We always want you to feel that you made the right decision to use our products. If you have suggestions, comments,
compliments or complaints about our products, documentation, or support, please write or call us.
ProSoft Technology
Technology, Inc. All other brand or product names are or may be trademarks of, and are used to identify products
and services of, their respective owners.
®
, ProLinx ®, inRAx ®, ProTalk ®, and RadioLinx ® are Registered Trademarks of ProSoft
ProSoft Technology® Product Documentation
In an effort to conserve paper, ProSoft Technology no longer includes printed manuals with our product shipments.
User Manuals, Datasheets, Sample Ladder Files, and Configuration Files are provided on the enclosed CD-ROM,
and are available at no charge from our web site: www.prosoft-technology.com
Printed documentation is available for purchase. Contact ProSoft Technology for pricing and availability.
North America: +1.661.716.5100
Asia Pacific: +603.7724.2080
Europe, Middle East, Africa: +33 (0) 5.3436.87.20
Latin America: +1.281.298.9109
Important Installation Instructions
Power, Input, and Output (I/O) wiring must be in accordance with Class I, Division 2 wiring methods, Article 501-4 (b)
of the National Electrical Code, NFPA 70 for installation in the U.S., or as specified in Section 18-1J2 of the Canadian
Electrical Code for installations in Canada, and in accordance with the authority having jurisdiction. The following
warnings must be heeded:
A WARNING - EXPLOSION HAZARD - SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR
CLASS I, DIV. 2;
B WARNING - EXPLOSION HAZARD - WHEN IN HAZARDOUS LOCATIONS, TURN OFF POWER BEFORE
REPLACING OR WIRING MODULES
C WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN
SWITCHED OFF OR THE AREA IS KNOWN TO BE NON-HAZARDOUS.
D THIS DEVICE SHALL BE POWERED BY CLASS 2 OUTPUTS ONLY.
MVI (Multi Vendor Interface) Modules
WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN
SWITCHED OFF OR THE AREA IS KNOWN TO BE NON-HAZARDOUS.
AVERTISSEMENT - RISQUE D'EXPLOSION - AVANT DE DÉCONNECTER L'ÉQUIPEMENT, COUPER LE
COURANT OU S'ASSURER QUE L'EMPLACEMENT EST DÉSIGNÉ NON DANGEREUX.
Warnings
North America Warnings
A Warning - Explosion Hazard - Substitution of components may impair suitability for Class I, Division 2.
B Warning - Explosion Hazard - When in Hazardous Locations, turn off power before replacing or rewiring
modules.
Warning - Explosion Hazard - Do not disconnect equipment unless power has been switched off or the area is
known to be nonhazardous.
C Suitable for use in Class I, division 2 Groups A, B, C and D Hazardous Locations or Non-Hazardous Locations.
ATEX Warnings and Conditions of Safe Usage:
Power, Input, and Output (I/O) wiring must be in accordance with the authority having jurisdiction
A Warning - Explosion Hazard - When in hazardous locations, turn off power before replacing or wiring modules.
B Warning - Explosion Hazard - Do not disconnect equipment unless power has been switched off or the area is
known to be non-hazardous.
C These products are intended to be mounted in an IP54 enclosure. The devices shall provide external means to
prevent the rated voltage being exceeded by transient disturbances of more than 40%. This device must be used
only with ATEX certified backplanes.
D DO NOT OPEN WHEN ENERGIZED.
Warning: This module is not hot-swappable! Always remove power from the rack before inserting or removing this
module, or damage may result to the module, the processor, or other connected devices.
Battery Life Advisory
The MVI46, MVI56, MVI56E, MVI69, and MVI71 modules use a rechargeable Lithium Vanadium Pentoxide battery to
backup the real-time clock and CMOS. The battery should last for the life of the module. The module must be
powered for approximately twenty hours before the battery becomes fully charged. After it is fully charged, the battery
provides backup power for the CMOS setup and the real-time clock for approximately 21 days. When the battery is
fully discharged, the module will revert to the default BIOS and clock settings.
