PEERLESS MI SERIES, MIH SERIES, MI-03, MI-04, MI-05 Installation, Operation & Maintenance Manual

...
MI/MIH
Boilers
Installation,
Operation Maintenance
Manual
Pr=-EI_LESS _
MI Model Available for Natural or LP Gas
Standit_g Pilot (3 9 sectior_) with 8(7_ AFUE
[-Ioneywell SmartValve ® Intermittent Ignition (3-9 section)
with 82% AFUE
MIH Mid-E._f_ency Model Available in 3-6 Sections
for Natural Gas
Honeywell SmartValve ®Intermittent Ignition with 83% AFUE
Qualifies for Utility Company Energy Rebates in Some Areas
Natural Draft (Chimney) Venting Low Profile Design
Internal Horizontal to Vertical Draft Diverter
Ideal for Ir_stallations with Low Ceilings
Steel Push Nipples
Provici( _ a Permar_ent _Vct_'r 7"(c)hl Seed Between Sections
Unaffected by PetroIcum alzd Oilier Contaminants
Deluxe Insulated Enameled Steel Jacket
Reduces Boiler Heat Loss
Completely Encloses Gas Valve and Burners
Safety Controls
Vent Safety ShutoffSwitch
Flame Rollout Safety ShutoffSwitch
Standing Pilot or Honeywell SmartValve _
Intermittent Ignition
Honeywell Operating Controls
Taco Circulator
Elec. Operated Automatic Vent Damper
Grundfos Circulator
50 PSI Safety Relief Valve
Non-Combustible Floor Pan
c_xStltartVah;_t i._ r_ rt,gislt_rt,d Ircldt,illark o I llo¢letlw(tll Corporcltion.
l_crless q[f_,r on_ of tll_" mosl c:omprelt_.nsive wctrrarlly prof.jrarrus in tttt_ ind_Lslr_/. All I_ (_rlt'ss r_'sidt't_ticd c_¢_t iro,_ !_oil<.rs inc'!_d_, c_ lidl one tj_!(_r Illarl€_rlltj. A limited. ['_[_[_-r_kl_SS ®
I{]_'limt_ ivtlrranQj Ls p¢'ovlcl_'d.]_?r tlt_' ('(t_%l ilOtl _;('('lioll.% of l)(t('rl_'._;:_ rt'sid_'llti_ll hot Ivat_:r Ix)liters
[)(y(!ll({s._; _IL'_o provld(,s cl IIIIlil('_l. It'll II(!(_lr ttl(lYltllllt] (.ill Ih¢" C(l.'ql IYOtl N(!(?liolls q['il.s I'_Si(Jt_IIli_ll
s I(_(__I_ I)oilt,rs. l'_t _(, tz!I(1 It"_I _1_"(_r_"xt_"r_(1<'(1tmt_rrczl iIi(".s (ati l X ii f_ (11id I_ll)ol ar(_ _to_v (_v(_ lied)& ". CAST IRON BOILERS
/'/(,cLs(_ co¢l._tdt ['(,('rli,ss [ ](,_ll(,_ (2)m[J(lll{/ ]OF Coltll)l(.lt, it)(iFK(llll!j it!]orlnaliorL
Peerless Heater Company * 231 North Walnut Street * Boyertown. PA 19512 1021 * 610 367 2153 * www,peerless-heater.eom
FAB MI l_l {3/02 5M)
Pnnled _n U S A
USING THIS MANUAL 1
A. INSTALLATION SEQUENCE ............. 1
B. SPECIAL ATTENTION BOXES ........... 1
1. PREINSTALLATION 2
A. ACCESSIBILITY CLEARANCES .......... 2
B. CLEARANCE FROM COMBUSTIBLE
CONSTRUCTION ..................... 2
C. AIR FOR COMBUSTION AND
VENTILATION ....................... 2
D. LIQUEFIED PETROLEUM (LP) GAS ....... 4
E. INSTALLATION SURVEY ............... 4
E PLANNING THE LAYOUT ............... 4
7. START-UP PROCEDURES 20
A. COMPLETING THE INSTALLATION ...... 20
B. CONTROL DESCRIPTIONS ............. 24
C. ADJUSTMENT OF GAS PRESSURE
REGULATOR ....................... 24
D. ADJUSTMENT OF PILOT GAS FLOW .... 24
E. CHECKING BURNER INPUT ............ 24
E CHECK-OUT PROCEDURE ............. 25
8. TROUBLESHOOTING 26
A. SHUT-DOWN CAUSED BY PILOT OUTAGE,
BLOCKED VENT SHUT-OFF SWITCH OR
FLAME ROLL-OUT SAFETY SHUT-OFF
SWITCH ........................... 26
B. TROUBLESHOOTING GUIDES .......... 26
A. BOILER SUPPLY AND RETURN .......... 6
B. SAFETY RELIEF VALVE ................ 7
C. PIPING FOR ZONED SYSTEMS .......... 8
D. EXPANSION TANK .................... 9
E. INDIRECT-FIRED WATER HEATER ........ 9
E FREEZE PROTECTION ................. 9
A. INTEGRAL DRAFT HOOD ............. !0
B. VENT DAMPER INSTALLATION -
GENERAL .......................... 10
