We always want you to feel that you made the right decision to use our products. If you have suggestions, comments,
compliments or complaints about our products, documentation, or support, please write or call us.
ProSoft Technology ®, ProLinx ®, inRAx ®, ProTalk ®, and RadioLinx ® are Registered Trademarks of ProSoft
Technology, Inc. All other brand or product names are or may be trademarks of, and are used to identify products
and services of, their respective owners.
In an effort to conserve paper, ProSoft Technology no longer includes printed manuals with our product shipments.
User Manuals, Datasheets, Sample Ladder Files, and Configuration Files are provided on the enclosed DVD, and are
available at no charge from our web site: http://www.prosoft-technology.com
Content Disclaimer
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of
these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate
and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or
use thereof. Neither ProSoft Technology nor any of its affiliates or subsidiaries shall be responsible or liable for
misuse of the information contained herein. Information in this document including illustrations, specifications and
dimensions may contain technical inaccuracies or typographical errors. ProSoft Technology makes no warranty or
representation as to its accuracy and assumes no liability for and reserves the right to correct such inaccuracies or
errors at any time without notice. If you have any suggestions for improvements or amendments or have found errors
in this publication, please notify us.
No part of this document may be reproduced in any form or by any means, electronic or mechanical, including
photocopying, without express written permission of ProSoft Technology. All pertinent state, regional, and local safety
regulations must be observed when installing and using this product. For reasons of safety and to help ensure
compliance with documented system data, only the manufacturer should perform repairs to components. When
devices are used for applications with technical safety requirements, the relevant instructions must be followed.
Failure to use ProSoft Technology software or approved software with our hardware products may result in injury,
harm, or improper operating results. Failure to observe this information can result in injury or equipment damage.
Printed documentation is available for purchase. Contact ProSoft Technology for pricing and availability.
North America: +1.661.716.5100
Asia Pacific: +603.7724.2080
Europe, Middle East, Africa: +33 (0) 5.3436.87.20
Latin America: +1.281.298.9109
Agency
ATEX; Category 3, Zone 2
CE Mark
CSA; CB Safety
Environmental
KCC
RoHS Compliant
UL/cUL; Class 1, Div. 2 Groups A, B, C, D
Important Safety Information - MVI69E-MBS
North America Warnings
A This Equipment is Suitable For Use in Class I, Division 2, Groups A, B, C, D or Non-Hazardous Locations Only.
B Warning – Explosion Hazard – Substitution of Any Components May Impair Suitability for Class I, Division 2.
C Warning – Explosion Hazard – Do Not Disconnect Equipment Unless Power Has Been Switched Off Or The
Area is Known To Be Non-Hazardous.
D The subject devices are powered by a Switch Model Power Supply (SMPS) that has regulated output voltage of
5 VDC.
ATEX Warnings and Conditions of Safe Usage:
Power, Input, and Output (I/O) wiring must be in accordance with the authority having jurisdiction
A Warning - Explosion Hazard - When in hazardous locations, turn off power before replacing or wiring modules.
B Warning - Explosion Hazard - Do not disconnect equipment unless power has been switched off or the area is
known to be non-hazardous.
C These products are intended to be mounted in an IP54 enclosure. The devices shall provide external means to
prevent the rated voltage being exceeded by transient disturbances of more than 40%. This device must be used
only with ATEX certified backplanes.
DO NOT OPEN WHEN ENERGIZED
Agency Approvals and Certifications
MVI69E-MBS ♦ CompactLogix Platform Contents
Communication Module User Manual
Contents
Your Feedback Please ........................................................................................................................ 2
How to Contact Us .............................................................................................................................. 2
Important Safety Information - MVI69E-MBS ..................................................................................... 3
1 Start Here 9
1.1 System Requirements ............................................................................................. 10
Installing the Module in the Rack ........................................................... 13
DVD Contents ....................................................................................... 17
Communication Module User Manual
1 Start Here
To get the most benefit from this User Manual, you should have the following
skills:
Rockwell Automation® RSLogix™ software: launch the program, configure
ladder logic, and transfer the ladder logic to the processor
Microsoft Windows: install and launch programs, execute menu commands,
navigate dialog boxes, and enter data
Hardware installation and wiring: install the module, and safely connect
Modbus and CompactLogix devices to a power source and to the MVI69EMBS module’s application port(s)
ProSoft Technology, Inc. Page 9 of 162
January 6, 2014
Start Here MVI69E-MBS ♦ CompactLogix Platform
User Manual Communication Module
1.1 System Requirements
The MVI69E-MBS module requires the following minimum hardware and
software components:
Rockwell Automation CompactLogix® processor (firmware version 10 or
higher), with compatible power supply, and one free slot in the rack for the
MVI69E-MBS module.
Important: The MVI69E-MBS module has a power supply distance rating of 4 (L43 and L45
installations on first 2 slots of 1769 bus). It consumes 500 mA at 5 Vdc.
Important: For 1769-L23E-QBFC1B processors, please make note of the following limitations.
1769-L23E-QBFC1B = 450 mA at 5 Vdc (No MVI69E module can be used with this
processor.)
The module requires 500 mA of available 5 Vdc power
Rockwell Automation RSLogix 5000 programming software version 16 or
higher
Rockwell Automation RSLinx® communication software version 2.51 or higher
ProSoft Configuration Builder (PCB) (included)
ProSoft Discovery Service (PDS) (included in PCB)
Pentium® II 450 MHz minimum. Pentium III 733 MHz (or better)
recommended
Supported operating systems:
o Microsoft Windows
o Microsoft Windows Vista
o Microsoft Windows XP Professional with Service Pack 1 or 2
o Microsoft Windows 2000 Professional with Service Pack 1, 2, or 3
o Microsoft Windows Server 2003
128 Mbytes of RAM minimum, 256 Mbytes of RAM recommended
100 Mbytes of free hard disk space (or more based on application
requirements)
256-color VGA graphics adapter, 800 x 600 minimum resolution (True Color
1024 768 recommended)
DVD drive
®
7
Note: The Hardware and Operating System requirements in this list are the minimum
recommended to install and run software provided by ProSoft Technology®. Other third party
applications may have different minimum requirements. Refer to the documentation for any third
party applications for system requirements.
Page 10 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform Start Here
Qty.
Part Name
Part Number
Part Description
1
MVI69E-MBS Module
MVI69E-MBS
Modbus communication module
2
Adapter Cable
Cable 14
RJ45 to DB9 Male Adapter cable. For DB9
connection to module’s serial application
ports
2
Screw Terminal
Adapter
1454-9F
DB9 female to 9-pin screw terminal. Used
for RS422 or RS485 connections to Port 1
and 2 of the module
1
Ethernet Cable
RL-CBL025
Ethernet straight-through cable
1
ProSoft Solutions
DVD
DVD-001
Contains ProSoft Configuration Builder
(PCB) and ProSoft Discovery Service (PDS)
software.
Files can also be found at
www.prosoft-technology.com
Communication Module User Manual
1.2 Deployment Checklist
Before configuring the module, consider the following questions.
Is this a new application or an integration into an existing application?
Most applications use the Sample Add-On Instruction without any edits.
What slot number in the rack will the MVI69E-MBS module occupy?
Are RSLogix 5000 and RSLinx software installed?
RSLogix and RSLinx are required to communicate to the CompactLogix
processor.
How many words of data are needed to transfer in the application (from
CompactLogix to Module / to CompactLogix from Module)?
1.3 Package Contents
The following components are included with the MVI69E-MBS module, and are
all required for installation and configuration.
Important: Before beginning the installation, please verify that all of the following items are
present.
If any of these components are missing, please contact ProSoft Technology
Technical Support for replacement parts.
ProSoft Technology, Inc. Page 11 of 162
January 6, 2014
Start Here MVI69E-MBS ♦ CompactLogix Platform
User Manual Communication Module
1.4 Setting Jumpers
When the module is manufactured, the port selection jumpers are set to RS-232.
To use RS-422 or RS-485, you must set the jumpers to the correct position. The
following diagram describes the jumper settings.
Note: Jumper pin placement on the circuit board may vary.
The Setup Jumper acts as "write protection" for the module’s firmware. In "write
protected" mode, the Setup pins are not connected, and the module’s firmware
cannot be overwritten. The module is shipped with the Setup jumper OFF. If an
update of the firmware is needed, apply the Setup jumper to both pins.
Page 12 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform Start Here
Communication Module User Manual
The following illustration shows the MVI69E-MBS jumper configuration, with the
Setup Jumper OFF.
1.5 Installing the Module in the Rack
Make sure the processor and power supply are installed and configured before
installing the MVI69E-MBS module. Refer to the Rockwell Automation product
documentation for installation instructions.
Warning: Please follow all safety instructions when installing this or any other electronic devices.
Failure to follow safety procedures could result in damage to hardware or data, or even serious
injury or death to personnel. Refer to the documentation for each device to be connected to verify
that suitable safety procedures are in place before installing or servicing the device.
After you verify the jumper placements, insert the MVI69E-MBS into the rack.
Use the same technique recommended by Rockwell Automation to remove and
install CompactLogix modules.
Warning: This module is not hot-swappable! Always remove power from the rack before
inserting or removing this module, or damage may result to the module, the processor, or other
connected devices.
ProSoft Technology, Inc. Page 13 of 162
January 6, 2014
Start Here MVI69E-MBS ♦ CompactLogix Platform
User Manual Communication Module
1 Align the module using the upper and lower tongue-and-groove slots with the
adjacent module and slide forward in the direction of the arrow.
2 Move the module back along the tongue-and-groove slots until the bus
connectors on the MVI69 module and the adjacent module line up with each
other.
Page 14 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform Start Here
Communication Module User Manual
3 Push the module’s bus lever back slightly to clear the positioning tab and
move it firmly to the left until it clicks. Ensure that it is locked firmly in place.