Note: The battery is not user replaceable.
Markings
Electrical Ratings
Backplane Current Load: 800 mA @ 5 Vdc
Operating Temperature: 0°C to 60°C (32°F to 140°F)
Storage Temperature: -40°C to 85°C (-40°F to 185°F)
Shock: 30 g operational, 50 g non-operational; Vibration: 5 g from 10 Hz to 150 Hz
Relative Humidity 5% to 95% (with no condensation)
All phase conductor sizes must be at least 1.3 mm(squared) and all earth ground conductors must be at least
4mm(squared).
Label Markings
Agency Approvals and Certifications
Agency Applicable Standards
ANSI / ISA ISA 12.12.01 Class I Division 2, GPs A, B, C, D
CSA/cUL C22.2 No. 213-1987
CSA CB Certified IEC61010
ATEX EN60079-0 Category 3, Zone 2
EN60079-15
243333
MVI71-DFNT ♦ PLC 5 Contents
EtherNet/IP Client/Server Communication Module User Manual
Contents
Your Feedback Please ........................................................................................................................ 2
How to Contact Us .............................................................................................................................. 2
o Microsoft Windows XP
o Microsoft Windows 2000
o Microsoft Windows NT v4.0 with Service Pack 3 or greater
o Microsoft Windows ME
o Microsoft Windows 98
64 Mbytes of RAM minimum, 256 Mbytes of RAM recommended
100 Mbytes of free hard disk space (or more based on application
requirements)
256-color VGA graphics adapter, 800 x 600 minimum resolution (True Color
1024 × 768 recommended)
CD-ROM drive
HyperTerminal or other terminal emulator program capable of file transfers
using Zmodem protocol.
®
100 MHz minimum. Pentium III 700 MHz (or better) recommended
Page 12 of 175 ProSoft Technology, Inc.
February 3, 2011
MVI71-DFNT ♦ PLC 5 Start Here
EtherNet/IP Client/Server Communication Module User Manual
1.2 Package Contents
The following components are included with your MVI71-DFNT module, and are
all required for installation and configuration.
Important: Before beginning the installation, please verify that all of the following items are
present.
Qty. Part Name Part Number Part Description
1 MVI71-DFNT Module MVI71-DFNT EtherNet/IP Client/Server Communication
1 Cable Cable #15, RS232
3 Cable Cable #14, RJ45 to
2 Adapter 1454-9F Two Adapters, DB9 Female to Screw
1 ProSoft Solutions CD Contains sample programs, utilities and
If any of these components are missing, please contact ProSoft Technology
Support for replacement parts.
Module
For RS232 Connection to the CFG Port
Null Modem
For DB9 Connection to Module’s Port
DB9 Male Adapter
cable
Terminal. For RS422 or RS485
Connections to Port 1 and 2 of the Module
documentation for the MVI71-DFNT
module.
ProSoft Technology, Inc. Page 13 of 175
February 3, 2011
Start Here MVI71-DFNT ♦ PLC 5
User Manual EtherNet/IP Client/Server Communication Module
1.3 Setting Jumpers
The Setup Jumper acts as "write protection" for the module’s flash memory. In
"write protected" mode, the Setup pins are not connected, and the module’s
firmware cannot be overwritten. Do not jumper the Setup pins together unless
you are directed to do so by ProSoft Technical Support.
The following illustration shows the MVI71-DFNT jumper configuration.
Note: If you are installing the module in a remote rack, you may prefer to leave the Setup pins
jumpered. That way, you can update the module’s firmware without requiring physical access to
the module.
Page 14 of 175 ProSoft Technology, Inc.
February 3, 2011
MVI71-DFNT ♦ PLC 5 Start Here
EtherNet/IP Client/Server Communication Module User Manual
1.4 Install the Module in the Rack
If you have not already installed and configured your PLC processor and power
supply, please do so before installing the MVI71-DFNT module. Refer to your
Rockwell Automation product documentation for installation instructions.
