Pilz PNOZ ex Data Sheet

E-STOP relays, safety gate monitors
Category 4, EN 954-1
PNOZ Ex
Safety relay for monitoring E-STOP pushbuttons and safety gates in po­tentially explosive atmospheres
Approvals
PNOZ Ex
Unit features
` Positive-guided relay outputs:
– 3 safety contacts (N/O), instanta-
neous
– 1 instantaneous auxiliary contact
(N/O) in the intrinsically safe area
– 1 instantaneous auxiliary contact
(N/O) for fusing in the intrinsically safe area
– 1 instantaneous auxiliary contact
(N/C) in the non-intrinsically safe area
` Connection options for:
– E-STOP pushbutton – Safety gate limit switch – Reset button
` LED indicator for:
– Switch status channel 1/2 – Supply voltage
` Ex area II (1)GD [EEx ia] IIB/IIC ` See order reference for unit types
Unit description
The safety relay meets the require­ments of EN 60947-5-1, EN 60204-1 and VDE 0113-1 and may be used in applications with
` E-STOP pushbuttons ` Safety gates
The safety relay provides an intrinsi­cally safe output circuit and volt-free contacts for potentially explosive are­as (standards used: EN 50014 +A1-A2 and EN 50020). The unit is suitable for non-contact barriers (e.g. light curtains) because a dynamic start is possible.
Safety features
The relay meets the following safety requirements:
` The circuit is redundant with built-in
self-monitoring.
` The safety function remains effec-
tive in the case of a component fail­ure.
` The correct opening and closing of
the safety function relays is tested automatically in each on-off cycle.
Block diagram
A1 A2 13 23 33 41
S11 S12 S21 S22
~
=
Power
Feed-
back
Y1 Y2
Grey area = intrinsically safe area
Input
Y36 Y37
Reset/
Start
S12 S34
Reset/
Start
K1
K2
14 24 34 42
535463
64
S52 Y36
InputInput
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-355-2006-08
E-STOP relays, safety gate monitors
Category 4, EN 954-1
PNOZ Ex
Function description
` Dual-channel operation with detec-
tion of shorts across contacts: re­dundant input circuit, detects – earth faults in the reset and input
circuit,
– short circuits in the input circuit
and, with a monitored reset, in the reset circuit too,
Timing diagram
1 2
POWER
Reset/Start
Input
Output safe
Output aux.
t1 t2
t1 t2
Key
` Power: Supply voltage ` Reset/start: Reset circuit S12-S34,
Y36-Y37, Y1-Y2
` Input: Input circuits S11-S12, S21-
S21, S52, Y36
` Output safe: Safety contacts 13-14,
23-24, 33-34
– shorts between contacts in the
input circuit.
` Automatic start: Unit is active once
the input circuit has been closed.
` Manual reset: Unit is active once
the input circuit is closed and then the reset circuit is closed.
` M on it or ed re se t: Un i t i s ac ti ve on c e
– the input circuit is closed and
then the reset circuit is closed
ab
t1
t1
t2
t2
` Output aux: Auxiliary contacts 41-
42, 53-54, 63-64
` c: Automatic reset ` d: Manual reset ` e: Monitored reset ` a: Input circuit closes before reset
circuit
and opened again.
– the reset circuit is closed and
then opened again once the in­put circuit is closed.
` Increase in the number of available
contacts by connecting contact ex­pander modules or external contac­tors/relays.
ab
t1
3
t2
t2
t1
` b: Reset circuit closes before input
circuit
: Switch-on delay
` t
1
` t2: Delay-on de-energisation
Wiring
Please note:
` Information given in the “Technical
details” must be followed.
` Sufficient fuse protection must be
provided on all output contacts with capacitive and inductive loads.
` Outputs 13-14, 23-24, 33-34 are
safety contacts, outputs 41-42, 53­54, 63-64 are auxiliary contacts (e.g. for display).
` To prevent contact welding, a fuse
should be connected before the output contacts (see technical de­tails).
` Calculation of the max. cabling runs
in the input circuit:
l
max
R
lmax
=
I
max
Rl / km
R
= max. overall cable resist-
lmax
ance (see technical details)
/km = cable resistance/km
R
l
` Use copper wire that can withstand
60/75 °C.