C. VENT PIPING AND CHIMNEY .......... 11
D. BOILER REMOVAL FROM COMMON
VENTING SYSTEM ................... 12
A. GENERAL .......................... 29
B. DAILY (WITH BOILER IN USE) .......... 29
C. WEEKLY (WITH BOILER IN USE) ........ 29
D. MONTHLY (WITH BOILER IN USE) ....... 29
E. ANNUALLY (BEFORE START OF HEATING
SEASON) .......................... 30
10. BOILER DIMENSIONS _ _TINGS 31
A. BASE/COMBUSTIBLE FLOOR PAN ....... 32
B. MANIFOLD/GAS TRAIN ............... 34
C. BLOCK/DRAFT HOOD ................ 36
D. JACKET ........................... 38
E. CONTROLS/CIRCULATOR/VENT
DAMPER .......................... 40
A. WIRING ........................... 15
B. ZONED SYSTEM WIRING ............. 15
C. CONTROLS ........................ 15
D. SEQUENCE OF OPERATION ........... 16
Follow thetnsta[lattoninstructionspro',,'_dedill this
manual m the order shown The order ot these mstructLons has been set m order to provide the installer
with a logical sequence ol steps that wdl mulmllze
potenhal interferences and maximize safety, during
boiler mstallatLon
Indicates a condition or hazard which will cause severe personal injury, death or major property
damage.
Throughout thLs manual you will see speoal attenuon
boxes intended to supplement the mstmct=ons and make speoal nohce of potenhal hazards These categories mean m the judgment of Peerless Heater Company
indicates a condition or hazard which may cause
severe personal injury, death or major property damage.
Indmates a condition or hazard which will or can cause minor personal injury or property damage.
indicates special attention is needed, but not directly related to potential personal injury or property damage.
1.!B INS
Read carefully, study these msh-uchons before beginning work
This bo,le_ must be installed by a quahfled con_ac_or The bonler warranty can be voided _t the boder Is not installed, maintained and serviced correctly
The equipment must be installed m accordance with those installation requirements of the authority having jurisdiction or, in the absence of such requirements, to the current edition of the National Fuel Gas Code, ANSI
Z223.1/NFPA 54. Where requtred by the authority having jurisdiction, the installation must conform to American Society of
Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, ASME CSD-I.
r_*wr:_o,[o.]:[.."[.."]I:]I ! / ik'd_a,]l :f;1 :_r_*l_[q _
Install boiler not less than 24" between the left slde. top, and tront ot the boiler and adjacent wall or other
apphance, when access is reqmred for servicing
The design of ths boiler _scertffled for alcove mstallatlon wlth the following clearances
I 6" between s,des and combustible construction
2 24" between top of jacket and combushble
construction
3 6" between draft hood and combustible
COl_ls_uctlon
4 6" between vent pipe and combustLble construction 5 10" between rear of ]acket and combushble
consiluctlon
Do not install this boiler on combusttble flooring
unless it is installed on a special combustible floor pan provided by Peerless Heater Company. Boiler
installation on combustible flooring without the special pan is a fire hazard.
To order combustible floor pan, use the 5-digit stock codes listed in Section 11A of this manual.
Do not install this boiler on carpeting. Boiler installation on carpeting asa fire hazard. Install this boder on non.combustible flooring or use a
combustible floor pan to install thts boder on other
non-carpeted flooring.