Warning: You must follow all safety instructions when installing this or any other electronic
devices. Failure to follow safety procedures could result in damage to hardware or data, or even
serious injury or death to personnel. Refer to the documentation for each device you plan to
connect to verify that suitable safety procedures are in place before installing or servicing the
device.
After you have checked the placement of the jumpers, insert MVI71-DFNT into
the PLC™ chassis. Use the same technique recommended by Rockwell
Automation to remove and install PLC modules.
Warning: This module is not hot-swappable! Always remove power from the rack before
inserting or removing this module, or damage may result to the module, the processor, or other
connected devices.
1 Turn power OFF.
2 Align the module with the top and bottom guides, and slide it into the rack
until the module is firmly against the backplane connector.
3 With a firm but steady push, snap the module into place.
4 Check that the holding clips on the top and bottom of the module are securely
in the locking holes of the rack.
5 Make a note of the slot location. You will need to identify the slot in which the
module is installed in order for the sample program to work correctly. Slot
numbers are identified on the green circuit board (backplane) of the PLC
rack.
6 Turn power ON.
Note: If you insert the module improperly, the system may stop working, or may behave
unpredictably.
ProSoft Technology, Inc. Page 15 of 175
February 3, 2011
Start Here MVI71-DFNT ♦ PLC 5
User Manual EtherNet/IP Client/Server Communication Module
1.5 Connect your PC to the Processor
1 Connect the right-angle connector end of the cable to your controller at the
communications port.
2 Connect the straight connector end of the cable to the serial port on your
computer.
Page 16 of 175 ProSoft Technology, Inc.
February 3, 2011
MVI71-DFNT ♦ PLC 5 Start Here
EtherNet/IP Client/Server Communication Module User Manual
1.6 Download the Sample Program to the Processor
To download the sample program from RSLogix 5 to the PLC processor
Note: The key switch on the front of the PLC processor must be in the REM position.
1 If you are not already online to the processor, open the Communications
menu, and then choose Download. RSLogix will establish communication
with the processor.
2 Click the Download button to transfer the sample program to the processor.
3 When prompted, choose Computer to PLC
4 RSLogix will compile the program and transfer it to the processor. This
process may take a few minutes.
ProSoft Technology, Inc. Page 17 of 175
February 3, 2011
Start Here MVI71-DFNT ♦ PLC 5
User Manual EtherNet/IP Client/Server Communication Module
5 When the download is complete, RSLogix will open another confirmation
dialog box. Click OK to switch the processor from Program mode to Run
mode.
Note: If you receive an error message during these steps, refer to your RSLogix documentation to
interpret and correct the error.
1.6.1 Configuring the RSLinx Driver for the PC COM Port
If RSLogix is unable to establish communication with the processor, follow these
steps.
1 Open RSLinx.
2 Open the C
OMMUNICATIONS menu, and choose CONFIGURE DRIVERS.
This action opens the Configure Drivers dialog box.
Note: If the list of configured drivers is blank, you must first choose and configure a driver from the
Available Driver Types list. The recommended driver type to choose for serial communication with
the processor is RS-232 DF1 Devices.
Page 18 of 175 ProSoft Technology, Inc.
February 3, 2011
MVI71-DFNT ♦ PLC 5 Start Here
EtherNet/IP Client/Server Communication Module User Manual
3 Click to select the driver, and then click CONFIGURE. This action opens the
Configure RS-232 DF1 Devices dialog box.
4 Click the AUTO-CONFIGURE button. RSLinxwill attempt to configure your
serial port to work with the selected driver.
5 When you see the message Auto Configuration Successful, click the OK
button to dismiss the dialog box.
Note: If the auto-configuration procedure fails, verify that the cables are connected correctly
between the processor and the serial port on your computer, and then try again. If you are still
unable to auto-configure the port, refer to your RSLinx documentation for further troubleshooting
steps.
