XFyre™- Type H
Condensing Heating Boilers
Models 300-850
94% Thermal Efficiency at Full Rate, up to 99% at Part Load |
|
Indoor/Outdoor Construction Standard |
|
PVC, CPVC, or Stainless Venting Certified |
|
Soft Start, Electronic Modulation, 5:1 Turndown |
|
LCD Status Display and Full Diagnostics and Fault Memory |
|
Footprint: Less Than 8-1/3 ft2 |
|
Zero Clearance to Combustibles |
|
Meets NOx Requirements Thru 2012 (< 20 ppm) |
|
Maximum Outlet Water Temperature: 210ºF |
|
Maximum System Temperature: 200ºF |
|
Limited 25 Year Thermal Shock Warranty |
|
Limited Ten-Year Heat Exchanger Warranty |
Proudly Made in the USA |
Heat Exchanger
All Stainless Steel Construction with copper connections
Gasketless Heat Exchanger Design
ASME H Stamped
160 PSIG Working Pressure
National Board Approved
ASME Pressure Relief Valve
60 PSIG – Standard
PSIG – Optional
Temperature and Pressure Gauge, Shipped Loose
Control
120V, 60Hz, 1Ø, Power Supply
Digital Operating Control with LCD display.
Outdoor reset with Indirect Priority
0-10 VDC input for BMS
Cascade up to 8 boilers
Spark Ignition (DSI)
Remote Flame Sensor
High Limit, Manual Reset, Fixed, 200ºF
Auto Limit, Fixed, 200ºF
Alarm Dry Contact Connection
On/Off Power Switch
Flow Switch
Blocked Vent Pressure Switch
Boiler, DHW & System Pump Contacts
Water Temperature Sensors (3)
Burner
Ultra-Low NOx: Less than 20 PPM
Gas Train
Fuel
Natural Gas
Propane
Zero Governor Regulator
Dual-Seat Combination Valve
Electronic Modulating Firing Mode (H7)
Construction
Indoor/Outdoor Construction
Front Controls Enclosed
PolyTuf Powder Coat Finish
Rear Connections (Electrical, Gas, Vent, Combustion Air)
Top Connections (Water)
Design Certified ANSI Z21.13/ CSA 4.9
Combustion Air Filter
Condensate Trap
Venting (PVC-CPVC-Stainless.)
Vent Termination
Indoor, Vertical – Option D-11
Indoor, Horizontal – Option D-15
Outdoor
Extractor - Optional
By others
Not required
Multi-Boiler System Controllers
B-36 TempTracker Mod+ Hybrid Digital
Controller, 2-4 Boilers, OA Reset
B-37 TempTracker Mod+ Hybrid Digital
Controller, 5-10 Boilers, OA Reset
B-38 TempTracker Mod+ Hybrid Digital
Controller, 11-16 Boilers, OA Reset
Options |
|
|
|
||
D-21 |
TruSeal™ Combustion Air Inlet |
||||
|
|
|
(Mounted) |
|
|
D-22 |
TruSeal™ Combustion Air Inlet |
||||
|
|
|
(Loose) |
|
|
P- |
Pump: |
HP, 120V, 1 , |
|||
|
|
|
60Hz |
|
|
|
|
|
Cast Iron |
|
Bronze/SS
S-1/S-2 High/Low Gas Pressure Switch,
Manual Reset
Z-12 Condensate Neutralizer Kit
Regulatory Agency Requirements