2
Prowde adequate facflltnes for combustlon and
vent]lahon a_r unaccordance w_th Sechon 5 3. ALrfor
Combustion and Ventilation Nanonal Fuel Gas
Code ANSI -7223 1/NFPA 54, or apphcable
prows_ons of the local budding code Subsechons 2
through 6 below are based on National Fuel Gas
Code ANSI Z223 1!NFPA 54 requnrements
DehnltlOnS
Unconfined Space: a space whose volume usnot
less than fifty (50) cubnc feet per 1000 Btu/hr of the
total input rahng of all apphances installed Jnthat
space Rooms commumeatmg dnrectly w_th the space
m which the apphances are installed, through
opemngs not furmshed w_th doors, are considered
part of the unconfined space
Unusually Tight Construction: Constmchon
where
Walls and cenlmgs exposed to the outsMe atmosphere have a continuous water vapor
retarder wlth a rating of i perm or less wLth openings gasketed or sealed, and
b Weatherstnppmg has been added on openable
windows and doors, and
CaulkLng or sealants are supphed to areas such as joints around window and door frames. between sole plates and floors, between wall- ceflmg joints, between wall panels, at penetratlons for plumbing, electrical and gas hnes, and at other openings
2
3 Appliances Located in Unconfined Spaces:
For installations in unconfined spaces with other than unusually tight construction, the supply of air for combustion and ventilation can usually be considered adequate.
4. Unusually Tight Construction:
For equipment located in buildings of unusually tight construction as defined on the previous page, provide air for combustion and ventilation using the
methods described in 5a or 5b below.
5. Appliances Located in Confined Spaces:
a. All air from inside the building: Provide two
permanent openings communicating directly with an additional room or rooms of sufficient volume
so that the combined volume of all spaces meets the criteria for an unconfined space. Use the total
input of all gas utilization equipment installed in
the combined space in making this determination.
Size each opening with a minimum free area of one square inch per 1000 Btu/hr. of the total
rating of all gas utilization equipment in the
confined space, but not less than I00 square inches. Begin with one opening 12 inches from
the top, and begin the other opening within 12 inches of the bottom of the enclosure. See Figure
1. Provide air openings with minimum dimensions not less than three (3) inches.
b. All air from outside the building. Connect the
confined space with the outdoors in accordance with methods i) or ii) below. Provide air openings
with minimum dimensions not less than three (3) inches. Where ducts are used, make certain that they are the same cross-sectional area as the free area of the openings to which they connect.
Provide two permanent openings, one commencing within 12 inches of the top and one commencing within 12 inches of the
bottom of the enclosure. Connect the
openings directly or by duets, with the outdoors or spaces (crawl or attic) that freely
communicate with the outdoors.
Where directly communicating with the
outdoors (see Figure 2) or where communicating to the outdoors through vertical ducts (see Figure 3), size each opening with a minimum free area of one (I) square inch per 4000 Btu/hr. of total rating of all equipment in the enclosure.
i ?
I
12" max
TWO AIR OPENINGS:
Minimum
Free Area Each -
1 in2per 1000 Btuh
at Least 100 in2
BUILDING
Must communicatefreely
withoutdoors
Must notbeunder
negativepressure
12" max
Figure 1: Air Openings - All Air from Indoors
TWO AIR OPENINGS:
Minimum
Free Area Each -
1 in_per 4000 Btuh
Figure 2: Air Openings - All Air Directly from
Outdoors
Figure 3: Air Openings - All Air from Outdoors
through Vertical Ducts
6.
:_ IIL_l_uf±lUHff±_ugl[e]L_l[_'q_|J;kVJ_k
7.
Where communicating with the outdoors
through horizontal ducts, size each opening
with a minimum free area of one (1) square
inch per 2000 Btu/hr of total input rating of
all equipment in the enclosure. See Figure 4.
ii) Where the equipment has clearances of at
least one (1) inch from the sides and back and six (6) inches from the front of the appliance, the code allows one permanent opening, commencing within 12 inches of the top of the enclosure. Connect the opening directly with the outdoors or through
a vertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely
communicate with the outdoors. Size the opening with a minimum free area of one
square inch per 3000 Btu!hr. of the total input rating of all equipment in the enclosure,
and not less than the sum of the areas of all vent connectors in the confined space.