ProSoft Technology, Inc. Page 19 of 175
February 3, 2011
Start Here MVI71-DFNT ♦ PLC 5
User Manual EtherNet/IP Client/Server Communication Module
1.7 Connect your PC to the Module
With the module securely mounted, connect your PC to the Configuration/Debug
port using an RJ45-DB-9 Serial Adapter Cable and a Null Modem Cable.
1 Attach both cables as shown.
2 Insert the RJ45 cable connector into the Configuration/Debug port of the
module.
3 Attach the other end to the serial port on your PC.
Page 20 of 175 ProSoft Technology, Inc.
February 3, 2011
MVI71-DFNT ♦ PLC 5 Installing and Configuring the Module
EtherNet/IP Client/Server Communication Module User Manual
This chapter describes how to install and configure the module to work with your
application. The configuration process consists of the following steps.
1 Modify the module’s configuration files to meet the needs of your application,
and copy the updated configuration to the module. Example configuration
files are provided on the CD-ROM. Refer to the Modifying the Example
Configuration File section, later in this chapter, for more information on the
configuration files.
2 Modify the example ladder logic to meet the needs of your application, and
copy the ladder logic to the processor. Example ladder logic files are provided
on the CD-ROM.
Note: If you are installing this module in an existing application, you can copy the necessary
elements from the example ladder logic into your application.
ProSoft Technology, Inc. Page 21 of 175
February 3, 2011
Installing and Configuring the Module MVI71-DFNT ♦ PLC 5
User Manual EtherNet/IP Client/Server Communication Module
The rest of this chapter describes these steps in more detail.
Set up of the MVI71-DFNT module requires software configuration using the
RSLogix 5 program and the DFNT.CFG file on the Compact Flash Disk in the
module. The easiest method to implement the module is to start with the
appropriate example provided with the module MVI71DFNT_BT.RSP for the
block transfer interface and the default configuration file. If you are installing this
module in an existing application, you can copy the elements required from the
example ladder logic to your application.
It is now time to edit the DFNT.CFG file to set up the module for the specific
application. Refer to the Configuration File section of this document. Download
this configuration to the module along with the associated ladder logic.
Enter the ladder logic to handle the blocks transferred between the module and
the PLC. Download the program to the PLC and test the program with the
module.
The module is now set up and ready for your application. Insert the module in the
rack (with the power turned off) and attach the serial communication cables.
Download the new application to the controller and place the processor in run
mode. Download the new DFNT.CFG file to the module using a terminal
emulation program. If all the configuration parameters are set correctly and the
module is attached to a network, the module’s Application LED (APP LED)
should remain off and the backplane activity LED (BP ACT) should blink very
rapidly. Refer to Diagnostics and Troubleshooting if you encounter errors. Attach
a computer or terminal to Port 0 on the module and look at the status of the
module using the Configuration/Debug Menu in the module.
Page 22 of 175 ProSoft Technology, Inc.
February 3, 2011
MVI71-DFNT ♦ PLC 5 Installing and Configuring the Module
EtherNet/IP Client/Server Communication Module User Manual
2.1 Module Configuration
This section contains the setup procedure, data, and ladder logic for successful
application of the MVI71-DFNT module. Each step in the setup procedure is
defined in order to simplify the use of the module.
2.1.1 Obtain the Sample Configuration Files
The ProSoft Solutions CD is organized in folders by module name. In the folder
for the module you are using, you will find sample configuration files and other
information.
1 Use Windows Explorer to locate the sample configuration files for your MVI71
module on the MVI71 CD.
2 When you have located the correct configuration files, use the C
P
ASTE commands to move the files to a location on your PC’s hard drive. We
recommend C:\temp.
3 Files copied from a CD-ROM are read-only. You must make the files writable.
Navigate to the directory where you copied the files, then select the files and
click the right mouse button to open a shortcut menu. On the shortcut menu,
select P
4 Next, open the configuration files in a text editor such as Notepad, which
comes with Windows. To start Notepad, click the S
choose P
5 When Notepad starts, open the F
to the folder where you copied the configuration file on your PC and select
the file. Click O
editing.
