The following Parr publications are also included to
further your understanding of this instrument and
its component parts:
Part No.Description
201MLimited Warranty
554MCD for A2110E Controller
Explanation of Symbols
IOn position
OOff Position
Scope
These instructions cover the installation and
operation of Parr Model A2110E Motor Controller as
used with Parr Laboratory Reactors and Pressure
Vessels. The users should study the instructions
carefully before using any of these controllers so
that they will fully understand the capabilities of
this equipment and the safety precautions to be
observed in its operation.
Applications
These units are designed specifi cally for use with
Parr reactors and pressure vessels and are to be
used only with Parr equipment.
~Alternating Current (AC)
This CAUTION symbol may be present on the Product Instrumentation and literature. If
present on the product, the user must consult the appropriate part of the accompanying
product literature for more information.
Protective Earth (PE) terminal. Provided for connection of the protective earth (green or
green/yellow) supply system conductor.
www.parrinst.com
3
Page 4
Motor Controller
Safety Information
To avoid electrical shock, always:
1. Use a properly grounded electrical outlet of
correct voltage and current handling capability.
2. Ensure that the equipment is connected to
electrical service according to local national
electrical codes. Failure to properly connect may
create a fi re or shock hazard.
3. For continued protection against possible
hazard, replace fuses with same type and rating
of fuse.
4. Disconnect from the power supply before
maintenance or servicing.
To avoid personal injury:
1. Do not use in the presence of fl ammable or
combustible materials; fi re or explosion may
result. This device contains components which
may ignite such material.
2. Refer servicing to qualifi ed personnel.
Intended Usage
This controller has been designed for use with Parr
Pressure Vessels and Reactors. It has been designed, built, and tested to strict physical and electrical standards. However, it is the user’s responsibility to install and operate it in conformance with local
pressure and electrical codes.
If the instrument is used in a manner not specifi ed
by Parr Instrument Company, the protection provided by the equipment may be impaired.
General Specifi cations
Electrical Ratings
115VAC, 8.0 Amps, 50/60 Hz
or
230VAC, 8.0 Amps, 50/60 Hz
Before connecting a controller to an electrical outlet,
the user must be certain that the electrical outlet has
an earth ground connection and that the line, load
and other characteristics of the installation do not
exceed the following limits:
Voltage: Fluctuations in the line voltage should not
exceed 10% of the rated nominal voltage shown on
the data plate.
Frequency: Controllers can be operated from either a
50 or 60 Hertz power supply without affecting their
operation or calibration.
Current: The total current drawn should not exceed
the rating shown on the data plate on the controller
by more than 10 percent.
Environmental Conditions
This instrument is intended to be used indoors.
Operating: 15 ºC to 35 ºC; maximum relative humidity of 80% non-condensing. Installation Category II
(over voltage) in accordance with IEC 664.
Pollution degree 2 in accordance with IEC 664.
Altitude Limit: 2,000 meters.
Cleaning & Maintenance
Periodic cleaning may be performed on the exterior
surfaces of the controller with a lightly dampened
cloth containing mild soap solution. All power
should be disconnected and the power cord should
be unplugged when cleaning the A2110E Controller.
There are no user serviceable parts inside the product other than what is specifi cally called out and
discussed in this manual. Advanced troubleshooting
instructions beyond the scope of this manual can
be obtained by calling Parr Instrument Company in
order to determine which part(s) may be replaced or
serviced.
4
Parr Instrument Company
Storage: -25 ºC and 65 ºC; 10% to 85% relative humidity.
Caution!
Do not use in hazardous atmospheres.
Provisions for Lifting and Carrying
Before moving the instrument, disconnect all
connections from the rear of the apparatus. Lift the
instrument by grabbing underneath each corner.
Page 5
Motor Controller
User’s Responsibility
All Parr Reactors and Pressure Vessels are designed
and manufactured with great care to assure safe
operation when used within their prescribed
temperature and pressure limits.
But… the basic responsibility for safety when using
this equipment rests entirely with the user; who
must:
1. Select a reactor or pressure vessel that has the
capability, pressure rating, corrosion resistance,
and design features that are suitable for its
intended use. Parr engineers will be glad to
discuss available equipment and material
options with prospective users, but the fi nal
responsibility for selecting a reactor or pressure
vessel that will perform to the user’s satisfaction
in any particular reaction or test must rest with
the user - not with Parr.