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-355-2006-08Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-2
E-STOP relays, safety gate monitors
Category 4, EN 954-1
PNOZ Ex
Preparing for operation
` Supply voltage
Supply voltage AC DC
A1
A2
L1
N
` Input circuit
Input circuit Single-channel Dual-channel E-STOP
with detection of shorts across contacts
Y36 (S11) S52
S11 S21 S22
S12
S1
Safety gate with detection of shorts across contacts
Y36 (S11) S52
S11 S12 S21 S22
S1
` Reset circuit
Reset circuit Reset from the non-intrinsically safe area Reset from the intrinsically safe area Automatic reset
S12 S34
Y1 Y2
S2
Manual reset
Monitored reset
Y36 Y37
Y1 Y2
S12 S34
Y1 Y2
S12 S34
S3
S3
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
Y1 Y2
S3 S12 S34
Y1 Y2
S3 S12 S34
Y36
Y37
NSG-D-2-355-2006-08
E-STOP relays, safety gate monitors
Category 4, EN 954-1
PNOZ Ex
` Feedback loop
Feedback loop Reset from the non-intrinsically safe area Reset from the intrinsically safe area Contacts from external contactors
(manual reset)
S12
S34
Y1
Y2 13 (23, 33) 14 (24 ,34)
K5
K6
K5
K6
S3
L1 N
Y1 Y2
13 (23, 33) 14 (24, 34)
K5
K6
K5
K6
L1 N
Contacts from external contactors (monitored reset)
` Key
S1/S2 E-STOP/safety gate switch
S3 Reset button
Switch operated
Gate open
Gate closed
Y36 Y37 S12 S34
Y1
Y2 13 (23, 33) 14 (24 ,34)
K5
K6
K5
K6
S3
L1 N
Y1 Y2
13 (23, 33) 14 (24, 34)
K5
K6
K5
K6
L1 N
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-355-2006-08Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-4
E-STOP relays, safety gate monitors
Category 4, EN 954-1
PNOZ Ex
Terminal configuration
Installation
` The safety relay should be installed
in a control cabinet with a protec­tion type of at least IP54.
` Use the notch on the rear of the unit
to attach it to a DIN rail.
` Ensure the unit is mounted securely
on a vertical DIN rail (35 mm) by us­ing a fixing element (e.g. retaining bracket or an end angle).
` Always install the unit outside the
potentially explosive area. Only the intrinsically safe output circuit (ter­minals S11, S12, S21, S22, S34, S52, Y36, Y37 and GND) and the volt-free contacts (terminals 53, 54 and 63, 64) may be brought into the potentially explosive area.
` Air gaps between uninsulated parts
of intrinsically safe circuits and earthed metal parts must be a min­imum of 3 mm; air gaps between uninsulated parts of intrinsically safe circuits and uninsulated parts of non-intrinsically safe circuits must at least conform with the val­ues required in Table 4, Amend­ment 4 of EN 50020
18674-01
13
Dimensions
S12S11 S52
POWER CH. 1 IN CH. 2 IN FUSE CH.1/CH.2 FAULT
23
14
75 (2.95") 87 (3.42")
------
33
Y36
34
Typ :
121 (4.76")
PNOZ Ex 230 VAC 774 100 II (1) GD [EEx ia] IIC/IIB DMT 03 ATEX E 068 X
S21 S22 S34
24
Y37
41 42
54
6353
S33
Y1
112,5 (4.41")
64
A1Y2 A2
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-355-2006-08
E-STOP relays, safety gate monitors
Category 4, EN 954-1
PNOZ Ex
Notice
Service life graph
This data sheet is only intended for use during configuration. For installation
10
and operation, please refer to the op­erating instructions supplied with the
DC13: 24 V
unit.