ROPERTIES,and clear (uncheck) the READ ONLY check box.
ROGRAMS /ACCESSORIES /NOTEPAD.
PEN.The configuration file will open in Notepad, ready for
OPY and
TART button, and then
ILE menu, and then choose OPEN.Navigate
Note: We do not recommend opening the configuration file in a word processor such as Microsoft
Word, because the file may be saved in a format that cannot be read by the module.
ProSoft Technology, Inc. Page 23 of 175
February 3, 2011
Installing and Configuring the Module MVI71-DFNT ♦ PLC 5
User Manual EtherNet/IP Client/Server Communication Module
2.2 Configuration File
In order for the module to operate, a configuration file (DFNT.CFG) is required.
This configuration file contains information to set the data transfer characteristics
between the module and the processor, to configure the module's client and
command list, and to configure the pass-through features. Each parameter in the
file must be set carefully in order for the application to be implemented
successfully.
The configuration file is separated into sections with topic header names
enclosed in the [ ] characters. The configuration file consists of the following
sections:
[Section] Description
[Module] General module configuration information
[DFNT Client 0] Configuration for the DFNT client
[DFNT Client 0 Commands] Command list for the DFNT client
[DF1 Pass-Through Server Port 1] Parameters for the pass-through port of the second port
[DF1 Pass-Through Port] Parameters for the DF1 port emulated on the third port of
After each section header, the file contains a set of parameters. Unique labels
are used under each section to specify a parameter. Each label in the file must
be entered exactly as shown in the file for the parameter to be identified by the
program. If the module is not considering a parameter, look at the label for the
data item. Each parameter's value is separated from the label with the ":"
character. This character is used by the program to delimit the position in the
data record where to start reading data. All data for a parameter must be placed
after the ":" character. For numeric parameter values any text located after the
value will not be used. There must be at least one space character between the
end of the parameter value and the following text.
Any record that begins with the "#" character is considered to be a comment
record. These records can be placed anywhere in the file as long as the "#" character is found in the first column of the line. These lines are ignored in the
file and can be used to provide documentation within the configuration file.
Liberal use of comments within the file can ease the use and interpretation of the
data in the file.
The client command list section is formatted differently than the other sections.
These sections contain lists of parameters to be used. Each list begins with the
label START and when the END label is reached. When entering the records into
the list, make certain that the first character in each line is left blank.
The [DFNT CLIENT 0 COMMANDS] section defines the Ethernet/IP commands
to be issued from the module to server devices on the network. These
commands can be used for data collection and/or control of devices on the
TCP/IP network.
on the module
the module
Page 24 of 175 ProSoft Technology, Inc.
February 3, 2011
MVI71-DFNT ♦ PLC 5 Installing and Configuring the Module
EtherNet/IP Client/Server Communication Module User Manual
2.2.1 [Module]
This section provides the module with a unique name, identifies the method of
failure for the communications for the module if the processor is not in run, and
describes how to initialize the module upon startup.
Module Name
0 to 80characters
This parameter assigns a name to the module that can be viewed using the
configuration/debug port. Use this parameter to identify the module and the
configuration file.
Read Register Start
0 to 3999
This parameter specifies the starting register address of a block of data registers
to transfer from the module to the processor.
Read Register Count
0 to 3960
This parameter specifies the number of registers to be transferred from the
module to the processor.
Write Register Start
0 to 3999
This parameter specifies the starting register address of a module register block
where data transferred from the processor will be stored.
Write Register Count
0 to 3960
This parameter specifies the number of registers to transfer from the processor to
the module.
Failure Flag Count
0 through 65535
This parameter specifies the number of successive transfer errors that must
occur before halting communication on the application port(s). If the parameter is
set to 0, the application port(s) will continue to operate under all conditions. If the
value is set larger than 0 (1 to 65535), communications will cease if the specified
number of failures occur.