4 Close all DIN-rail latches.
ProSoft Technology, Inc. Page 15 of 162
January 6, 2014
Start Here MVI69E-MBS ♦ CompactLogix Platform
User Manual Communication Module
5 Press the DIN-rail mounting area of the controller against the DIN-rail. The
latches momentarily open and lock into place.
Page 16 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform Start Here
Communication Module User Manual
1.6 DVD Contents
The DVD contains all the necessary files for the module. The User Manual,
ProSoft Configuration Builder (PCB), and the sample Add-On Instruction are
included.
If the DVD is not present, please visit http://www.prosoft-technology.com for the
latest files.
ProSoft Technology, Inc. Page 17 of 162
January 6, 2014
Start Here MVI69E-MBS ♦ CompactLogix Platform
User Manual Communication Module
Page 18 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform Connecting to RSLogix 5000
Generating the AOI (.L5X File) in ProSoft Configuration Builder ........... 21
Creating a New RSLogix 5000 Project .................................................. 26
Creating the Module in an RSLogix 5000 Project .................................. 27
Importing the Add-On Instruction ........................................................... 35
Adding Multiple Modules in the Rack (Optional) .................................... 39
Communication Module User Manual
2 Connecting to RSLogix 5000
The .L5X file contains the Add-On Instruction (AOI), user-defined data types,
controller tags and ladder logic required to configure the MVI69E-MBS module.
This file is generated by ProSoft Configuration Builder (PCB) software and
imported into RSLogix 5000.
ProSoft Technology, Inc. Page 19 of 162
January 6, 2014
Connecting to RSLogix 5000 MVI69E-MBS ♦ CompactLogix Platform
User Manual Communication Module
2.1 Installing ProSoft Configuration Builder
The ProSoft Configuration Builder installation file is on the product DVD and our
web site: http://www.prosoft-technology.com. The filename contains the version
of PCB. For example, PCB_4.1.0.4.0206.exe
Copy the installation file to the local hard drive and run the PCB.exe file to start
the InstallShield Wizard. Follow the InstallShield Wizard to properly install PCB.
Page 20 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform Connecting to RSLogix 5000
Communication Module User Manual
2.2 Generating the AOI (.L5X File) in ProSoft Configuration Builder
The following sections describe the steps required to set up a new configuration
project in ProSoft Configuration Builder (PCB), and to export the .L5X file for the
project.
2.2.1 Creating a New Project in PCB
To begin, start the PCB software. PCB’s window consists of a tree view on the
left, and an information pane and configuration pane on the right side of the
window.
The tree view consists of folders for Default Project and Default Location, with a
Default Module in the Default Location folder. The following illustration shows the
ProSoft Configuration Builder window with a new project.
ProSoft Technology, Inc. Page 21 of 162
January 6, 2014
Connecting to RSLogix 5000 MVI69E-MBS ♦ CompactLogix Platform
User Manual Communication Module
To add the MVI69E-MBS module to the project
1 In the tree view, right-click DEFAULT MODULE and choose CHOOSE MODULE
TYPE from the shortcut menu. This opens the Choose Module Type dialog
box.
2 In the Product Line Filter area of the dialog box, click MVI69E. In the Select
Module Type dropdown list, choose MVI69E-MBS,and click OKto save the
settings and return to the ProSoft Configuration Builder window. The MVI69E-
MBS module icon is now visible in the tree view.
Page 22 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform Connecting to RSLogix 5000
Communication Module User Manual
2.2.2 Exporting the .L5X File from PCB
There are two parameters in the PCB configuration that affect the format of the
.L5X file that is exported. Before exporting the .L5X file to the PC/Laptop, check
the Block Transfer Size and Slot Number parameters.
1 Expand the MVI69E-MBS icon by clicking the [+] symbol beside it. Similarly,
expand the icon. Double-click the icon to open
the Edit - Module dialog box.
2 Set the Block Transfer Size to the desired size of the data blocks
transferred between the module and processor (60, 120 or 240 words).
Block transfer size information can be found starting on page 71.
ProSoft Technology, Inc. Page 23 of 162
January 6, 2014
Connecting to RSLogix 5000 MVI69E-MBS ♦ CompactLogix Platform
User Manual Communication Module
3 Edit the Slot Number indicating where the module is placed in the 1769 bus.
4 Click OK to close the Edit – Module dialog box. The .L5X file is now ready to
be exported to the PC/Laptop.
5 Right-click the MVI69E-MBS icon in the project tree and choose EXPORT AOI
FILE.
Page 24 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform Connecting to RSLogix 5000
Communication Module User Manual
6 Save the .L5X file to the PC/Laptop in an easily found location, such as
Windows Desktop.
ProSoft Technology, Inc. Page 25 of 162
January 6, 2014
Connecting to RSLogix 5000 MVI69E-MBS ♦ CompactLogix Platform
User Manual Communication Module
2.3 Creating a New RSLogix 5000 Project
1 Open the FILE menu, and choose NEW.
2 Select the CompactLogix processer model.
3 Select REVISION 16or newer.
4 Enter a name for the processor, such as My_Controller.
5 Select the CompactLogix chassis type.
Page 26 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform Connecting to RSLogix 5000
Communication Module User Manual
2.4 Creating the Module in an RSLogix 5000 Project
In an RSLogix 5000 project, you can use an Add-On Profile (AOP) to specifically
identify the MVI69E-MBS when selecting the type of module to be installed in slot
x. Add-On Profiles are supported in RSLogix 5000 version 15 and newer.
If using an AOP is not an option, please see page 31 to install the module using
a Generic 1769 Module profile.
2.4.1 Installing an Add-On Profile
Download the MPSetup.exe file from the product webpage (found at
www.prosoft-technology.com) or the ProSoft DVD onto the local hard drive. Make
sure RSLogix 5000 and RSLinx have been shut down before installing the AOP.
Run the MPSetup.exe file to start the Setup Wizard. Follow the Setup Wizard to
properly install the AOP.
Continue to follow the steps in the wizard to complete the installation.
ProSoft Technology, Inc. Page 27 of 162
January 6, 2014
Connecting to RSLogix 5000 MVI69E-MBS ♦ CompactLogix Platform
User Manual Communication Module
Click Finish when complete. The AOP is now installed in RSLogix 5000. There is
no need to reboot the PC.
Page 28 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform Connecting to RSLogix 5000
Communication Module User Manual
2.4.2 Creating a Module in the Project Using an Add-On Profile
1 In RSLogix 5000, expand theI/OCONFIGURATION folder in the Project tree.
Right-click the appropriate communications bus and choose NEW MODULE.
This opens the Select Module Type dialog box. In the Module Type Vendor Filters area, uncheck all boxes except the ProSoft Technology box. A list of
ProSoft Technology modules appears below.
ProSoft Technology, Inc. Page 29 of 162
January 6, 2014
Connecting to RSLogix 5000 MVI69E-MBS ♦ CompactLogix Platform
User Manual Communication Module
2 Select the MVI69E-MBS module in the list and click Create:
3 A New Module dialog box opens. Edit the Name and Slot of the module and
click OK
Page 30 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform Connecting to RSLogix 5000
Communication Module User Manual
Note : The I/O Table Sizes above should reflect the Block Transfer Size parameter set in PCB
(Section 3.2 on page 53).
A Block Transfer Size of 60 uses an I/O Table Size of 62/61 words.
A Block Transfer Size of 120 uses an I/O Table Size of 122/121 words.
A Block Transfer Size of 240 uses an I/O Table Size of 242/241 words.
The MVI69E-MBS module is now visible at the I/O Configuration tree.
2.4.3 Creating a Module in the Project Using a Generic 1769 Module
Profile
1 Expand theI/OCONFIGURATION folder in the Project tree. Right-click the
appropriate communications bus and choose NEW MODULE.
ProSoft Technology, Inc. Page 31 of 162
January 6, 2014
Connecting to RSLogix 5000 MVI69E-MBS ♦ CompactLogix Platform
User Manual Communication Module
This opens the Select Module Type dialog box. Enter generic in the search
text box and select the GENERIC 1769MODULE. If you're using an earlier
version of RSLogix, expand OTHER in the Select Module dialog box, and then
select the GENERIC 1769MODULE.
Page 32 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform Connecting to RSLogix 5000
Parameter
Value
Name
Enter a module identification string. Example: MVI69EMBS
Description
Enter a description for the module. Example: ProSoft
communication module for Serial Modbus communications.
Comm Format
Select Data-INT
Slot
Enter the slot number in the rack where the MV69E-MBS
module is installed.
Input Assembly Instance
101
Input Size
62 / 122 / 242
Output Assembly Instance
100
Output Size
61 / 121 / 241
Configuration Assembly Instance
102
Configuration Size
0
Block Transfer Size
Input Block Size
Output Block Size
60
62
61
120
122
121
240
242
241
Communication Module User Manual
2 Set the Module Properties values as follows:
The following illustration shows an example where the module was
configured for a block transfer size of 60 words (input block size = 62 words,
output block size = 61 words):
The following options are available:
ProSoft Technology, Inc. Page 33 of 162
January 6, 2014
Connecting to RSLogix 5000 MVI69E-MBS ♦ CompactLogix Platform
User Manual Communication Module
3 On the Connection tab, set the RPI value for your project. Click OK to
confirm.
The MVI69E-MBS module is now visible at the I/O Configuration tree.
Page 34 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform Connecting to RSLogix 5000
Communication Module User Manual
2.5 Importing the Add-On Instruction
1 Open the application in RSLogix 5000.
2 Expand the TASKS folder, and expand the MAINTASK folder.
3 Expand the MAINPROGRAM folder. The MAINROUTINE contains rungs of logic.
The very last rung in this routine is blank. This is where you can import the
AOI.
Note: You can place the Add-On Instruction in a different routine than the MainRoutine. Make sure
to add a rung with a jump instruction (JSR) in the MainRoutine to jump to the routine containing the
Add-On Instruction.
4 Select an empty rung in the routine. Right-click the rung and choose IMPORT
RUNGS from the shortcut menu.
ProSoft Technology, Inc. Page 35 of 162
January 6, 2014
Connecting to RSLogix 5000 MVI69E-MBS ♦ CompactLogix Platform
User Manual Communication Module
5 Select the .L5Xfile that was exported from PCB earlier.
This opens the Import Configuration dialog box. Click TAGS under
MAINROUTINE to display the controller tags to be created.
Note: If you are using RSLogix version 16 or earlier, the Import Configuration dialog box does not
contain the Import Content tree.
Page 36 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform Connecting to RSLogix 5000
Communication Module User Manual
6 If the module is not located in the default slot (or is in a remote rack), edit the
connection input and output variables that define the path to the module in
the FINAL NAME column (NAME column for RSLogix version 16 or less). For
example, if your module is located in slot 3, change Local:1:I in the FINAL NAME column to Local:3:I. Do the same for Local:1:O.
Note: If your module is located in Slot 1 of the local rack, this step is not required.
7 Click OKto confirm the import. RSLogix indicates that the import is in
progress:
ProSoft Technology, Inc. Page 37 of 162
January 6, 2014
Connecting to RSLogix 5000 MVI69E-MBS ♦ CompactLogix Platform
User Manual Communication Module
When the import is completed, the new rung with the Add-On instruction is
visible as shown in the following illustration.
The procedure has also imported new user defined data types, data objects
and the Add-On instruction to be used in the project.
Page 38 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform Connecting to RSLogix 5000
Communication Module User Manual
2.6 Adding Multiple Modules in the Rack (Optional)
Important: This procedure is for multiple MVI69E-MBS modules running in the same
CompactLogix rack
You must export a new Add-On Instruction from PCB for each module. You do
this by adding a new module to the PCB project and exporting the module
configuration as an L5X file. Finally you import the new .L5X file into RSLogix
5000 for the new module.
2.6.1 Adding a new module in PCB
1 Right click Default Location (which you can rename) and choose Add
Module.
2 Right-click New Module and choose Choose Module Type.
ProSoft Technology, Inc. Page 39 of 162
January 6, 2014
Connecting to RSLogix 5000 MVI69E-MBS ♦ CompactLogix Platform
User Manual Communication Module
3 In the Choose Module Type dialog box, select MVI69E in the Product Line
Filter area, and then select MVI69E-MBS as the Module Type.
4 Select the MVI69E-MBS module in the tree and repeat the above steps to
add a second (or more) module in the PCB project.
Note: You must give the duplicate MVI69E-MBS module a unique name. The default name on a
duplicate module appends a number to the end such as MVI69E-MBS_000, MVI69E-MBS_001,
etc.
5 You can rename the module by right clicking the module and selecting
Rename.
6 Configure the proper parameters as described in page 53 and export the AOI
.L5X file for the new module (as described in Exporting the .L5X File from
PCB on page 23).
Page 40 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform Connecting to RSLogix 5000
Communication Module User Manual
2.6.2 Adding a new module in RSLogix 5000
You can place multiple modules in the same rack provided it does not exceed
the power distance rating of the CompactLogix rack (see page 10). Adding an
additional module to the rack is similar to installing a new module earlier in
this chapter. However, the name of the module must be unique.
1 In RSLogix 5000, locate the I/OCONFIGURATION folder. Right click
CompactBus Local and choose NEW MODULE.
2 In the Select Module Type dialog box, select the MVI69L-MBS module as you
did on page 29. If using an AOP is not an option, select GENERIC 1769
MODULE and click Create.
ProSoft Technology, Inc. Page 41 of 162
January 6, 2014
Connecting to RSLogix 5000 MVI69E-MBS ♦ CompactLogix Platform
User Manual Communication Module
3 The New Module dialog box appears. Enter a unique name for the new
module. Also confirm the slot number of the new module.
4 Click OKto confirm. The new module is now visible:
5 You must also import the AOI for the new module. In the Controller Organizer
pane, double-click MAINROUTINE to open the ladder.
Page 42 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform Connecting to RSLogix 5000
Communication Module User Manual
6 Right-click the rung in the routine, and then choose IMPORT RUNGS…
ProSoft Technology, Inc. Page 43 of 162
January 6, 2014
Connecting to RSLogix 5000 MVI69E-MBS ♦ CompactLogix Platform
User Manual Communication Module
7 Select the .L5X file of the new module, and click IMPORT.Recall that the new
.L5X file will have a unique filename that is specific to the new module, as
edited on page 39.
Page 44 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform Connecting to RSLogix 5000
Communication Module User Manual
8 This action opens the IMPORT CONFIGURATION window, showing the tags to
be imported. You must edit the Final Name column of the tags for the second
module to make them unique.
ProSoft Technology, Inc. Page 45 of 162
January 6, 2014
Connecting to RSLogix 5000 MVI69E-MBS ♦ CompactLogix Platform
User Manual Communication Module
9 Associate the I/O connection variables to the correct module in the
corresponding slot number. The default values are Local:1:I and Local:1:O.
You must edit these values if the card is placed in a slot location other than
slot 1 (Local:1:x means the card is located in slot 1). Since the second card is
placed in slot 2, change the Final Name to Local:2:I and Local:2:O. Also, you
can append a ‘_2’ at the end of the Final Name of ‘AOI69_MBS’ and ‘MBS’
arrays as shown below.
Page 46 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform Connecting to RSLogix 5000
Communication Module User Manual
10 Click OKto confirm.
The setup procedure is now complete. Save the project. It is ready to download
to the CompactLogix processor.
ProSoft Technology, Inc. Page 47 of 162
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform
User Manual Communication Module
Page 48 of 162 ProSoft Technology, Inc.
January 6, 2014
Downloading the Configuration File to the Processor ............................ 62
Uploading the Configuration File from the Processor ............................ 64
Communication Module User Manual
3 MVI69E-MBS Configuration
ProSoft Configuration Builder software provides a quick and easy way to manage
module configuration files customized to meet the application needs.
You build and edit the module’s configuration in ProSoft Configuration Builder
(PCB). You use PCB to download the configuration file to the CompactLogix
processor, where it is stored in the MBS.CONFIG controller tag generated by the
previously exported AOI (page 21). When the MVI69E-MBS module boots up, it
requests the processor to send the configuration over the backplane in special
Configuration Blocks.
Chapter 2 contains the procedures for creating a new PCB project and exporting
a .L5X file for the processor. Chapter 3 offers more insight into using PCB. It
describes the configuration parameters in detail, as well as how to download the
configuration to the processor.
ProSoft Technology, Inc. Page 49 of 162
January 6, 2014
MVI69E-MBS Configuration MVI69E-MBS ♦ CompactLogix Platform
User Manual Communication Module
3.1 Basic PCB Functions
3.1.1 Creating a New PCB Project and Exporting an .L5X File
Please see Chapter 2.
3.1.2 Renaming PCB Objects
You can rename PCB objects such as the Default Project and Default Location
folders as well as the Module icon to customize the project.
1 Right-click the object to be renamed, and choose RENAME from the shortcut
menu.
2 Type the name for the object and press Enter.
3.1.3 Editing Configuration Parameters
1 Click on the [+] sign next to the MODULE icon to expand module information.
2 Click on the[+]sign next to any icon to view module information and
configuration options.
3 Double-click any icon to open an Edit dialog box.
To edit a parameter, highlight the parameter name in the left pane and edit
the field in the right pane.
Note: Depending on the parameter, you must enter text, or a valid number, or select from a list of
options.
Page 50 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform MVI69E-MBS Configuration
Communication Module User Manual
4 Double-click any icon to open an Edit dialog box with a table. Use this
dialog box to build and edit Modbus Master commands.
To add a row to the table, click the ADD ROW button.
ProSoft Technology, Inc. Page 51 of 162
January 6, 2014
MVI69E-MBS Configuration MVI69E-MBS ♦ CompactLogix Platform
User Manual Communication Module
To edit the row, click the EDIT ROW button. This opens an Edit dialog box.
3.1.4 Printing a Configuration File
1 In the main PCB window, right-click the MODULE icon and choose VIEW
CONFIGURATION from the shortcut menu. This action opens the View
Configuration window.
2 In the View Configuration window, open the FILE menu, and choose PRINT.
This action opens the Print dialog box.
3 In the Print dialog box, choose the printer to use from the drop-down list,
select printing options, and then click OK.
Page 52 of 162 ProSoft Technology, Inc.
January 6, 2014
Assigns a name to the module that can be viewed using
the configuration/debug port. Use this parameter to
identify the module and the configuration file.
Read Register Start
0 to 9999
Specifies the start of the Read Data area in the module’s
database. Data in this area is transferred from the module
to the processor.
Read Register Count
0 to 10,000
Specifies the size of the Read Data area.
Write Register Start
0 to 9999
Specifies the start of the Write Data area in module
memory. Data in this area is transferred in from the
processor.
Write Register Count
0 to 10,000
Specifies the size of the Write Data area.
Backplane Fail Count
0 to 65535
Specifies the number of consecutive backplane transfer
failures that can occur before communications are halted.
Error/Status Block
Pointer
-1 to 9939
Starting register location in the module’s database for the
error/status table. If a value of -1 is entered, the
error/status data is not placed in the database. All other
valid values determine the starting location of the data.
This data must be placed in the read data range of
module memory.
This data area includes the module version information
and all server error/status data. Refer to MBS.STATUS on
page 92 for more information.
Initialize Input Image
Yes or No
This parameter determines if the input image data and the
module’s Read Register Data values is initialized with
Read Register Data values from the processor. If the
value is set to No, the Read Register Data values in the
module is set to 0 upon initialization. If the value is set to
Communication Module User Manual
3.2 Module Configuration Parameters
3.2.1 Module
This section contains general module configuration parameters, including
database allocation and backplane transfer options.
In PCB’s tree view, double-click the MODULE icon.
ProSoft Technology, Inc. Page 53 of 162
January 6, 2014
Yes, the data is initialized with Read Register Data values
from the processor. Using this option requires associated
ladder logic to pass the data from the processor to the
module.
Block Transfer Size
60, 120 or
240
Specifies the number of words in each block transferred
between the module and processor.
Slot Number
1 to x
Specifies the slot in the CompactLogix rack for the
module.
Parameter
Value
Description
Start Active
Yes or No
Specifies whether or not the port and commands are active
upon module boot-up.
Type
Master, Slave,
or Slave with
Pass-Through
This parameter specifies which device type the port emulates.
Refer to Slave on page 76 for more information on Slave
Pass-Through options.
Protocol
RTU or ASCII
Specifies the Modbus protocol to be used on the port.
Baud Rate
Multiple
options
Specifies the baud rate to be used on the port.
Parity
None
Odd
Even
Specifies the type of parity error checking to use. All devices
communicating through this port must use the same parity
setting.
User Manual Communication Module
Important: The sum of the Read Register Count and Write Register Count cannot exceed 10,000
total registers. Furthermore, neither the Read Data nor the Write Data area may extend above
module register 9999. The Read Data and Write Data areas must not overlap.
3.2.2 Modbus Port x
The information in this section applies to both Port 1 and Port 2.
In PCB’s tree view, double-click the MODBUS PORT X icon.
Configuration Parameters Common to Master and Slave
Page 54 of 162 ProSoft Technology, Inc.
January 6, 2014
Sets the number of data bits for each word used by the
protocol. All devices communicating through this port must
use the same number of data bits.
Stop Bits
1 or 2
Sets the number of stop bits that signal the end of a character
in the data stream. For most applications, use one stop bit.
For slower devices that require more time to re-synchronize,
use two stop bits. All devices communicating through this port
must use the same number of stop bits.
RTS On
0 to 65535
milliseconds
Sets the number of milliseconds to delay after Ready To Send (RTS) is asserted before data is transmitted.
RTS Off
0 to 65535
milliseconds
Sets the number of milliseconds to delay after the last byte of
data is sent before the RTS modem signal is set low.
Use CTS Line
Yes or No
Specifies if the Clear To Send (CTS) modem control line is to
be used or not. If the parameter is set to NO, the CTS line is
not monitored. If the parameter is set to YES, the CTS line is
monitored and must be high before the module sends data.
Normally, this parameter is required when half-duplex
modems are used for communication (2-wire). This procedure
is commonly referred to as hardware handshaking.
Float Flag
Yes or No
Specifies how the Slave driver responds to Function Code 3,
6, and 16 commands (read and write Holding Registers) from
a remote Master when it is moving 32-bit floating-point data.
Note: Most applications using floating-point data do not need
this parameter enabled.
If the remote Master expects to receive or sends one
complete 32-bit floating-point value for each count of one (1),
then set this parameter to YES. When set to YES, the Slave
driver returns values from two consecutive 16-bit internal
memory registers (32 total bits) for each count in the read
command, or receive 32-bits per count from the Master for
write commands. Example: Count = 10, Slave driver sends 20
16-bit registers for 10 total 32-bit floating-point values.
If, however, the remote Master sends a count of two (2) for
each 32-bit floating-point value it expects to receive or send,
or, if you do not plan to use floating-point data in your
application, then set this parameter to NO, which is the default
setting.
You also need to set the Float Start and Float Offset
parameters to appropriate values whenever the Float Flag
parameter is set to YES.
Float Start
0 to 32767
Defines the first register of floating-point data. All requests
with register values greater-than or equal to this value is
considered floating-point data requests. This parameter is
only used if the Float Flag is enabled. For example, if a value
of 7000 is entered, all requests for registers 7000 and above
is considered as floating-point data.
Float Offset
0 to 9999
Defines the start register for floating-point data in the internal
database. This parameter is used only if the Float Flag is
enabled. For example, if the Float Offset value is set to 3000
and the float start parameter is set to 7000, data requests for
register 7000 uses the internal Modbus register 3000.
Communication Module User Manual
ProSoft Technology, Inc. Page 55 of 162
January 6, 2014
Specifies the command response timeout period in 1
millisecond increments. This is the time that a port configured
as a Master waits for a response from the addressed slave
before re-transmitting the command (Retries) or skipping to
the next command in the Command List. The value to specify
depends on the communication network used and the
expected response time (plus or minus) of the slowest device
on the network.
Retry Count
0 to 10
Specifies the number of times a command is retried if it fails.
Minimum
Command
Delay
0 to 32767
milliseconds
Specifies the number of milliseconds to wait between
receiving the end of a slave's response to the most recently
transmitted command and the issuance of the next command.
You can use this parameter to place a delay after each
command to avoid sending commands on the network faster
than the slaves can receive them. This parameter does not
affect retries of a command, as retries are issued when a
command failure is recognized.
Error Delay
Counter
0 to 60000
Specifies the number of poll attempts to be skipped before
trying to re-establish communications with a slave that has
failed to respond to a command within the time limit set by the
Response Timeout parameter. After the slave fails to
respond, the master skips sending commands that should
have been sent to the slave until the number of skipped
commands matches the value entered in this parameter. This
creates a sort of slow poll mode for slaves that are
experiencing communication problems.
Inter-character
Timeout
0 to 65535
milliseconds
Specifies a time delay in milliseconds to be added to the 3.5
character time delay used by the module to recognize the end
of a message. Certain applications may require validation of
Modbus messages with more than 3.5 character time
between consecutive bytes (example: modem applications).
A value of 0 causes the default end of message delay to be
used
Command Error
Offset
-1 to 9998
This parameter sets the address in the module’s database
where the command error data is placed. If the value is set to
-1, the data is not transferred to the database. The valid
range of values for this parameter is -1 to 4899. For example,
if this parameter is configured for 1000, the command errors
are copied to the database as follows:
1000: error code for command 0
1001: error code for command 1
…
An error code of 0 means that the command was successfully
sent (no error).
User Manual Communication Module
Additional Configuration Parameters (As a Master)
The Type parameter must be “Master” to configure these parameters. See
“Configuration Parameters Common to Master and Slave” on page xx.
Page 56 of 162 ProSoft Technology, Inc.
January 6, 2014
Sets the number of milliseconds to wait before responding to
a command received on the port from a remote Master. This
delay is sometimes required to accommodate slower Master
devices.
Internal Slave ID
1 to 247
Defines the Slave Node Address for the internal database. All
requests received by the port with this address are processed
by the module. Verify that each device has a unique address
on a network.
Bit Input Offset
0 to 9998
Specifies the offset address into the internal Modbus
database for network requests for Modbus function 2
commands. For example, if the value is set to 150, an
address request of 0 returns the value at register 150 in the
database.
Word Input
Offset
0 to 9998
Specifies the offset address into the internal Modbus
database for network requests for Modbus function 4
commands. For example, if the value is set to 150, an
address request of 0 returns the value at register 150 in the
database.
Output Offset
0 to 9998
Specifies the offset address into the internal Modbus
database for network requests for Modbus function 1, 5 or 15
commands. For example, if the value is set to 100, an
address request of 0 corresponds to register 100 in the
database.
Holding Register
Offset
0 to 9998
Specifies the offset address in the internal Modbus database
for network requests for Modbus function 3, 6, or 16
commands. For example, if the value is set to 50, a request
for address 0 corresponds to the register 50 in the database.
Communication Module User Manual
Additional Configuration Parameters as a Slave
The Type parameter must be “Slave” or “PassThru Slave” to configure these
parameters. See “Configuration Parameters Common to Master and Slave” on
page xx.
ProSoft Technology, Inc. Page 57 of 162
January 6, 2014
This field defines whether the command is to be executed
and under what conditions.
Disabled (0) = The command is disabled and is not
executed in the normal polling sequence.
Continuous (1) = The command is executed each scan of
the command list if the Poll Interval (see below) is set to
zero. If the Poll Interval is set to a nonzero value, the
User Manual Communication Module
3.2.3 Modbus Port x Commands
The Modbus Port x Commands section defines the master command list
specifications for a Master port. The information in this section applies to both
Port 1 and Port 2.
In PCB’s tree view, double-click the "Modbus Port x Commands” icon.
In order to interface the MVI69E-MBS module with Modbus slave devices, you
must create a command list. The commands in the list specify the slave device to
be addressed, the function to be performed (read or write), the data area in the
device to interface with and the registers in the internal database to be
associated with the device data.
The Master command list supports up to 250 commands. The command list is
processed from top (Command #0) to bottom.
Read commands are executed without condition. You can set write commands to
execute only if the data in the write command changes (Conditional Enable). If
the register data values in the command have not changed since the command
was last issued, the command is not executed. You can use this feature to
optimize network performance.
The MBS Modbus Master (and Slave) communication drivers support several
data read and write commands. When a command is configured, the type of data
(bit, 16-bit integer, 32-bit float, etc), and the level of Modbus support in the slave
equipment needs to be considered. For information on floating-point support,
please See Floating-Point Support on page 125.
Page 58 of 162 ProSoft Technology, Inc.
January 6, 2014
command is executed when the interval timer expires.
Conditional (2) = For write commands only. The command
executes only if the internal data associated with the
command changes.
Bit/Word Override upon Error (3) = For read commands
only. If a command error occurs, the module overrides the
associated database area with the Override Value Upon Error parameter value.
