Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety
Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1
your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/
important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference,
and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment
must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from
the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous
environment, which may lead to personal injury or death, property damage, or economic loss.
available from
) describes some
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death,
property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the
consequence
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that
dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that
surfaces may reach dangerous temperatures.
Identifies information that is critical for successful application and understanding of the product.
Allen-Bradley, Rockwell Automation, ArmorBlock, RSLogix 500 0, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Preface
Read this preface to familiarize yourself with the rest of the manual. It provides
information concerning:
• who should use this manual
• the purpose of this manual
• related documentation
• conventions used in this manual
Who Should Use this
Manual
Purpose of this Manual
ResourceDescription
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Analog
Modules 1732E-WD003
Use this manual if you are responsible for designing, installing, programming, or
troubleshooting control systems that 1732E ArmorBlock™ EtherNet/IP Dual
Port 4-Point Thermocouple and RTD Modules.
You should have a basic understanding of electrical circuitry and familiarity with
relay logic. If you do not, obtain the proper training before using this product.
This manual is a reference guide for the 1732E-IT4IM12R, 1732E-IR4IM12R
modules. It describes the procedures you use to install, wire, troubleshoot, and
use your module.
Related Documentation
The following documents contain additional information concerning Rockwell
Automation products. To obtain a copy, contact your local Rockwell Automation
office or distributor.
Information on wiring the ArmorBlock Dual-Port EtherNet/IP 4-Point Analog
Modules (1732E-IF4M12R, 1732E-OF4M12R, 1732E-IT4IM12R,
1732E-IR4IM12R).
The following conventions are used throughout this manual:
• Bulleted lists such as this one provide information, not procedural steps.
Information on installing the ArmorBlock EtherNet/IP module.
A manual on how to install, configure and maintain linear and Device-level
Ring (DLR) networks using Rockwell Automation EtherNet/IP devices with
embedded switch technology.
A manual on how to use EtherNet/IP modules with Logix5000 controllers and
communicate with various devices on the Ethernet network.
Information on how to install and navigate RSLogix 5000. The guide includes
troubleshooting information and tips on how to use RSLogix 5000 effectively.
A glossary of industrial automation terms and abbreviations.
• Numbered lists provide sequential steps or hierarchical information.
• Italic type is used for emphasis.
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012iii
Notes:
ivRockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Table of Contents
Preface
Who Should Use this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iii
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012vii
Table of Contents
Notes:
viiiRockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Chapter
Overview of the 1732E ArmorBlock
Thermocouple and RTD Input Modules
1
Overview
Module Features
This chapter provides an introduction to the features and functionalities of the
1732E ArmorBlock Thermocouple and RTD Input Modules. It includes the
following sections.
TopicPage
Module Features1
Physical Features of Your Module2
Types of Modules3
Hardware/Software Compatibility3
Thermocouple Types3
RTD Sensor Types4
Digital Filters6
Module Alarms5
The 1732E-IT4IM12R and 1732E-IR4IM12R modules let you configure a
sensor type for each of four input channels that linearizes analog signal into a
temperature value. The RTD module, 1732E-IR4IM12R, linearizes ohms into
temperature and the Thermocouple module, 1732E-IT4IM12R, linearizes
millivolts into temperature.
The modules have the following features:
• Sensor type
• Preset temperature selection
• Fault mode
• Level alarms
• overrange and underrange detection
To learn more about module features, see Configurable Features for the
Thermocouple and RTD Input Modules on page 35.
You must use RSLogix 5000 to configure these features. For a detailed how-toconfigure instructional guide, see the chapter, Configure Your Thermocouple
and RTD Input Modules with RSLogix 5000 Software on page 13.