ProSoft Technology, Inc. Page 25 of 175
February 3, 2011
Installing and Configuring the Module MVI71-DFNT ♦ PLC 5
User Manual EtherNet/IP Client/Server Communication Module
Initializing Output Data
YES or NO
This parameter determines if the output data for the module should be initialized
with values from the processor. If the value is set to N
be initialized to 0. If the value is set to Y
ES (1), the data will be initialized with
O (0), the output data will
data from the processor. Use of this option requires associated ladder logic to
pass the data from the processor to the module.
DFNT Server File Size
100 or 1000
Sets the maximum file size (100 or 1000) for the servers
2.2.2 [DF1 Pass-Through Server Port 1]
This section is used to define the DF1 pass-through server on Port 1 (the second
port)
[DF1 Pass-Through Server Port 1]
Enabled : Yes #Y=Use server, N=Do not use server
Service Port Number : 15000 #TCP service port for this server
Busy Timeout : 500 #Time to wait for not Busy (100-65535
milliseconds)
Baud Rate : 19200 #Baud rate for port 110-19200
Parity : N #N=None,O=Odd,E=Even,M=Mark,S=Space
Data Bits : 8 #5, 6, 7 or 8
Stop Bits : 1 #1 or 2
Enabled
Yes or No
This parameter determines if the server will be utilized by the module. If a value
of "Yes" is entered, the server will be used. Any other value will disable the
server.
Service Port Number
1 to 65535
This parameter sets the TCP/IP service port for this server. Each server can
have its own unique service port or can share the same number with other
servers.
Busy Timeout
100 to 65535 milliseconds
This parameter sets the number of milliseconds the server will wait for the serial
pass-through port to become available. Valid data range for this parameter is 100
to 65535.
Page 26 of 175 ProSoft Technology, Inc.
February 3, 2011
MVI71-DFNT ♦ PLC 5 Installing and Configuring the Module
EtherNet/IP Client/Server Communication Module User Manual
Baud Rate - 110 to 19200
110 to 19200
This parameter specifies the baud rate for the primary port on the module. Baud
rate entries are 110, 150, 300, 600, 1200, 2400, 4800, 9600 or 19200
Parity
None, Odd, Even
Parity is a simple error checking algorithm used in serial communication. This
parameter specifies the type of parity checking to use.
All devices communicating through this port must use the same parity setting.
Data Bits
5, 6, 7 or 8
This parameter sets the number of data bits for each word used by the protocol.
All devices communicating through this port must use the same number of data
bits.
Stop Bits
1 or 2
Stop bits signal the end of a character in the data stream. For most applications,
use one stop bit. For slower devices that require more time to re-synchronize,
use two stop bits.
All devices communicating through this port must use the same number of stop
bits.
2.2.3 [DF1 Pass-Through Port]
This section is used to define the configuration for the DF1 pass-through port on
Port 2 (the third port)
[DF1 Pass-Through Port]
Enabled : Y #Y=Use port, N=Do not use port
Local Station ID : 1 #DF1 node address
Protocol : H #F=Full-Duplex, H=Half-Duplex
Termination Type : CRC #B=BCC, C=CRC
Baud Rate : 38400 #Baud rate for port 1200-38400
Parity : None #N=None,O=Odd,E=Even,M=Mark,S=Space
Data Bits : 8 #5, 6, 7 or 8
Stop Bits : 1 #1 or 2
RTS On : 0 #0-65536 mSec before message
RTS Off : 0 #0-65536 mSec after message
Use CTS Line : N #Use CTS modem control line (Y/N)
ProSoft Technology, Inc. Page 27 of 175
February 3, 2011
Installing and Configuring the Module MVI71-DFNT ♦ PLC 5
User Manual EtherNet/IP Client/Server Communication Module
Enabled
Yes or No
This parameter determines if the server will be utilized by the module. If a value
of "Yes" is entered, the server will be used. Any other value will disable the
server.