1
D Nennbetriebstrom (A)
GB Nominal operating current (A)
F Courant coupé (A)
Technical details
Electrical data
Supply voltage Supply voltage U
AC 115 V, 120 V, 230 V
B
Voltage tolerance -15 %/+10 % Power consumption at U
AC 8.0 VA
B
Frequency range AC 50 - 60 Hz Voltage and current at Input circuit DC: 6.0 V 25.0 mA Reset circuit DC: 6.0 V 15.0 mA Feedback loop DC: 24.0 V 20.0 mA Number of output contacts Safety contacts (S) instantaneous: 3 Auxiliary contacts (N/C): 3 Category of output contacts in accordance with EN 954-1 Safety contacts (S) instantaneous: 4 Utilisation category in accordance with EN 60947-4-1 Safety contacts: AC1 at 240 V I
Safety contacts: DC1 at 24 V I
Auxiliary contacts (intrinsically safe): DC1 at 30 V I
0.1
E Corriente nominal de servicio (A)
I Corrente di esercizio nominale (A)
NL Nominale bedrijfsstroom (A)
10 100 1000 10000
D Schaltspielzahl x 10 GB Cycles x 10 F Nombre de manvres x 10
: 0.01 A , I
min
P
: 1000 VA
max
: 0.01 A , I
min
: 48 W
P
max
: 0.01 A, I
min
P
: 10 W
max
3
3
max
max
max
AC1: 230 V
3
: 4.00 A
: 2.0 A
: 0.5 A
DC1: 24 V
AC15: 230 V
E Número de ciclos x 10 I Numero dei cicli di commutazione x 10 NL Aantal schakelingen x 10
3
3
3
Auxiliary contacts: AC1 at 240 V I
Auxiliary contacts: DC1 at 24 V I
: 0.01 A , I
min
: 1000 VA
P
max
: 0.01 A , I
min
: 48 W
P
max
max
max
Utilisation category in accordance with EN 60947-5-1 Safety contacts: AC15 at 230 V I Safety contacts: DC13 at 24 V (6 cycles/min) I Auxiliary contacts: AC15 at 230 V I Auxiliary contacts: DC13 at 24 V (6 cycles/min) I
max max max max
: 4.0 A : 2.0 A : 4.0 A : 2.0 A
Contact material AgSnO2 + 0.2 µm Au
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
: 4.0 A
: 2.0 A
NSG-D-2-355-2006-08Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-6
E-STOP relays, safety gate monitors
Category 4, EN 954-1
PNOZ Ex
Electrical data
External contact fuse protection (IK = 1 kA) to EN 60947-5-1 Blow-out fuse, quick Safety contacts: 4 A Auxiliary contacts: 4 A Blow-out fuse, slow Safety contacts: 4 A Auxiliary contacts: 4 A Circuit breaker 24 VAC/DC, characteristic B/C Safety contacts: 4 A Auxiliary contacts: 4 A Max. overall cable resistance R input circuits, reset circuits single-channel at U dual-channel without detect. of shorts across contacts at U dual-channel with detect. of shorts across contacts at U Max. line capacitance EX IIB EX IIC Max. line inductance EX IIB
EX IIC
Times
Switch-on delay with automatic reset typ. 150 ms with automatic reset max. 200 ms with automatic reset after power on typ. 165 ms with automatic reset after power on max. 210 ms with manual reset typ. 145 ms with manual reset max. 200 ms on monitored reset with rising edge typ. 115 ms on monitored reset with rising edge max. 150 ms Delay-on de-energisation with E-STOP typ. 10 ms with E-STOP max. 30 ms with power failure typ. 110 ms with power failure max. 150 ms Recovery time at max. switching frequency 1/s after E-STOP 50 ms after power failure 200 ms Min. start pulse duration with a monitored reset 30 ms Simultaneity, channel 1 and 2 150 ms Supply interruption before de-energisation 35 ms
Environmental data
EMC EN 60947-5-1, EN 61000-6-2 Vibration to EN 60068-2-6 Frequency 10 - 55 Hz Amplitude 0.35 mm Climatic suitability EN 60068-2-78 Airgap creepage VDE 0110-1 Ambient temperature -20 - 55 °C Storage temperature -40 - 85 °C Protection type Mounting (e.g. cabinet) IP54 Housing IP40 Terminals IP20
AC 40 Ohm
B
lmax
AC 80 Ohm
B
AC 15 Ohm
B
2 µF 1 µF
200 µH 100 µH
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-355-2006-08
E-STOP relays, safety gate monitors
Category 4, EN 954-1
PNOZ Ex
Mechanical data
Housing material Housing PPO UL 94 V0 Front ABS UL 94 V0 Max. cross section of external conductors with screw terminals 1 core flexible 0.20 - 4.00 mm² , 24 - 10 AWG 2 core, same cross section, flexible: with crimp connectors, without insulating sleeve 0.20 - 2.50 mm² , 24 - 14 AWG without crimp connectors or with TWIN crimp connectors 0.20 - 2.50 mm² , 24 - 14 AWG Torque setting with screw terminals 0.60 Nm Dimensions Height 87.0 mm Width 112.5 mm Depth 121.0 mm Weight 720 g
The standards current on 05/04 apply.
Order reference
Type Features Terminals Order no.
PNOZ Ex 230 VAC Screw terminals 774 100 PNOZ Ex 115 VAC Screw terminals 774 104 PNOZ Ex 120 VAC Screw terminals 774 105
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-355-2006-08Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany