Pilz PNOZ XV2 Data Sheet

E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ XV2
Safety relay for monitoring E-STOP pushbuttons and safety gates.
PNOZ XV2
Unit features
` Positive-guided relay outputs:
– 2 safety contacts (N/O), instanta-
neous
– 2 safety contacts (N/O), delay-on
de-energisation
` Connection options for:
– E-STOP pushbutton – Safety gate limit switch – Reset button
` LED indicator for:
– Switch status channel 1/2 – Supply voltage – Reset circuit
` Delay-on de-energisation, fixed or
selectable
` Delay time can be cancelled via re-
set button
` See order reference for unit types
Unit description
The safety relay meets the require­ments of EN 60204-1 and IEC 60204­1 and may be used in applications with
` E-STOP pushbuttons ` Safety gates
The max. category the safety contacts can achieve in accordance with EN 954-1 is stated in the technical details.
Safety features
The relay conforms to the following safety criteria:
` The circuit is redundant with built-in
self-monitoring.
` The safety function remains effecti-
ve in the case of a component failu­re.
` The correct opening and closing of
the safety function relays is tested automatically in each on-off cycle.
` The unit has an electronic fuse.
Block diagram
A1 A2
=
Power
=
S11 S12
Reset/
Start
S13 S14
S21 S22
InputInput
Reset/
Start
S33 S34
S31 S32
Input
Reset
t
Y39 Y40
K3
K1
K4
K2
13 23
14 24
37 47
38 48
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-062-11/04
E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ XV2
Function description
` Single-channel operation: no red-
undancy in the input circuit, earth faults in the reset circuit are detec­ted.
` Dual-channel operation with detec-
tion of shorts across contacts: red­undant input circuit, detects
Timing diagram
POWER
Reset/Start
Reset t
v
Input
Output safe
Output safe del
– earth faults in the reset and input
circuit,
– short circuits in the input circuit
and, with a monitored reset, in the reset circuit too,
– shorts between contacts in the
input circuit.
` Automatic start: Unit is active once
the input circuit has been closed.
1 2
t4
t1 t2
t1
t3 t2
t3
t1
` Monitored reset: Unit is active once
the input circuit is closed and once the reset circuit is closed after the waiting period has elapsed (see technical details).
` Increase in the number of available
contacts by connecting contact ex­pander modules or external contac­tors/relays.
t2
t3 t4 t3
t2t1
Key
` Power: Supply voltage ` Reset/start: Reset circuit S13-S14,
S33-S34
` Reset t
: Y39-Y40
v
` Input: Input circuits S11-S12, S21-
S22, S31-S32
Wiring
Please note:
` Information given in the “Technical
details” must be followed.
` Outputs 13-14, 23-24 are instanta-
neous safety contacts, outputs 37­38, 47-48 are delay-on de-energi­sation safety contacts.
` To prevent contact welding, a fuse
should be connected before the output contacts (see technical de­tails).
` Calculation of the max. cable runs
in the input circuit:
l
max
R
lmax
=
I
max
Rl / km
= max. overall cable resi-
R
lmax
stance (see technical details)
/km = cable resistance/km
R
l
` Use copper wire that can withstand
60/75 °C.
` Output safe: Safety contacts, in-
stantaneous 13-14, 23-24
` Output safe del: Safety contacts,
delayed 37-38, 47-48
` c: Automatic reset ` d: Monitored reset
` Sufficient fuse protection must be
provided on all output contacts with capacitive and inductive loads.
: Switch-on delay
` t
1
` t2: Delay-on de-energisation
: Delay time
` t
3
` t4: Waiting period
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-062-11/04Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-2
E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ XV2
Preparing for operation
` Supply voltage
Supply voltage AC DC
` Input circuit
Input circuit Single-channel Dual-channel E-STOP
without detection of shorts across contacts
S21 S22
S12 S11 S32
S31
S1
E-STOP with detection of shorts across con­tacts
S11 S12
Safety gate without detection of shorts across contacts
S21 S22
S12 S11 S32
S31
S1
A1
A2
S22 S32 S31 S21
L+
L-
S1
Safety gate with detection of shorts across con­tacts
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
S11 S12
S22 S21 S32
S31
S1
NSG-D-2-062-11/04