In exercising the responsibility for the selection
of pressure equipment, the prospective user
is often faced with the choice between over
or under-designed equipment. The hazards
introduced by under-designed pressure vessels
are readily apparent, but the penalties that
must be paid for over-designed apparatus are
often overlooked. Recognizing these criteria,
Parr reactors and pressure vessels are offered
in several different styles, each designed for
convenient use in daily operation within certain
temperature and pressure limits, using gaskets,
closures, and other elements carefully selected
for safe operation within the limits specifi ed for
that design. But in order to preserve the validity
of these designs, all temperature and pressure
limits must be observed, and no attempt should
be made to increase these limits by making
alterations or by substituting components
which are not recommended by Parr Instrument
Company.
2. Install and operate the equipment within a
suitable barricade, if required, with appropriate
safety accessories and in full compliance with
local safety codes and rules.
All standard Parr pressure vessels are provided
with either suitable relief device or a means to
attach one (typically in the form of a plugged
opening). When a pressure vessel is delivered
without a pressure venting device, it is the customer’s responsibility to provide pressure relief
in order to protect the operator and the equipment from destructive high pressures. If you
need more information or need help in selecting
a proper relief device, please contact Parr Instrument Company.
3. Establish training procedures to ensure that any
person handling the equipment knows how to
use it properly.
4. Maintain the equipment in good condition and
establish procedures for periodic testing to be
sure the vessel remains structurally sound.
Unpack Carefully
Unpack the equipment carefully and check all the
parts against the packing list. If shipping damage is
discovered, report it immediately to the delivering
carriers. Examine the components closely for any
loose parts or shipping damage and be sure to
check all layers of packing materials thoroughly so
as not to overlook any parts which might otherwise
be discarded.
www.parrinst.com
5
Page 6
Motor Controller
Installation
General Instructions
Set the controller near the reactor on a sturdy bench
or table where there is convenient access to an
electrical outlet capable of carrying the appropriate current. Leave a space of at least twelve inches
between the controller and the reactor so that the
controller will not be affected by radiant heat.
Motor:
Secure a clamp on motor cord to
controller with provided screw next to
motor socket for safety purposes.
The motor output connector is to be used only with
Parr Instrument Company motor assemblies supplied with the appropriate motor power cord.
Other appropriate connectors are provided on the
rear panel of the controller.
The RPM Input connection is for the RPM Module
sensor input.
The Comm connector is for Communication output.
Rear View A2110E Motor Controller (230V shown)
6
Parr Instrument Company
Page 7
Switches and Indicators
Motor Controller
Front View A2110E Motor Controller
Main power switch
This switch will cut off power to the controller.
The Motor Controls consist of an on-off switch
and a speed control knob. The speed control knob
should be turned down to a minimum setting before
turning on the motor switch to minimize electrical
surges within the speed control unit.
The optional digital display shows the stirring
speed from the sensor mounted on the reactor. If
equipped with a motor control module, there will
also be a remote/local switch. When the remote/
local switch is in local mode, the speed control
knob will adjust the motor stirring speed. When the
remote/local switch is in remote mode, the motor
stirring speed may be adjusted from the RPM module. If there is no motor control module installed,
the remote/local port will be plugged and the speed
control knob is the sole control for the stirring
speed.
www.parrinst.com
7
Page 8
Motor Controller
Rear View A2110E Motor Controller (115V shown)
Protective Fuses and Relays
An instrument fuse is mounted on the back panel.
This is intended to protect the display module and
internal hardware. A hole plug is provided for units
that do not have a display module.
The motor reset fuse provides overload protection
for 0-90VDC motors. This is a re-settable breaker
designed to protect the motor if it becomes overloaded. The breaker will have a rating selected to
match the motor on the apparatus.
A lighted fuse holder provides protection for 0-180
VDC motors. A light will come on if the motor becomes overloaded and the fuse burns out. The fuse
rating will be selected to match the motor on the
apparatus.
A main fuse is mounted on the back panel on 115V
systems. This fast-acting, 250VAC, 10 amp fuse is
intended to protect the controller and prevent an
electric shock hazard from occurring.
Two main fuses are mounted on the back panel
on 230V systems. These are fast-acting, 10 Amp,
250VAC and are intended to protect the controller
and to prevent an electric shock hazard from occurring.
Caution!
Unplug unit before servicing. For
continued protection against possible
hazard, replace fuses with same type
and rating of fuse.
8
Parr Instrument Company
Page 9
Motor Controller
Access to the Controller Cabinet
To open the controller cabinet, unplug the power
cord and remove the four screws on the sides of the
top panel. Then lift the top panel off, providing full
access to all internal components.
Caution!
Inside of controller cabinet should be
accessed by qualifi ed personnel only.
Fuses
The A2110E Controller has a number of fuses which
are intended to be fi eld serviceable. The instrument
fuse is only provided if there is a digital display meter installed.
