Raypak H7-1104 Manual

5 (2)
Raypak H7-1104 Manual

Job:

Engineer:

Contractor:

Prepared By:

 

Date:

Model: Indoor/Outdoor:

MVB® - Type H

Heating Boilers

Models 504-2004

84% Thermal Efficiency at Full Rate

100% Factory Fire Tested

Maximum Outlet Water Temperature: 220°F Minimum Acceptable Inlet Water Temperature: 120°F Full Safety Diagnostics with History

Footprint: Less Than 5-1/2 ft2

Limited Twenty-Year Thermal Shock Warranty Limited Ten-Year Heat Exchanger Warranty Electronic Modulation, Constant Ratio 1.4:1 Turndown Soft-Start Modulating Controller with LCD Display Status Display Lights

Heat Exchanger

Headers

Cast Iron – Standard

Bronze – Option A-1

ASME H Stamped

160 PSIG Working Pressure

National Board Approved

Fin Tubing

Copper – Standard

Cupro Nickel – Option A-3

ASME Powder-Coated Tube Sheet

Silicone High Temp O-Rings

ASME Pressure Relief Valve

60 PSIG – Standard

PSIG – Optional

Temperature and Pressure Gauge, Shipped Loose

Stainless Steel Evaporator Plate

Control

120V, 60Hz, 1Ø, Power Supply

120/24V 60Hz Transformer

Ignition Module

3-Try – Standard

Single-Try – Option C-6

Hot Surface Ignition (HSI)

Remote Flame Sensor

High Limit, Manual Reset, Fixed, 240ºF

On/Off Power Switch

Flow Switch

Blocked Vent Pressure Switch

Combustion Air Proving Switch

Pump Switch

Pump Time Delay

Control (cont.)

Diagnostics Panel

Modulating Temperature Control

Water Temperature Sensors (3)

Burner

Ultra-Low NOx: Less than 20 PPM

Gas Train

Fuel

Natural Gas

Propane

Zero Governor Regulator

Dual-Seat Combination Valve

Electronic Modulating Firing Mode

Construction

Indoor/Outdoor Construction

Front Controls Enclosed

PolyTuf Powder Coat Finish

Rear Connections (Water, Electrical, Gas, Vent, Combustion Air)

Design Certified ANSI Z21.13/ CSA 4.9

Venting

Vent Termination

Outdoor - Option D-11

Indoor, Horizontal – Option D-15

Indoor, Vertical (by others)Combustion Air

In-Line Filter Kit – Option D-17

Air Intake Elbow – Option D-16

Extractor – Optional

By others

Not required

Temperature Controllers

B-36

TempTracker Mod+ Digital

 

 

 

Controller, 2-4 Boilers, OA Reset

B-37

TempTracker Mod+ Digital

 

 

 

Controller, 5-10 Boilers, OA Reset

B-38

TempTracker Mod+ Digital

 

 

 

Controller, 11-16 Boilers,

 

 

 

OA Reset

 

Y-241

Electronic Sequencer, 2-4 Boilers

Y-281

Electronic Sequencer, 5-8 Boilers

Options

 

 

 

A-30

Air Vent, Auto, 150 PSI

F-10

Low Water Cut-Off, Remote Probe

I-1

High Limit, Auto Reset, Adj.,

 

 

 

100-240°F

 

I-2

High Limit, Manual Reset, Adj.,

 

 

 

100-240°F

 

P-

 

 

Pump:

 

HP, 120V, 1 , 60Hz

 

 

Water Hardness:

 

GPG

 

 

Cast Iron

Bronze

 

 

Loose

Mounted

P-

 

Cold Water Start

 

 

P-

 

Cold Water Run

 

 

S-1

Low Gas Pressure Switch,

 

 

Manual Reset

 

 

S-2

High Gas Pressure Switch,

 

 

Manual Reset

 

 

Regulatory Agency Requirements

Catalog No.: 2000.364C

Effective: 7-15-08

Replaces: 2-1-08