In calculating free area of an opening, take into account the blocking affect of louvers, grilles and
screens. Do not use screens smaller than i/4" mesh. If the free area is known, use this value in calculating
the size of the opening required. If it is not known, assume that wood louvers provide 20-25% free area,
and metal louvers and grilles provide 60-75% free area.
Remove sources of hydrocarbons (bleaches, cleaners, chemicals, sprays, paint removers, fabric
softeners, etc.) from the boiler area. The vapors generated by these substances can contaminate the combustion air and contribute to shortened
boiler/vent system life.
I_ff±!_l_ll_[dl|ll:lt_VLelll
Liquefied Petroleum (LP) is heavier than air and may
collect or "pool" in a low area in the event of a leak from defective equipment.This gas may then ignite,
resulting in a fire or explosion. See the instructions below.
ii-i ..
12"maxl [ i 1--
, _t [jT TWO AIR OPENINGS: |
) 1' Minimum l
Free Area Each =
in_per 2000 Btuh !
_ min
?
12"max
Figure 4: Air Openings - All Air from Outdoors
through Horizontal Ducts
For new and existing installations, a Water Installation Survey is available from Peerless Heater Company. The
survey will provide information on how a hot water boiler works with your specific system and will provide
an overview of hot water system operation in general.
You can also use this survey to locate system problems
which will have to be corrected. To obtain copies of the
Water Installation Survey, contact your Peerless
representative.
Prepare sketches and notes of the layout to minimize the possibility of interferences with new or existing equipment, piping, venting and wiring.
I IJ ! [o|lJ :l ;i I:ll]'.J :Eld:{o] ! ::[IILVA|_[€-r_,_..
The following LP requirements from the Uniform Mechanical Code, section 304.6, may be in effect in
your geographic area:
"Liquefied peh'oleum gas-burning appliances shall not be installed in a pit, basement or similar location
where heavier-than-air gas might collect. Appliances
so fueled shall not be installed in an above-grade under-floor space or basement unless such location
is provided with an approved means for removal of unburned gas."
l_.]llF'4T_'i:i_IrJ_
2
3
Provide a sound, level foundahon Locate boiler as near to the chmney or outside v_ali as possLble and
cennahzed v_Jth respect to the heahng system
Locate boiler [n front of installation pos[hon before _movll_g crate
If using combushble floor pan, poslhon pan on foundat,on or flooring
4 Separate the wood shppmg pallet from the boiler
base by removing two (2) hold-down bolts at each end of the boder base
5 Move boder into hnal poslhon If using combustLble
floor pan, install boder on pan as outhned ,n the instructions included wlth the pan
3. WATER PIPING AND CONTROLS
"-I [:{=]ll_;l[.-llJ'J_Jl_'m_,]l_ll] I;l:i[IJ;|k'
1. Size the supply and return to suit the system. A
t_pical piping arrangement is shown in Figure 5. Refer also to the I-B-R Installation Guide No. 200
and the Peerless Water Survey for additional guidance during water piping installation.
2. Return Piping: a. For boilers equipped with a factory mounted
circulator, pipe the return to the inlet connection of the circulator.
b. For boilers equipped with a separate, unmounted
circulator, pipe the outlet connection of the circulator to a tee, provided with a drain valve, at the 1-1/4 NPT return tapping near the bottom of the left section. Pipe the return to the inlet
connection of the circulator.
3
4.
5.
Supply Piping: Pipe the supply to the I i/2 NPT supply tapping at
the top and rear of the boiler.
When system return water temperature will be below
130°E pipe the boiler with a bypass arrangement to blend the system return and hot supply to obtain at least 130°F entering the boiler. For more information on bypass piping, consult the Peerless Water Survey.
If desired, install the circulator in the alternate location shown in Figure 5. Consult the Peerless Water Survey for more information on circulator
location.
COLD
WATER
FILL
VAL VE
DRAIN
VAI VE J
TO
DRAIN
l
i
,7
Figure 5: Supply and Return Piping
6. Install this boiler so that the gas ignition system components are protected from water (dripping, spraying, etc ) during appliance operation and service (circulator replacement, condensate trap, control replacements, etc )
7. If this boiler and distribution system is used in conjunction with a refrigeration system, pipe the chilled medium in parallel with the boiler and install the proper valve to prevent the chilled medium from
entering the boiler. A drawing illustrating this hook- up is provided in Figure 6
8. When the boiler is connected to heating coils located
in air handling units where they may be exposed to
refrigerated air circulation, install flow control valves
or other automatic means to prevent gravity
circulation of the boiler water during the cooling
cycle.