FuseRatingPart number
Instrument
Fuse
Main Fuse(s)Fast acting, 10
Motor fuse /
reset
Motor Board
Fuse (A+)
Motor Board
Fuse (L)
Fast acting, 1
Amp, 250VAC
Amp, 250VAC
check back
panel for specifi cations
Very Fast acting, 8 Amp,
250VAC
Fast acting, 10
Amp, 250VAC
Caution!
Unplug unit before servicing. For
continued protection against possible
hazard, replace fuses with same type
and rating of fuse.
139E6
185E2
check part list
959E5
185E2
www.parrinst.com
9
Page 10
Motor Controller
Instructions for the A2110E Motor
Controller
Motor Control Module (MCM)
RPM
This optional module can provide a means for
continuously monitoring the stirring speed in a Parr
reactor. It consists of an optical sensor installed in
the overarm drive on the reactor which is then connected to the A2110E Controller.
The connecting cable has a plug which fi ts the
marked socket on the back panel of the controller.
The digital display will show the stirring speed over
a range of 0-2200 rpm with a 1 rpm resolution and
+/- 10 rpm accuracy.
The left display in red shows the stirring speed,
and the right hand display in green shows the rpm
setpoint. The A2110E Controller is designed to run in
either Local or Remote stirring mode. The local/re-
mote switch on the front panel will toggle between
these two modes.
In Local mode, the stirring speed is controlled by
turning the speed control knob on the front panel.
The rpm setpoint has no bearing on the stirring
speed.
In Remote mode, the motor will stir at the rpm setpoint using closed loop PI control. The speed control knob has no bearing on the stirring speed.
The RPM setpoint may be adjusted by following the
steps below.
Note: The MCM leaves the factory in STOP mode.
Before the MCM may be used in remote mode it
must be set to RUN mode. Press the circular arrow
key to display the RUN/STOP screen.
For best results, use the RUN/STOP mode as the
fi nal switch. Return the MCM to STOP mode when
the setpoint motor control is not desired, and return
it to RUN mode as the last step to initiate the setpoint motor control.
10
Parr Instrument Company
1. Ensure the local/remote switch is in the REMOTE
position and the motor is motor switch is in the
ON (I) position.
2. Ensure the MCM is in STOP mode. This can be
done by momentarily pressing the return key
(circular arrow) once, then using the up or down
arrow to toggle between run and stop and pressing the SET key to solidify the change. Momentarily press the SET key to return to the operating display.
3. Press the UP arrow key until the red display indicates the desired setpoint. The display will blink
indicating that the value has not been set.
4. Press the SET key to solidify the change and the
display will stop blinking.
5. Return the controller to RUN mode by referencing step 1 above.
Motor Speed Control
Parr A2110E Controllers are equipped with a solid
state speed control module for use with the variable
speed, DC motors installed on Parr stirred reactors.
The module itself (approximately 4 inches square) is
mounted inside the chassis on the bottom panel. A
motor switch and a speed adjustment potentiometer
are mounted on the front panel. Each speed control module also requires a resistor matched to the
horsepower of the motor with which it will be used,
as listed in the table below:
Motor
Rating
1/17 HP90 VDC0.25 ohm876E6
1/8 HP90 VDC0.10 ohm876E3
1/4 HP90 VDC0.05 ohm876E
1/4 HP180 VDC0.10 ohm876E3
1/2 HP90 VDC0.025 ohm876E2
1/2 HP 180 VDC0.05 ohm876E
3/4 HP180 VDC0.035 ohm876E5
A2110E Controllers furnished as a part of a complete
Parr stirred reactor system will have the proper
resistor installed at the factory. Any controller sold
separately will require a motor specifi cation so that
the proper resistor may be provided.
Always turn the speed control knob fully counterclockwise to the off position before turning on the
motor switch, then advance the knob clockwise
slowly to develop the desired speed. Do not overload the motor. Any high speed or high viscosity
load which trips the circuit breaker is too heavy.
Reduce the speed to avoid overloading and use the
reset button on the rear panel to restart the motor.
Motor
Voltage
Resistor
Required
Parr
Number
Page 11
Motor Controller
Adjustments To Speed Control Board
There are fi ve trimpots in the speed control module
that can be used to adjust the performance of the
motor. These are set at the factory for optimum
performance and should not be disturbed unless
customized settings are required to match a particular set of operating conditions. The instructions
below should be followed carefully if these controls
are to be readjusted.
The CL, current limiting/torque adjustment is set at
the factory to 1.5 times the motor rating. It is intended to protect both the module and the motor against
overloads and heavy surge currents during startup.