Local Station ID
0 to 254
This parameter specifies the local station ID for all DF1 messages sent to this
port. A value of 255 is not permitted as this is the broadcast address. The
application will only accept messages with this node address.
Protocol
F (Full duplex) or H (Half duplex)
The value selected should match that set for the PLC processor.
Termination Type
BCC or CRC
This parameter specifies the error checking for all DF1 messages. Enter BCC or
CRC.
Baud Rate - 1200 to 38400
1200 to 38400
This is the baud rate to be used for the port. Enter the baud rate as a value. Baud
rate entries are 1200, 2400, 4800, 9600, 19200, 28800 or 38400.
Parity
None, Odd, Even, Mark, Space
Parity is a simple error checking algorithm used in serial communication. This
parameter specifies the type of parity checking to use.
All devices communicating through this port must use the same parity setting.
Data Bits
5, 6, 7 or 8
This parameter sets the number of data bits for each word used by the protocol.
All devices communicating through this port must use the same number of data
bits.
Page 28 of 175 ProSoft Technology, Inc.
February 3, 2011
MVI71-DFNT ♦ PLC 5 Installing and Configuring the Module
EtherNet/IP Client/Server Communication Module User Manual
Stop Bits
1 or 2
Stop bits signal the end of a character in the data stream. For most applications,
use one stop bit. For slower devices that require more time to re-synchronize,
use two stop bits.
All devices communicating through this port must use the same number of stop
bits.
RTS On
0 to 65535milliseconds
This parameter sets the number of milliseconds to delay after Ready To Send
(RTS) is asserted before data will be transmitted.
RTS Off
0 to 65535 milliseconds
This parameter sets the number of milliseconds to delay after the last byte of
data is sent before the RTS modem signal will be set low.
Use CTS Line
YES or NO
This parameter specifies if the Clear To Send (CTS) modem control line is to be
used or not. If the parameter is set to N
the parameter is set to Y
ES, the CTS line will be monitored and must be high
O, the CTS line will not be monitored. If
before the module will send data. Normally, this parameter is required when halfduplex modems are used for communication (2-wire). This procedure is
commonly referred to as hardware handshaking.
Retry Count
0 to 10
This parameter specifies the number of times a command will be retried if it fails.
Request Timeout
0 to 10000 milliseconds
This parameter specifies the number of milliseconds to wait for a complete
request message. The timer is started after the DLE-STX character sequence is
received for the full-duplex protocol or the DLE-SOH sequence for the halfduplex protocol. If the timer expires, the current request message will be aborted.
Busy Timeout
0 to 10000 milliseconds
This parameter specifies the number of milliseconds to wait for the pass-through
port to become available.
ProSoft Technology, Inc. Page 29 of 175
February 3, 2011
Installing and Configuring the Module MVI71-DFNT ♦ PLC 5
User Manual EtherNet/IP Client/Server Communication Module
ACK Timeout
0 to 10000 milliseconds
This parameter specifies the number of milliseconds to wait for a DLE-ACK
character sequence after a response is issued.
2.2.4 [DFNT Client 0]
This section is used to define the configuration for the master device simulated
on network port
0 to 65535 milliseconds
This parameter specifies the number of milliseconds to wait between the initial
issuances of a command. This parameter can be used to delay all commands
sent to servers to avoid "flooding" commands on the network. This parameter
does not affect retries of a command as they will be issued when failure is
recognized.
Response Timeout
0 to 65535 milliseconds
This is the time in milliseconds that a Client will wait before re-transmitting a
command if no response is received from the addressed server. The value to use
depends on the type of communication network used, and the expected
response time of the slowest device on the network.
Retry Count
0 to 10
This parameter specifies the number of times a command will be retried if it fails.
Page 30 of 175 ProSoft Technology, Inc.
February 3, 2011
Loading...
+ 145 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.