Float Override upon Error (4) = For read commands only.
If a command error occurs, the module overrides the
associated database area (2x word count) with the Override Value Upon Error parameter value.
Internal Address
0 to 9999 (wordlevel)
or
0 to 65535 (bit-
level)
Specifies the module’s internal database register to be
associated with the command. Allowable range is 0 to 9999
for Modbus Function Codes 3, 4, 6, or 16, and 0 to 65535
for Modbus Function Codes 1, 2, 5, or 15.
If the command is a read function, the data read from the
slave device is storedbeginning at the module’s internal
database register value entered in this field. This register
value must be in the Read Data area of the module’s
memory, defined by the Read Register Start and Read Register Count parameters in the Module section.
If the command is a write function, the data to be written to
the slave device is sourcedbeginning from the module’s
internal database register specified. This register value must
come from the Write Data area of the module’s memory,
defined by the Write Register Start and Write Register Count parameters in the Module section.
Poll Interval
0 to 65535
seconds
Specifies the minimum interval between executions of
continuous commands (Enable code = 1).
Example: If the value is set to 10, the command executes
no more frequently than once every 10 seconds. When the
command reaches the top of the command queue and 10
seconds has not elapsed, it is skipped until the poll interval
has expired.
Register Count
1 to 125 (words)
or
1 to 800 (coils)
Specifies the number of registers or digital points to be
associated with the command. Modbus Function Codes 5
and 6 ignore this field as they only apply to a single data
point.
For Modbus Function Codes 1, 2 and 15, this parameter
sets the number of single bit digital points (inputs or coils) to
be associated with the command.
For Modbus Function Codes 3, 4 and 16, this parameter
sets the number of 16-bit registers to be associated with the
command.
Swap Code
0,1,2,3
Defines if the data received from the Modbus slave is to be
ordered differently than received from the slave device. This
parameter is helpful when dealing with floating-point or other
multi-register values, as there is no standard method of
storage of these data types in slave devices. You can set
this parameter to order the register data received in an order
useful by other applications.
No Change (0)= No change is made in the byte ordering
(ABCD = ABCD)
Communication Module User Manual
ProSoft Technology, Inc. Page 59 of 162
January 6, 2014
Word Swap (1)= The words are swapped (ABCD= CDAB)
Word and Byte Swap (2) = The words are swapped, then
the bytes in each word are swapped (ABCD=DCBA)
Byte Swap (3) = The bytes in each word are swapped
(ABCD=BADC)
Note: Each pair of characters is a byte. Ex: AB and CD.
Two pairs of characters is 16-bit register Ex: ABCD.
Node Address
1 to 255
(0 = broadcast)
Specifies the Modbus slave node address on the network to
be considered. Most Modbus devices only accept an
address in the range of 1 to 247. If the value is set to zero,
the command is a broadcast message on the network. The
Modbus protocol permits broadcast commands for write
operations. Do not use this node address for read
operations.
Modbus
Function
1,2,3,4,5,6,15,16
Specifies the Modbus function to be executed by the
command. These function codes are defined in the Modbus
protocol.
Specifies the register or digital point address offset within
the Modbus slave device. The MBS Master reads or writes
from/to this address within the slave.
Refer to the documentation of each Modbus slave device for
their register and digital point address assignments.
Note: The value entered here does not need to include the
“Modbus Prefix” addressing scheme. Also, this value is an
offset of the zero-based Modbus addressing scheme.
Example: Using a Modbus Function Code 3 to read from
address 40010 in the slave, a value of ‘9’ would be entered
in this parameter. The firmware (internally) adds a ‘40001’
offset to the value entered. This is the same for all Modbus
addresses (0x, 1x, 3x, 4x).
Override Value
Upon Error
This parameter is only applicable for Enable Codes 3
(Bit/Word Override) or 4 (Float Override).
If an error occurs associated to a read command the module
automatically populates the associated database area with
this override value.
User Manual Communication Module
Page 60 of 162 ProSoft Technology, Inc.
January 6, 2014
This section defines the permanent IP address, Subnet Mask, and Gateway of
the module.
In PCB’s tree view, double-click the "Ethernet 1" icon in PCB.
ProSoft Technology, Inc. Page 61 of 162
January 6, 2014
MVI69E-MBS Configuration MVI69E-MBS ♦ CompactLogix Platform
User Manual Communication Module
3.3 Downloading the Configuration File to the Processor
1 In PCB’s tree view, right-click the module icon and choose DOWNLOAD FROM
PC TO DEVICE from the shortcut menu.
2 In the Download Configuration File dialog box, click RSWHO.
Page 62 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform MVI69E-MBS Configuration
Communication Module User Manual
3 Browse to, and then highlight the CompactLogix processor and click OK.
4 Notice the CIPConnect path has been updated in the Download Configuration
File dialog box. Click TEST CONNECTION to verify the path is active and can
successfully connect to the processor.
ProSoft Technology, Inc. Page 63 of 162
January 6, 2014
MVI69E-MBS Configuration MVI69E-MBS ♦ CompactLogix Platform
User Manual Communication Module
5 When ready, click DOWNLOAD to download the configuration file to the
processor. Following the download process, the module is automatically
rebooted.
6 After rebooting, the ladder logic sends the configuration data from the
processor to the module. When that is complete, the module starts Modbus
communications.
3.4 Uploading the Configuration File from the Processor
1 In PCB’s tree view, right-click the module icon and choose UPLOAD FROM
DEVICE TO PCfrom the shortcut menu.
Page 64 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform MVI69E-MBS Configuration
Communication Module User Manual
2 In the Upload Configuration File dialog box, the CIPConnect path should
already be constructed if you have previously downloaded the configuration
file from the same PC. If not, click RSWHO, browse to, then select the
CompactLogix Processor, and click OK.
ProSoft Technology, Inc. Page 65 of 162
January 6, 2014
MVI69E-MBS Configuration MVI69E-MBS ♦ CompactLogix Platform
User Manual Communication Module
3 Click TEST CONNECTION to verify the path is active and can successfully
connect to the processor.
4 When ready, click UPLOAD. When upload is complete, click Close.
Page 66 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform MVI69E-MBS Configuration
Communication Module User Manual
5 PCB now displays the uploaded configuration file.
ProSoft Technology, Inc. Page 67 of 162
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform
User Manual Communication Module
Page 68 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform MVI69E-MBS Backplane Data Exchange
Communication Module User Manual
4 MVI69E-MBS Backplane Data Exchange
In This Chapter
General Concepts of the MVI69E-MBS Data Transfer .......................... 70
Backplane Data Transfer ....................................................................... 70
Normal Data Transfer ............................................................................ 71
Data Flow Between the Module and Processor ..................................... 75
ProSoft Technology, Inc. Page 69 of 162
January 6, 2014
MVI69E-MBS Backplane Data Exchange MVI69E-MBS ♦ CompactLogix Platform
User Manual Communication Module
4.1 General Concepts of the MVI69E-MBS Data Transfer
The MVI69E-MBS module uses ladder logic to communicate with the
CompactLogix processor across the backplane. The ladder logic handles the
module data transfer, configuration data transfer, special block handling, and
status data receipt.
The following topics describe several concepts that are important for
understanding the operation of the MVI69E-MBS module.
1. On power up the module begins the following logical functions:
- Initialize hardware components
- Initialize CompactLogix backplane driver
- Test and clear all RAM
2. Read configuration from the CompactLogix processor via ladder logic
3. Allocate and initialize Module Register space
4. Enable Modbus application ports
5. After the module has received the Module Configuration, the module
begins communicating with other nodes on the Modbus network,
depending on the Modbus configuration of the module.
4.2 Backplane Data Transfer
The MVI69E-MBS module communicates directly over the CompactLogix
backplane. Data is paged between the module and the CompactLogix processor
across the backplane using the module's input and output images. The update
frequency of the images is determined by the scheduled scan rate that you
define for the module and the communication load on the module. Typical
updates are in the range of 1 to 10 milliseconds per block of information.
This bi-directional data transfer is accomplished by the module filling in data in
the module's input image to send to the processor. Data in the input image is
placed in the Controller Tags in the processor by the ladder logic. The input
image for the module may be set to 62, 122, or 242 words depending on the
block transfer size parameter set in the configuration file. This data area permits
fast throughput of data between the module and the processor.
Page 70 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform MVI69E-MBS Backplane Data Exchange
Communication Module User Manual
The processor inserts data to the module's output image to transfer to the
module. The module's program extracts the data and places it in the module's
internal database. The output image for the module may be set to 61, 121, or 241
words depending on the block transfer size parameter set in the configuration
file.
The following illustration shows the data transfer method used to move data
between the CompactLogix processor, the MVI69E-MBS module and the
Modbus Network.
All data transferred between the module and the processor over the backplane is
through the input and output images. Ladder logic in the CompactLogix
processor interfaces the input and output image data with data defined in the
Controller Tags. All data used by the module is stored in its internal database.
This database is defined as virtual MBS data tables with addresses from 0 to the
maximum number of points for each data type.
4.3 Normal Data Transfer
Normal data transfer includes the paging of the user data found in the module’s
internal database (Registers 0 to 9999) and the status data. These data are
transferred through read (input image) and write (output image) blocks. The
following topics describe the structure and function of each block.
ProSoft Technology, Inc. Page 71 of 162
January 6, 2014
MVI69E-MBS Backplane Data Exchange MVI69E-MBS ♦ CompactLogix Platform
Offset
Description
Length (words)
0
Write Block ID
1
1 to (n)
Write Data
(n)
Offset
Description
Length (words)
0
Read Block ID
1
1
Write Block ID
1
2 to (n+1)
Read Data
(n)
User Manual Communication Module
4.3.1 Write Block: Request from the Processor to the Module
These blocks of data transfer information from the processor to the module. The
structure of the output image used to transfer this data is shown below:
(n) = 60, 120, or 240 depending on the Block Transfer Size parameter (refer to the configuration
file).