It can also serve as a torque limiting device by re-
ducing the maximum power output of the system.
The IR, compensation adjustment is used to improve motor control under varying load conditions.
If the loads do not fl uctuate, this control can remain
at approximately one-fourth of full setting. But if the
motor speed drops more than 2% under load, this
adjustment should be increased. If it is set too high,
the motor speed will fl uctuate in a cyclical manner.
The MAX, maximum speed adjustment controls the
maximum speed of the motor. To increase the mo-
tor speed, turn the control knob on the front panel
to its maximum setting, then use the MAX trimpot
to raise the speed to the desired level. Care should
be taken to ensure the setting will not allow the mo-
tor to turn faster than its maximum rated speed.
The MIN, minimum speed adjustment can be used
to raise the minimum motor speed. To change this
setting, turn the control knob on the front panel to
its minimum setting, then adjust the MIN trimpot
to obtain the desired minimum speed, this adjust-
ment will also affect the maximum setting, making it
necessary to adjust both MAX and MIN trimpots to
obtain the desired spread.
The ACCEL, acceleration adjustment is normally set
to provide controlled acceleration from zero to full
speed in 2 seconds. It can be adjusted to higher or
lower acceleration times anywhere between 0.5 and
4 seconds, but changing this setting will affect the
MAX speed and IR compensation which will have to
be readjusted. If the acceleration time is reduced to
0.5 seconds (6 o’clock trimpot position), increase the
IR trimpot one quarter turn clockwise and decrease
the MAX trimpot one fi fth turn counterclockwise. If
the acceleration time is increased to the maximum
time of 4 seconds (full rotation), the IR trimpot must
be decreased and the MAX increased in the same
rotation amounts mentioned above.
Speed Control Board
www.parrinst.com
11
Page 12
Motor Controller
Communication with PC
When a motor controller is present, the A2110E
Controller is provided with RS-485 port to connect
to a USB port on a PC with optional communication
cable. With this arrangement, many parameters can
be set and read by the host computer.
Quick Start Instructions for Connecting with PC
1. Put the 554M CD into the CD-ROM.
2. Connect the A1925E4 communication cable
between the RS-485 port on the back of the
A2110E controller and an open USB slot on the
PC.
3. The PC should open an "Install Hardware" wizard
automatically when the cable is connected to the
USB slot. If it does not, go to the Control Panel
and select "Add Hardware" to start the wizard.
4. When prompted, check the box to search
removable media for the proper driver. The
wizard should fi nd the driver on the 554M
CD and install the USB driver. It may prompt
that the driver has not been validated; select
"continue anyway" to continue the installation.
After this it will repeat the installation process
for the RS-485 converter.
5. Copy the controller software to the PC. The
software is located on the CD at: "Software\
ParrCom.exe".
6. Once copied to the PC, open the ParrCom.exe
fi le. No installation is necessary.
7. At the main ParrCom program screen, select
"protocol >> set PC". Ensure that the following
values are set:
Baud: 9600
Data length: 8
Parity: even
Stop bit: 1
ASCII: RTU
Click OK to return to the main screen.
8. At the main screen, select "Program >> Monitor".
The Monitor screen will come up. There will be
a generic icon on the left, and four mini screens
on the right. Use one mini screen to connect to
the A2110E Controller.
9. In the fi rst mini screen, select 1 for the Address,
and click Connect. It should connect to the
digital display on the A2110E Controller, and
the bottom half of the screen should show
parameters for the controller. These may be
modifi ed here.
12
Parr Instrument Company
Page 13
Motor Controller
Datalogging and Charting
The A2110E Controller comes equipped with a charting and datalogging program. This program cannot
be run simultaneously with the control program, but
once the user is satisfi ed that the controller is set,
the control program may be closed, allowing the
charting and datalogging program to run. The module on the A2110E may still be modifi ed manually at
the physical panel during datalogging and charting.
1. Open the ParrCom.exe fi le. No installation is
necessary.
2. At the main program screen, select "protocol >>
set PC" (if you have already done previously, you
may skip this step). Ensure that the following
values are set:
Baud: 9600
Data length: 8
Parity: even
Stop bit: 1
ASCII: RTU
Click OK to return to the main screen.
3. At the main screen, select "Program >>
Recorder". The Recorder screen will come up.
5. Click the Save button and save a REC
fi le to an appropriate place on the PC.
When the chart is generated, it will write
to this fi le.
6. When you return to the main Recorder
screen, notice that the Save button
is depressed. Hit the Start button to
begin recording.