9. If this boiler is installed above radiation level,
provide a low water cutoff device, either as a part of
the boiler or at the time of boiler installation.
C HECj VAILVEI
SUPPLY
LINE
LINE
WATER THREE WAY
_HILLER VALVE
Figure 6: Parallel Hook-up with Water Chiller
I:m l-'f!1=:lL'dI;t=l!l=l:l krl±lLvd
i I Locate safety relief valve and fittings in bag
assembly.
2. If air elimination is not required at the safety relief valve tapping, install valve and piping as shown in Figure 7.
3. For air elimination at the safety relief valve tapping, install valve and piping as shown in Figure 8.
SAFETY RELIEF
VALVE
x6"
NIPPLE
Pipe the discharge of safety relief valve to prevent injury in the event of pressure relief, Pipe the discharge to a drain. Provide piping that is the same size as the safety relief valve outlet.
Figure 7: Safety Relief Valve Hook-Up Installation
with Air Elimination in System Piping
TO AIR
ELIMINATION
DE_CE
SUPPLY TEE
SAFETY X 6 _ RELIEF NIPPLE
VALVE
NIPPLE
TO DRAIN
5/4" STREET
ELBO_
Figure 8: Safety Relief Valve Hook-Up with
Air Elimination
7
loll I'JI_IL'_[_ l;:[e];l v_[o]L'ql:lm]F.._'_"-]Ii :hVj_
1. See Figures 9 and 10 for basic zoned system layouts.
2 Run each zone pipe down then up to zone to
prevent air accumulation in piping
3. If required, provide means to isolate and drain each zone separately,
TO SYSTEM
ZONE ZONE ZONE
5 2 /
ZONE
VALVES
I
I
TO
SUPPLY
FROM SYSTEbl
BAL _,NCINO
VAi VES m',
CONNECT TO
RETURN
(CIRCULATOR INLET)
ZONE ZONE ZONE
I 2 3
I
I
±
Figure 9: Zone Piping with Zone Valves
TO SYSTEM
ZONE ZONE ZONE
5 2 1
FROM SYSTEM
ZONE ZONE
1 2 3
FLOW
CONTROL _]
VALVES
I-
q
CONNECT
TO
SUPPLY
ZONE
CIRCULATORS
CONNECT TO
RETURN
TAPPING
Figure 10: Zone Piping with Circulators
8
I_ I:l;f:l:_,l: I;J;{e]i:_l,]i[o]_
1. Consult the tank manufacturer's instructions for
specific information relating to tank installation Size the expansion tank for the required system volume and capacity. See Table 8 in Section 10 for boiler water capacity.
2.
Expansion tanks are available with built-in fill valves and check valves for reducing supply water pressure
and maintaining minimum system pressure. Check the design features of the tank and provide valves as
necessary.
Refer back to Figure 5 for typical expansion tank piping.
I::m I I£qm]I:| =[o,]iI_ :ll:t ::1e]I_l,__ii =1;t I:I_,__ii ::1
If the boiler is to be used in conjunction with an indirect- fired water heater, refer to Figure 11 for typical piping. Follow the instructions provided by the water heater manufacturer. Pipe the water heater as a separate zone.
For new or existing systems that must be freeze- protected:
Use only inhibited propylene glycol solutions of up to 50% by volume with water. Ethylene glycol is toxic and can attack gaskets and seals used in hydronic systems.
1.
Glycol in hydronic applications is specially formulated for this purpose. It includes inhibitors
which prevent the glycol from attacking metallic system components. Make certain that the system
fluid is checked for the correct glycol concentration and inhibitor level.
2. The anitfreeze solution should be tested at least once a year and as recommended by the antifreeze
manufacturer.
3.
4.
Antifreeze solutions expand more than water. For example, a 50% by volume solution expands 4.8%
in volume for a temperature increase from 32°F to
180°F, while water expands 3% with the same temperature rise. Allowance must be made for this expansion in system design.
For more information, consult the Peerless Water
Installation Survey and the antifreeze manufacturer.