Rockwell Automation Publication 1732E-UM004A-EN-E - July 20121
Chapter 1 Overview of the 1732E ArmorBlock Thermocouple and RTD Input Modules
45871
Link 1 status indicator
EtherNet/IP D-code
M12 connector
Node address switches
M12 style
I/O connectors
Micro-style power in
Micro-style power out
I/O status
indicators
EtherNet/IP D-code
M12 connector
Link 2 status indicator
Node address switches
Network status indicator
Module status indicator
Auxiliary Power
status indicator
Functional Earth Ground
(1)
Physical Features of
Your Module
The modules have the following components:
• Node address switches
• Connectors (two EtherNet/IP D-code M12 connectors, two micro-style
Power in/out connectors, four I/O M12 connectors)
• Status indicators (Link, I/O, Module, Network, and Auxiliary power
status indicators)
• Functional earth ground
Physical Features of 1732E-IT4IM12R and 1732E-IR4IM12R Modules
(1)
Functional Earth grounds the I/O block’s EtherNet/IP communication circuitry which is designed to mitigate the
effect of noise on the network. The device requires a solid earth ground connection, either through a metal
screw to a grounded metal panel or through a wire.
2Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Overview of the 1732E ArmorBlock Thermocouple and RTD Input Modules Chapter 1
Types of Modules
Hardware/Software
Compatibility
The Thermocouple and RTD modules are as follows.
Catalog NumberDescriptionNetwork
1732E-IT4IM12R24V DC power, 4-Point Isolated
Thermocouple Input, Dual-Port
EtherNet/IP Module
1732E-IR4IM12R24V DC power, 4-Point Isolated RTD
Input, Dual-Port EtherNet/IP Module
Connector
Dual D-code
M12
Power
Connector
Dual 4-pin
micro
The module and the applications described in this manual are compatible with
the following firmware versions and software releases.
ProductFirmware Version / Software Release
1732E-IT4IM12R and 1732E-IR4IM12RFirmware rev. 1.1 or later
1756-EN2T, 1756-EN2TR, 1756-EN3TR3.x version when using RSLogix 5000 v20 or later
RSLogix 5000 software20 or later
RSLinx software2.56 or later
Thermocouple Types
The 1732E-IT4IM12R module supports the following thermocouples.
Supported Thermocouple Types
TypeMaterialTemperature Range
BPt /30% Rh vs. Pt/5% Rh40…1820(104…3308)0.000…13.820 mV
CW/5% Re vs. W/26% Re0…2320(32…4208)0.000…37.107 mV
ENi/Cr vs. Cu/Ni-270…1000(-454…1832)-9.835…76.373 mV
JFe vs. Cu/Ni-210…1200(-346…2192)-8.095…69.553 mV
KNi/Cr vs. Ni/Al-270…1372(-454…2501.6)-6.458…54.886 mV
NNi/14.2%Cr/1.4%Si vs.
Ni/4.4%Si/0.1%Mg
RPt/13%Rh vs. Pt-50…1768(-58…3214.4)-0.226…21.101 mV
SPt/10%Rh vs. Pt-50…1768(-58…3214.4)-0.236…18.693 mV
TCu vs. Cu/Ni-270…400(-454…752)-6.258…20.872 mV
°C (°F)
-270…1300(-454…2372)-4.345…47.513 mV
Voltage Range
Cold Junction Compensation
When using thermocouples, cold junction compensation is required at the
termination of the thermocouple wire. The actual cold junction exists outside of
the module at the wiring block internal to the CJC module and is representative
of the ambient temperature.
Accomplish a cold junction in the following ways:
Rockwell Automation Publication 1732E-UM004A-EN-E - July 20123
Chapter 1 Overview of the 1732E ArmorBlock Thermocouple and RTD Input Modules
Thermistor resistance used by the module to
determine a baseline for the thermocouple
Thermocouple
Hot junction
Cold junction
Face of module connector
871A-TS4CJC-DM or 871A-TR4CJC-DM
Terminal Chamber shown
• Enter an estimated temperature (Cold Junction Compensation Offset).
• Use external cold junction compensators to measure the cold junction
temperature directly.
To compensate for cold junction temperature voltage, the 1732E-IT4IM12R
Thermocouple module has to determine actual cold junction temperature. If the
module is configured to provide cold junction compensation, then the user must
use a CJC Terminal Chamber (such as Allen-Bradley 871A-TS4CJC-DM or
871A-TR4CJC-DM
(1)
as shown in the next diagram).
The module uses this thermistor(s) resistance to deduce the cold junction
generated voltage to be applied to accurately measure the hot junction absolute
temperature.
RTD Sensor Types
The compensation voltage to be applied can also be estimated by applying fixed
cold junction correction using a fixed offset directly through the RSLogix 5000
software. The module supports thermistor compensation range at 0…70 °C.
The Thermocouple module also supports CJC error detection if a channel CJC
module is selected but is not correctly connected to the correct channel. The
module detects open circuit condition and triggers the warning status bit and
fault LED.
Cold junction compensation is supported on all four channels of the
1732E-IT4IM12R module.
The 1732E-IR4IM12R module supports 100Ω- 200Ωμ = 0.00385/0.003916 Pt
RTDs, 100/120Ω Ni RTDs, and a 10Ω Cu α =0.00427 RTD.
(1) The Allen-Bradley 871A-TS4CJC-DM or 871A-TR4CJC-DM terminal chamber has an embedded thermistor,
which facilitates thermocouple-based temperature measurement. The thermistor types supported are
Thermometrics MF65F302V/W, or DC95F302V/W.
4Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Overview of the 1732E ArmorBlock Thermocouple and RTD Input Modules Chapter 1
It supports 3-wire and 2-wire RTDs using a jumper in the wiring at the input
connector of the module. The following RTD input types are supported.
Supported RTD Types
RTD typeTemperature Range °C (°F)Voltage Range
100 Ω Pt 3850…390.48 Ω-200…850 °C (-328…1562 °F)0…150 mV
200
Ω
Pt 3850…781 Ω-200…650 °C (-328…1202 °F)0…300 mV
100 Ω Pt 39160…337.03 Ω-200…630 °C (-328…1166 °F)0…156.25 mV
200 Ω Pt 39160…674.06 Ω-200…630 °C (-328…1166 °F)0…312.5 mV
10
Ω
Cu 4270…19.116 Ω-320…500 °C (-544…932 °F)0…19.47 mV
120 Ω Ni 6720…445.10 Ω-70…445 °C (-94…833 °F)0…156.25 mV
100 Ω Ni 6180…198.88 Ω-60…180 °C (-76…356 °F)0…75 mV
120
Ω
Ni 6180…238.65 Ω-90…140 °C (-130…284 °F)0…75 mV
The module uses a third sensor wire to measure and correct for the cable lead
resistance for each RTD type. The compensation circuit depends on an outside
module jumper to connect the third wire if the compensating lead wire is not
available (that is, if a 2-wire RTD is connected to the I/O connector).
Module Alarms
If the lead resistance is not directly measured with the third lead wire, the user can
specify a lead wire resistance offset to be applied to the data for direct
compensation via RSLogix 5000.
The ArmorBlock Thermocouple and RTD modules are capable of generating the
following alarms.
• Overrange
• Und erra ng e
• Level (low, low-low, high, high-high)
• Open-wire detection
Overrange Alarm
The channel overrange alarm is set if the input is greater than the maximum
temperature (thermocouple or RTD range dependent), millivolt (+78 mV) or
resistance (600 Ω) range value, or above the maximum range of the thermocouple
or RTD.
Underrange Alarm
The channel underrange alarm is set if the input is less than the minimum
temperature (thermocouple or RTD range dependent), millivolt (-78 mV) or
Rockwell Automation Publication 1732E-UM004A-EN-E - July 20125
Chapter 1 Overview of the 1732E ArmorBlock Thermocouple and RTD Input Modules
resistance (10 Ω) range value, or below the minimum range of the thermocouple
or RTD.
Level Alarms
The following level alarms are available.
• Low
• Low-Low
• High
• High-High
When the channel input goes below a low alarm or above a high alarm, a bit is set
in the data table. All Alarm Status bits can be read individually or by reading the
Channel Status Byte (seepage 35
You can configure each channel alarm individually.
).
Digital Filters
Chapter Summary
The modules also support a digital filter to smooth input data noise transients on
each input channel. This value specifies the time constant for a digital first order
lag filter on the input. It is specified in units of milliseconds. A value of 0 disables
the filter.
To learn how to configure digital filters, see page 21
In this chapter, you were introduced to the ArmorBlock Thermocouple and RTD
input modules.
.
6Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Install Your ArmorBlock Module
Chapter
2
Overview
Install the Module
This chapter shows you how to install and wire the 1732E ArmorBlock
EtherNet/IP Dual Port 4-Point Thermocouple and RTD Input modules. The
only tools you require are a flat or Phillips head screwdriver and drill. This
chapter includes the following topics:
TopicsPage
Install the Module7
Set the Network Address7
Mount the Module9
Wire the Module10
To install the module:
• Set the network address
• Mount the module
• Connect the I/O, Network, and Auxiliary cables to the module.
Set the Network Address
The I/O block ships with the rotary switches set to 999 and DHCP enabled. To
change the network address, you can do one of the following:
• adjust the node address switches on the front of the module.
• use a Dynamic Host Configuration Protocol (DHCP) server, such as
Rockwell Automation BootP/DHCP.
• retrieve the IP address from nonvolatile memory.
The I/O block reads the switches first to determine if the switches are set to a
valid number. To set the network address:
1. Remove power.
2. Remove the switch dust caps.
3. Rotate the three (3) switches on the front of the module using a small
blade screwdriver.
4. Line up the small notch on the switch with the number setting you wish to
use.
Valid settings range from 001…254.
Rockwell Automation Publication 1732E-UM004A-EN-E - July 20127
Chapter 2 Install Your ArmorBlock Module
44233
Note: You need to remove the
protective switch dust caps before you
can adjust the address settings.
Example shows network switches set
at 163, which sets the module IP
address to 192.168.1.163.
5. Replace switch dust caps. Make sure not to over tighten.
6. Reapply power.
7. Record IP address on product label found on the side of enclosure.
Set Network Address
2
0
2
4
0
6
8
4
8
6
2
0
4
6
8
When the switches are set to a valid number, the I/O block’s IP address is
192.168.1.xxx, where xxx represents the number set on the switches. The I/O
block’s subnet mask is 255.255.255.0 and default gateway address is set to
192.168.1.1.
When the I/O block uses the network address set on the switches, the I/O block
does not have a host name assigned to it or use any Domain Name Server.
If the switches are set to an invalid number (for example, 000 or a value greater
than 254 excluding 888), the I/O block checks to see if DHCP is enabled. If
DHCP is enabled, the I/O block asks for an address from a DHCP server. The
DHCP server also assigns other Transport Control Protocol (TCP) parameters.
(The modules are shipped with the network switches set to 999.)
If DHCP is not enabled, the I/O block uses the IP address (along with other
TCP configurable parameters) stored in nonvolatile memory.
Network Address Switch value 001
The module IP address cannot be the same as the gateway address. If the address
switches are set to 001, the module IP address becomes 192.168.1.1, which is the
same as the default gateway address. In this case, the module gateway address will
be set to 0.0.0.0.
Default Factory Configuration
The switch value 888 resets the module to default factory configuration on power
up. The module will not operate properly when powered up with this setting.
The switches must be set to a different (and valid) value and then power cycled
after a reset.
8Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
While in reset state, the module LED flashes red and the network LED goes off.
Install Your ArmorBlock Module Chapter 2
37 (1.46)
16.2 (0.64)
168.6 (6.64)
(1.26)
32
(1.70)
43.3
(0.78)
19.8
166.5 (6.56)
27
(1.06)
6LGH0RXQWLQJ
)URQW0RXQWLQJ
179 (7.05)
18
(0.71)
Millimeters
(Inches)
45870
Functional Earth
Grounds the I/O block
EtherNet/IP communication
circuitry which is designed to
mitigate the effect of noise on
the network. It requires a solid
earth ground connection,
either through a metal screw
to a grounded metal panel or
through a wire.
Mount the Module
To mount the module on a wall or panel, use the screw holes provided in the
module. Refer to the drilling dimensions illustration to guide you in mounting
the module.
Mounting Dimensions
Install the mounting base as follows:
1. Lay out the required points as shown above in the drilling dimension
drawing.
2. Drill the necessary holes for #6 (M3) pan head screws.
3. Mount the module using #6 (M3) screws.
Mount the Module in High Vibration Areas
If you mount the module in an area that is subject to shock or vibration, we
recommend you use a flat and a lock washer to mount the module. Mount the flat
Rockwell Automation Publication 1732E-UM004A-EN-E - July 20129
and the lock washer as shown in the mounting illustration. Torque the mounting
screws to 0.68 Nm (6 lb-in.).
High Vibration Area Mounting
Wire the Module
The 1732E-IT4IM12R and 1732E-IR4IM12R modules have 5-pin micro-style
M12 I/O connectors. We provide caps to cover the unused connectors on your
module. Connect the quick-disconnect cord sets you selected for your module to
the appropriate ports.
Use the 1585D–M4DC–H: Polyamide small body unshielded mating
connectors for the D-Code M12 female network connector.
Note that the distance between the center of each Ethernet connector
is 16.2 mm (see Mounting Dimensions on page 9
recommends the use of suitable cable based on this measurement.
Some of the recommended cables are 1585D-M4TBJM-x and 1585DM4TBDM-x for daisychains.
Install Your ArmorBlock Module Chapter 2
). Rockwell Automation
Use two twisted pair CAT5E UTP or STP cables.
Power Connectors
Attach the micro-style 4-pin connector to the micro-style 4-pin receptacle as
shown below.
Micro-style 4-Pin Input Male Receptacle
Rockwell Automation Publication 1732E-UM004A-EN-E - July 201211
The power required by the module is based on a 4-pin micro-style connector
system. Power can be daisy chained through the module either left to right or
right to left. The standard configuration is with Module/Auxiliary power
entering the module on the left connector.
Chapter 2 Install Your ArmorBlock Module
IMPORTANT
Both modules require two 24V DC (nominal) supplies. These supplies are called
the Module Power and the Auxiliary Power. The Module power supplies the
microprocessor and Ethernet portions of the module, while Auxiliary power
supplies the I/O circuits.
Internally, the Module Power and Auxiliary Power are electrically isolated.
The maximum current that any pin on the power connectors can
carry is 4 A.
ATTENTION: To comply with the CE Low Voltage Directive (LVD), this
equipment and all connected I/O must be powered from a source
compliant with the following:
Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).
ATTENTION: To comply with UL restrictions, this equipment must be
powered from a source compliant with the following: Limited Voltage/
Limited Current.
ATTENTION: The device meets UL Type 1 Enclosure rating.
Chapter Summary
In this chapter, you learned how to install and wire your module.
12Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Chapter
3
Configure Your Thermocouple and RTD Input
Modules with RSLogix 5000 Software
Introduction
This chapter guides you through the steps required to configure your modules
using the RSLogix 5000 software. Note that the modules presented in this
chapter can be configured using RSLogix 5000 software, version 20, or later.
TopicPage
Set Up the Hardware14
Create the Example Application15
Configure Your I/O Module16
Overview of the Configuration Process through RSLogix 500016
Add a New Bridge and Module to Your RSLogix 5000 Project16
Download the Program to Your Controller20
Edit Your Module Configuration21
Chapter Summary33
Configuring the two modules through RSLogix 5000 involve the same general
procedure. Note, however, that the two modules do not have exactly similar
Module Definition properties. These are distinctly covered in this chapter.
Rockwell Automation Publication 1732E-UM004A-EN-E - July 201213
Chapter 3 Configure Your Thermocouple and RTD Input Modules with RSLogix 5000 Software
Local
Chassis
1732E
ArmorBlock
Logix5565
Controller (slot 1)
1756-EN2T
192.168.1.20 (slot 3)
Data
Switch
192.168.1.100
Programming
Terminal
0
1732E ArmorBlock
Ethernet Module
192.168.1.3
44971
32Slot1
Embedded
Technology
Set Up the Hardware
In this example, a ControlLogix chassis contains the Logix5565 processor in slot
1 and a 1756-EN2T bridge module in slot 3. The 1732E ArmorBlock module is
mounted remotely.
Logix5565
EtherNet/IP
Logix5565
1756-EN2T
To work along with this example set up your system as shown.
• Note that in the example application, the Logix5565 controller and
1756-EN2TR module (firmware version 2.3 or higher) are assumed to be
in the slots shown.
• Verify the IP addresses for your programming terminal, 1756-EN2TR
module and 1732E ArmorBlock Ethernet module.
• Verify that you connected all wiring and cabling properly.
• Be sure you configured your communication driver (for example,
AB_ETH-1 or AB-ETHIP-1) in RSLinx software.
14Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Configure Your Thermocouple and RTD Input Modules with RSLogix 5000 Software Chapter 3
Create the
Example Application
Perform the following steps to create the example application:
1. From the File menu, select New.
The New Controller dialog opens.
2. Enter an appropriate name for the Controller, for example,
ArmorBlock_IO_Controller.
3. Select the correct version, chassis type, and slot number of the controller,
and the folder where you want to save the RSLogix 5000 software file
(Create In). The Description is optional.
To use redundancy in your system, select the Redundancy Enabled
checkbox.
4. Click OK.
Rockwell Automation Publication 1732E-UM004A-EN-E - July 201215
Chapter 3 Configure Your Thermocouple and RTD Input Modules with RSLogix 5000 Software
IMPORTANT
Configure Your I/O Module
Overview of the
Configuration Process
through RSLogix 5000
You must configure your module upon installation. The module will not work
until it has been configured with at least the default configuration.
RSLogix 5000 Configuration Software
You must use RSLogix 5000, version 20 or later, to configure your module. You
have the option of accepting default configuration for your module or writing
point-level configuration specific to your application.
Both options are explained in detail, including views of software screens, in this
chapter.
When you use the RSLogix 5000 software to configure a module, you must
perform the following steps:
1. Add the Local EtherNet/IP Bridge (1756-EN2T, 1756-EN2TR, or
1756-EN3TR) to your project’s I/O Configuration.
2. Add the 1732E-IT4IM12R or 1732E-IR4IM12R module as a child of the
1756-EN2T module.
Add a New Bridge and
Module to Your
RSLogix 5000 Project
3. Accept the default configuration or change it to specific configuration for
the module.
4. Edit configuration for a module when changes are needed.
After you have started RSLogix 5000 software and created a controller, you must
add a new bridge and a new module to your project. The bridge allows your
module to communicate with the controller.
The wizard allows you to create a new module and write configuration. You can
use default configuration or write specific configuration for your application.
Click Help on the configuration dialogs shown in this section if you
need assistance in selecting and setting the parameters.
16Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Configure Your Thermocouple and RTD Input Modules with RSLogix 5000 Software Chapter 3
If you are not offline, use this
pull-down menu to go offline.
A. Right-click 1756 Backplane.
B. Select New Module.
A. Select the 1756-EN2T
EtherNet/IP Bridge.
B. Click OK.
Add the Local EtherNet/IP Bridge to the I/O Configuration
1. If necessary, go offline.
2. Add the EtherNet/IP Bridge to your RSLogix 5000 project.
3. Expand Communications and select the new module in the Select Module
dialog that appears. Select the 1756-EN2T EtherNet/IP Bridge.
Rockwell Automation Publication 1732E-UM004A-EN-E - July 201217
Chapter 3 Configure Your Thermocouple and RTD Input Modules with RSLogix 5000 Software
A. Name the bridge.
B. Enter the IP address.
C. Select slot 3 for the EtherNet/IP bridge.
D. Make sure the Minor Revision number
matches your module revision number.
E. Choose an Electronic Keying method.
For more information, see page 22
.
F. Click OK.
4. The New Module dialog opens.
Configure the bridge module as illustrated below.
Note that we have entered the following properties in this example:
NameTEST_1756EN2T
IP address192.168.1.20
Slot3
Revision3.1
Electronic KeyingCompatible Module
The local 1756-EN2T communication module will communicate with the
1732E ArmorBlock module on Ethernet. Before you can communicate with your
module, you need to add it as a child of the 1756-EN2T communication module.
For more information about using 1756 controller and EtherNet/IP products, see
publication ENET-UM001
.
Add the I/O module as a child of the 1756-EN2T module
1. Right-click the Ethernet folder that appears below the 1756-EN2T bridge
you added to the I/O Configuration tree and select New Module.
18Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Loading...
+ 60 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.