7. The chart will show the process values of each
module represented. As the values change, the
chart will automatically scale to show the values.
8. When you wish to stop recording, click the stop
button. The chart has already been saved in the
REC fi le created in step 5. You may
view the chart by clicking the record
button (shown on the left).
9. You can convert the fi le to a txt fi le for export to
a spreadsheet as well.
Converting a Chart File to TXT
Once a chart REC fi le has been created, you can con-
vert it to a TXT fi le for export into a spreadsheet.
4. Select the proper address for the digital display.
The digital display has address 2.
1. Insert the 554M CD into the CD-ROM. Locate the
conversion fi le at " \software\convert.exe". Copy
it to the PC.
2. Open the convert.exe fi le. No installation is
necessary.
3. Click the "CONVERT" button. Locate the REC fi le
to be converted, and click "Open".
4. The conversion program will create a new TXT
fi le in the same location as the REC fi le with the
name "CONVFILE.TXT".
www.parrinst.com
13
Page 14
Motor Controller
Parts List
Part numberDescription
A1925E4RS-485 to USB Conversion Cable
FuseRatingPart Number
Instrument FuseFast acting, 1 Amp, 250VAC139E6
Line Fuse(s)Fast acting, 10 Amp, 250VAC185E2
Motor Board Fuse (A+)Very Fast acting, 8 Amp, 250VAC959E5
Motor Board Fuse (L)Fast acting, 10 Amp, 250VAC185E2
Motor breaker / fuse
1/2 hp, 180VDCSlo-blo, 2.5 Amp, 250VAC139E8
1/4 hp, 180VDCSlo-blo, 1.5 Amp, 250VAC139E19
3/4 hp, 180VDCSlo-blo, 4.0 Amp, 250VAC139E20
1/12 hp, 90VDCCircuit breaker, 1.0 Amp801E
1/17 hp, 90VDCCircuit breaker, 1.0 Amp801E
1/8 hp, 90VDCCircuit breaker, 1.5 Amp801E3
1/4 hp, 90VDCCircuit breaker, 2.5 Amp801E2
1/2 hp, 90VDCCircuit breaker, 5.0 Amp801E4
Communication
Fuses
Caution!
For continued protection against possible hazard, replace fuses
with same type and rating of fuse.
Speed Control Board
Part numberDescription
A410E7EBSpeed control board, 1/17 hp, 115V
A410E7EESpeed control board, 1/17 hp, 230V
A410E10EBSpeed control board, 1/8 hp, 115V
A410E10EESpeed control board, 1/8 hp, 230V
A410E8EBSpeed control board, 1/4 hp, 90VDC, 115V
A410E8EESpeed control board, 1/4 hp, 90VDC, 230V
A410E9EBSpeed control board, 1/2 hp, 90VDC, 115V
A410E9EESpeed control board, 1/2 hp, 90VDC, 230V
A1252E2EESpeed control board, 1/4 hp, 180VDC, 115V
A1252EEESpeed control board, 1/2 hp, 180VDC, 230V
A1252E3EESpeed control board, 3/4 hp, 180VDC, 230V
911EFilter
2076EMotor switch
2078Local / Remote switch
2077EMain switch
A1695EExcitation / Conditioning board
2068EPower supply, 24VDC
1588ESignal Isolator for Remote Input
14
Parr Instrument Company
Page 15
Motor Controller
Tachometer Module (TDM) or Motor Control Module (MCM)
Part numberDescription
A10 01EOptical sensor for cart reactor
A1001E2Optical sensor for bench reactor
A1001E3Optical sensor for gear box drives
A1001E4Optical sensor for 4553/54/77/78
A1001E6Optical sensor for 5100 reactor
A1001E8Optical sensor for 3:1 gear box drive
A1001E9Optical sensor for 4555 reactor
A10 01E10Optical sensor for 10:1 gear box drive
A1831EOptical sensor for 5500 Compact Lab Reactor
1564HCSlotted wheel for cart, bench, and low pressure (1:1) reactors
1564HC2Slotted wheel for low pressure (2:1) reactors
3056HCSlotted wheel for 5500 Compact Lab Reactor
A1177E8Tachometer harness, 5-ft
A1177ETachometer harness, 10-ft
A1177E4Tachometer harness, 15-ft
A1177E2Tachometer harness, 20-ft
A1177E5Tachometer harness, 25-ft
A1177E3Tachometer harness, 30-ft
A1177E6Tachometer harness, 35-ft
A1177E7Tachometer harness, 40-ft
2084ERPM meter
www.parrinst.com
15
Page 16
Revision 05/28/13
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.