This value causes the Ch<0...3>LAlarm bit to trigger when the input signal
moves beneath the configured trigger point, in engineering units.
INT The high alarm trigger point. This value causes the Ch<0...3>HAlarm bit to trigger when the input signal
moves above the configured trigger point, in engineering units.
INT The high high alarm trigger point. This value causes the Ch<0...3>HHAlarm bit to trigger when the input
signal moves above the configured trigger point, in engineering units.
INT The high high alarm trigger point. This value causes the Ch<0...3>HHAlarm bit to trigger when the input
signal moves above the configured trigger point, in engineering units.
SINT Enables latching for all four process alarms: low, low low, high and high high. Latching causes the
process alarm to remain set until an unlatch service is explicitly sent to the channel or alarm.
70 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Configuration Tags (1732E-IR4IM12R)
Tag Name Data Type Definition
C.Ch0AlarmDisable C.Ch1AlarmDisable C.Ch2AlarmDisable C.Ch3AlarmDisable
C.Ch0SensorType C.Ch1SensorType C.Ch2SensorType C.Ch3SensorType
Ch0TempMode Ch1TempMode Ch2TempMode Ch3TempMode
SINT Disables all alarms for the channel:
0 - Alarms are not disabled 1 - Alarms are disabled
SINT Configures the channel’s sensor type settings.
See Sensor Type on page 36 for list of valid input values.
SINT Controls the temperature scale to use on the module.
0 = Celsius 1 = Fahrenheit
Module Tag Definitions Appendix C

Access the Module Tags

When you access tags, you have two options. You can:
monitor tags – this option allows you to view tags and change their values
edit tags – this option allows you to add or delete tags but not to change
their values
When you click Edit Tags or Monitor Tags, you can view and/or edit the tags through the following screen that shows all the tags for your modules:
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 71
Appendix C Module Tag Definitions
Notes:
72 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012