SUPPLY TO
SYSTEM
RETURN FROM
SYSTEM
ZONE VALVES
INDIRECT FIRED
WATER HEATER
HOT DOMESTIC
WATER
SUPPLY
COLD
DOMESTIC _-
WATER SUPPLY
SUPPLY
TO
TANK
J
BALANCING
VALVE
]
BALANCING
VALVE
i I
SYSTEM
CIRCULATOR _
DRAIN
Figure 11: Typical Piping with Indirect-Fired Water Heater
9
Lt/:1_/Jl_[,':t
4; VENTING
|_,!1 h,'_ii::[d; f_,_ II o] ;f_,_;Iil -"[o_o]g
1.
The MIiMIH boiler is equipped with a built in draft hood This device is designed to:
a provide for the ready escape of flue gases from
the boiler in the event of no draft.
b. prevent a backdraft [Tomentering the boilen
c. control stack draft during operation.
These tasks are accomplished without the extra height requirements of a separate draft hood.
2.
The draft hood relief opening is the large rectangular passage at the front of the boiler. Make certain that
there are no obstructions to airflow in front of this opening.
3.
A vent safety shut off switch is located within the draft relief opening to shut off the boiler in case of a blocked vent condition. See Section 7B for details
regarding this device. See Figure 16 in Section 6 (Electrical) for spill switch location.
4.
The vent damper can be mounted directly onto the round draft hood outlet (vent connector) on top of
the boiler, or in vent piping close to the boiler. See the Vent Damper Installation Instructions below.
].
2.
3.
4.
Do not use one vent damper to control two or more heating appliances. See Figure 12.
Follow these and the installation instructions that are included with the vent damper. Observe the cautions
and warnings that accompany all instructions.
Make certain that minimum clearances provided in the vent damper manufacturer's instructions are maintained and that adequate space is available for
damper accessand service.
Orient the damper operator to facilitate connection of the harness with the vent damper and boiler. Note flue gas flow arrow on vent damper and orient as required. For installation with damper mounted in
vertical position, see Figure 13. For installation with damper mounted in horizontal position, mount the
unit as shown in Figure 14 to avoid excessive heat
on the operator or condensation drips into the operator.
BOILER
c:::::::_ c:::::::_
c:::=_ c:::::_ c:::::::_ c:::::::_
OTHER
HEATING
&PPLIANCE
INCORRECT
CORRECT
Figure 12: Venting Multiple Appliances
10
_o,,NkVJ:h,_/ uI:JI:,,]h,1[€_V_*l_._I D][o,]-"I hVjh._I_"
1. Install vent piping in accordance with Part 7. Venting of Equipment, National Fuel Gas Code, ANSI Z223. I/NFPA 54 or applicable provisions of the local building codes.
2. Inspect the existing chimney and lining for structural soundness, corrosion and perforations. Repair as
neces_Fy.
3. Install vent pipe to slope upward at least I/4" per lineal foot between the draft hood outlet and the
chimney.
4.
5.
6.
7.
Before connection of joints, inspect the vent pipe interior for foreign objects such as tools, equipment,
rags, etc. and remove if present.
Insert vent pipe into but not beyond the inside wall of the chimney flue.
Do not connect vent connectors serving appliances vented by natural draft into any portion of
mechanical draft systems operating under positive
pressure.
Support horizontal portions of the venting system to prevent sagging by use of metal strapping or equivalent means. Locate supports at no more than four (4) foot intervals.
SLOPE uP A MINIMUM
OF 1/4" PER FOOT
VENT
DAMP
DRAFT _ _
f¢3
HOOD
RELIEF
flVENT TO
CHIMNEY
SUPPORT AS REQUIRED,
DRAFT HOOD OUTLET
Figure 13: Venting with Vent Damper in Vertical Position
SLOPE UP VENT A MINIMUM DAMPER
OF I/4" PER FOOT_,,_
_VENT TO
CHIMNEY
11 O'CLOCK i O'CLOCK
POSITION POSITION
!
SUPPORT AS REQUIRED
r i
HEAT
_CONDENSATION
ZONE
7 O'CLOCK _5 O'CLOCK
POSITION POSIT'ON
DO NOT MOUNT DAMPER
OPERATOR IN SHADED REGION
SECTION A
Figure 14: Venting with Vent Damper in Horizontal Position
11
Loading...
+ 31 hidden pages