The Write Block ID is an index value used to determine the location in the
module’s database where the data is placed.
4.3.2 Read Block: Response from the Module to the Processor
These blocks of data transfer information from the module to the processor. The
structure of the input image used to transfer this data is shown below:
(n) = 60, 120, or 240 depending on the Block Transfer Size parameter (refer to the configuration
file).
Page 72 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform MVI69E-MBS Backplane Data Exchange
Communication Module User Manual
4.3.3 Read and Write Block Transfer Sequences
The Read Block ID is an index value that determines the location where the data
is placed in the processor controller tag array of module read data. The number
of data words per transfer depends on the configured Block Transfer Size
parameter in the configuration file (possible values are 60, 120, or 240).
The Write Block ID associated with the block requests data from the processor.
Under normal program operation, the module sequentially sends read blocks and
requests write blocks. For example, if the application uses three read and two
write blocks, the sequence is as follows:
R1W1R2W2R3W1R1W2R2W1R3W2R1W1
This sequence continues until interrupted by other write block numbers sent by
the controller or by a command request from a node on the Modbus network or
operator control through the module’s Configuration/Debug port.
The following example shows a typical backplane communication application.
If the backplane parameters are configured as follows:
The backplane communication would be configured as follows:
Database address 0 to 479 is continuously transferred from the module to the
processor. Database address 480 to 959 is continuously transferred from the
processor to the module.
The Block Transfer Size parameter configures how the Read Data and Write
Data areas are broken down into data blocks (60, 120, or 240).
ProSoft Technology, Inc. Page 73 of 162
January 6, 2014
MVI69E-MBS Backplane Data Exchange MVI69E-MBS ♦ CompactLogix Platform
User Manual Communication Module
4.3.4 If Block Transfer Size = 60
4.3.5 If Block Transfer Size = 120
Page 74 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform MVI69E-MBS Backplane Data Exchange
Communication Module User Manual
4.3.6 If Block Transfer Size = 240
4.4 Data Flow Between the Module and Processor
The following topics describe the flow of data between the two pieces of
hardware (CompactLogix processor and MVI69E-MBS module) and other nodes
on the Modbus network. You can configure each port on the module to emulate a
Modbus Master device or a Modbus Slave device.
ProSoft Technology, Inc. Page 75 of 162
January 6, 2014
MVI69E-MBS Backplane Data Exchange MVI69E-MBS ♦ CompactLogix Platform
Step
Description
1
Any time the module restarts (boots or reboots), the Modbus slave port driver receives
configuration information from the MBS controller tags. This information configures the
serial ports and defines slave node characteristics. The configuration information may also
contain instructions to offset data stored in the database to addresses different from
addresses requested in the received messages.
2
A Modbus Master device, such as a Modicon PLC or an HMI application, issues a read or
write command to the module’s node address. The port driver qualifies the message before
accepting it into the module. Rejected commands cause an Exception Response.
3
After the module accepts the command, the data is immediately transferred to or from the
module’s internal database. On a read command, the data is read from of the database and
a response message is built. On a write command, the data is written directly into the
database and a response message is built.
4
After Steps 2 and 3 have been completed, either a normal response message or an
Exception Response message is sent to the Master.
5
Counters are available in the Status Block to permit the ladder logic program to determine
the level of activity of the Slave driver.
User Manual Communication Module
4.4.1 Slave Mode
In Slave driver mode, the MVI69E-MBS module responds to read and write
commands issued by a master on the Modbus network. The following diagram
shows the data flow for normal Slave mode.
In Slave Pass-Through mode, write commands from the Master are handled
differently than they are in Normal mode. In Slave Pass-Through mode, all write
requests are passed directly to the processor and data is not written directly into
the module’s database.
This mode is especially useful when both a Modbus Master and the module’s
processor logic need to be able to read and write values to the same internal
database addresses.
Page 76 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform MVI69E-MBS Backplane Data Exchange
Step
Description
1
Same as normal mode.
2
Same as normal mode.
3
a. In Pass-Through mode, if the Slave driver receives a read request, it looks for the data
in module’s internal database, just as it would in Normal mode.
b. The data needed to respond to the read command is retrieved directly from the
internal database and returned to the Slave driver so it can build a response message.
c. In Pass-Through mode, if the Slave Driver receives a write request, it does not send
the data directly to the module’s internal database. It puts the data to be written into a
special Input Image with a special Block ID code to identify it as a Pass-Through Write
Block and substitutes this special block in place of the next regular Read Data Block. The
special block is processed by the ladder logic and the data to be written is placed into the
WriteData controller tag array at an address that corresponds to the Modbus Address
received in the write command.
d. During normal backplane communications, the data from the WriteData array,
including the data updated by the Pass-Through Write Block, is sent to the module’s
internal database. This gives the ladder logic the opportunity to also change the values
stored in these addresses, if need be, before they are written to the database.
Note: The ReadData array is not used in Pass-Through mode.
4
Same as normal mode.
5
Same as normal mode.
Communication Module User Manual
The following diagram shows the data flow for a slave port with pass-through
enabled:
ProSoft Technology, Inc. Page 77 of 162
January 6, 2014
MVI69E-MBS Backplane Data Exchange MVI69E-MBS ♦ CompactLogix Platform
User Manual Communication Module
4.4.2 Master Mode
In Master mode, the MVI69E-MBS module issues read or write commands to
slave devices on the Modbus network. These commands are user-configured in
ProSoft Configuration Builder as the Port x Master Command List (page 58). This
list is transferred to the module when the module receives its configuration from
the processor.
The commands can also be issued directly from the CompactLogix processor
(Special Command Blocks).
Command status is returned to the processor for each individual command in the
command list. The location of this command status list in the module’s internal
database is user-defined. The following flow chart and associated table describe
the flow of command data into and out of the module.
Page 78 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform MVI69E-MBS Backplane Data Exchange
Step
Description
1
Upon module boot-up, the Master driver obtains configuration data from the MBS
controller tags. The configuration data obtained includes port configuration and the
Master Command List.
Special Commands can be issued directly from the CompactLogix processor using Event
Commands and Command Control. These command values are used by the Master
driver to determine the types and order of commands to send to slaves on the network.
2
After configuration, the Master driver begins transmitting read and/or write commands to
slave nodes on the network. If the Master driver is writing data to a slave, the data for the
write command is obtained from the module’s internal database.
3
Once the specified slave has successfully processed the command, it returns a response
message to the Master driver for processing.
4
Data received from a slave in response to a read command is stored in the module’s
internal database.
5
Status is returned to the processor for each command in the Master Command List.
Communication Module User Manual
Important: Take care when constructing each command in the list to ensure predictable operation
of the module. If two commands write to the same internal database address of the module, the
results are invalid. All commands containing invalid data are ignored by the module.
Master Command List
For a port to function in Master Mode, its Master Command List must be defined
in PCB (page 58). This list contains up to 310 individual entries, with each entry
containing the information required to construct a valid command. A valid
command includes the following items:
Command enable mode: (0) disabled, (1) continuous or (2) conditional
Source or destination database address: The module database address
where data is written or read.
Count: The number of words or bits to be transferred – up to 125 words for
Function Codes 3, 4, or 16, and up to 2000 bits for Function Codes 1, 2, or
15.
Note: 125 words is the maximum count allowed by the Modbus protocol. Some field devices may
support less than the full 125 words. Check with the device manufacturer for the maximum count
supported by the particular slave device.
Slave node address
Modbus Function Code: This is the type of command that is issued.
Source or destination address in the slave device
ProSoft Technology, Inc. Page 79 of 162
January 6, 2014
MVI69E-MBS Backplane Data Exchange MVI69E-MBS ♦ CompactLogix Platform
User Manual Communication Module
Command Error Codes
As the list is read in from the processor and as the commands are processed, an
error value is maintained in the module for each command. The definition for
these command error codes is listed in Communication Error Codes on page
107. You can view the command error codes through the Ethernet diagnostics
port (see chapter 6, Diagnostics and Troubleshooting). They can also be transferred from the module’s database to the processor.
To transfer the Command Error List to the processor, set the Command Error Offset parameter in the port configuration to a module database address that is in
the module’s Read Data area.
Note: The Command Error List must be placed in the Read Data area of the database, so it can be
transferred to the processor in the input image.
Page 80 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform Using Controller Tags
User-Defined Data Types (UDTs) ......................................................... 84
MBS Controller Tag Overview ............................................................... 87
Communication Module User Manual
5 Using Controller Tags
Ladder logic is required for managing communication between the MVI69E-MBS
module and the CompactLogix processor. The ladder logic handles tasks such
as:
Module backplane data transfer
Special block handling
Status data receipt
Additionally, a power-up handler may be needed to initialize the module’s
database and may clear some processor fault conditions.
The sample Import Rung with Add-On Instruction (from the ProSoft DVD or
www.prosoft-technology.com) is extensively commented to provide information
on the purpose and function of each user-defined data type and controller tag.
For most applications, the Import Rung with Add-On Instruction works without
modification.
ProSoft Technology, Inc. Page 81 of 162
January 6, 2014
Using Controller Tags MVI69E-MBS ♦ CompactLogix Platform
User Manual Communication Module
5.1 Controller Tags
Data related to the MVI69E-MBS is stored in the ladder logic in variables called
controller tags. Individual controller tags can be grouped into collections of
controller tags called controller tag structures. A controller tag structure can
contain any combination of:
Individual controller tags
Controller tag arrays
Lower-level controller tag structures
The controller tags for the module are pre-programmed into the Add-On
Instruction Import Rung ladder logic. You can find them in the Controller Tags
subfolder, located in the Controller folder in the Controller Organizer pane of the
main RSLogix 5000 window.
This controller tag structure is arranged as a tree structure. Individual controller
tags are found at the lowest level of the tree structure. Each individual controller
tag is defined to hold data of a specific type, such as integer or floating-point
data. Controller tag structures are declared with user-defined data types, which
are collections of data types.
5.1.1 MVI69E-MBS Controller Tags
The main controller tag structure, MBS, is broken down into five lower-level
controller tag structures.
The five lower-level controller tag structures contain other controller tags and
controller tag structures. Click the [+] sign next to any controller tag structure to
expand it and view the next level in the structure.
Page 82 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform Using Controller Tags
Communication Module User Manual
For example, if you expand the MBS.DATA controller tag structure, you see that
it contains two controller tag arrays, MBS.DATA.ReadData and MBS.DATA.WriteData, which are 600-element integer arrays by default.
The controller tags in the Add-On Instruction are commented in the Description
column.
Notice that the Data Type column displays the data types used to declare each
controller tag, controller tag array or controller tag structure. Individual controller
tags are declared with basic data types, such as INT and BOOL. Controller tag
arrays are declared with arrays of basic data types. Controller tag structures are
declared with user-defined data types (UDTs).
ProSoft Technology, Inc. Page 83 of 162
January 6, 2014
Using Controller Tags MVI69E-MBS ♦ CompactLogix Platform
User Manual Communication Module
5.2 User-Defined Data Types (UDTs)
User-defined data types (UDTs) allow you to organize collections of data types
into groupings. You can use these groupings, or data type structures, to declare
the data types for controller tag structures. Another advantage of defining a UDT
is that you may reuse it in other controller tag structures that use the same data
types.
The Add-On Instruction Import Rung ladder logic for the module has pre-defined
UDTs. You can find them in the User-Defined subfolder, located in the Data Types folder in the Controller Organizer pane of the main RSLogix window. Like
the controller tags, the UDTs are organized in a multiple-level tree structure.
5.2.1 MVI69E-MBS User-Defined Data Types
Twenty different UDTs are defined for the MVI69E-MBS Add-On Instruction.
The main UDT, MBSMODULEDEF, contains all the data types for the module
and was used to create the main controller tag structure, MBS. There are five
UDTs one level below MBSMODULEDEF. These lower-level UDTs were used to
create the MBS.CONFIG, MBS.DATA, MBS.CONTROL, MBS.STATUS, and MBS.UTIL controller tag structures.
Click the [+] signs to expand the UDT structures and view lower-level UDTs.
Page 84 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform Using Controller Tags
Communication Module User Manual
For example, if you expand MBS.DATA, you see that it contains two UDTs,
ReadData and WriteData. Both of these are 600-element integer arrays by
default.
Notice that these UDTs are the data types used to declare the
MBS.DATA.ReadData and MBS.DATA.WriteData controller tag arrays.
The UDTs are commented in the Description column.
ProSoft Technology, Inc. Page 85 of 162
January 6, 2014
Using Controller Tags MVI69E-MBS ♦ CompactLogix Platform
User Manual Communication Module
Tip: If more than 600 words of Read or Write Data are needed, the MBS.DATA.ReadData and
MBS.DATA.WriteData controller tag arrays can be expanded. Simply edit the size of the ReadData
or WriteData integer array in the Data Type column of the MBSDATA UDT. In the example below,
the ReadData array size has been changed to 2000. Save and download the ladder program for
this change to take effect.
Page 86 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform Using Controller Tags
Tag Name
Description
MBS.CONFIG
Configuration information
MBS.DATA
MBS input and output data transferred between the processor
and the module
MBS.CONTROL
Governs the data movement between the PLC rack and the
module
MBS.STATUS
Status information
MBS.UTIL
Generic tags used for internal ladder processing (DO NOT
MODIFY)
Tag Name
Description
MBS.CONFIG.FileData
This parameter contains the MBS configuration data after it has
been downloaded from PCB. It is displayed in ASCII format.
Note: MBS configuration changes cannot be made directly in this
array; the configuration must be downloaded via PCB.
MBS.CONFIG.FileSize
Configuration file size (MBS.CONFIG.FileData array) in bytes.
MBS.CONFIG.FileCRC32
CRC checksum of the configuration file stored in the array.
You use controller tags to:
View the read and write being transferred between the module and the
processor.
View status data for the module.
Set up and trigger special functions.
Initiate module restarts (Warm Boot or Cold Boot).
The following sections describe each of these controller tag structures in more
detail.
5.3.1 MBS.CONFIG
When PCB downloads the configuration file from the PC to the processor, the
processor stores the configuration file data in the MBS.CONFIG.FileData array.
Its CRC is also included in this array.
You cannot edit this array directly. You must use PCB for configuration edits. All
configuration edits must be done in PCB since a unique CRC is calculated for
data integrity. Any change to the configuration parameters directly in this array
will not match the calculated CRC.
ProSoft Technology, Inc. Page 87 of 162
January 6, 2014
Using Controller Tags MVI69E-MBS ♦ CompactLogix Platform
Tag Name
Description
MBS.DATA.ReadData
Data area copied from the module to the processor. This array
stores the Modbus data coming into the module from the
Modbus network.
MBS.DATA.WriteData
Data area copied from the processor to the module. This array
stores the outgoing data sent from the module to the Modbus
network.
Tag Name
Range
Description
MBS.CONTROL.PortControl.Set
0 or 1
Sends Port Control to module
MBS.CONTROL.PortControl.Get
0 or 1
Reads Port Control from module
MBS.CONTROL.PortControl.Portx
n/a
Definition of Port x Control
MBS.CONTROL.PortControl.Portx.
Active
0 or 1
Port Control: Disable = 0, Enable = 1
MBS.CONTROL.PortControl.Portx.
CmdEnableBits[x]
0 or 1
Index of command to be controlled.
Example: Command 20 in port 1
command list can be controlled at
CmdEnableBits[1].3 - This is the 20th
bit offset.
Tag Name
Range
Description
MBS.CONTROL.CmdControl.
CmdControlTrigger
0 or 1
Command Control: Disable = 0, Enable = 1
MBS.CONTROL.CmdControl.
NumberOfCommands
0 to 6
Total number of commands to be executed via
Command Control
MBS.CONTROL.CmdControl.
PortNumber
1 or 2
Port number to be associated with Command
Control function
MBS.CONTROL.CmdControl.
CommandIndex[x]
0 or 1
Command Index of port command [x] to be
enabled. Up to 6 command indexes can be
populated at a time.
User Manual Communication Module
5.3.2 MBS.DATA
This structure contains the Read Data and Write Data arrays for processor-tomodule communication.
5.3.3 MBS.CONTROL
This array handles special tasks requested by the processor.
5.3.3.1 MBS.CONTROL.PortControl
This array allows port commands to be controlled by the processor.
5.3.3.2 MBS.CONTROL.CmdControl
This array allows the processor to dynamically enable configured commands for
execution.
Page 88 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform Using Controller Tags
This array allows the processor to dynamically build Modbus commands with
data associated to the MBS database. This feature is meant for periodic
execution such as resetting the clock and zeroing-out counters.
5.3.3.4 MBS.CONTROL.EventCmd_ProcessorData
This array allows the processor to dynamically build Modbus commands with
processor data. This feature is meant for periodic execution such as resetting the
clock and zeroing-out counters.
ProSoft Technology, Inc. Page 89 of 162
January 6, 2014
Using Controller Tags MVI69E-MBS ♦ CompactLogix Platform
Triggers a cold boot of the module
0 = Disable, 1 = Enable
Tag Name
Range
Description
MBS.CONTROL.WarmBoot
0 or 1
Triggers a warm boot the module
0 = Disable, 1 = Enable
Communication Module User Manual
5.3.3.7 MBS.CONTROL.GetStatus
This tag allows the processor to retrieve status from the module.
5.3.3.8 MBS.CONTROL.ResetStatus
This tag allows the processor to reset the module status counters.
5.3.3.9 MBS.CONTROL.ColdBoot
This tag allows the processor to Coldboot the module (full reboot).
5.3.3.10 MBS.CONTROL.WarmBoot
This tag allows the processor to Warmboot the module (driver reboot).
ProSoft Technology, Inc. Page 91 of 162
January 6, 2014
Using Controller Tags MVI69E-MBS ♦ CompactLogix Platform
Tag Name
Description
MBS.STATUS.PassCnt
Program cycle counter – this value is
incremented each time a complete
program cycle occurs in the module
MBS.STATUS.Product
Product code
MBS.STATUS.Rev
Firmware revision level number
MBS.STATUS.OP
Operating level number
MBS.STATUS.Run
Run number
MBS.STATUS.PortxStats
Port x status
MBS.STATUS.PortxStats.CmdListReq
Total number of requests made from
this port to slave devices on the network
MBS.STATUS.PortxStats.CmdListResp
Total number of slave response
messages received on the port
MBS.STATUS.PortxStats.CmdListErr
Total number of command errors
processed on the port. These errors
could be due to a bad response or
command
MBS.STATUS.PortxStats.PortReq
Total number of messages sent out of
the port
MBS.STATUS.PortxStats.PortResp
Total number of messages received on
the port
MBS.STATUS.PortxStats.PortErrSent
Total number of message errors sent
out of the port.
MBS.STATUS.PortxStats.PortErrRec
Total number of message errors
received on the port
MBS.STATUS.PortxStats.CurrErr
Not used
MBS.STATUS.PortxStats.LastErr
Not used
MBS.STATUS.Block
Backplane transfer status
MBS.STATUS.Block.Read
Total number of read blocks transferred
from the module to the processor
MBS.STATUS.Block.Write
Total number of write blocks transferred
from the processor to the module
MBS.STATUS.Block.Parse
Total number of blocks successfully
parsed that were received from the
processor
MBS.STATUS.Block.Event
Total number of event command blocks
received from the processor
MBS.STATUS.Block.Cmd
Total number of command blocks
received from the processor
MBS.STATUS.Block.Err
Total number of block transfer errors
recognized by the module
MBS.STATUS.PortxLastErr
For a slave port, this field contains the
value of the current error code returned.
For a master port, this field contains the
index of the currently executing
command.
MBS.STATUS.PortxPreviousErr
For a slave port, this field contains the
value of the last error code returned.
For a master port, this field contains the
index of the command with an error.
User Manual Communication Module
5.3.4 MBS.STATUS
This array contains status data for the module.
Page 92 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform Using Controller Tags
Tag Name
Description
MBS.UTIL.ReadDataSizeGet
Holds Read Data array size
MBS.UTIL.WriteDataSizeGet
Holds Write Data array size
MBS.UTIL.ReadDataBlkCount
Number of Read Data blocks – this value is
the Read Register Count divided by the Block Transfer Size
MBS.UTIL.WriteDataBlkCount
Number of Write Data blocks – this value is
the Write Register Count divided by the Block Transfer Size
MBS.UTIL.RBTSremainder
Remainder from the Read Register Count
divided by the Block Transfer Size
MBS.UTIL.WBTSremainder
Remainder from the Write Register Count
divided by the Block Transfer Size
MBS.UTIL.BlockIndex
Computed block offset for data
MBS.UTIL.LastRead
Latest Read Block ID received from the
module
MBS.UTIL.LastWrite
Latest Write Block ID to be sent to the
module
MBS.UTIL.LastWriteInit
Latest Write Block ID used during initialization
MBS.UTIL.ConfigFile
Holds variables for configuration file transfer
MBS.UTIL.ConfigFile.WordLength
Length of configuration data to be included in
block transfer
MBS.UTIL.ConfigFile.BlockCount
Not used
MBS.UTIL.ConfigFile.FileOffset
Offset in configuration file to use as a starting
point for copying over configuration data
MBS.UTIL.ConnectionInputSize
Holds size of the Connection Input array
MBS.UTIL.BlockTransferSize
Size of the backplane transfer blocks
MBS.UTIL.SlotNumber
Slot number of the module in the rack
MBS.UTIL.EventBlockID
Holds Block ID for Event Command
MBS.UTIL.EventCmdPending
Keeps an Event Command message from
being sent to the module before the previous
Event Command is completed
MBS.UTIL.PollStatusOffset
Offset in slave status data array to use as a
starting point for copying over slave status
data
MBS.UTIL.CmdsAddedToQueue
Number of Command Control messages
added to the command queue
MBS.UTIL.CmdControlBlockID
Holds Block ID for Command Control
MBS.UTIL.CmdCntrlPending
Keeps a Command Control message from
being sent to the module before the previous
Command Control is completed
MBS.UTIL.EventDataCmdPending
Keeps an Event Command with Data
message from being sent to the module
before the previous Event Command with
Data is completed
MBS.UTIL.BootTimer
Timer used to clear both cold and warm boot
requests
MBS.UTIL.PassThru[ ] Array
Holds variables used for processing passthrough messages
Communication Module User Manual
5.3.5 MBS.UTIL
The array is used for internal ladder processing, and must not be modified.
ProSoft Technology, Inc. Page 93 of 162
January 6, 2014
Using Controller Tags MVI69E-MBS ♦ CompactLogix Platform
User Manual Communication Module
Page 94 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform Diagnostics and Troubleshooting
In This Chapter
Ethernet LED Indicators ........................................................................ 96
LED Status Indicators ............................................................................ 96
Connecting the PC to the Module's Ethernet Port ................................. 99
Using the Diagnostics Menu in ProSoft Configuration Builder ............. 102
Communication Error Codes ............................................................... 107
Connecting to the Module’s Webpage ................................................. 108
Communication Module User Manual
6 Diagnostics and Troubleshooting
The module provides information on diagnostics and troubleshooting in the
following forms:
LED status indicators on the front of the module provide information on the
module’s status.
Status data contained in the module can be viewed in ProSoft Configuration
Builder through the Ethernet port.
Status data values that are transferred from the module to the processor.
ProSoft Technology, Inc. Page 95 of 162
January 6, 2014
Diagnostics and Troubleshooting MVI69E-MBS ♦ CompactLogix Platform
LED
State
Description
Data
OFF
Ethernet connected at 10Mbps duplex speed
AMBER Solid
Ethernet connected at 100Mbps duplex speed
Link
OFF
No physical network connection is detected. No Ethernet
communication is possible. Check wiring and cables.
GREEN Solid
or Blinking
Physical network connection detected. This LED must be ON solid
for Ethernet communication to be possible.
LED
Status
Indication
ETH
On
Ethernet communications are ok
Off
No Ethernet cable connected
P1
Green
Data is being transferred between the module and the Modbus
network on Port 1
Red
Communication error detected
Off
No Modbus network activity detected
P2
Green
Data is being transferred between the module and the Modbus
network on Port 2
Red
Communication error detected
Off
No Modbus network activity detected
CFG
Green
Configuration is ok
Yellow
Module is reading configuration
Red
Error setting up Modbus protocol driver, failed startup, or module
shutting down
Off
Processor is in Program mode
BP
Green
The LED is on when the module is performing a write operation on
the backplane. Under normal operation, the LED should blink
rapidly on and off.
Red
Major fault or module shutting down
OK
Green
Module is ok
Red
The program has detected an error or is being configured. If the
LED remains red for over 10 seconds, the program has probably
halted.
User Manual Communication Module
6.1 Ethernet LED Indicators
The Ethernet LEDs indicate the module's Ethernet port status.
6.2 LED Status Indicators
The LEDs indicate the module’s operating status.
Page 96 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform Diagnostics and Troubleshooting
Communication Module User Manual
During module configuration, the OK LED is red and the BP ACT LED is on. If
the APP, BP ACT and OK LEDs blink at a rate of every one-second, this
indicates a serious problem with the module. Call ProSoft Technology Technical
Support to arrange for repairs.
6.2.1 Clearing a Fault Condition
Typically, if the OK LED on the front of the module remains RED for more than
ten seconds, a hardware problem has been detected or the program has exited.
To clear the condition, follow these steps:
1 Turn off power to the rack.
2 Remove the card from the rack.
3 Verify all jumpers are set correctly.
4 Re-insert the card in the rack and turn the power back on.
5 Verify correct configuration data is being transferred to the module from the
CompactLogix controller.
If the module's OK LED does not turn GREEN, verify that the module is inserted
completely into the rack. If this does not cure the problem, contact ProSoft
Technology Technical Support.
ProSoft Technology, Inc. Page 97 of 162
January 6, 2014
Diagnostics and Troubleshooting MVI69E-MBS ♦ CompactLogix Platform
Problem Description
Steps to take
Processor Fault
Verify the module is securely plugged into the slot that has been
configured for it in the I/O Configuration of RSLogix.
Verify the slot location in the rack has been configured correctly in the
ladder logic.
Processor I/O LED
flashes
This indicates a problem with backplane communications. A problem
could exist between the processor and any installed I/O module, not just
the MVI69E-MBS. Verify all modules in the rack are configured correctly.
Problem Description
Steps to take
BP LED remains OFF
or blinks slowly
This indicates that backplane transfer operations are failing. Connect to
the module’s Configuration/Debug port to check this.
To establish backplane communications, verify the following items:
The processor is in RUN or REM RUN mode.
The backplane driver is loaded in the module.
The module is configured for read and write data block transfer.
The ladder logic handles all read and write block situations.
The module is properly configured in the processor I/O configuration
and ladder logic.
OK LED remains RED
The program has halted or a critical error has occurred. Connect to the
communication port to see if the module is running. If the program has
halted, turn off power to the rack, remove the card from the rack and reinsert the card in the rack, and then restore power to the rack.
User Manual Communication Module
6.2.2 Troubleshooting the LEDs
Use the following troubleshooting steps if problems occur when the module is
powered up. If these steps do not resolve the problem, please contact ProSoft
Technology Technical Support.
Processor Errors
Module Errors
Page 98 of 162 ProSoft Technology, Inc.
January 6, 2014
MVI69E-MBS ♦ CompactLogix Platform Diagnostics and Troubleshooting
Communication Module User Manual
6.3 Connecting the PC to the Module's Ethernet Port
With the module securely mounted, connect one end of the Ethernet cable to the
ETH1 Port, and the other end to an Ethernet hub or switch accessible from the
same network as the PC. Or, connect directly from the Ethernet Port on the PC
to the ETH1Port on the module.
6.3.1 Setting Up a Temporary IP Address
Important:ProSoft Configuration Builder locates MVI69E-MBS modules through UDP broadcast
messages. These messages may be blocked by routers or layer 3 switches. In that case, ProSoft Discovery Service is unable to locate the modules.
To use ProSoft Configuration Builder, arrange the Ethernet connection so that there is no router/
layer 3 switch between the computer and the module, OR reconfigure the router/ layer 3 switch to
allow routing of the UDP broadcast messages.
1 In the tree view in ProSoft Configuration Builder (PCB), select the MVI69E-
MBSmodule. (For instructions on opening and using a project in PCB, please
refer to Chapter 2.)
ProSoft Technology, Inc. Page 99 of 162
January 6, 2014
Diagnostics and Troubleshooting MVI69E-MBS ♦ CompactLogix Platform
User Manual Communication Module
2 Right-click the module icon in the tree and choose DIAGNOSTICS.
3 In the Diagnostics window, click the SET UP CONNECTION button.
Page 100 of 162 ProSoft Technology, Inc.
January 6, 2014
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.