Index

Numerics
1732E ArmorBlock
embedded web server 63 navigate 65
1732E-IR4IM12R 1
configurable features 36 configuration 24 configuration data 41 connectors 3 I/O Configuration 16 input specifications 58 input tags 69 RTD sensor types 4 supported sensor types 37 troubleshooting 53 wiring 10
1732E-IT4IM12R 1
configurable features 36 configuration 26 configuration data 40 configuration tags 68 connectors 3 I/O Configuration 16 input tags 67 produced data 43 supported sensor types 36 supported thermocouples 3 troubleshooting 53 wiring 10
1756-EN2T 3, 14, 16 1756-EN2TR 3, 16 1756-EN3TR 3, 16 871A-TR4CJC-DM 58 871A-TS4CJC-DM 58
A
accuracy 58, 59 alarms 1, 5, 28
high 29 low 29 low-low 29 process 29
Allen-Bradley 871A-TR4CJC-DM 4 Allen-Bradley 871A-TS4CJC-DM 4 analog signal 1 auxiliary power 2, 11, 53
B
bridge
add new 16 new 16
browser requirements
embedded web server 63
C
calibration 31, 59
process 45 recommended instrument range 45
CE 61 CE Low Voltage Directive 12 certifications 61 channel 25, 27, 29 CJC error detection 4 CJC Terminal Chamber 4 cold junction compensation 3, 27, 35, 38, 58
Average Selected 39 Channel Independent 39 enable 35 mode 28, 35, 38, 39 offset 28, 35, 38, 39
common mode rejection rate 58, 59 common techniques used in this manual iii communication rate 57 compensation voltage 4 conducted RF immunity 60 configuration
bridge 18 default 16 edit 21 I/O 16 port 31 process 16 software 16
connections
input only 23 unicast 24
connectors 2
EtherNet/IP D-code M12 2 I/O M12 2, 10 micro-style power in/out 2 power 11
controller
download program 20
ControlLogix 14 conventions iii C-Tick 61 c-UR-us 61
D
data
access 63 format 57, 59 module 63 monitor 63
default configuration 16
use 16
default gateway 8 defaults 7 DHCP 7 diagnostic
information 66
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 73
Index
digital filters 6, 35, 25, 27, 38 dimensions 57 DNS Server Address
primary 30 secondary 30
domain name 30 dynamic reconfiguration 21
E
EFT/B immunity 60 electronic keying 22
choosing in RSLogix 5000 18 compatible module 22 disable keying 22 exact match 22
embedded web server
1732E Armorblock 63 browser requirements 63
emissions 60 enclosure type rating 60 ESD immunity 60 EtherNet/IP 61 exclusive owner 23
F
factory defaults 8 fault 24, 54
communication 55 general module 55 LED 4 mode 1 notification 55 warning signal 55
features
configurable 35 fault mode 1 overview 1 physical 2 preset temperature selection 1 sensor type 1
filters 58, 59 firmware version 3 Functional Earth 9 functional earth ground 2
G
gateway 8
H
hardware
set up 14
hardware/software compatibility 3 high alarms 6 high engineering 25, 27 high vibration 9 high-high alarms 6, 5 home page
web server 64
host name 30
I
I/O Configuration 13, 16
tree 21
indicators
status 54
Inhibit Module 24 input resistance 59 input specifications 58 input tags 67 input voltage range 58 installation 7
connect cables 7 mount module 7 set network address 7
IP
address 20 settings 30
isolation voltage 57
K
KC 61 keying
electronic 18
L
latch alarms 28, 29 LED
flashing red 54 flashing red/green 54 flashing yellow 54 green 54 red 54
level alarms 1, 5
low 6
link 53 listen only 23 Logix5565 14 low alarms 5 low engineering 25, 27 low-low 6 low-low alarms 5 LVD 12
74 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Index
M
manuals
related iii
millivolt 5 minor revision
setting in RSLogix 5000 18
module
data 63 LED 8 mount 9 power 11, 57 properties 21 revision 22 series 22 tags 67
monitoring 63 mounting 9
dimensions 9 module 9
N
network
address 7 LED 8
node address switches 2 noise transients 6 normal mode rejection rate 58, 59 notch filter 25, 27, 37
O
open-wire detection 5 overrange detection 1, 5
P
pan head screws 9 PELV 12 physical features 2 port configuration 30 port speed
configure 31
power
connectors 11 consumption 57
publications
related iii
purpose of this manual iii
R
radiated RF immunity 60 redundancy
use 15
related documentation iii relative humidity 60 requested packet interval (RPI) 23 resistance 5 resolution 58 RSLinx software3, 14 RSLogix 5000 3, 4, 5, 13, 15, 16, 20, 45, 53, 54
Calibration tab 31 choosing an electronic keying method 18 Configuration tab 24 Connection tab 23 General tab 22 I/O Configuration 13 Internet Protocol tab 30 Port Configuration tab 30 setting the minor revision 18 use 16
RTD
sensor type 4, 25
S
screws 9 SELV 12 sensor types 1, 25, 27, 35, 36 set up
hardware 14
setting 7 shock
nonoperating 60 operating 60
software
configuration 16
specifications 57
general 57 resolution 57 voltage 57 weight 57
status indicators 2, 53, 57
auxiliary power 2, 54 I/O 2, 54 link 2, 54 module 2, 53, 54 network 2, 53, 54
status monitoring 32 surge transient immunity 60 switches 2, 7
001 8 888 8
T
temperature
ambient 60 nonoperating 60 operating 60 units 27, 35, 37
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 75
Index
thermistor 39 thermistors 4 thermocouple types 3 Thermometrics DC95F302V/W 58 Thermometrics MF65F302V/W 58 torque 10 troubleshooting 53, 54 troubleshoot module 54
U
UL Type 1 enclosure 12 underrange detection 1, 5 use
default configuration 16 redundancy 15 RSLogix 5000 16 screw holes 9
V
vibration 9, 60
W
web server 63, 64
home page 64 log in 64
wiring 10
76 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 77
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/ application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/support/
Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual. You can contact Customer Support for initial help in getting your product up and running.
United States or Canada 1.440.646.3434 Outside United States or
Canada
Use the Worldwide Locator your local Rockwell Automation representative.
, you can find technical manuals, a knowledge base of FAQs, technical and
.
at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain
Outside United States Please contact your local Rockwell Automation representative for the return procedure.
one) to your distributor to complete the return process.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002
, available at http://www.rockwellautomation.com/literature/.
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 78
Copyright © 2012 Rockwell Automation, In c. All rights reserved. Printed in the U.S.A.
Loading...